Wayne B23/5 Installation & Operation Manual

Ovation Dispensers
INSTALLATION
OPERATION
DANGER
READ THIS MANUAL BEFORE YOU BEGIN
Dispensers have both electricity and a hazardous, flammable and potentially explosive liquid. Failure to follow the below precautions and the Warning and Caution instructions in this manual may result in serious injury. Follow all rules, codes and laws that apply to your area and installa­tion.
SAFETY PRECAUTIONS - INSTALLATION AND MAINTENANCE
Always make sure ALL power to the dispenser is turned OFF before you open the dispenser cab­inet for maintenance. Physically lock, restrict access to, or tag the circuit breakers you turn off when servicing the dispenser. Be sure to trip (close) the emergency valve(s) under the dispenser BEFORE beginning maintenance.
Make sure that you know how to turn OFF power to the dispenser and submersible pumps in an emergency. Have all leaks or defects repaired immediately.
EQUIPMENT PRECAUTIONS
Be sure to bleed all air from product lines of remote dispensers and prime suction pumps before dispensing product, otherwise, damage to the equipment may occur. Always use the approved method for lifting the dispenser. Never lift by the nozzle boot, sheet metal, valance, etc., other­wise equipment damage or personal injury may occur.
HOW TO CONTACT WAYNE
Technical questions related to the installation of the dispenser should be referred to Wayne Technical Support (1-800-926-3737). Customers needing help with the operation of the dis­penser should call the Wayne Help Desk (1-800-289-2963).
INDICATORS AND NOTATIONS
DANGER
WARNING
CAUTION
NOTE:
Danger indicates a hazard or unsafe practice which, if not avoided, will result in severe injury or possibly death.
Warning indicates a hazard or unsafe practice which, if not avoided, may injury or possibly death.
Caution indicates a hazard or unsafe practice which, if not avoided, may
Important information to consider, otherwise, improper installation and/or damage to compo­nents may occur.
result in severe
result in minor injury.
November 2008 Part No. 920559 Rev H
Ovation Series
Dispensers
Installation & Operation
November 2008 Part No. 920559 Rev H
November 2008 Part No. 920559 Rev H
Table of Contents
Title Page
1 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.1 Dispensers Covered . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 Local, State, and Federal Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.3 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.1 Inspect the Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.2 Island Construction, Dispenser Anchoring, and Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.3 Emergency Shut-off Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.4 Vapor Return Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.5 Lifting and Installing the Dispenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.6 Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.6.1 General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.6.2 Dispenser to Control System Wiring Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.6.3 Field Wiring for Dispensers Without a Junction Box. . . . . . . . . . . . . . . . . . . . . . . . 9
2.6.4 Full Service (Stand-Alone) Dispenser Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.6.5 Multiple Dispenser Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.6.6 Optional Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.6.7 Veeder-Root Vapor Flow Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.6.8 Non-Dispenser Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.7 Hose and Hose Retractor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.8 Bleeding Product Lines (Remote Dispensers). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.9 iMeter or Xflo™ Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.10 Balance Vapor Recovery System Installation Requirements . . . . . . . . . . . . . . . . . . . . . 16
2.10.1 Dynamic Back Pressure Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.10.2 Back Pressure System Check List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.10.3 Nozzles Approved for Balance System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.11 Wayne Vac Vapor Recovery System Installation Requirements . . . . . . . . . . . . . . . . . . 18
2.11.1 Dispenser Vacuum Decay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2.11.2 Wayne Pressure/Vacuum Tester . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3 START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.1 Initial Checkout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.2 IR Remote Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.3 Logical Nozzle/Hose Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.4 Setting the Clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3.5 Setting Unit Prices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3.6 Setting Blend Ratios . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
3.7 Setting Fueling Point ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
3.8 Authorizing the Dispenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
3.9 Initial Delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
3.10 Disable Stand-alone Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
November 2008 Part No. 920559 Rev H
iii
Table of Contents (continued)
Title Page
3.11 Totalizer Readings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
3.11.1 Totalizer Readings by Product Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
3.11.2 Totalizer Volume Readings by Meter Position . . . . . . . . . . . . . . . . . . . . . . . . . . 30
3.11.3 Electro-Mechanical Totalizer Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
3.12 Nozzle Boot Switch Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3.13 Annunciator Check. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
3.14 QCAT Dispensers Self-test and CAT Address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3.15 iX™ Pay Secure Payment Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3.16 Wayne Vac Motor Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3.17 Audit Report Display Mode (For Weights & Measures Officials/Service Purposes Only) 33
3.18 IDPOS Dispensers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
3.19 iX™ CAT Dispensers Self-test and CAT Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
3.20 Bill Acceptor (BAC) Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
4 OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
4.1 Safety Items You Should Know . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
4.1.1 Portable Tanks and Containers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
4.1.2 Health Note . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
4.2 How To Get Service On Your Dispenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
4.3 Basic Dispenser Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
4.4 Operating the Dispenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
4.5 Restarting After Power Failure or Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
4.6 Cycling Power to Clear Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
4.7 Error Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
4.8 Resetting After All Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
4.9 Stand-alone Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
4.10 Printer Paper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
4.10.1 Changing Paper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
4.10.2 Paper Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
4.10 Hazardous Zone Area Classifications for Dispensers . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
5 OPERATOR MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
5.1 Preventive Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
5.2 Filter/Strainer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
5.3 Dispenser Cleaning Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
5.4 Vapor Recovery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
5.4.1 Wayne Vac . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
5.4.2 Balance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
5.5 Meter Maintenance Issue . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
APPENDIX A1 QCAT SELF-TEST PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
APPENDIX A2 iX CAT SELF-TEST PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
APPENDIX B INSTALLATION DRAWINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
APPENDIX C LOCAL AUTHORIZE/STAND-ALONE OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . 73
APPENDIX D DISPENSER / BACKROOM INTERCONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . 75
iv
Part No. 920559 Rev H November 2008
1 INTRODUCTION
This revision of the manual includes new installation footprint drawings. These drawings show the location of the conduits for entering the new smaller junction box. The smaller junction box will be standard on pro­duction Ovation dispensers in November 2008. This junction box gives the installation personnel more room to make inlet and conduit connections, and it also allows for bottom entry of conduits coming up out­side of the containment box.
1.1 Dispensers Covered
Ovation series dispenser models use the iGEM computer and, either the iMeter assembly with the Wayne Intelligent Pulser (WIP), or the new Xflo meter assembly have the letter X in the model number after the second / in the number, for example, B23/4220D1/JKX/L. There is no difference in the installation and startup of these dispensers, with the only exception being a one inch change in the location of the field conduit on those models that do not have a junction box. On those models, the primary conduit location is moved from 1.37 to 2.37 inches off the cen­ter line towards the front of the dispenser. Components in a typical Xflo dispenser are shown in Figure 1-1.
E85 Ovation models have the letter E at the very beginning of the model number and use the Xflo meter assembly. In addition to the noted change above for Xflo models, internal parts such as the Xflo meter, prod­uct tubes, and outlet castings, as well as external parts, such as pipes, pipe nipples, hoses, nozzles, break­aways and swivels that come into contact with the Ethanol fuel must be Ethanol compatible; they must be either nickel-plated or stainless steel. Pipe nipples at the meter inlets need to be made of stainless steel. Replacement filters should be 1 micron. The recommended filter for Wayne Ethanol dispensers is Cim-Tek's Bio-Tek, 1 Micron filter. Standard gasoline dispensers commonly use filters rated at 10 microns.
meter assembly with the XWIP. Models with the new Xflo
The iGEM computer runs on software that can be downloaded by a laptop. Dispenser models with the Xflo meter and XWIP use iGEM rev 46 or later pump software; servTerm version 5.4.2 or later is required for servicing (loading the computer software or dispenser configuration template), however, this is not required for installation/startup of the dispenser. If it becomes necessary to reload pump software, always use the lat­est version. Note: The XWIP case is blue and the iMeter WIP case is black; they are not interchangeable.
Computer function settings that are necessary for Ovation dispenser startup and operation, such as prices, blending ratios, fueling point number, etc., are included in this manual. If additional information on function settings and statistics is required, refer to the Ovation Dispenser Service manual, part number 920525-002.
Any questions concerning installation and operation of the dispenser that are not covered in this manual should be referred to Wayne Technical Support (1-800-926-3737).
XWIP Pulser
Xflo Meter Dome
Check Valves underneath Cover Plates
Proportional Valve and Coil
Figure 1-1 Location of Components in Lower Section. MGD, three Xflo Meters, side 2.
November 2008 Part No. 920559 Rev H
Filter
Product Inlet
1
1.2 Local, State, and Federal Codes
All tanks (both underground and above ground), piping and fittings, foot valves, leak detectors, cor­rosion protection devices, wiring, venting systems, etc., must be installed in accordance with the manufacturer’s instructions and in compliance with local and regional building codes and require­ments pertaining to service stations (or other locations where the dispenser may be installed).
These requirements may include references to the National Electrical Code (NFPA 70), Automotive and Marine Service Station Code (NFPA 30A); Flammable and Combustible Liquids Code (NFPA
30); Code of Federal Regulations, Title 40, Section 280 (40 CFR 280); United States Environmental Protection Agency (U.S. EPA) Technical Regulations of 9-23-88 and U.S. EPA Financial Responsibil­ity Regulations of 10-26-1988.
Where local requirements do not specify applicable codes, Wayne recommends using the codes listed above. These codes are comprehensive and detailed, often requiring interpretation to cover unusual situations, and, therefore, the associated handbooks (where applicable) should also be con­sulted. (The handbooks are also available from the same sources.)
Due to the variety of locations encountered, further information on installation cannot be dealt with in this document except as the codes relate directly to the installation of the dispenser. Therefore, it is strongly recommended that a qualified engineer or contractor familiar with local regulations
and practices be consulted before starting installation.
Sources for various codes are listed on the following page.
2
Part No. 920559 Rev H November 2008
Pertinent information and codes are available from the following sources:
Association for Composite Tanks (ACT)
North State Street Suite 720 Chicago, IL 60602 (301) 355-1307 (for information requests)
Fiberglass Petroleum Tank and Pipe Institute
One SeaGate, Suite 1001 Toledo, OH 43604 (419) 247-5412
National Fire Protection Association (NFPA)
One Batterymarch Park Quincy, MA 02269-9101 (617) 770-3000
Petroleum Equipment Institute (PEI)
Box 2380 Tulsa, OK 74101 (918) 494-9696
Underwriters Laboratories Inc.
333 Pfingsten Road Northbrook, IL 60062 (312) 272-8800
United States Environmental Protection Agency
Office of Underground Storage Tanks 401 M St., SW (05-400WF) Washington, DC 20640 (703) 308-8850 (Underground Storage Tanks)
American Petroleum Institute (API)
1220 L Street, N.W. Washington, DC 20005 (202) 682-8000
National Assoc. Corrosion Engineers
(NACE) Box 218340 Houston, TX 77218 (713) 492-0535
National Leak Prevention Association
(NLPA) 685 Fields Ertel Road Cincinnati, OH 45241 (513) 489-9844 or 1-(800) 543-1838
Steel Tank Institute
P. O. Box 4020 Northbrook, IL 60065 (312) 498-1980
Underwriters Laboratories of Canada
7 Crouse Road Scarsborough, Ontario, Canada N1R3A9 (416) 757-3611
Western Fire Chiefs Association
5360 South Workman Mill Road Whittier, CA 90601 (213) 699-0541
U. S. Department of Labor,
Occupational Safety and Health Administration (OSHA) Washington, DC 20402
Call OSHA at (202) 523-8148 to determine specific needs; OSHA rules are covered by Title 29 of the Code of Federal Regulations (29 CFR.)
Order OSHA publications from: Government Printing Office (GPO) Washington, DC 22304 (202) 783-3238
NOTE: Other regulatory codes may apply. Consult your local and regional code requirements to
determine which codes are applicable for your location.
November 2008 Part No. 920559 Rev H
3
1.3 SAFETY PRECAUTIONS
NFPA 30A states that:
“When maintenance to Class I dispensing devices becomes necessary and such maintenance may allow the accidental release or ignition of liquid, the following precautions shall be taken before such maintenance is begun:
Only persons knowledgeable in performing the required maintenance shall perform the work.
All electrical power to the dispensing device and pump serving the dispenser shall be shut off at the main electrical disconnect panel.
The emergency shut-off valve at the dispenser, if installed, shall be closed.
All vehicle traffic and unauthorized persons shall be prevented from coming within 20 ft.(6 m)
of the dispensing device.
WARNING
Electric shock hazard! More than one disconnect switch may be required to de-energize the dispenser for maintenance and servicing. Use a voltmeter to make sure ALL circuits in the dispenser are de-energized. Failure to do so may result in serious injury.
1
Lockout/Tagout requirements of the U. S. Dept. of Labor, Occupational Safety and Health Adminis­tration (OSHA) may also apply. Refer to Title 29, Part 1910 of the Code of Federal Regulations (29CFR1910), Control of Hazardous Energy Source (Lockout/Tagout).
NOTE: To prevent damage to components located in the hydraulic cabinet, dispenser doors should be
in place during rainy and/or icy weather conditions. Also, check the nozzle boot flipper for freedom of movement. If ice has formed on the flipper, it should be cleared to prevent unnecessary damage.
1. Reprinted with permission from NFPA 30A-90, Automotive and Marine Service Station Codes, Copyright ©1990, National Fire Protection Association, Quincy MA 02269. This reprinted material is not the complete and official position of the National Fire Protection Association on the referenced subject, which is repre­sented only by the standard in its entirety.
4
Part No. 920559 Rev H November 2008
2 INSTALLATION
2.1 Inspect the Equipment
Examine the shipment immediately upon arrival to make certain there has been no damage or loss in transit. Make sure that all the component parts, including keys and optional equipment (if any), are accounted for. Check and save the Packing Slip, Bill of Lading, Invoice, and all other documents included in the shipment. Damaged or lost equipment must be reported to the carrier. Any damage or loss that may occur in transit is not covered under the Wayne/Dresser Warranty.
2.2 Island Construction, Dispenser Anchoring, and Piping
Product lines must avoid the creation of vapor in the lines and deliver a minimum pressure of 25 psi at the dispenser inlet when all dispensers at the station dispensing the same product are operating.
A concrete foundation must be provided for the dispenser. Do not pour concrete around product lines or electrical conduit risers.
Anchor bolts must be installed in the island to allow the dispenser to be bolted down in accordance with NFPA requirements. The base of the dispenser contains six bolt hole slots (5/8 inch by 2 inch) for anchoring the dispenser to the island. Use of all anchoring locations is re-commended. Position the anchor bolts in accordance with the dimensions shown on the Installation Instruction drawing for the dispenser model. These drawings are located in Appendix B.
Vertical supply risers and electrical conduits must be located per the Installation Instruction for the appropriate model. Proper height must be maintained to avoid undue stress on the dispenser.
For E85 Ovation models, product piping, pipe nipples, etc., containing Ethanol fuel must be Ethanol compatible. See the information in Section 1.1 on page 1.
For convenience, a 6” high pedestal is available to install under the dispenser base at locations where there are no islands. The pedestal, shown in Figure 2-1, can be ordered separately. See the complete assembly drawing 888813 in Appendix B.
Figure 2-1 Pedestal. See Note under the shear valve drawing on the following page.
November 2008 Part No. 920559 Rev H
5
2.3 Emergency Shut-off (Shear) Valves
WARNING
For remote dispensers, a Listed1, rigidly anchored emergency shut-off valve must be installed, in accor­dance with the manufacturer’s instructions, in each supply line at the base of each dispenser. For a typi­cal emergency valve installation see Figure 2-2. Failure to install the proper emergency shut-off valve will present a hazardous condition that could result in serious injury.
Figure 2-2 Typical Emergency Valve Installation. The Emergency valve is designed to close the product line due
to shock or fire. The shear section, shown above, functions if the dispenser is knocked out of position. NOTE: The shear valve must always be at the ground plane. The pedestal shown on the previous page, is con­sidered an extension of the dispenser, not the island.
Note: Wayne does not supply the meter inlet pipe nipple or the union shown above.
2.4 Vapor Return Piping
NFPA 30A Section 4-3-72 states that a vapor return pipe inside the dispenser housing shall have a shear sec­tion or flexible connector so that the liquid emergency shut-off valve will function properly. Wayne’s vapor connections are secured to the chassis allowing for the use of a shear section.
Wayne dispensers provide 1" NPT pipe connections at the base of the dispenser for vapor return connections. (See the installation foot print for location in Appendix B.) A minimum 1" riser at each dispenser is con­nected to a minimum 2" return piping to the underground tank. If more than six (6) fueling points are con­nected, then underground piping must be a minimum of 3". All lines should be sloped at a minimum of 1/8” per foot (1/4” per foot preferred) from the dispenser to the tank to avoid liquid traps. Note: There is no vapor recovery for the Ethanol product on E85 Ovation dispensers.
1. “Listed” means published on a list by a nationally recognized testing laboratory (NRTL) which is responsible for prod­uct evaluation and is acceptable to the authority having jurisdiction. Underwriters Laboratories, Inc. is one example of a Nationally Recognized Testing Laboratory. For more information on NRTL’s, see Title 29, Parts 1907 and 1910 of the Code of Federal Regulations, Safety Testing or Certification of Certain Workplace Equipment and Materials.
2. Reprinted with permission from NFPA 30A-90, Automotive and Marine Service Stations Codes, Copyright 1990, National Fire Protection Association, Quincy MA 02269. This material is not the complete and official position of the National Fire Protection Association on the referenced subject, which is represented only by the standard in its entirety.
6
Part No. 920559 Rev H November 2008
2.5 Lifting and Installing the Dispenser
Remove the shipping carton from the dispenser and, if the dispenser is equipped with an optional val­ance, survey the site to determine if it should be installed before or after the dispenser is set on the island. Wayne recommends installing the valance after the dispenser is installed, if practical, to protect it from installation damage. See the Valance Module drawing in the back of this manual.
Use door key (p/n 1-202022) to unlock and then remove the lower doors, see Figure 2-3 for location.
Install (2) eye-bolts in the dispenser top castings and lift the dispenser onto the island as per Lifting Instructions drawing 888514-001 in Appendix B. When handling Ovation dispensers, lift only as per the Lifting Instructions drawing contained in this manual. Do not lift by the electronic enclosure, nozzle boot, or any external panels.
Bolt the dispenser into place (Section 2.2), remove the shipping discs from the meter inlets and connect the product piping per the appropriate Installation Instruction drawing in Appendix B. When installing a blending dispenser, make sure the Lo and Hi product inlets (and, if applicable, the single product inlet) are correctly located.
To ensure tight, leak-proof connections when making piping connections, wash all cutting oils off the threads and use a UL-classified pipe joint sealing compound, rated for use with petroleum-based prod­ucts.
WARNING
Explosive or flammable vapors may accumulate within the dispenser housing. All piping connec­tions in the final installation must be accurately fitted and all threaded joints tightly made up with a Listed gasoline-resistant pipe joint compound. Put the compound on male threads only, being careful not to get excess inside the pipe or fittings. Failure to perform the above will present a haz­ardous condition that could result in serious injury.
VGA Screen
Upper Door Locks
Lower Door Locks (2)
Option
Figure 2-3 DOOR LOCK LOCATIONS. One door key fits upper and lower door locks.
November 2008 Part No. 920559 Rev H
Optional VGA display screen shown.
7
2.6 Electrical Wiring
2.6.1 General
Wayne recommends employing a qualified electrician for all wiring. A hazardous liquid is being handled, so it is important to ensure that all wiring is in accordance with the National Electrical Code (NFPA 70) as well as all federal, state and local regulations. Note: U.L. requires that all electrical connections to the dispenser be made with threaded, rigid conduit and properly sealed conductors. Note: All dispensers and electrical connection boxes must be grounded per NFPA 70.
2.6.2 Dispenser to Wayne Control System Interconnection
Dispenser installation wiring diagrams are provided in Appendix B. The system interconnection wiring diagrams supplied are for reference purposes. Use these diagrams along with the wiring diagrams supplied with the control system for laying out the system wiring requirements for a new site or when making changes to an existing one.
Two da t a wires to the Data Distribution Cabinet are required for the Wayne control system console operation.
Two da t a wires to the Site Controller Cabinet are required for dispenser card processing CAT operation.
Two da t a wires to the Site Controller Cabinet are required for Wayne TRAC operation.
One ethernet cable (gas and oil resistant) is required for dispensers equipped with the IDPOS or iX CAT option
from the switch in the dispenser to the switch in the building, see Section 2.6.6, Figure 2-5 and Figure 2-6. A UL
AWM Ethernet cable, Category 5 or higher, rated at least 300 V, 60 degrees C with a gasoline and oil resistant
jacket may be used. The conduit in the dispenser must be potted at the end of the installation.
Optional equipment wires, see Section 2.6.6.
NOTE: When data wires are installed, only the two data wires from the Data Distribution Cabinet used for pump control
are to be terminated at the dispenser’s terminal strip. The additional data wires should not be physically connected to the data terminals on the dispenser’s terminal strip. Instead they should be properly terminated individually using wire nuts.
Figure 2-4 shows the location of dispenser components that may need to be accessed during installation. If the dispenser is not equipped with a junction box in the hydraulic cabinet, field wiring will terminate at the terminal strip inside the electronic enclosure as shown in Figure 2-5 and the conduit fittings shown will be potted in the field.
E-M TOTALIZERS
WIP PULSER
CHECK VALVES (under Valve Plates in iMeter Dome)
PROPORTIONAL
/
VALVE
VALVE COIL
JUNCTION BOX
PRODUCT INLET
FILETR/STRAINER CASTING
Figure 2-4 Location of Components in Lower Section (iMeter model shown). Side 1. See Appendix B for new footprint drawings with the smaller junction box (above) effective in November 2008.
8
Part No. 920559 Rev H November 2008
VAPOR RECOVERY
OUTLET
WARNING
Electric Shock Hazard! No connections (including neutral) may be shared between groups of dispensers. A separate Control Power Circuit Breaker must be provided for each group. Failure to do so may result in serious injury.
2.6.3 Field Wiring for Dispensers Without a Junction Box
All field wiring must enter the Electronic Head via potted conduit/conduit fittings. When a dispenser does not contain a junction box, the conduits must be potted in the field during dispenser installation. Note: This also applies to the secondary conduit containing the Ethernet cable and the intercom call button/ speaker wires even if the dispenser does have a junction box since these wires do not connect in the junction box.
1. Install (2) 3/4” field conduits from the UL approved seal-offs at the base of the dispenser to the conduit at the vapor barrier as identified in Figure 2-5. One conduit will contain, as applicable, the Ethernet cable and the intercom (call button and speaker) wires (low voltage - Class 2 circuits). The other conduit will contain the pump power, relay selects, valance lighting and data wires (Power - Class 1 circuits).
Potted conduit for Ethernet and Intercom Call Button/speaker wires only.
,
Note: With or without j-box, this conduit now goes directly to the seal offs under the dispenser to allow for a straight run of Ethernet cable
from building switch to dispenser switch.
Terminal Block used when junction box
is not installed.
MGD Wiring Shown.
Potted Fitting contains Pump Power, Data, Relay Selects, Valance lighting
Note: Main potted fitting contains intercom speaker wires (Brown pair)
These must run in separate underground
conduit along with the call button wires.
See optional equipment section.
Figure 2-5 Terminal Block Inside Electronic Enclosure. Field wiring connects to this terminal block when the junction box shown in Figure 2-4 is not installed.
2. Clean conduit threads before connecting.
3. Pull continuous uninterrupted lengths of wires from the station electrical panels and control boxes to the dispenser electronic head. Allow an extra 18” lengths past the vapor barrier fitting for terminating, separating, potting and connecting to the terminal block. If installing iX CAT or IDPOS dispensers, allow an extra 3 ft. of Ethernet cable past the top of the conduit in the vapor barrier.
4. From each conduit, separate the wires using 3-201623 Wire Separator Gasket. See Photo 1.
5. Roll separator gasket and wires into a cylinder and secure with electrical tape. Photo 2 and Photo 3.
6. Pull separator gasket and wires back through the conduit fitting (Photo 4) forming a dam in the conduit, with the top of the separator down in the conduit past the dimple in the conduit.
November 2008 Part No. 920559 Rev H
9
2.6 Electrical Wiring, continued
7. Trim wires to appropriate length, terminate ends and connect to the terminal block as per Wiring Diagram drawing 888445-001 located in the Appendix B of this manual. Note: Field wires are to be connected to the lower terminals on the block.
8. Prepare the potting compound by pouring 4 oz. Rockite into an eight oz. paper cup.
9. Add 1-1/2 oz. of water.
10. Stir one to two minutes until reaching a consistency similar to pancake batter.
11. Pour mix into fitting and fill to within 1/8” of top of fitting (or top of conduit if the Ethernet conduit).
12. Close the service door.
13. Let fitting set for 12 hours. The wires must not be moved during this time.
Photo 1. Photo 2.
Photo 3. Photo 4.
10
Part No. 920559 Rev H November 2008
2.6.4 Full Service (Stand-Alone) Dispenser Wiring
For full service operation, make electrical connections as shown on the Installation Wiring Diagram in Appendix B. The electrical connections illustrated are typical when additional like model dispensers are used.
Data wires shown on the wiring diagram are for connecting the dispenser to the Data Distribution Cabi­net and the Site Controller Cabinet in a Wayne Control System. These data wires are not required for the full service (stand-alone) dispenser. However, the six optional data wires and cable, whichever are applicable, as described in Section 2.6.2, should be run at initial installation if a control system or optional equipment is being installed or may be installed in the future.
Remote dispensers require a relay to control the submersible pump motor. These relays are available as an option with the Wayne control system. If the dispenser is not connected to a Wayne control system, a UL Listed magnetic motor controller assembly, constructed with Potter and Brumfield Relay No. PRD7AYO (120) or equivalent, shall be used.
A maximum of 12 dispensers (24 fueling points) may be connected to a single PRD7AYO (120) relay; other relays may have different limitations. All dispensers operating the same pump control relay must be connected to the same circuit breaker; this may require multiple control relays for a submersible pump.
Ensure that the submersible pump receives its power from its own separate circuit breaker as illustrated in the Typical Site Wiring Diagram in Appendix B.
2.6.5 Multiple Dispenser Wiring
A primary requirement in dispenser installation wiring is to provide a means for disconnecting all power connections, including the neutral, to the dispensers for safe shutdown and servicing of the units. Each dispenser could be provided with a separate control Power Circuit Breaker. If this is not desirable or practical, several dispensers can be grouped together and tied to the same Control Power Circuit Breaker as illustrated in the Typical Site Wiring Diagram in Appendix B. A group of dispensers would then con­sist of all the dispensers and associated Submersible Pump Control Relay coils supplied by the same Control Power Circuit Breaker.
When more than one dispenser within the group activates the same submersible pump, the Relay Select lines may be commoned at the Submersible Pump Control Relay Coil terminal up to a maximum of 12 connections (24 fueling points). Where more than 12 connections activate the same submersible pump, additional relays should be used and the contacts paralleled as illustrated in the Typical Site Wiring Diagram.
In larger installations, dispensers can be separated into multiple groups.
November 2008 Part No. 920559 Rev H
11
2.6.6 Optional Equipment
Dispensers contain an extra pair of data wires in the junction box for Wayne TRAC as shown in Figure 2-6 below. These wires are also identified in the installation wiring diagram in Appendix B.
Dispensers with the letter I in the model number will have an intercom call button. Brown wires are speaker connections. Yellow wires are call button connections see Figure 2-6. Both circuits are low voltage NEC Class 2 only.
Dispensers with a 3 or 6 in the main body of the model number indicates the dispensers are equipped with iX CAT board option, VGA or QVGA, respectively. And, dispensers with the letter “L” in the 1st suffix of the model number indicates iX Secure Keypad. All of these dispensers will require an unin-
terrupted run of Ethernet cable from the switch in the building to the switch in the dispenser elec­tronic head. These dispensers will need a secondary underground conduit for this cable and other NEC Class 2 wiring as shown below. From the factory, these dispensers will contain a short section of conduit that can be used for making the connection to the secondary conduit seal off under the dispenser.
NOTE: The field Ethernet cable and Intercom (Call Button and Speaker) wires (NEC Class 2) must be
installed via a separate underground conduit to the dispenser. The intercom/speaker and call button wires should be terminated with wire nuts in the electronics head.
Call Button
Ethernet Cable for
iX CAT or
(NEC Class 2) Underground Conduit
for Ethernet cable and Intercom (call button and speaker) wires only.
Note: This conduit now goes directly to the seal offs under the dispenser to allow for a straight run of Ethernet cable from building switch to dispenser switch.
IDPOS option
Secondary Conduit in Electronic Head
Y
••
Y
Speaker
Junction Box
Electronic Head
Terminal Strip
BN pair
BU
OR
_
+
(NEC Class 1) Underground Conduit for Pump Power,
and Data, Valance lighting and relay select wires.
Speaker
Main Conduit in Electronic Head
Data Wires for
Wayne TRA C
option
Wire Nut (typical)
Figure 2-6 Ethernet, Intercom Call Button and Speaker Wiring. Ethernet and Intercom (Call Button and Speaker) wiring must run in a separate underground conduit to the dispenser.
2.6.7 Veeder-Root Vapor Flow Meter
Refer to the installation procedures in the Veeder-Root Manual No. 577013-796 Rev E (page 6, instruc­tion steps 11 and 12) supplied with dispensers equipped with the Veeder-Root option.
2.6.8 Non-Dispenser Equipment
Do not run wiring for any non-dispenser equipment, in the same conduit as the dispenser wiring; this wiring must be run in a separate conduit.
12
Part No. 920559 Rev H November 2008
2.7 Hose and Hose Retractor
Hose assemblies should be U.L. Listed and installed in accordance with the manufacturer’s instructions. To ensure a proper joint, wash all cutting oil off the threads and use a U.L. classified gasoline-resistant pipe joint sealing compound. Place the compound on male threads only; be careful not to get any excess compound inside fittings. Install the fixed end of the hose to the dispenser outlet; secure according to the instructions of the sealing compound and hose manufacturers. Install the swivel end of the hose or other swivels to the noz­zle according to the manufacturer’s instructions.
Exception: Do not use the sealant on balanced or inverted hoses used with vapor recovery.
NFPA code requires a Listed emergency breakaway device, designed to retain liquid on both sides of the breakaway point, must be installed on each hose dispensing Class I liquids; these devices must be installed and maintained per the manufacturer’s instructions. Refer to your state and local codes for breakaway device requirements that apply to your installation.
On E85 Ovation dispensers, all hoses, nozzles, breakaways, etc., containing the Ethanol fuel must be Ethanol compatible. See the information in Section 1.1 on page 1.
On Wayne vapor recovery dispensers all hoses, nozzles, and breakaways, etc., must be CARB certified.
Hose Retractor: Caution!: On dispensers equipped with the Hose Retractor option, the hose clamp must be mounted upstream of the breakaway device to avoid damage to the dispenser in the event of a drive-off.
The combined hose, breakaway, and whip maximum lengths are listed below.
Crossover Type 1 Hose per Side
Wayne Vac 14’ 0’’
Non-Vapor 3/4” 10’ 0’’ 10’ 0’’
Non-Vapor 5/8” 14’ 0’’ 14’ 0’’
WARNING
Use only Listed hoses and nozzles. Continuity must be present between the dispenser outlet and nozzle spout to prevent static discharge while fueling. Continuity must be checked for each outlet/hose assem­bly to insure that the nozzle is grounded. Failure to do so may result in a hazardous condition that could cause serious injury.
Loopback Type 1 Hose per Side
Loopback Type 2 Hose per Side
2.8 Bleeding Product Lines (Remote Dispensers)
NOTE: To avoid severe damage to the dispenser, all air and air pockets must be bled from the product trunk
lines before attempting to dispense product.
Step 1 Make sure the power to the appropriate submersible pump is OFF.
Step 2 To bleed air from a trunk line, remove the pipe plug from the safety impact valve on the dispenser
farthest from the storage tank. For pipe plug location see Figure 2-2 earlier in this section.
Step 3 Attach a flexible hose to the pipe plug opening in the safety impact valve. Energize the appropriate
submersible pump and allow the air to bleed out of the trunk line into a test can until product flows into the test can. De-energize the submersible pump and replace the pipe plug. Repeat the procedure for each product and each trunk line.
November 2008 Part No. 920559 Rev H
13
2.9 iMeter or Xflo™ Meter Calibration Procedure
Sufficient product must be run through each meter to thoroughly flush out all air and completely fill the system prior to the calibration process.
Each meter assembly contains two meters. The WIP pulser (or XWIP for Xflo meter) contains two sets of sen­sors, one set for each meter. On the front of the pulser, there are two calibration doors, one for each meter in the assembly. The door closest to the front of the dispenser controls calibration of the front meter and the other door controls calibration of the rear meter.
(only one meter at a time can be calibrated).
assure the correct door is opened during the calibration process.
Dispensers have an operation mode setting that establishes the pulser’s calibration mode. This is set at the fac­tory in the dispenser template (Read Only function F16). The imeter and the Xflow meter are calibrated using the same procedure as shown below.
Verification Accuracy:
1. Dispense some product into the test measure to wet the container and then drain the container thor­oughly, 10 seconds or more.
2. Dispense product into test measure until exactly 5 gallons (20 liters) are shown on dispenser display. See Note 1.
3. Compare reading on site glass of test measure to dispenser display. Volume in test measure should be within +/- 3 cu. in. (+/- 50 ml). See Note 2.
Only one door may be opened at one time during meter calibration
It is important to verify the product grade for each assembly to
4. If values are out of range, calibrate as described below.
Calibration:
1. Identify calibration door for meter in need of calibration.
2. Remove seal wire and pin to allow access to door.
3. Dispense some product into the test measure to wet the container and then drain the container thor­oughly, 10 seconds or more.
4. Open calibration door of meter to be calibrated. (Only one door can be opened at a time during the cali­bration process).
5. Dispense exactly 5 gallons (20 liters) into the test measure exactly to the “0” mark on the sight glass (read the bottom of the meniscus).
6. Close the calibration door. (This now redefines the calibration factor in the pulser).
7. Empty the test measure (drain completely, 10 seconds or more) and verify accuracy as described above.
8. Seal calibration door.
Note 1: In the Liter mode, in addition to 20 liters, a 10 liter or 5 liter test measure may be used if required by the application. However, you should check with your jurisdiction on Weights & Measures tolerance requirements.
Note 2: For the U.S. and Canada, acceptance tolerance of ±3 cu.in. for a 5 gallon measurement and ± 50 ml for a 20 liter measurement is only required for newly installed, newly placed in service devices for 30 days. After 30 days, the tolerance is increased to ±6 cu.in. for 5 gallons and ±100 ml for 20 liters.
14
Part No. 920559 Rev H November 2008
Dispenser Front (Side 1)
iMeter
(Side 2)
Meter A
Meter B
(Side 2)
Pulser Connector located inside of cover
XWIP Pulser (Blue Case)
Check Valve Covers
Xflo Meter
Meter B
Meter A
Dispenser Front (Side 1)
Figure 2-7 Meter Assemblies. The WIP and the XWIP are physically the same size, but have a different
Note:If for any reason the pulser is replaced, be sure the replacement pulser’s tabs snap
into place in the meter slots before tightening the two screws securing the pulser.
November 2008 Part No. 920559 Rev H
colored case because they are not functionally interchangeable.
15
2.10 Balance Vapor Recovery System Installation Requirements
2.10.1 Dynamic Back Pressure Testing
At initial installation, balance vapor recovery dispensers should have a dynamic back pressure test performed at each nozzle to ensure there are no blockages in the vapor recovery system.
The dispenser should be connected to the underground and the hanging hardware (hoses, nozzles, breakaways, etc.) should be installed.
The following test methods or equivalent methods can be used:
“ST-27 Gasoline Dispenser Facility Back Pressure.” Available from the California Bay Air Management District via the Internet at http://www.baaqmd.gov/mop/vol4/v4index.htm
“TP201.4” Determination of Dynamic Pressure Performance of Vapor Recovery Systems of Dispensing Facilities.” Available from the California Air Resources Board.
Maximum allowable dynamic back pressure for an individual dispenser nozzle using either test pro­cedure is listed below:
60 cu. ft. per hr. < 80 cu. ft. per hr. <
0.35 in. of water
0.62 in. of water
Note: Very low numbers for back pressure results may indicate a leak in the system and it should
be checked.
2.10.2 Back Pressure System Check List
Note: Check test equipment for up-to-date calibration stickers. Normal use of rotameters and pressure gauges necessitates yearly calibration; calibration is also required if this equipment has been dropped or mishandled.
1. Check test equipment for leaks prior to use. Pressurize with nitrogen supply (plug nozzle end of the fill pipe). Adjust nitrogen until 50% on pressure gauge is reached. Close off supply. A pres­sure decay must not be more than 0.2 in. of water in five minutes.
2. If facility has a vapor pod (condensate pot), drain prior to testing.
3. Open dry break poppets.
4. Completely drain hoses and nozzles prior to test. A pulsating needle indicates fluid in the lines. Re-drain if necessary.
5. The following information should be included on the field data sheet:
• Facility address and ID
• Pump number and grade ID
• Nozzle make and model
• Back pressure in inches of water
• Nitrogen flow rate
16
Part No. 920559 Rev H November 2008
2.10 Balance Vapor Recovery System Installation Requirements, continued
6. If back pressure readings are very low (less than .02 @ 20 CFH; 0.18 @ 60 CFH; 0.4 @ 100 CFH):
1. Check test fixture for tight seal at nozzle entry point.
2. Check bellows and face seal for tears.
3. Check vapor piping for leaks.
7. If back pressure readings are high:
1. Check hoses and nozzle bellows are completely drained.
2. Check dry break is open. (If only allowed to have one dry break open during the test, try all.)
3. Check vapor pod.
4. Check vapor impact valve to be open.
5. Check piping under dispenser. Should be a minimum of 1 inch diameter piping and fitting.
6. Check dispenser back pressure, disconnected from the underground and compare to dispenser base line data.
7. Check hanging hardware separate from dispenser and compare to balance hardware matrix base line data.
8. Check outlets, hose, and underground, for suspect blockage problems due to fitting bottomed out or casting flashing. Flashing is aluminum edges left over when the casting was made. This should be your last resort to diagnosing high back pressure readings since piping will have to be removed to look inside the casting for flashing. A large amount of flashing would be required to affect readings.
2.10.3 Nozzles Approved for Balance System
The Ovation nozzle boot hook can be adjusted to accommodate different nozzles. Table 2-1 shows the nozzles approved for use with a balance system and the hook position for each nozzle. Position 1 is the standard posi­tion. The hook is in position 1 in the accompanying photo. To change positions, remove the (4) screws shown, slide the hook down to the new position, and reinstall the (4) screws to secure the hook to the boot.
Table 2-1 Nozzle and Nozzle Hook Position
NOZZLE HOOK POSITION
Emco Wheaton A4005 3
Emco Wheaton A4015 1
OPW 11VF47 4
Husky V Model 5010 and 5020 3
Husky V(short) Model 5110 and 5210 1
1/4-20 Screws (4)
November 2008 Part No. 920559 Rev H
17
2.11 Wayne Vac Vapor Recovery System Installation Requirements
2.11.1 Dispenser Vacuum Decay
At initial installation, Wayne Vac vapor recovery dispensers should have a 27” decay test performed on each point to ensure there are no vapor leaks in the dispenser/hanging hardware - hose, nozzle, break­away, etc. This test is used to verify the dispenser/hanging hardware integrity so the vapor assist system will operate at its peak performance.
The test should be performed with the proper hanging hardware installed on the dispenser and the dis­penser disconnected from the underground piping.
Connect the test equipment to the discharge of the vapor piping in the dispenser and apply 27” of water vacuum to the vapor line. Then close off the vapor line and determine if the closed vapor system can maintain the 27” of water vacuum.
The system should hold the vacuum for one minute. If it does not, apply 10” of water pressure to the sys­tem, soaping all connections to find the leak. Use a light soap solution; a heavy soap solution could mask leaks. If the system piping is tight, check hanging hardware by bagging the nozzles and doing a vacuum test again, while looking for the bags to deflate. The Wayne vacuum tester, as discussed below, is also used to test nozzles for leaks.
2.11.2 Wayne Pressure/Vacuum Tester
The Wayne Pressure/Vacuum Tester, part number 1-921168-KIT, is available from Wayne to perform this test. The Operation manual, part number 920372 included in the kit, explains the various tests that can performed using both vacuum and pressure.
Additional information on these tests is contained in the Compliance Testing and Preventative Mainte­nance manual, part number 917947, supplied with each Wayne Vac equipped dispenser.
18
Part No. 920559 Rev H November 2008
3START-UP
3.1 Initial Checkout
Before applying power to the dispenser, double-check the wiring to make sure the wires are correctly routed and terminated. Turn on the dispenser control power circuit breaker and the submersible pump or suction pump motor circuit breakers. Make sure the dispenser comes on and all lights work. The dispenser displays will show some numbers, usually the last sale run during factory test.
The dispenser template, which configures the dispenser, has been loaded in the dispenser and tested at the fac­tory. The dispenser will have the necessary data such as unit prices and blend ratios to allow the dispenser to operate in stand-alone at installation to purge product lines and test operation. At start-up, the procedures in this section should be performed in sequential order to ensure proper operation before the dispenser is switched over to control system operation.
3.2 IR Remote Control
The Infrared Remote (IR) Control shown in Figure 3-1 is similar to a television remote control. It has 16 buttons and, when held close (12-18 inches) to the infrared eye located on the sales display board, is used to access dispenser functions and statistics. The IR remote, as discussed in the following sections, is used to set the clock, unit prices, fueling point IDs, blend ratios, and read electronic totalizers.
Figure 3-1 IR Remote Control. Hold remote close to the sales display to set the clock, unit prices, blend ratios and fueling point ID, read totals, view error codes and other dispenser diagnostic functions.
November 2008 Part No. 920559 Rev H
19
3.3 Logical Nozzle/Hose Positions
The physical number of hoses on one side of the dispenser is not the same as the number of electronic hose positions on that side. Unit prices and blend ratios are set in electronic hose position or logical nozzle order. B23/3, B23/4 and B23/5 model Blenders each have 2 hoses per side and 3 inlets, but either 3, 4 or 5 grade selects/logical nozzles as shown in Figures 3-2 A-C. Logical nozzles are assigned positions 1 through 7, depending on the dispenser model as shown in Table 3-1.
Three product MGD models have one hose per side and three logical nozzles, which are positions: 1, 2, and
3. For these non-blending models, such as the R13/3, these products are shown as the X, Y, Z products in Tab l e 3-1.
Logical nozzle positions for the Ovation models listed below are also shown in the examples in Figures 3-2 and 3-3 on the following pages.
Table 3-1 Hose (Logical Nozzle) Positions Defined by Values of N.
Ovation Model # begins with
B23/5 Two Hose (1+4)
B23/4 Two Hose (1+3)
B23/3 Two Hose (1+2)
B12/5 Single Hose 5 Grade
B12/4 Single Hose 4 Grade
B12/3 Single Hose 3 Grade
B12/2 Single Hose 2 Grade
R13/3 3 Grade
R22/2 2 Grade
Dispenser Description
Blender
Blender
Blender
Blender
Blender
Blender
Blender
Non-Blender
Non-Blender
N=7 N=6 N=5 N=4 N=3 N=2 N=1
Lo Feedstock
Lo Feedstock
Lo Feedstock
Lo Feedstock
Lo Feedstock
Lo Feedstock
Lo Feedstock
Lo-BL Mid-BL Hi-BL Hi
Lo-BL Hi-BL Hi
Lo-BL Hi-BL Hi
Feedstock
BL Hi
Feedstock
Hi Feedstock
Feedstock
Feedstock
BL Hi
Feedstock
Hi Feedstock
ZYX
Single Grade
Single Grade
Single Grade
Y X
R11/1 1 Grade
Non-Blender
Model number designations are defined as follows: B23/5 model, B = Blender, 2 = two hoses per side, 3 = three inlets, 5 = five grade selects. R13/3 model, R = Regular piped non-blender, 1 = one hose per side, 3 = three inlets, 3 = three grade selects.
20
Part No. 920559 Rev H November 2008
X
position
1
positions 6,5,4,3
positions 7,3
Model B23/5220D1 Model B12/2220D3
positions 7,6,5,4
position
1
positions 6,5,4
Model B23/4220D1 Model B12/4220D3
position
1
positions 6,4
positions 7,5,3
Model B23/3220D1 Model B12/3220D3
Figure 3-2 Blending Models.
21
November 2008 Part No. 920559 Rev H
Loading...
+ 61 hidden pages