Wayne 331301-001, RPPCAP50 User Manual

REMINDER: Keep your dated proof of purchase for warranty purposes! Attach it to this manual or file it for safekeeping.
Description
This sewage pump is suitable for pumping sewage, effluent, wastewater, groundwater and other nonexplosive, noncorrosive liquids with up to two inch solids. The RPP50 pump includes a wide angle float switch that turns the pump on and off as the fluid level rises and falls. The RPPCAP50 is provided with a “Switch Genius” capacitive water sensor. When water is detected, the pump will start automatically. These pumps are intended for use in domestic sewage lift stations.
Unpacking
Inspect this unit before it is used. Occasionally, products are damaged during shipment. If the pump or components are damaged, return the unit to the place of purchase for replacement. Failure to do so could result in serious injury or death.
Safety Guidelines
This manual contains information that is very important to know and understand. This information is provided for SAFETY and to PREVENT EQUIPMENT PROBLEMS. To help recognize this information, observe the following symbols.
Operating Instructions Models RPP50 and RPPCAP50
331301-001 12/07
Danger
indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
Warning
indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Caution
indicates a potentially hazardous situation which, if not avoided, MAY result in minor or moderate injury.
Notice
indicates important information, that if not
followed, may cause damage to equipment.
General Safety Information
CALIFORNIA PROPOSITION 65
This
product or its power cord may contain chemicals known to the State of California to cause cancer and birth defects or other reproductive harm. Wash hands after handling.
GENERAL SAGETY INFORMATION
1. Know the pump application, limitations, and po ten tial hazards.
Do not use to pump flammable or explosive fluids such as gasoline, fuel oil, kerosene, etc. Do not use in flammable and/or explosive atmospheres. Use pump only with liquids compatible with pump component materials. Failure to follow this warning can result in personal injury and/or property damage.
2. Make certain that the power source (electric motor) conforms to the requirements of the equipment.
Disconnect power before servicing. If the power dis ­con nect is out of sight, lock in the open po si tion and tag it to prevent unexpected application of power. Failure to do so could result in fatal electrical shock!
3. Release all pressure within the system before ser vic ing any component.
4. Drain all liquids from the system before servicing.
This
pump contains dielectric motor oil for motor heat transfer. Care should be taken when disposing of this oil. Do not use this pump in ponds or fountains because the motor oil can be harmful to aquatic life.
5. Secure the discharge line before
starting the pump. An unsecured discharge line will whip, possibly
© 2007 Wayne Water Systems
Specifications RPP50 RPPCAP50
Power supply requirements 120V, 60 hz 120V, 60 hz Circuit requirements 15 amps (min) 15 amps (min) Motor duty Intermittent Intermittent Motor 120V, 1 Phase 120V, 1 Phase Horsepower 1/2 1/2 Motor full load 6.3 amps 6.3 amps Liquid temperature range 40°F to 120°F 40°F to 120°F Max. operating position 45ofrom vertical 45ofrom vertical Dimensions 14” x 12” 14” x 12” Intake 2” 2” Discharge 2” NPT female 2” NPT female Cut-in level (factory set) 16” 11” Cut-out level (factory set) 7.5” 7” Differential 8.5” 4” Switch 90owide angle “Switch Genius”
mechanical tether switch capacitive water sensor
Power cord 18 gauge 3 Conductor 18 gauge 3 Conductor
with plug with plug
Construction
Motor housing.......Cast iron
Volute ....................Cast iron
Impeller...................Glass reinforced PBT
Seal plate ...............Cast Iron
Shaft seal ...............Mechanical
GALLONS PER HOUR AT TOTAL
HEAD IN FEET
0 5 10 15
5700 4560 3240 900
Performance
1/2 HP Cast Iron Sewage Pump
For parts, product & service information
visit www.waynepumps.com
Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with instructions could result in personal injury and/or property damage! Retain instructions for future reference.
Where a
2-prong wall receptacle is encountered, it must be replaced with a properly grounded 3-prong re cep ta cle installed in accordance with the NEC and local codes and ordinances.
12. All wiring should be performed by a
qualified elec tri cian.
13. It is strongly recommended that this
unit is plugged into a Ground Fault Circuit Interrupter (GFCI). Con sult a local electrician for installation and availability.
The pump
motor is equipped with automatic resetting thermal protector and may restart unexpectedly. Protector tripping is an indication of motor overloading as a result of operating the pump at low heads (low discharge restriction), excessively high or low voltage, inadequate wiring, incorrect motor conditions, or a defective motor or pump.
14. This pump is designed to transfer
water in cycles. Using this pump in a continuous duty application by ma ­nip u lat ing the switch to stay on, will effect the per for mance and the life of the product.
15. Protect electrical cord from sharp
objects, hot sur fac es, oil, and chemicals. Avoid kinking the cord. Re place or repair damaged or worn cords im me di ate ly. Use wire of adequate size to minimize voltage drop at the motor.
causing personal injury and/or property damage.
6. Check hoses for weak and worn condition before each use, making certain that all connections are secure.
7. Periodically inspect the pump and system com po nents. Perform routine maintenance as required (See Maintenance Section).
8. Provide a means of pressure relief for pumps whose discharge line can be shut-off or obstructed.
9. Personal Safety:
a.Wear safety glasses at all times
when working with pumps.
b.Keep work area clean, uncluttered
and properly lighted; replace all unused tools and equipment.
c.Keep visitors a safe distance from the
work area. Make workshop child­proof with pad locks, master switch es, and by re mov ing starter keys.
10. When wiring an elec tri cal ly driven pump such as this, fol low all electrical and safety codes, as well as the most recent National Electrical Code (NEC) and the Oc cu pa tion al Safety and Health Act (OSHA).
Risk of electric shock! Never connect the green (or green and yellow) wire to a live terminal!
11. This equipment is only for use on 120 volt (single-phase) and is equipped with an ap proved 3-con ­duc tor cord and 3-prong, grounding­type plug as shown in Fig ure 1.
2
Operating Instructions
16. Do not handle a pump or pump motor with wet hands or when standing on a wet or damp surface, or in water.
17. Do not hang this product by the carry handle. Sewage pumps should be set firmly on their legs and supported by rigid piping. This eliminates twisting and damage during pump operation.
18. Do not use an extension cord.
Do not walk on wet area until all power has been turned off. If the shut-off box is in basement, call the electric company to shut-off service to the house, or call the local fire department for instructions. Remove pump and repair or replace. Failure to follow this warning can result in fatal electrical shock.
Installation
In any
Installation where property damage and/or personal injury might result from an inoperative or leaking pump due to power outages, discharge line blockage or any other reason, use a backup system(s).
1. Thread the discharge pipe or pipe
nipple into the dis charge connection.
2. If a check valve is used in a solids
handling system mount the check valve in a horizontal position or at a 45° angle with the valve pivot on top. In a vertical position, solids will tend to lodge on the valve flapper and can prevent it from opening.
3. Drill a 1/16" hole in the discharge
pipe ap prox i mate ly 1" to 2” above the pump discharge when a check valve is used. The hole prevents air locking of the pump at the initial start-up and if it should lose prime.
Grounding Blade
Figure 1
Main waste line to sewer or septic tank
Upper level drainage
Three prong grounded outlet equipped with a ground fault interruptor
2” Discharge pipe
Float switch
Sewage pump passes 2” dia. solids
Cleanout
Vent pipe
2” Gate Valve
Union
2”
Check
Valve
45
o
Elbow
Laundry tubs
Washer
Dryer
Floor drain
Washer drain
Lavatory
Toilet
Shower
Flange
Figure 2 - Typical Installation
www.waynepumps.com
General Safety Information (Continued)
4. A gate valve should be installed in the system after the check valve. This gate valve should be a full port valve which will pass 2" solids or as required by state and local codes. This gate valve permits removal of the pump and/or check valve for servicing.
5. A union should be installed between the check valve and the pump so the pump can be removed with least disturbance of the piping.
6. The RPP50 pump has a detachable tether switch with a piggyback plug (see Figure 3A). The length of the tether (distance of cord from float to clamp) should not be set shorter than 3-1/4 inches and should not be used in a basin smaller than 14 inches in diameter. If using a differential other than the factory setting, be sure when the pump shuts off at least 4” of fluid is left in the basin so the impeller remains submerged.
7. When any switch is used, rigid dis ­charge pipe is required. If the pump is allowed to move, the tether switch could be re strict ed by the basin wall, pre vent ing the pump from operating.
8. RPPCAP50 models are supplied with a “Switch Genius” capacitive water sensor. Orient the pump in the basin so that the “Switch Genius” water sensor is 180° away from the inlet.
3
Make certain the incoming water stream does not hit the “Switch Genius” surface (See Figure 3B).
Before
removing pump from basin for service, always disconnect electrical power to pump and control switch. For any work on pump or switch, ALWAYS unplug the power cord. Do not just turn off circuit break er or unscrew fuse.
Maintenance
Make
certain that the pump is unplugged before attempting to service or remove any component. This pump is assembled in the factory using special equipment; therefore only authorized service dealers or qualified electricians should attempt to repair this unit. Improper repair can cause an electrical shock hazard.
The pump
contains oil that may be under pressure because of heat. Let the pump cool for a minimum of two hours before servicing this unit.
1. Disassembly of the motor prior to
expiration of war ran ty will void the warranty. It might also cause internal leakage and damage to the unit. If repairs are required, return the pump to the dealer from whom it was pur ­chased or call 1-800-237-0987.
2. After the basin cover is removed
and necessary dis charge piping disconnected, lift pump from basin.
Check valve 45
o
Vent
Inlet
Gasket
1/2” Min.
Clearance
Basin
Figure 3A - Prefabricated Basins (RPP50)
3. Pump should be checked on a regular basis for proper op er a tion. If anything has changed since unit was new, the unit should be removed and replaced. Only qualified electricians or service peo ple should at tempt to repair this unit. Improper repair and/or assembly can cause an electrical shock hazard.
4. Place the pump in a suitable area where it can be cleaned thoroughly. Remove all scale and deposits on pump.
5. Submerge the complete pump in a disinfectant so lu tion (10% chlorine bleach solution) for at least one hour before handling the pump.
6. For the RPP50, clean all dirt and deposits from the pump float. Make sure float moves freely after cleaning. For the RPPCAP50 clean “Switch Genius” water sensor surface.
7. Clean all dirt and deposits away from pump inlet and volute.
This pump
contains dielectric motor oil for lubrication and motor heat transfer. This oil can be harmful to the environment. Check state environmental laws before disposing of this oil. This oil can be harmful to aquatic life so consideration should be exercised in the application of this pump.
www.waynepumps.com
Installation (Continued)
Check valve 45
o
Vent
Inlet
Gasket
Basin
Figure 3B - Prefabricated Basins (RPPCAP50)
Orient the pump so that the “Switch­Genius” is 180° away from the inlet. Make sure the incoming water stream does not hit the “Switch­Genius” surface.
Models RPP50 and RPPCAP50
www.waynepumps.com
4
Operating Instructions
Troubleshooting Chart - RPP50
Symptom Possible Cause(s) Corrective Action
Pump will not start or run
Pump starts and stops too often
Pump shuts off and turns on independently of switch (trips thermal overload protection)
Pump operates noisily or vibrates excessively
Pump will not shut off
Pump operates but delivers little or no water
1. Water level too low
2. Blown fuse or tripped circuit breaker
3. Low line voltage
4. Defective motor
5. Defective float switch
6. Impeller (pump filled with debris)
7. Tangled switch
8. Insufficient liquid level
1. Backflow of water from piping
2. Faulty float switch
3. Check valve not installed or leaking
4. Discharge head is less than manufacturer’s minimum
1. Excessive water temperature
2. Defective switch or entangled switch is causing pump to run dry
3. Low line voltage
1. Worn bearings
2. Debris in impeller cavity or broken
3. Piping attachments to building structure too rigid or too loose
1. Defective float switch
2. Float switch movement restricted
3. Restricted discharge (obstruction in piping)
4. Excessive inflow or pump not properly sized for application
1. Low line voltage
2. Debris caught in impeller or discharge
3. Worn or defective pump parts or plugged impeller
4. Pump not properly sized for application
5. Check valve stuck closed or installed backwards
6. Shut off valve closed
1. Pump switch will not turn on unless water covers top of pump
2. If blown, replace with proper sized fuse or reset breaker
3. If voltage is under recommended min i mum, check wiring size from the main switch on property. If OK, contact power company.
4. Return for service or replace motor
5. Replace float switch
6. If impeller will not turn, remove housing and remove debris
7. Arrange switch so the switch moves free ly. Re po si tion pump if necessary
8. Make sure liquid level is at least 13" from the basin floor
1. Install check valve
2. Replace float switch
3. Remove and examine check valve for prop er in stal la tion and free operation
4. Recheck all sizing calculations to determine proper pump size
1. Pump should not be used for water above 120°
2. Replace or reposition pump
Pump may start unexpectedly. Disconnect power supply before
ser vic ing
3. If voltage is under recommended min i mum, check wiring size from the main switch on property. If OK, contact power company
1. Replace pump
2. Remove housing, clean impeller and/or replace broken impeller
3. Replace portion of discharge pipe with flexible connector
1. Replace float switch
2. Reposition pump or clean basin as required to provide adequate clearance for float
3. Remove pump and clean pump & piping
4. Recheck all sizing calculation to determine proper pump size
1. If voltage is under rec om mend ed minimum, check wiring size from the main switch on prop er ty. If OK, contact power company
2. Remove, clean and check for tight ness
3. Replace entire pump. Clean parts if required
4. Recheck all sizing calculations to determine proper pump size
5. Remove and examine check valve for proper installation and free operation
6. Open valve
www.waynepumps.com
5
Troubleshooting Chart - RPPCAP50
Symptom Possible Cause(s) Corrective Action
Pump will not start or run
Pump starts and stops too often
Pump shuts off and turns on independently of switch (trips thermal overload protection)
Pump operates noisily or vibrates excessively
Pump will not shut off
Pump operates but delivers little or no water
1. Water level too low
2. Blown fuse or tripped circuit breaker
3. Low line voltage
4. Defective motor
5. Defective “Switch Genius
6. Impeller (pump filled with debris)
7. Insufficient liquid level
1. Backflow of water from piping
2. Dirty “Switch Genius” water sensor
3. Check valve not installed or leaking
4. Discharge head is less than manufacturer’s minimum
1. Excessive water temperature
2. Low line voltage
1. Worn bearings
2. Debris in impeller cavity or broken
3. Piping attachments to building structure too rigid or too loose
1. Defective “Switch Genius” switch
2. Restricted discharge (obstruction in piping)
3. Excessive inflow or pump not properly sized for application
1. Low line voltage
2. Debris caught in impeller or discharge
3. Worn or defective pump parts or plugged impeller
4. Pump running backwards
5. Pump not properly sized for application
6. Check valve stuck closed or installed backwards
7. Shut off valve closed
1. “Switch Genius” water sensor will not turn pump on unless water is within 1 inch of the top of the sensor.
2. If blown, replace with proper sized fuse or reset breaker
3. If voltage is under recommended min i mum, check wiring size from the main switch on property. If OK, contact power company.
4. Return for service or replace motor
5. Replace “Switch Genius
6. If impeller will not turn, remove housing and remove debris
7. Make sure liquid level is at least 11" from the basin floor
1. Install check valve
2. Reposition pump, clean sensor face.
3. Remove and examine check valve for prop er in stal la tion and free operation
4. Recheck all sizing calculations to determine proper pump size
1. Pump should not be used for water above 120°
Pump may start unexpectedly.
Disconnect power supply before
ser vic ing
2. If voltage is under recommended min i mum, check wiring size from the main switch on property. If OK, contact power company
1. Return for service or replace
2. Remove housing, clean impeller and/or replace broken impeller
3. Replace portion of discharge pipe with flexible connector
1. Replace “Switch Genius” switch
2. Remove pump and clean pump & piping
3. Recheck all sizing calculation to determine proper pump size
1. If voltage is under rec om mend ed minimum, check wiring size from the main switch on prop er ty. If OK, contact power company
2. Remove, clean and check for tight ness
3. Replace worn parts or entire pump. Clean parts if required
4. Check rotation. (CCW from bottom) Return if CW
5. Recheck all sizing calculations to determine proper pump size
6. Remove and examine check valve for proper installation and free operation
7. Open valve
Models RPP50 and RPPCAP50
6
Limited Warranty
For one (1) year on RPP50 and three (3) years on RPPCAP50, from the date of purchase, Wayne Water Systems ("Wayne") will repair or re place, at its option, for the original purchaser any part or parts of its Sump Pumps or Water Pumps (“Product”) found upon examination by Wayne to be defective in materials or work man ship. Please call Wayne (800-237-0987) for instructions or see your dealer. Be pre pared to provide the model number and the serial number when exercising this warranty. All transportation charges on Products or parts submitted for repair or replacement must be paid by purchaser.
This Limited Warranty does not cover Products which have been damaged as a result of accident, abuse, misuse, neglect, improper installation, improper maintenance, or failure to operate in accordance with Wayne’s written instructions.
THERE IS NO OTHER EXPRESS WARRANTY. IMPLIED WARRANTIES, IN CLUD ING THOSE OF MER CHANT ABIL I TY AND FITNESS FOR A PARTICULAR PUR POSE, ARE LIMITED TO ONE YEAR ON RPP50 AND THREE (3) YEARS ON RPPCAP50, FROM THE DATE OF PURCHASE. THIS IS THE EXCLUSIVE REM E DY AND ANY LIABILITY FOR ANY AND ALL INDIRECT OR CONSEQUENTIAL DAM AG ES OR EXPENSES WHATSOEVER IS EXCLUDED.
Some states do not allow limitations on how long an implied warranty lasts, or do not allow the exclusions or limitations of incidental or consequential damages, so the above lim i ta tions might not apply to you. This limited war ran ty gives you specific legal rights, and you may also have other legal rights which vary from state to state.
In no event, whether as a result of breach of contract warranty, tort (in clud ing negligence) or otherwise, shall Wayne or its suppliers be liable for any special, consequential, incidental or penal damages including, but not limited to loss of profit or revenues, loss of use of the products or any associated equipment, damage to associated equip ment, cost of capital, cost of substitute products, facilities, services or replacement power, downtime costs, or claims of buyer’s cus ­tom ers for such damages.
You MUST retain your purchase receipt along with this form. In the event you need to exercise a warranty claim, you MUST send a copy of the purchase receipt along with the material or correspondence. Please call Wayne (800-237-0987) for return authorization and instructions.
DO NOT MAIL THIS FORM TO WAYNE. Use this form only to maintain your records. MODEL NO._______________ SERIAL NO.__________________________ INSTALLATION DATE_____________
ATTACH YOUR RECEIPT HERE
Operating Instructions
www.waynepumps.com