Wayne EH, EHA, EHASR User Manual

SPECIFICATIONS
Firing Capacities:
Model EHA & EHASR
0.75 – 3.00 gal/hr 105,000 – 420,000 Btu/hr Input Model EH
3.00 – 6.00 gal/hr 420,000 – 840,000 Btu/hr Input
Fuel Pumps
Single Stage Standard
Electrical
Power Supply ……….120 Vac 60Hz, 230 Vac 60 Hz 1 Phase; optional 230 Vac 50 Hz 1 Phase Motor ………………...3450 rpm, Automatic Reset Overload Protection Ignition ……………….14,000 V secondary, Continuous Duty or Interrupted Duty
WAYNE COMBUSTION SYSTEMS
801 GLASGOW AVE.
FORT WAYNE, IN 46803
PHONE: (260) 425-9200
(855) WAYNECS
(800) 443-4625
FAX: (260) 424-0904
www.waynecombustion.com
MODEL
EH, EHA &
EHASR
OIL BURNERS
Fuels: Use No.1 or No.2 heating oil (ASTM D-396),
Kerosene, Diesel (ASTM D975-18), JP8
Dimensions (Standard):
Height ……………………….…..…..12 1/2” Width ……………………….…..……15 1/2” Depth ………………………….…….. 8 1/4”
Center Line of Tube to Floor ......... 8 1/16”
Mounting:
Rigid Flange, Adjustable Flange, or Pedestal Mount
READ THIS MANUAL BEFORE USING THIS PRODUCT. FAILURE TO FOLLOW THE INSTRUCTIONS AND SAFETY PRECAUTIONS IN THIS MANUAL CAN RESULT IN SERIOUS INJURY OR DEATH. KEEP THIS MANUAL FOR FUTURE REFERENCE. INSTALLER: LEAVE THIS MANUAL WITH THE END USER.
INSTALLATION OF THE BURNER MUST BE DONE BY A QUALIFIED INSTALLER IN ACCORDANCE WITH REGULATIONS OF THE NATIONAL FIRE PROTECTION AGENCY, NFPA NO. 31, AND IN COMPLETE ACCORDANCE WITH ALL LOCAL CODES AND AUTHORITIES HAVING JURISDICTION.
A QUALIFIED INSTALLER IS THE PERSON WHO IS RESPONSIBLE FOR THE INSTALLATION AND ADJUSTMENT OF THE EQUIPMENT AND WHO IS LICENSED TO INSTALL OIL-BURNING EQUIPMENT IN ACCORDANCE WITH ALL CODES AND ORDINANCES.
Manual 21530 | Revision 10 | Publication Date: 9/14/18
1
INSTALLATION LOG
BURNER MODEL:
SPECIFICATION NUMBER:
FUEL:
Nozzle Size and Pattern:
Pump Fuel Pressure (psi):
CO2 (%):
Smoke Spot:
CO (PPM):
INSTALLER’S NAME:
CONTRACTOR NAME:
CONTRACTOR
ADDRESS:
CONTRACTOR PHONE
NUMBER:
CONTRACTOR LICENSE #:
DATE OF INSTALLATION:
COMMENTS ABOUT INSTALLATION/START UP:
BURNER/APPLIANCE SERVICE LOG
SERVICE
DATE
TECHNICIAN
COMPANY
/ ADDRESS
CONTRACTOR
LICENSE #
WORK PERFORMED
/ /
/ /
/ /
/ /
/ /
/ /
/ /
/ /
/ /
/ /
/ /
/ /
/ /
/ /
/ /
/ /
/ /
THESE INSTRUCTIONS SHOULD BE AFFIXED TO THE BURNER OR ADJACENT TO THE
HEATING APPLIANCE.
2
Overview of Safety Warning System and Your Responsibilities
Indicates a hazardous situation, which, if not avoided, will result in death or serious bodily injury.
Indicates a hazardous situation, which, if not avoided, could result in death or serious bodily injury.
Indicates a hazardous situation, which, if not avoided may result in minor or moderate bodily injury.
Indicates a situation that may result in equipment-related damage.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. The meaning of this safety alert symbol is as follows: Attention! Become alert! Your safety may be at risk. The message that appears next to the warning describes the hazard, which can be either written or pictorially presented. NEVER remove or tamper with the warning labels, safety devices or guards fitted on the unit.
Wayne Combustion Systems is NOT responsible for any bodily injury and/or property damage that may result from operation outside of the stated operating conditions for which this unit was intended.
The safety of you and others depends upon you thoroughly reading and understanding this manual. If you have questions or do not understand the information presented in this manual, please call Wayne Combustion Systems or see
www.waynecombustion.com.
Hazard Definitions:
3
Hazard Level
Pictogram
Type
Hazard Explanation
Fire or
Explosion
Failure to follow safety warnings exactly could result in serious injury, death or property damage.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
Never attempt to use gasoline as a fuel for this burner, as it is more combustible and could result in a serious explosion.
Electric Shock
or Burn
High voltages are present in this equipment. Follow these rules to avoid electric shock:
Use only a properly grounded circuit. A ground
fault interrupter is recommended.
Do not spray water directly on burner.  Turn off power before servicing.  Read the owner’s manual before using.
Overheating
Should overheating occur:
Shut off the manual oil valve to the appliance.  Do not shut off the control switch to the pump
or blower.
Carbon Monoxide Poisoning
Carbon monoxide is a colorless, odorless gas that can kill. Follow these rules to control carbon monoxide:
Do not use this burner if in an unvented,
enclosed area. Carbon monoxide may accumulate.
Check flue gases for carbon monoxide. This
check requires specialized equipment.
Allow only qualified burner service persons to
adjust the burner. Special instruments and training are required.
Read the burner manual before using. CARBON MONOXIDE POISONING: Early signs of carbon monoxide poisoning are similar to the flu with headaches, dizziness, weakness, nausea, vomiting, sleepiness, and confusion. If you suspect carbon monoxide poisoning, get outside to fresh air immediately, and then call 911. Some people are more affected by carbon monoxide than others. These include pregnant women, people with heart or lung disease or anemia, those under the influence of alcohol, and those at high altitudes.
Proposition 65
material
This product can expose you to chemicals, including lead, nickel, carbon monoxide and sulfur dioxide, which are known to the State of California to cause cancer or birth defects or other reproductive harm. For more information, go to www.p65Warnings.ca.gov.
Special
Requirements
When contacting Wayne Combustion Systems for service information, please have the burner specification and model number when calling or writing. Specification number will be located on a 1” X 2” rectangular sticker on the back of the burner and model number is on the big square sticker that has the
manufacturer’s logo and contact information. This
sticker will be above the specification label.
4
Contents
GENERAL INFORMATION ............................................................................................................................... 6
TROUBLESHOOTING....................................................................................................................................... 7
GENERAL TROUBLESHOOTING GUIDE ..................................................................................................... 7
BURNER DOES NOT LIGHT, HONEYWELL CONTROL REMAINS ON STANDBY .................................... 10
BURNER WILL LIGHT, BUT WILL NOT STAY LIT DURING “CALL FOR HEAT” ........................................ 11
WIRING DIAGRAMS ....................................................................................................................................... 16
SEQUENCE OF OPERATION: BURNERS WITH R7284G AND R8184G CONTROLS .................................. 17
SEQUENCE OF OPERATION: BURNER WITH R7284P CONTROL .............................................................. 18
SEQUENCE OF OPERATION: BURNER WITHOUT CONTROL .................................................................... 19
OPERATIONAL CHECK OF BURNER ............................................................................................................ 19
START SYSTEM ......................................................................................................................................... 19
CHECK SAFETY FEATURES ...................................................................................................................... 19
GENERAL INSTALLATION INFORMATION ................................................................................................... 20
COMBUSTION CHAMBER .......................................................................................................................... 20
FUEL PUMPS .............................................................................................................................................. 20
FUEL LINES ................................................................................................................................................ 20
FUEL TANKS ............................................................................................................................................... 21
ELECTRICAL WIRING OF BURNER ........................................................................................................... 21
CHIMNEY INSTALLATION .......................................................................................................................... 21
DRAFT REGULATORS ............................................................................................................................... 21
AIR SUPPLY FOR COMBUSTION .............................................................................................................. 22
NOZZLE AND AIR CONE SELECTION ....................................................................................................... 22
NOZZLE INSTALLATION ............................................................................................................................ 22
SETTING GUN DEPTH ............................................................................................................................... 27
STARTING PROCEDURE ............................................................................................................................... 30
STARTING BURNER ................................................................................................................................ ... 30
FINAL ADJUSTMENTS ............................................................................................................................... 32
SETTING COMBUSTION EFFICIENCY ...................................................................................................... 32
FINAL CHECKS ........................................................................................................................................... 33
MAINTENANCE .............................................................................................................................................. 33
REFERENCE INFORMATION ......................................................................................................................... 34
REFERENCE FIGURES .............................................................................................................................. 36
OIL PIPE SIZING INFORMATION ............................................................................................................... 37
WARRANTY .................................................................................................................................................... 39
5
GENERAL INFORMATION
Read this manual carefully and in it’s entirety prior to performing any maintenance or service on
the burner.
WARRANTY
Wayne Combustion Systems warrants its burner’s specifically to organizations that have purchased it for resale, including your dealer. If you have a problem with your burner, or its installation, you should contact your dealer for assistance, for a full description of the warranty see page 39.
MAINTENANCE
Wayne Combustion Systems recommends yearly inspection/service of your oil heating system by a qualified service agency or individual.
A qualified service agency or individual must be:
Licensed or certified to install and provide technical service to oil heating systems.  Experienced with all applicable codes, standards and ordinances.  Responsible for the correct installation and commission of the equipment.
Skilled in the adjustment of oil burners using combustion test instruments
APPROVALS
This burner complies with ANSI/UL Standard 296 and is for use with No. 1 fuel oil or No. 2 fuel oil and is UL listed for use with Group I or Group II primary safety controls. The states of Massuchusetts, New York and local approvals are shown on the burner’s nameplate label. All burners must be installed in accordance with the National Fire Protection Association, and in complete accordance with all local codes and authorities having jurisdiction. Regulation of these authorities takes precedence over the general instructions provided in this manual.
MANUAL ORGANIZATION
This manual is organized so that the licensed contractor can troubleshoot the service issue with the burner by working through the GENERAL TROUBLESHOOTING GUIDE on page 7. The GENERAL TROUBLESHOOTING GUIDE is organized by the performance issue or “problem” requiring attention. Each problem will list potential root causes that may result in the problem listed in order from most likely to least likely, and the solution to correct each root cause that may be affecting burner performance. The solution listed for each root cause will reference supplemental information regarding normal burner/component operation and service instructions depending on the problem and root-cause. If this is a new installation see GENERAL INSTALLATION INFORMATION on page 20.
MODEL DIFFERENCES
The EHASR burner utilizes unique air cones and oil gun assemblies to optimize burner performance in its rated firing range. The air cone is a single piece construction and is fixed to the air tube. The oil gun depth is set in reference to the fixed air cone The EH and EHA have the flamelock attached to the nozzle adaptor on the oil gun, this allows the burner to have a variable gun depth setting based on the firing rate needed. An EHA burner is different from a EH because the EHA uses an oil pump that is rated up to 3 gal/hr, while the EH model will use a larger pump that is rated up to 7 gal/hr to attain the higher firing rates.
BURNER COMPONENTS
The EHASR, EHA, and EH model burners are constructed with components of varying design. For example, the ignition device may be an iron core transformer or a solid state igniter. Both devices perform the same function, and they use the same troubleshooting methodology. There are also two distinct types of motors utilized by these burners. The “Permanent
Split Capacitor” or PSC motors (silver in color) utilize a thermal protection device that automatically resets when the motor cools down. The “Split-Phase” motors (black jacket) utilize a manual reset thermal protector. Appliance or equipment
manufacturers may specify one type of component over another. Please contact Wayne Combustion Systems for assistance with replacement component selection.
6
TROUBLESHOOTING
PROBLEM
POSSIBLE CAUSE
SOLUTION
BURNER WILL NOT LIGHT
Little or no fuel
Fill tank with fuel.
Improper fuel or water in fuel
Drain fuel tank and fill with proper fuel.
Limit switch open
Close limit or thermostat switch, and check limit switch for proper cycling operation.
Improper electrode spacing, gap to small
Clean and position electrode tips according to Figure 14 or Figure 15 on pages 26-27.
Plugged fuel filter
Replace as needed.
Misadjusted burner air bands
Re-adjust air bands for clean burn.
Little or no fuel pressure from fuel pump
Increase fuel pressure to manufacturer's specifications. See Figure 25 on page 36 for pump features. Check that plastic coupler (see Figure 1 on page 13, item 10) is not slipping on pump shaft, replace as needed and/or replace pump.
Before troubleshooting, familiarize yourself with the startup procedures and sequence of operation. Check the burner, ignitor or transformer, oil primary control (if equipped), and cad cell (if equipped) for proper operation and condition.
The Honeywell R7284 oil primary control’s reset button is the “i” button, the R7184, R8184 and
Wayne control is the big red button. Pressing the reset button and restarting the burner more than once with the burner not lighting could cause oil buildup in the firing chamber. This will cause smoking and possible detonation that could damage the equipment if the burner does light
Preliminary Steps
Check the following common causes of issues:
Wiring connections, fuses, power supply to the burner blower motor, controls, and ignition device.  Limit control is closed.  Thermostat (controller) is calling for heat.  Contacts between ignition device and electrodes.  Electrode gap is properly set at nozzle.  Oil piping to burner and tank is properly sized and is in good condition (see Oil Pipe Sizing Information on
page 37 ).
Oil pump pressure.  Oil nozzle is correctly sized for application.  Check cad cell location and photo eye cleanliness.
GENERAL TROUBLESHOOTING GUIDE
7
PROBLEM
POSSIBLE CAUSE
SOLUTION
BURNER WILL NOT LIGHT
(continued)
Air bubble sucked and trapped in pump
Bleed pump (see page 31 for instructions) and check all fuel lines for air leaks, replace lines as needed. See Figure 25 on page 36 for pump features.
Burner motor thermal protector actuated
If tripped, check voltage, connections, and extensions for cause. Check fuel pump shaft rotation for binding causing motor to overheat.
Flex-coupling slipping on fuel pump shaft or burner motor shaft
Replace as needed. See Figure 1 on page 13, Item 10.
Fuel not reaching combustion chamber
Check fuel system for proper flow going through the burner. Clogged burner nozzle
Replace. See page 22 for instructions.
Low voltage at burner wire leads
Check for proper 120/230 Vac going to the burner
Fuel solenoid malfunction
Replace as needed. See Figure 1 on page 13 for replacement part.
Faulty burner ignition device
Test ignition device for proper arc between contacts. Replace as needed. See Figure 1 on page 13 for replacement part.
Disconnected or short in electrical wiring
All wire contacts should be clean and tight. No breaks in wire insulation, replace as needed. See page 21 for wire size recommendations.
Oil primary control sees light during safety check and remains in standby mode (Applicable only if burner comes with oil primary control).
Press and hold the reset button for 2 seconds on a Honeywell control, (push and hold for 3 seconds if it is an older style Wayne control), observe burner sequence of operations. If burner remains on standby see Burner does not light, Honeywell controls remains on standby, on page 10.
Oil gun depth spaced too far ahead causing electrodes too short to ground through air cone.
Identify burner model and position oil gun depth according to Figure 16 and Figure 17. See page 27 for instructions.
Heavy sooting on burner electrodes, and air cone causing a weak arc between the electrodes.
Clean as required. Check ceramic for any chips and cracks that could affect arc between the electrodes, replace as required. See Table 2 on page 15 for replacement parts.
BURNER WILL LIGHT, BUT NOT STAY LIT DURING CALL FOR HEAT
Oil primary control goes into nuisance lockout (Applicable only if burner comes with oil primary control).
Press and hold the reset button for 2 seconds on a Honeywell control, (push and hold for 3 seconds if it is an older style Wayne control), observe burner sequence of operations. If burner locks out again see Burner Will Light, But Will Not Stay Lit During “Call For Heat”, on page 11.
BURNER SMOKES
Improper fuel or water in fuel
Drain tank and replace contaminated fuel. Improper air adjustment
Re-adjust air bands on burner assembly for clean burn.
Low fuel pressure
Increase fuel pressure to manufacturer's specifications. See Figure 25 on page 36 for pump features.
Air leaks in fuel lines
Check fuel lines for leaks or air bubbles. Tighten or replace as needed.
Plugged or dirty burner nozzle
Replace burner nozzle. See page 22 for instructions.
Improper nozzle size installed, nozzle size too big
Contact appliance manufacturer for proper nozzle size, and replace. See page 22 for instructions.
8
PROBLEM
POSSIBLE CAUSE
SOLUTION
BURNER SMOKES
(continued)
Heavy accumulation of soot on heat exchanger and burner assembly
Remove burner assembly from heat exchanger. Clean thoroughly.
Faulty burner nozzle spray pattern
Replace. See page 22 for instructions.
Misaligned or damaged electrode
Realign electrodes according to Figure 14 or Figure 15 on pages 26-27, and the oil gun depth according to Figure 16 or Figure 17 on pages 27-28.
Obstruction in smoke stack
Check for blockage or other foreign objects.
BURNER RUNS CONTINOUSLY WITHOUT SATISFYING CALL FOR HEAT
Improper fuel or water in fuel
Drain fuel tank and fill with proper fuel.
Reduced fuel pressure
Check fuel pump pressure. Check that fuel filter isn’t partially clogged, replace as necessary. Increase fuel pressure to manufacturer's specifications. See Figure 25 on page 36 for pump features. Replace pump if needed.
Soot build-up on heat exchanger.
Clean heat exchanger with soot remover.
Improper burner nozzle installed, nozzle size too small.
Contact appliance manufacturer for proper nozzle size, and replace. See page 22 for instructions.
BURNER RUNS BUT APPLIANCE IS OVERHEATING
Fuel pump pressure too high
Readjust fuel pressure to appliance manufacturer's specs. See Figure 25 on page 36 for pump features.
Oil primary control keeps energizing
burner past “call for heat”. (Applicable
only if burner comes with oil primary control).
Identify control model. Replace Control, and wire accordingly to Figure 3 or Figure 4 on page 16.
Faulty fuel pump shut-off valve
Replace fuel pump shut-off valve.
Defective high limit switch or Thermostat
Replace.
Incorrect fuel nozzle size, nozzle size too big
Contact appliance manufacturer for proper nozzle size, and replace. See page 22 for instructions.
BURNER MOTOR WILL NOT RUN
Overload protector activated
Wait 20 minutes for motor to cool down, will restart automatically.
Faulty oil primary control. (Applicable only if burner comes with oil primary control).
Observe burner sequence of operations. Check voltage going to the burner motor if it does not run during the 15 second trial for ignition, replace control.
Fuel pump seized
Replace fuel pump. See Figure 1 on page 13 for replacement parts
Burner fan loose or misaligned
Identify fan part number by measuring O.D of fan then reference Table 1 on page 14 and position the fan spacing according to Figure 26 on page 36 and tighten set screw.
Defective control switch
Replace switch.
Loose wire
Check and replace or tighten wiring.
Defective burner motor
Replace motor.
BURNER STAYS ON WHEN NO CALL FOR HEAT
Faulty oil primary control. (Applicable only if burner comes with ignition control).
Observe burner sequence of operations. Replace control if necessary
Thermostat defective
Check for proper operation, replace if necessary.
Fuel solenoid defective
Replace fuel solenoid.
9
Procedure
Status
Corrective Actions
1. Make sure limit switches are closed
---------------------
---------------------
2. Check for line voltage power at primary Control. 120 vac.
---------------------
Check breaker and investigate appliance wiring
3. Check R7284G or R8184G indicator light, (LED Screen if R7284P control) with burner off, no call for heat. No Flame.
R7284G & R8184G indicator
light is pulsing (1/4 sec. ON, 4
sec. OFF), R7284P display
would say “STANDBY
Sees external light during safety check or
connections are shorted,
4. Shield cad cell from external light
R7284G & R8184G indicator
light starts pulsing (1/4 sec. ON,
4 sec. OFF), R7284P display
will read “STANDBY”
Energize thermostat to verify that burner goes
through proper sequence of operations.
If burner does not light go to step 5
5. Jumper oil primary T-T terminals
Burner starts
Trouble in thermostat or limit circuit. Check wiring
connections
Burner does not start
Disconnect line voltage and open thermostat or
limit switch.
If burner does not start, replace primary control.
NOTE: This section refers to Honeywell R7284 and R8184 series controls. The R7284G and R8184G control use a LED light to display the troubleshooting status, and the R7284P control comes with a display screen that will output the current operating state of the burner or any troubleshooting errors that might arise in normal burner operation.
Troubleshooting tables on pages 10-11 are specific to burners that come equipped with an oil primary control, and these sections only apply if the general troubleshooting guide tells the licensed contractor to consult these sections while servicing the burner.
BURNER DOES NOT LIGHT, HONEYWELL CONTROL REMAINS ON STANDBY
10
BURNER WILL LIGHT, BUT WILL NOT STAY LIT DURING “CALL FOR HEAT”
Procedure
Status
Corrective Actions
1. Check limit switches
---------------------
---------------------
2. Check for line voltage at the oil primary control (120 volts)
---------------------
---------------------
3. Check R7284G or R8184G indicator light, (LED Screen if R7284P control) with burner on, call for heat.
R7284 or R8184 control is in
lockout. The R7284G &
R8184G control LED flashes for
½ seconds ON, ½ seconds
OFF. The R7284P control reads
“Lockout Mode”
Control is sensing bad flame signal, cad cell or
controller is defective, sees external light or connections are shorted. Go to step 5.
The R7284P display reads
Valve on Delay
Go to step 4.
4. Applications with “valve
on delay”, verify that oil
valve is closed during
the “valve on delay”
period by opening view port and verifying that no flame is present
during 15 second “valve
on delay”
R7284P display still reads
“Valve on Delay”
If flame is present, replace valve.
5. Jumper oil primary T-T terminals
Burner starts, and stays
running.
Trouble is in thermostat or limit circuit.
Burner starts, but doesn’t stay
running.
Disconnect line voltage and open thermostat or
limit switch.
Check all wiring connections  If burner does not stay running, go to step 6
6. Check that nozzle size is per appliance manufacturer recommendation
Burner nozzle incorrect.
Change nozzle and fuel pressure to factory settings
and retest, if burner doesn’t stay lit go to step 7
Burner nozzle correct
Go to step 7
7. Check burner air band setting is set up per manufacturer recommendation
Burner air band setting too low.
Could cause black puff of smoke on ignition if the
fuel-air mixture is too rich.
Use a combustion test kit to measure the CO2 %
and smoke spot in the exhaust.
Adjust air band opening until CO2 % measures
between 10-12 %, and smoke spot is a 1 or less.
If problem persists go to step 8
Burner air band setting too high
Could cause delayed ignition on start-up if the fuel-
air mixture is too lean.
Use a combustion test kit to measure the CO2 %
and smoke spot in the exhaust.
Adjust air band opening until CO2 % measures
between 10-12 %, and smoke spot is a 1 or less.
If problem persists go to step 8
Burner air band set at
manufacturers
recommendations
Go to step 8
11
8. Check cad cell sighting for view of flame.
- Disconnect line
voltage power and open line switch.
- Unplug cad cell and
clean face with soft cloth. Check sighting for view of flame. Place cad cell back in socket.
- Reconnect line
voltage and close line switch.
- Start burner,
Burner locks out.
Go to step 9
Burner keeps running, until “call
for heat” is satisfied.
System is okay.
9. Check Control & Cad cell.
- Remove cad cell
wires from connectors on primary and leave lead wires open.
- Apply power to
device
- Place jumper
across cad cell terminals after burner motor turns on.
Burner doesn’t run.
Replace primary control.
Burner runs.
Control is okay, replace cad cell.
12
Loading...
+ 28 hidden pages