Output expansion module
1 WECON Technology Co., Ltd.
General
This manual is applied to LX3V-8EY and LX3V-16EY digital output expansion modules.
1. Naming rule
Naming rule of LX3V I/O output expansion module:
① WECON PLC;
② Main module;
③ Expansion module;
④ Product type, E means expansion;
⑤ Expansion output(Y);
⑥ T: transistor, R: relay;
2. Dimensions
① Extension cable and connector
② State LED: Light when normal condition
③ Power LED: Light when connect to 24V
④ Module name

Output expansion module
2 WECON Technology Co., Ltd.
⑤ digital signal output terminal
⑥ Extension module interface
⑦ DIN rail mounting slot
⑧ DIN rail hook
⑨ Mounting holes (φ4.5)
2.1 Crimp terminations
3. Output specification
Less than AC250V or DC 30V
Light when relay is energized
Light when photo-coupling is
energized
2A/ point
8A/ four points
8A/ eight points
0.5A/ point
0.8A/ four points
1.6A/ eight points
Please use crimp terminals as indicated on the graph.
The tightening torque should be applied 5 to 8 Kg.cm.
Other terminals should be empty but only wiring
terminals mention in this manual.