Cylink Corporation provides this Manual “as is,” without warranty of any kind, either express or implied,
including, but not limited to, the implied warranties of merchantability and fitness for a particular purpose.
Cylink Corporation may make improvements and changes to the product described in this Manual at any
time and without any notice. Cylink Corporation assumes no responsibility for its use, nor any infringements
of patents or other rights of third parties that would result.
This Manual could contain technical inaccuracies or typographical errors. Periodic changes are made to the
information contained herein; these changes will be incorporated in new editions of the Manual.
No part of this publication may be stored in a retrieval system, transmitted, or reproduced in any way,
including but not limited to photocopy, photograph, magnetic or other records, without the prior written
permission of Cylink Corporation.
CYLINK is a registered trademark of Cylink Corporation; AirLink is a trademark of Cylink Corporation.
PRODUCT COMPATIBILITY
While every effort has been made to verify operation of this product with many different communications
products and networks, Cylink Corporation makes no claim of compatibility between its products and other
vendors’ equipment. It is assumed that users have thoroughly evaluated this product’s performance in the
communications environment in which it will be used.
SAFETY
The following general safety precautions must be observed during all phases of operation and service of this
product. Failure to comply with these precautions or with specific warnings elsewhere in this Manual willfully
violates standards of design, manufacture, and intended use of the product. Cylink Corporation assumes no
liability for the customer’s failure to comply with these requirements.
This product must be grounded. In the event of a short circuit, grounding reduces the risk of electrical shock
by providing an escape wire for the current.
Do not install or operate this product in the presence of flammable gases or fumes. Operation of any
electrical instrument in such an environment constitutes a definite safety hazard.
No user maintained or adjustable components are present within this product. The covers should not be
removed by anyone other than authorized Cylink service personnel. The potential for electrical shock exists
within the enclosure at all times unless it is unplugged.
Do not install substitute parts or perform any unauthorized modification to the AirLink Pro T1or E1. Return
the product to Cylink Corporation for service and repair to ensure that safety features are maintained. Prior
to returning any product(s) for repair, contact Cylink at the telephone numbers or address located on the
front of this Manual, and obtain a Return Material Authorization (RMA) number.
Changes or modifications not expressly approved by Cylink Corporation can void the user’s authority to
operate the equipment.
LITHIUM BATTERY
The digital module in the AirLink Pro T1/E1 Rack Mount contains a lithium battery molded into the real-time
clock component. The lithium battery is NOT a customer-replaceable part. The lithium battery could explode
if mistreated. Do not attempt to expose the battery by opening the real-time clock component. Do not
attempt to recharge the battery. Do not dispose of the component by fire.
SYSTEM GROUNDING
Direct grounding of the antenna, mast, and tower serves as protection from lightning strikes and static
buildup. A direct electrical connection should be made to a suitable grounding rod at the base of the tower or
mast using at least #10 AWG ground wire, or its equivalent, and non corrosive hardware. For details and
safety standards, consult the appropriate local Electrical Codes or a similar document. Use lightning
arresters in appropriate places.
TOWER CONSTRUCTION
Compliance with local zoning and tower construction regulations is recommended when AirLink Pro T1/E1
Rack Mount systems require a tower. These regulations generally mandate that permits be obtained before
any tower construction begins. Check with local zoning and aviation authorities for more information.
FCC NOTICE TO USERS
The Airlink Pro T1 complies with Part 15 of the FCC rules. Operation is subject to the condition that this
device does not cause harmful interference.
Federal Communications Commission (FCC) Rules on spread spectrum devices, such as the AirLink Pro T1
or E1, require that you be notified of the following:
FCC regulations require that this device be professionally installed by a person knowledgeable in electronics
and trained in the correct installation of this device.
All interface cables must be shielded.
Operation of this device is subject to the following two conditions:
(1) This device may not cause harmful interference.
(2) This device must accept any interference that may cause undesired operation.
Changes or modifications not expressly approved by Cylink Corporation can void the user’s authority to
operate the equipment.
STATEMENT OF WARRANTY
CYLINK products, except as stated otherwise in an applicable price list, are warranted against defects in
workmanship and material for a period of one (1) year from date of delivery as evidenced by CYLINK’s
packing slip or other transportation receipt.
CYLINK’s sole responsibility under this warranty shall be to either repair or replace, at its option, any
component which fails during the applicable warranty period because of a defect in workmanship and
material, provided PURCHASER has promptly reported same to CYLINK in writing. All replaced Products or
parts shall become Cylink’s property.
CYLINK shall honor the warranty at CYLINK’s repair facility in Sunnyvale, California. It is PURCHASER’s
responsibility to return, at its expense, the allegedly defective Product to CYLINK. PURCHASER must
obtain a Return Materials Authorization (RMA) number and shipping instructions from CYLINK prior to
returning any Product under warranty. Transportation charges for the return of the Product to PURCHASER
shall be paid by CYLINK within the United States. For all other locations, the warranty excludes all costs of
shipping, customs clearance and other related charges. If CYLINK determines that the Product is not
defective within the terms of the warranty, PURCHASER shall pay CYLINK all costs of handling,
transportation and repairs at the then prevailing repair rates.
All the above warranties are contingent upon proper use of the Product. These warranties will not apply (i) if
adjustment, repair or parts replacement is required because of accident, unusual physical, electrical or
electromagnetic stress, negligence of PURCHASER, misuse, failure of electric power environmental
controls, transportation, not maintained in accordance with CYLINK specifications, or abuses other than
ordinary use (ii) if the Product has been modified by PURCHASER or has been repaired or altered outside
CYLINK’s factory, unless CYLINK specifically authorizes such repairs or alterations; (iii) where CYLINK
serial numbers, warranty data or quality assurance decals have been removed or altered.
CYLINK also reserves the right to make product improvements without incurring any obligation or liability to
make the same changes in Products previously manufactured or purchased. In no event shall CYLINK be
liable for any breach of warranty in an amount exceeding the net selling price of any defective Product. No
person, including any dealer, agent or representative of CYLINK is authorized to assume for CYLINK any
other liability on its behalf except as set forth herein. Nonpayment of any invoice rendered within the stated
payment terms automatically cancels any warranty or guarantee stated or implied. If any payment is due
CYLINK for services performed hereunder, it shall be subject to the same payment terms as the original
purchase.
CYLINK HEREBY DISCLAIMS ALL IMPLIED WARRANTIES ON PRODUCTS INCLUDING WITHOUT
LIMITATION, ALL IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR
PURPOSE. The warranties expressly stated herein are the sole obligation or liability on the part of CYLINK
arising out of or in connection with the sale or performance of the products.
Products Manufactured by Others - For products not manufactured by CYLINK the original manufacturer’s
warranty shall be assigned to PURCHASER to the extent permitted and is in lieu of any other warranty,
express or implied. For warranty information on a specific product, a written request should be made to
CYLINK.
IN NO EVENT WILL CYLINK BE LIABLE TO PURCHASER FOR (i) REPROCUREMENT COSTS; (ii) SPECIAL,
INDIRECT OR CONSEQUENTIAL DAMAGES; (iii) ANY DAMAGES WHATSOEVER RESULTING FROM LOSS
OF USE, DATA OR PROFITS ARISING OUT OF OR IN CONNECTION WITH THIS AGREEMENT, OR THE
USE OF PERFORMANCE OF CYLINK PRODUCTS, REGARDLESS OF WHETHER THE CAUSE OF ACTION
IS IN CONTRACT, TORT, INCLUDING NEGLIGENCE, OR ANY OTHER FORM.
No action, whether in contract or tort, including negligence, arising out of or in connection with this
Agreement, may be brought by either party more than eighteen (18) months after the cause of action has
accrued, except that an action for nonpayment may be brought within eighteen (18) months of the date of
last payment.
Figure 4-5 AirLink Pro T1/E1 Rack Mount QRSS Test.......................4-14
Figure 4-6 AirLink Pro T1/E1 Rack Mount Loopback Tests................4-16
Rev. B - 1/97
ix
Figure 4-7 AirLink Pro T1/E1 Rack Mount in Normal Operation ......4-17
Figure 4-8 AirLink Pro T1/E1 Rack Mount in
Local Loop Test, Near End..............................................4-18
Figure 4-9 AirLink Pro T1/E1 Rack Mount in
Remote Loop Test, Near End...........................................4-19
Figure 4-10 AirLink Pro T1/E1 Rack Mount in
Local Loop Test, Far End................................................4-20
Figure 4-11AirLink Pro T1/E1 Rack Mount in
Remote Loop Test, Far End..............................................4-20
Figure B-1 Terminal Cable: AirLink Pro T1 Terminal Port
to a DB-25 Terminal Port................................................B-16
Figure B-2 Modem Cable: AirLink Pro T1 Terminal Port
to a DB-25 Modem Port...................................................B-16
Figure B-3 Terminal Cable: AirLink Pro T1 Terminal Port
to a DB-9 Terminal Port..................................................B-17
Figure B-4 Modem Cable: AirLink Pro T1 Terminal Port
to a DB-9 Modem Port....................................................B-17
x
Rev. B - 1/97
P
REFACE
REFACE
P
About This Guide
About This Guide
The AirLink Pro T1/E1 Rack Mount Installer’s Guide covers the
information needed to unpack, install, configure, and operate the
AirLink Pro T1 or the Airlink Pro E1 system. Begin by reading this
preface for more information about how this guide supports your use
of the AirLink Pro T1/E1 Rack Mount system.
Inside this chapter:
Who Should Read This Manual...............................................xiii
Customer Support ............................................................... xvii
Reader Response ................................................................. xviii
Rev. B - 1/97 xi
AirLink Pro T1/E1 Rack Mount Installer’s Guide
About This Guide
Who Should Read This Manual
This is an installation guide for persons who must perform or coordinate the
tasks associated with unpacking and installing the AirLink Pro T1/E1 Rack
Mount.
Prerequisite Knowledge
Throughout this guide are explanations and procedures that presume working
familiarity with basic telephone trunking and transmission concepts and
practices, as well as basic digital data communications concepts and practices.
If you are not familiar with the concepts and practices involved in these
disciplines, we recommend that you familiarize yourself with them before
proceeding.
Also, this guide does not attempt to provide any detailed system planning or
installation information on radio frequency (RF) antenna assemblies or Path
analysis . For details about these topics, please refer to the Airlink Applicationsand Site Planning Guide.
Guide Organization
Each of the chapters and appendices in this guide begins by introducing the
contents of that chapter or appendix. Before beginning the installation process,
you should read the introductions to all of the guide portions so that you have a
sense of what each portion provides.
When you come to a procedure, you should skim through the entire procedure
before you begin performing the step-by-step instructions. By doing this, you
will know what is coming, and will be prepared with the appropriate
information, equipment, or tools.
The information in this guide is organized according to the sequence of tasks
necessary to plan for unpacking, installing, and configuring, as well as operating
and maintaining the AirLink Pro T1/E1 Rack Mount system.
NOTEThe Airlink Pro T1 and the Airlink Pro E1 are similar radio units. The installation, system
administration, and the operational procedures for the two units have therefore been
combined into this manual. The minor differences between the two units are indicated
wherever necessary.
xii
Rev. B - 1/97
The guide is divided into the following sections:
Guide SectionDescription
AirLink Pro T1/E1 Rack Mount Installer’s Guide
About This Manual
Chapter 1:
Product Description
Chapter 2:
Installation and
SystemAdministration
Chapter 3:
Configuring the AirLink Pro
T1/E1 Rack Mount
Chapter 4:
Operations and Maintenance
Appendix A:
Messages
Appendix B:
Specifications
Appendix C:
Commands
Appendix D:
Glossary
IndexProvides a quick reference to assist you in locating
Describes the features and capabilities of the AirLink
Pro T1/E1 system.
Outlines the procedures for unpacking and installing the
AirLink Pro T1/E1 Rack Mount system hardware,
connecting the antenna, and performing initial operation
checks.
Provides instructions for configuring the AirLink Pro
T1/E1.
Contains information on the operation and maintenance
of the AirLink Pro T1/E1 system.
Lists the system alarm, status, and error messages.
Contains a quick reference to the AirLink Pro T1/E1
Rack Mount system specifications.
Provides a list of frequently used commands.
Provides definitions for the terms commonly used
throughout this guide.
important topics in the guide.
Guide Conventions
The procedures and instructions in this guide use the following conventions:
❚Typography that highlights information within text, including screen
displays, figures, and tables.
❚Keyboard usage conventions.
❚Notes that add information, point to other important considerations, or
alert you to possible risks to yourself, your equipment, or your data.
Rev. B - 1/97
xiii
AirLink Pro T1/E1 Rack Mount Installer’s Guide
About This Guide
Typographic Conventions
❚Terminal displays are shown as text in the Courier font:
AIRLINK PRO T1> get configuration
Site Name: Sunnyvale 2
Application: 6. Slave unit in a point-to-point Link
Burst Mode: Normal
Coding: B8ZS
Equalization: 0 - 133 ft
PN Code: 1
RF Power: 10 dBm
Alarm Reporting: Immediate
Alarm Level: Status
Date/Time: May 1 1996 10:35:00
❚Bold Courier font indicates a command keyword or operand that you
are expected to type exactly as shown.
❚Italic Courier font indicates a command operand that you must
replace with a selected value when you type the command.
❚Named keys in text are shown enclosed in angle brackets. The notation
<Return> is used to indicate either the Return key or the Enter key.
Keyboard Usage
❚All command examples shown in text are executed by typing the command
and then pressing <Return>.
❚Two or more keys that must be pressed simultaneously are shown in text
linked with a plus (+) sign: <Ctrl>+C.
Notes, Cautions, and Warnings
NOTEThe standard text note highlights important or additional
CAUTIONThese notes warn you of situations that could result in damage
information for you to consider.
to your equipment or loss of data if you do not heed the
instructions.
xiv
Rev. B - 1/97
WARNINGThese notes warn you of situations that could endanger your
Customer Support
If after reading this guide you encounter any trouble installing or using the
AirLink Pro T1/E1 Rack Mount, please contact your local distributor. If
problems are not resolved, you can call Cylink’s Customer Service for assistance.
The telephone numbers are:
Domestic (USA)
1-800-545-6608Sunnyvale, CA
1-800-814-5587Jersey City, NJ
International
AirLink Pro T1/E1 Rack Mount Installer’s Guide
About This Manual
personal health if you do not heed the instructions.
1-408-735-5822Sunnyvale, CA
1-201-333-3400Jersey City, NJ
+65-297-6196Singapore
+44-1256-841919United Kingdom
+91-11-301-0090India
+92-21-215-7264Pakistan
Domestic and International Customer Service Fax
1-408-735-6641Sunnyvale, CA
1-201-333-8560Jersey City, NJ
+65-297-6195Singapore
+44-1256-24156United Kingdom
+91-11-379-3584India
+92-21-587-0065Pakistan
You can also contact Cylink’s Tech Support through the Internet at the
following address:
support@cylink.com
If you need to return equipment, call Customer Service to obtain a Return
Material Authorization (RMA) number prior to returning the equipment. The
RMA number must be placed on the outside of the shipping carton. Please be
prepared to provide the unit serial number, software version, and a detailed
description of the problem.
Rev. B - 1/97
xv
AirLink Pro T1/E1 Rack Mount Installer’s Guide
About This Guide
Return all equipment to:
Cylink Corporation
1350 Bordeaux Drive
Sunnyvale, CA 94089
Attn: Repair and Return Department
RMA No: xxxxxxxxxx
Reader Response
Cylink’s Technical Publications Department wants its documents to meet your
requirements. To this end, your ideas about the documentation are valuable.
After you have had a chance to read and use the guide, we encourage you to
submit your comments to
Manager, Technical Publications
Cylink Corporation
910 Hermosa Court
Sunnyvale, CA 94086
You may also submit your comments through the Internet at the following
address:
techpubs@cylink.com
Cylink may use or distribute any of the information you supply in any way it
believes appropriate without incurring any obligations whatsoever.
xvi
Rev. B - 1/97
C
HAPTER
HAPTER
C
Product Description
Product Description
This chapter introduces the AirLink Pro T1/E1 Rack Mount and
provides an overview of the features and capabilities.
1
1
Inside this chapter:
Introduction to the AirLink Pro
T1/E1 Rack Mount ...........................................................1-2
Features and Capabilities ...................................................1-3
Rev. B - 1/971-1
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Product Description
Introduction to the AirLink Pro
T1/E1 Rack Mount
The AirLink Pro T1 and the AirLink Pro E1 systems are spread-spectrum
transceivers that operate in the license-free 5.725 to 5.850 GHz (C-band)
Industrial Scientific Medical (ISM) band. The AirLink Pro T1/E1 Rack Mount
uses a Spread Spectrum modulation technique to create a high-quality, pointto-point radio link between itself and another AirLink Pro T1/E1 Rack Mount
located many miles away.
The AirLink Pro T1/E1 Rack Mount (Figure 1-1) unit is a rack mount unit that
mounts in a 19 or 23 inch equipment rack or cabinet. The design of the unit can be
aisle or flush mounted. Status and Alarm LEDs are duplicated on the unit’s
rear panel so that it can be flush mounted against a wall.
1-2
Figure 1-1
AirLink Pro T1/E1 Rack Mount - Full View
Rev. B - 1/97
Features and Capabilities
The AirLink Pro T1/E1 Rack Mount supports a range of sophisticated control
capabilities and options, including:
❚Remote control of far-end
❚Built-In Testing Equipment (BITE)
❚Flexible, interactive user interface through an ASCII terminal
❚Easily modified configuration parameters
❚Local and remote monitoring, diagnostic, and maintenance capabilities
❚Separate end-to-end communication channel for control and order wire
signals. Control signals and order wire voice signals do not disturb the T1
channel
❚Every radio-frequency (RF) burst verified by an error-checking algorithm
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Product Description
The AirLink Pro T1 and E1 are similar radio units with minor differences in
their internal structures. These are:
❚The AirLink Pro T1 and E1 have different internal clock oscillators
❚The AirLink Pro T1 supports the Bipolar with 8-Zero Substitution (B8ZS)
coding format
❚The AirLink Pro E1 supports the High Density Bipolar 3 (HDB3)
coding format
❚The AirLink Pro E1 allows an electrical-interface option between Balanced
and Unbalanced
❚The AirLink Pro T1 operates at 1.544 Mbps and the E1 at 2.048 Mbps
❚ The operating range between two AirLink Pro T1 units is up to 40 km and
that of two E1 units is 35 km
In a typical installation, an AirLink Pro T1 or E1 pair is installed between a
user’s communication facility—Data Circuit Equipment (DCE) or network—and
the Data Terminating Equipment (DTE). Figure 1-2 shows the AirLink Pro
T1/E1 Rack Mount in a typical operating environment.
Rev. B - 1/97
1-3
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Product Description
Figure 1-2
Typical AirLink Pro T1/E1 Rack Mount Operating Environment
The AirLink Pro T1/E1 Rack Mount link is effectively transparent to the T1/E1
equipment on either end:
❚Accepts T1/E1 as input
❚Presents T1/E1 as output
AirLink Pro T1 operation is independent of the protocol used, so the AirLink Pro
T1 supports both the Bipolar with Eight-Zero Substitution (B8ZS) and the
Alternate Mark Inversion (AMI) coding formats. The AirLink Pro E1 supports
both the High Density Bipolar 3 (HDB3, and AMI) coding formats. These
formats do not interfere with the framing and maintenance channel used
between T1/E1 links so the AirLink Pro T1/E1 Rack Mount works with Extended
Frame format, ISDN Primary Rate Services, and so on.
The AirLink Pro T1/E1 Rack Mount provides full-duplex, radio-to-radio
communication that follows a Ping-Pong analogy: while one unit transmits a
radio burst, the other unit receives that burst. After the other unit receives a
complete burst, it waits through a guard interval before turning on its
transmitter and transmitting its burst.
The ping-pong radio-to-radio communication is invisible to the T1/E1
equipment on either end of the link because the digital buffering of the AirLink
Pro T1/E1 Rack Mount produces a smooth T1/E1 bit stream at the user interface.
1-4
Rev. B - 1/97
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Product Description
Buffering is only a few milliseconds, so no perceptable degradation occurs to
voice or data communications.
AirLink Pro T1/E1 Rack Mount Antenna
The antenna is usually a two-foot or four-foot solid-parabolic dish for the 5.7
GHz C-band, with a narrow beam and high gain. For other kinds of antennas,
contact your distributor.
The AirLink Pro T1/E1 Rack Mount ASCII Terminal User Interface
The AirLink Pro T1/E1 Rack Mount ASCII terminal user interface is an
EIA/TIA-232 interface that allows a terminal device or personal computer to
control and monitor AirLink Pro T1/E1 Rack Mount operation at either end of
the link. The connection to the EIA/TIA-232 interface can be either a direct
connection (device to port), or an indirect connection (device to modem to port)
for dial-up operation.
Programmed Configuration Parameters
AirLink Pro T1/E1 Rack Mount operation is governed by user-selectable
configuration and control parameters that reside in the non-volatile memory of
the unit. These parameters are displayed and controlled through a terminal
device that can access both the local and remote unit. When power is lost and
then restored, the system reconfigures itself from its protected configuration
database.
A long-life lithium battery protects all system configuration settings during
power losses. The battery is part of the non-volatile memory/real-time clock
circuitry on the digital module in the AirLink Pro T1 and has a 10-year storage
life (in the absence of power to the AirLink Pro T1/E1 Rack Mount).
Refer to Chapter 3, Configuration, for more information on changing
configuration parameter settings.
Monitoring and Diagnostic Capabilities
The AirLink Pro T1/E1 Rack Mount system constantly monitors the quality of
the wireless link, checking the receive RF signal level, bit errors, and many
other critical factors. This information is stored in an internal database of
status and performance information that the AirLink Pro T1/E1 Rack Mount
uses, in part, to derive the events that are stored in the event queue. As alarm
events occur, they are signaled through indicators on the front panel of the
Rev. B - 1/97
1-5
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Product Description
AirLink Pro T1/E1 Rack Mount and are entered in the event queue. To report
alarms, attach a modem and dial-out to the maintenance center.
Using the terminal user interface, query either the local AirLink Pro T1/E1
Rack Mount or the remote AirLink Pro T1/E1 Rack Mount for status, performance
and alarm information, and make configuration changes for either the local or
remote end of the link.
The AirLink Pro T1/E1 Rack Mount also provides bit-error and loopback tests to
isolate problems. Initiate tests in the local AirLink Pro T1/E1 Rack Mount or in
the remote AirLink Pro T1/E1 Rack Mount through the terminal user interface.
Refer to Chapter 4, Operations and Maintenance, for information on monitoring
operation and using diagnostic tools and procedures.
T1/E1 Link Backup Capability
The T1/E1 link backup capability built into the AirLink Pro T1/E1 Rack Mount
enables an AirLink Pro T1/E1 Rack Mount pair to provide a parallel T1/E1
path (the RF link) to a standard T1/E1 line (see Figure 1-3).
1-6
Figure 1-3
A Point-to-Point Backup Link
Under normal operating conditions, the primary (protected) T1/E1 line is routed
to an external device such as a CSU through the AirLink Pro T1/E1 Rack Mount
and carries its normal T1/E1 traffic.
In the event of a fault in the primary T1/E1 link, each DSU/CSU generates a
relay control signal that is transmitted to the attached AirLink Pro T1/E1 Rack
Rev. B - 1/97
Mount units. The AirLink Pro T1/E1 Rack Mount pair switch the protected
T1/E1 line to provide a protected bypass T1/E1 path.
The backup switch can be opened or closed by an external switch or relay wired
to the CSU SEL connector on the rear panel of the AirLink Pro T1/E1 Rack
Mount.
Alarm Relay Contacts
Major and minor alarm contacts are built into the AirLink Pro T1/E1 Rack
Mount. If an alarm occurs such that an entry is put into the event queue, the
alarm contacts switch to the alarm state for as long as the alarm event persists.
For more information on the AirLink Pro T1/E1 Rack Mount alarm relay
contacts, refer to Chapter 2, Installation and System Administration.
Order Wire Interface
The Order Wire interface is an end-to-end voice communication channel that is
carried on the radio link between the local and remote AirLink Pro T1/E1 Rack
Mount units. Maintenance and service personnel can connect telephones to order
wire ports on the local and remote AirLink Pro T1 units and have direct voice
communication between the local and the remote site.
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Product Description
Order Wire communication can only occur when there is an active radio link
between the local and remote AirLink Pro T1/E1 Rack Mount units (refer to
Chapter 2, Installation and System Administration). The Order Wire channel
is outside of the T1/E1 channel and does not affect the user’s data. The Order
Wire can also be used with 4-wire modems in a large network management
system.
Fail-Safe Link
A reliable link can be created by eliminating all “single points of failure.” This
is illustrated in Figure 3-1 and discussed in detail in Chapter 3, Point-to-Point
Link.
Block Diagram
The following illustration is a functional block diagram of the Cylink AirLink
Pro T1/E1 Rack Mount.
Rev. B - 1/97
1-7
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Product Description
1-8
Figure 1-4
Block Diagram of the AirLink Pro T1/E1 Rack Mount
Rev. B - 1/97
C
HAPTER
HAPTER
C
Installation and
Installation and
System Administration
System Administration
This chapter outlines general planning and the procedures for
unpacking, and installing the AirLink Pro T1/E1 Rack Mount
hardware, connecting cables, and performing power-up checks. This
chapter also contains important instructions regarding safety in setting
up the AirLink Pro T1/E1 Rack Mount system.
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Installation and System Administration
Overview
This chapter discusses the general technical requirements of antenna and RF
transmission line installation,and focuses on the task of installing the AirLink
Pro T1/E1 Rack Mount system at each end of the communication link,
integrating all of the equipment, and performing a system check and alignment
before turning the system over to normal customer traffic.
The components of AirLink Pro T1/E1 Rack Mount system are:
❚AirLink Pro T1/E1
❚AirLink Pro T1/E1 Rack Mount antenna and antenna cable
Depending upon your system plan, you will be installing all or some of these
AirLink Pro T1/E1 Rack Mount system components at each end of a link. The
following sections describe both required and optional system components.
Unpacking
The first step in the installation process is to take all of the materials out of
the shipping carton(s) and check that you have everything shown on the
packing list(s). If something is missing, contact your local distributor. Inspect
the unit for any possible damage.
If you discover shipping damage, repack the unit and notify the shipping
representative.
NOTESave the shipping cartons and packing materials. You will need the carton and materials if
you need to ship your equipment.
After unpacking and confirming the contents of the shipment, place the AirLink
Pro T1/E1 Rack Mount system components on a flat surface to allow enough space
to work around them.
2-2
Rev. B - 1/97
Identifying Physical Features
Figure 2-1
AirLink Pro T1/E1 Rack Mount Front Panel
Front Panel
The AirLink Pro T1/E1 Rack Mount front panel (Figure 2-1) consists of a metal
panel that contains five status and alarm LEDs identified with graphical icons
and two RJ-11 jacks.
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Installation and System Administration
Rear Panel
The AirLink Pro T1/E1 Rack Mount rear panel (Figure 2-2) consists of a metal
panel containing four external equipment connectors, seven terminal blocks, and
an n-type antenna connector. Table 2-1 lists the rear-panel connectors and
describes their functions.
Figure 2-2
AirLink Pro T1 /E1 Rack Mount Rear Panel
Rev. B - 1/97
2-3
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Installation and System Administration
Table 2-1
AirLink Pro T1/E1 Rack Mount Rear-Panel Connectors
ConnectorTypeFunction
Network Management9-Pin Male
Subminiature D
TerminalRJ - 11Terminal connection
CSU6-Pin Captive
Wire Terminal
Block
E1 OutBNCNot used for T1 unit; In E1 unit, used for
DTE4-Pin Captive
Wire Terminal
Block
E1 InBNCNot used for T1 unit; In E1 unit, used for
Order Wire4-Pin Captive
Wire Terminal
Block
BSYNC6 Pin Captive
Wire Terminal
Block
Minor Alarm4-Pin Captive
Wire Terminal
Block
Major Alarm6-Pin
CaptiveWire
Terminal Block
Power6-Pin Captive
Wire Terminal
Block
AntennaN type femaleAntenna connection
Connects a modem to the AirLink Pro
T1/E1.
Connects the T1/E1 Line from an external
device such as a CSU. Used for wire line
backup only.
configuring Unbalanced Interface option
T1/E1 connection to the DTE
Unbalanced Interface option
Connection for Four wire Order Wire unit
Burst sync connection
Minor alarm relay connection
Major alarm relay connection
Power connection
Preparing a Place
Because of the special planning requirements associated with installing a
microwave system, review some of the general guidelines regarding
installation preparation to ensure that the site is suitable to the purpose.
2-4
Rev. B - 1/97
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Installation and System Administration
General Physical and Environmental Characteristics
The AirLink Pro T1/E1 Rack Mount radio unit measures approximately 17
inches wide, 3 inches high, and 10 inches deep, and weighs approximately 10
pounds.
Lightning Protection
The AirLink Pro T1/E1 Rack Mount is provided with secondary protection on all
signal leads to the printed circuit assemblies in the unit. If the AirLink Pro
T1/E1 Rack Mount system is being installed in an area where lightning can be a
problem, primary protection, such as gas tubes or spark gaps, is required (Cylink
distributors can provide these).
Rack-Mounting
The AirLink Pro T1/E1 Rack Mount mounts indoors in a 19-inch or 23-inch
equipment rack or cabinet. The rack-mount hardware kit, which consists of a
pair of mounting brackets and all required fasteners, is included in the shipping
carton with the AirLink Pro T1/E1 Rack Mount.
Power and Grounding Requirements
The AirLink Pro T1/E1 Rack Mount operates at 24VDC or 48VDC. Either the
positive or negative input is connected to the ground, or left floating. External
circuit protection not exceeding 2 amps is required.
500 Ma @ 48 Volts
Input PolarityInput is floating. Either input may be grounded
Input ProtectionNominal fuse = 2.0 A Slow Blow
Input Reverse
Voltage Protection
Provided. Series diode. No current will flow if the
input voltage is reversed.
Rev. B - 1/97
2-5
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Installation and System Administration
NOTENo internal fusing is provided, because to do so would violate the specifications of
UL1459 section 70. (No fusing is allowed in the grounded side of a DC input circuit unless
the hot side is also fused.) When the fuse in the hot side blows, the fuse in the grounded
input must also blow. Since this equipment accepts either polarity, external circuit
protection must be provided in the hot side of the feeder circuit.
Setting Up the System
The following sections outline the procedures for installing, cabling, and
bringing up an AirLink Pro T1/E1 Rack Mount system. Some of the steps require
special knowledge, experience, tools, and assistance from another person.
Installing the Antenna
Antennas are generally installed by persons who have the knowledge,
experience, and tools to handle the somewhat specialized task. The following
sections are intended as a general summary of the process, and not as a complete
description. A successful antenna installation effort is the culmination of all
the site and route preparation, and path analysis.
Typical Antenna Mounts
An antenna for a microwave system such as the AirLink Pro T1/E1 Rack Mount
is typically equipped with mounting hardware that allows the antenna to
attach to a length of pipe that can then be mounted in several ways, depending
upon the user requirements, site conditions, and local building codes (see
Figure 2-3).
2-6
Rev. B - 1/97
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Installation and System Administration
Rev. B - 1/97
Figure 2-3
Typical Antenna Mounts
2-7
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Installation and System Administration
System Grounding
Direct grounding of the antenna, mast, and tower provides some protection
against lightning strikes and static buildup. A direct electrical connection
should be made to a suitable grounding rod at the base of the tower or mast using
at least #10 AWG ground wire, or its equivalent, and non-corrosive hardware.
For details and safety standards, consult the appropriate electrical code or a
similar document. Use lightning arrestors in appropriate places.
Aligning the Antenna
In order for an AirLink Pro T1/E1 Rack Mount pair to operate correctly, the
local antenna and the remote antenna must be aligned so that the signals from
one antenna are aimed directly at the center of the other antenna. Correct
antenna alignment maximizes the signal received at both ends of the radio
link. An outline of the antenna alignment procedure is at the end of this
chapter.
Installing the AirLink Pro T1/E1 Rack Mount
The following illustration shows how to connect the mounting ears on the unit
(center-mounted or flush-mounted).
2-8
Rev. B - 1/97
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Installation and System Administration
Rev. B - 1/97
2-9
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Installation and System Administration
The AirLink Pro T1/E1 Rack Mount can be installed into a standard 19-inch or
23-inch equipment rack using the rack-mount hardware included with the unit.
It requires 4U (7.0”) of rack mounting space, of which 1U space above and below
the unit is necessary for proper ventilation. Two standard blank panels can be
used over the openings.
To mount the AirLink Pro T1/E1 Rack Mount in an equipment rack:
1.Place the AirLink Pro T1/E1 Rack Mount on a table or bench.
2.Lay out the pieces of the rack mount hardware kit.
The rackmount hardware kit should contain the following parts:
❚Two 1-inch increment mounting brackets for 23-inch rack mount
❚Two EIA mounting brackets for 19-inch rack mount
❚Eight 10-32 x 3/8” Phillips pan-head screws, lock washers, and flat
washers
3.Orient the mounting brackets for front- or mid-mounting.
4.Attach the brackets to the AirLink Pro T1/E1 Rack Mount with the screws
provided in the hardware kit.
5.Position the AirLink Pro T1/E1 Rack Mount in the equipment rack and
fasten with screws.
2-10
Rev. B - 1/97
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Installation and System Administration
Figure 2-4
23” Rack Mount
Connecting the Antenna Cable
To connect the antenna cable to the AirLink Pro T1/E1:
1.Locate the N-type connector on the rear panel of the AirLink Pro T1/E1
Rack Mount (see Figure 2-2).
2.Plug the RF cable connector firmly into the N-type jack connector and handtighten the cable connector shell onto the jack connector collar.
3.Verify that the cable connector is seated securely and that the cable is not
kinked.
4.Recommend 1/2 or 7/8-inch case. Check the rating for 6 Ghz operation.
5.Recommend using short piece of more flexible coaxial to connect to the
AirLink, such as the RG-6/U or the RG-59/U from Cylink.
Rev. B - 1/97
2-11
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Installation and System Administration
T1 DTE Line Connection
To connect the T1 line cable to the DTE:
1.Locate the DTE terminal block on the Airlink Pro T1/E1 Rack Mount rear
panel (see Figure 2-2).
2.Prepare the cable wire so that individual leads are separate. Strip a small
portion of insulation off each wire lead.
3.With the help of a screw driver, push back one of the plastic levers located
on the terminal block.
The following is a list of some suitable coaxial cables:
U1 Rating System:
CM= General purpose, vertical tray. Tested per UL-1581.
CMP=Plenum Rated. Tested per UL-910.
AWGATTN1UL Rating
2
The following is a list of some suitable cables for the T1 or E1 Balanced.
The cable type usually specified for indoor T1 use is Western Electric ABAM or
equivalent. An equivalent cable is General Cable Specification 4162D. The
characteristics of these two cables are listed in the table. These cables are
rated in-building use and in-vertical risers and are not rated for use in
plenumbs. Both of these cables use solid wire.
CableGaugeImpedanceLoss at 1 Mhz
ATAM22100 Ohms4.0 dB
GT416222100 Ohms6.0 dB
2-12
A second class of indoor cable is 100 Ohms stranded, shielded 24 ga. These
cables have a characteristic impedance of 100 Ohms and a loss at 1 Mhz of
about 7 dB per 1000’. Representative cables of this type are listed in the
following table. These cables are also suitable for E1 applications.
Rev. B - 1/97
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Installation and System Administration
Belden Part No. 8729 (UL Rating CMP (Plenum))
Individually shielded twisted pairs.
Berk-Tek Part No. 230249 (Plenum)
Berk-Tek Part No. 230131 (Non Plenum)
These cables have an overall foil shield.
The recommended E1 cable: The E1 signal can be either unbalanced, in which
case the coaxial cables listed can be used or it can be unbalanced, in which case
the balanced twisted pair cables can be used.
4.While holding it in this position, insert one of the leads of the cable into
the spring pin connector, below the lever.
5.Release the lever.
6.Repeat Steps 3, 4 and 5 to connect each lead.
7.Ensure that each cable lead is securely held by the spring pin connectors.
T1 Backup Connections
1.Locate the CSU terminal block on the AirLink Pro T1/E1 Rack Mount rear
panel (see Figure 3-2).
2. Follow the same procedure used for connecting T1/E1 DTE line.
3. Locate the fault signal cable connector from the external device.
4.Connect the fault signal cable to the CSU -SEL connector on the major
Alarm terminal block.
In the event of a fault in the primary T1/E1 link, each CSU generates a relay
control signal that is transmitted to the attached AirLink Pro T1/E1 Rack
Mount. The T1/E1 pair switch the protected primary line in, to provide a
protected bypass T1/E1 path.
Alarm Relay Contact Connections
If you have an application that uses the alarm relay contacts in the MAJOR &
MINOR ALARM captive-wire terminal block on the rear panel of the AirLink
Pro T1/E1 Rack Mount, connect the device cable to the ALARM-C and ALARMNC or ALARM-NO contacts in the MAJOR & MINOR ALARM captive-wire
terminal block (see Figure 2-5).
Rev. B - 1/97
2-13
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Installation and System Administration
2-14
Figure 2-5
Alarm Relay Contacts
The major and minor alarm contacts built into the AirLink Pro T1 are SPDT
relay contacts rated at 8 VA (0.25 A maximum at 100 VDC maximum) isolated
from the ground. The alarm relays are de-energized when the AirLink Pro
T1/E1 Rack Mount is in an alarm state: the NO contact is closed; the NC contact
is open.
If an alarm occurs such that an entry is put into the event queue, the alarm
contacts switch to the alarm state for as long as the alarm event persists or until
the alarm is reset.
Terminal Connection
A simple ASCII terminal or personal computer can be connected to the RJ-11
Terminal Jack on the front or rear panels of the AirLink Pro T1/E1 Rack Mount
to monitor and configure its operation. A DB9 to RJ-11 adapter is included. In a
hub installation involving a number of AirLink Pro T1/E1 Rack Mount pairs, the
Rev. B - 1/97
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Installation and System Administration
terminal device can be “shared” across all the AirLink Pro T1 systems by a
terminal switching device.
A terminal device or a personal computer can have specific data cabling
requirements (refer to Appendix B, Specifications, for connector pin
assignments), and usually requires a grounded alternating current power outlet.
An adapter kit that connects between the AirLink Pro T1/E1 Rack Mount
terminal port and a male DB-9 connector is shipped with the equipment.
Figure 2-6
Terminal Connection to the AirLink Pro T1/E1 Rack Mount
Remote Connection
A remote terminal or personal computer can be connected to the Terminal port on
the front or rear panels of the AirLink Pro T1/E1 Rack Mount unit through a
modem (Figure 2-6). A modem requires a dedicated telephone line with a
modular RJ-11 jack as well as a source of power, usually a standard 115 VAC
grounded outlet.
Rev. B - 1/97
2-15
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Installation and System Administration
Figure 2-7
Modem Connection to the AirLink Pro T1/E1 Rack Mount
Order Wire Connection
The Order Wire interface is a 64 kbps pulse modulation (PCM) voice
communication channel. This part of the AirLink Pro T1/E1 Rack Mount RF
protocol does not use any part of the 1.544 Mbps T1 channel or the 2.048 Mbps E1
channel. The Order Wire interface meets V.21 and V.32 modem specifications.
A standard telephone (2 wire interface) can be plugged in to the Order Wire
jack on the front panel ( Figure 2-3). A telephone is required at each end of the
link.
2-16
Rev. B - 1/97
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Installation and System Administration
Figure 2-8
Two-Wire Order Wire Connection
Order Wire communication can only occur when there is an active radio link
between the local and remote AirLink Pro T1/E1 Rack Mount units and the RSQ
is 6 or higher. Communication across the order wire interface is initiated by
picking up the telephone at either end of the link. When the RSQ is below 6,
the AirLink Pro T1/E1 Rack Mount software mutes the order wire. Picking up
the order-wire telephone causes an audible tone (beeping ) at the remote
Airlink Pro T1/E1 Rack Mount. This tone continues until the telephone at the
remote end is picked up.
An external order wire unit can be connected to the designated terminal block on
the rear panel. When an external 4 wire interface is used, the order wire unit
provides its own signaling. The 4-wire interface allows multiple T1/E1 units at
a hub to be connected through a 4-way or 8-way 4-wire bridge (Figure 2-11).
Connect the input pair of the order wire to the T & R located on the ORDER
WIRE terminal block and connect the output pair to the T1 & R1.
Set the external order wire to transmit and receive at 0 dBm. The type of order
wire interface (2 or 4-wire) is selected from the Command Line Interface
Configuration screen. (See “Setting Link Parameters” in Chapter 3,
Configuration).
Rev. B - 1/97
2-17
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Installation and System Administration
Figure 2-9
Four-Wire Order Wire Connection
CAUTIONThe order wire interface must not be connected directly to the Public Switched
Telecommunications Network.
2-18
Rev. B - 1/97
External Power Supply Connection
Figure 2-10
ELPAC Power Supply
For the ELPAC Power Supply
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Installation and System Administration
1. Locate the Power terminal block on the unit’s rear panel and insert the red
wire of the power supply into the +V spring pin connector of the terminal
block.
2. Insert the white wire into the -V spring pin connector of the terminal block.
3. Ensure that the two wires are securely held by the connectors.
Rev. B - 1/97
2-19
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Installation and System Administration
Figure 2-11
FORTRON Power Supply
For the FORTRON Power Supply
1. Locate the Power terminal block on the rear panel of the unit and insert the
brown wire of the power supply into the +V of the terminal block.
2. Insert the black wire into the -V spring pin connector of the terminal block.
3. Ensure that the two wires are securely held by the connectors.
Wiring for Burst Synchronization
When you have either a hub configuration or a repeater site (more than one
AirLink Pro T1/E1 Rack Mount unit operating from the same central site), one of
the units must be set up as the source for burst synchronization. Refer to Chapter
3, Configuration, for Hub and Repeater configurations.
Installing the Burst Sync Wiring
The burst synchronization connections are made using unshielded twisted pair
wires. The equipment should be physically located as shown in Figure 2-12.
The primary and the backup masters should be the first units in the group. If
the distance between the primary master and the last secondary master is
greater than 100 ft, the burst sync bus(es) should be terminated at this unit (the
last secondary master).
2-20
Rev. B - 1/97
Figure 2-12
Burst Sync Wiring
Terminating the Burst Sync Bus
The burst sync bus is terminated by inserting a short jumper wire in the TERM A
and TERM B locations as defined by the rear panel labels.
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Installation and System Administration
Checking Operation
During start-up an AirLink Pro T1/E1 Rack Mount pair:
❚Establishes the radio link between the two radio units
❚Starts transferring data
When each radio unit is powered up, a power-on self-test begins that
determines whether the unit’s hardware and software are operating within
the required limits. When the test succeeds, the designated master unit begins
transmitting, attempting to establish a RF link with the slave unit.
AirLink Pro T1/E1 Rack Mount units leave the factory configured as master
units in a point-to-point configuration; configure one of the units as a slave.
Initial Unit Configuration
In a new point-to-point link installation, the configuration on one end must be
changed to application 6 (Slave Unit in a Point-to-Point Link, refer to
“Application” in Chapter 3).
Rev. B - 1/97
2-21
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Installation and System Administration
In a new hub installation, the units at the hub must all be masters, and the
corresponding remote units must be slaves. At a hub, set up each individual link
first as a point-to-point link and then align each link separately with all the
other AirLink Pro T1/E1 Rack Mount units turned off. After all the link pairs
have been configured and aligned as point-to-point links, you can then change
configurations for hub operation.
In a new repeater installation, treat each link segment as a point-to-point link,
progressing from the near-end to the far-end sites. After all the link pairs have
been configured and aligned as point-to-point links, you can change
configuration for repeater operation.
For more information about applications and burst synchronization, refer to
“Application Examples” in Chapter 3, Configuration.
No radio link exists until the AirLink Pro T1 pairs have been configured and
aligned, all system configuration must be done individually at each unit. After
a radio link is established between the units of an AirLink Pro T1 pair, the
remote unit can be configured from the local site across the radio link.
To configure one end of the link as a slave:
1.Connect a terminal to the Terminal port on the slave AirLink Pro T1/E1
Rack Mount or to the Terminal port on the AirLink Pro T1/E1 Rack Mount
attached to the slave unit.
The terminal must be set up to operate according to the attributes described
in “ Connecting a Terminal,” in this chapter.
2.Type the following command at the prompt:
AIRLINK PRO T1/E1> set application 6
The text you type is in boldfaced type; enter the spaces as shown.
3.To verify the configuration change, type the following command at the
prompt:
AIRLINK PRO T1/E1> get configuration
The terminal displays the configuration of the unit, similar to the
following:
AIRLINK PRO T1/E1> Get Configuration
Site Name:
Application: 6. Slave Unit in a Point-to-Point Link
Burst Mode: Normal
Coding: B8ZS or (HDB3)
Alarm Reporting: Immediate
Alarm Level: Status
Date/Time: May 1 1996 10:35:00
NOTEYou might need to alter more configuration values in order to ensure correct operation,
during your AirLink Pro T1/E1 Rack Mount installation. Refer to Chapter 3 for more
information on configuring the AirLink Pro T1/E1 Rack Mount.
Aligning the Antenna
After the link pair has been turned on and configured, the antennas must be
aligned. Since most AirLink Pro T1/E1 Rack Mount paths will be line-of-sight
paths, visually align the initial antenna. In most cases, this rough alignment is
sufficient for radio units to acquire radio synchronization lock.
NOTEWhen the radio link between two units is active, telephones can be plugged into the OW
jacks on the AirLink Pro T1/E1 Rack Mount units permitting persons at the two sites to talk
to one another. Picking up the order wire telephone causes an audible tone (pulsed
beeping) at the remote AirLink Pro T1/E1 Rack Mount unit. This tone continues until the
telephone at the other end is picked up.
To “fine tune” the antenna alignment, perform the following procedure:
1.Insert the probes of a DC voltmeter into test points (RSS) and (ground) on
the AirLink Pro T1/E1 Rack Mount (see Figure 2-11).
Rev. B - 1/97
2-23
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Installation and System Administration
2-24
Figure 2-13
Test Point Locations
2.Swing the antennas on both ends of the link horizontally and vertically
(but not at the same time!) until the observed voltage peaks.
Swing the antennas through the main lobe and both side lobes to check that
the antenna is aligned on the main lobe and not one of the side lobes.
After you align the antenna, use the terminal query status and queryperformance commands to check the receive signal strength (Rx Power) and
the receive signal quality (RSQ). Compare the receive signal level to the
expected signal level based on the path calculations.
3.Type the following command at the AirLink Pro T1/E1 Rack Mount prompt:
AIRLINK PRO T1/E1> query status
Rev. B - 1/97
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Installation and System Administration
The system displays a list of status information similar to the following:
AIRLINK PRO T1/E1> query status
Site Name: Sunnyvale 2
DTE Loss: NO
Radio Sync Loss: NO
Burst Sync Loss: N/A
Test in Progress: FE Radio Remote Loop
DTE AIS: OFF
RF AIS: OFF
Tx Fail: NO
Rx Power: -60.5 dBm
Tx Power: 12.0 dBm
Temperature: 5 C
4.Type the following command at the AirLink Pro T1/E1 Rack Mount prompt:
AIRLINK PRO T1/E1> query performance
The system displays a list of status information similar to the following:
The Receive Signal Quality (RSQ) is a figure of merit that is normalized on a
scale of 1 to 10, and is a function of the receive signal-to-noise and signal-tointerference ratio. A very strong signal that is severely corrupted with
interference results in a normal receive signal power indication and a low RSQ
number.
Assuming that the T1/E1 lines to and from the AirLink Pro T1/E1 Rack Mount
units are okay, T1/E1 data transfer begins as soon as the RF link is established.
If you need to alter other configuration values, refer to Chapter 3,
Configuration, for configuration procedures.
Rev. B - 1/97
2-25
C
HAPTER
HAPTER
C
Configuration
Configuration
This chapter describes how to use the AirLink Pro T1/E1 Rack Mount
command-line terminal user interface to set and change configuration
parameters. The information in this chapter includes descriptions of all
the AirLink Pro T1/E1 Rack Mount configuration commands and
options, and lists the default configuration settings.
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Configuration
Overview
To configure the AirLink Pro T1/E1 Rack Mount, connect an ASCII terminal or a
personal computer to the Terminal port of the AirLink Pro T1/E1 Rack Mount.
The AirLink Pro T1/E1 Rack Mount ASCII terminal interface provides a
command-line interface for manipulating the operation of the AirLink Pro
T1/E1 Rack Mount, including configuring operational parameters, monitoring
operation, and responding to alarm conditions. The command line interface also
provides an online help facility to aid you in entering commands. You can also
type in a help request for a particular command combination.
You can type a question mark (?) at the end of any command field, and the
command interpreter will display the next valid keyword or operand that you
can enter.
If you press <Return> before the command is complete, the command interpreter
displays the next valid keyword or operand that you can enter. If the command
is complete, the system will execute the command.
The command line interface is described in more detail in the following
sections.
Using the ASCII Terminal Interface
Terminal Setup Requirements
Before connecting the ASCII terminal to the unit, configure the terminal with
the following parameters:
Terminal Mode = VT100
Column = 80
Autowrap = ON
Monitor Mode = OFF
Cursor Keys = Normal
Newline Mode = ON
Character Set = DEC Supplemental
Key Code = ASCII
Break key = ON
Minimum Break Length = 2 character times (17 msec.)
Data/Parity = 8/No Parity
Stop Bits = 1
3-2
Rev. B - 1/97
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Configuration
Transmit Rate = 19200, 9600, 4800, 2400, or 1200 bps
Auto Answerback = OFF
Comm = FDX (No Echo)
RS232 Data Leads Only (RxD and TxD)
Local Echo = OFF
To connect the terminal, follow these steps:
1.Connect the terminal (or a computer in terminal emulation mode) to the
Terminal port with the EIA/TIA-232 cable as described in Chapter 2.
2.Turn on the terminal; adjust the contrast and brightness as required.
The AirLink Pro T1/E1 Rack Mount terminal interface software contains an
autobaud feature that automatically attempts to detect the operating baud
rate of the attached terminal device.
3.Press <Break> then <Return> on the terminal keyboard.
Pressing <Break> at the terminal puts the AirLink Pro T1/E1 Rack Mount
terminal interface software in “hunt” mode, where it looks for carriage
return (<Return>) characters at the attached terminal.
If the terminal is set for 19200, 9600, 4800, 2400, or 1200 bps, the terminal
interface software learns the operating baud rate by starting at 19200 bps
and dropping to the next lower speed in the sequence until it recognizes a
<Return> character.
When the AirLink Pro T1/E1 Rack Mount terminal interface detects a
<Return> keystroke, it displays the AirLink Pro command-line prompt:
AIRLINK PRO T1> or AIRLINK PRO E1>
Pressing <Break> puts the terminal interface software back into hunt mode.
If the prompt does not appear, press <Break>once, then press <Return>
repeatedly at one second intervals until the AirLink Pro T1/E1 Rack Mount
prompt appears. If the prompt does not appear after pressing <Return> six
times, press <Break> and try again.
Command-Line Interface
The command-line interface consists of commands for manipulating the
operation of the AirLink Pro T1/E1 Rack Mount, including configuring
operational parameters, monitoring operation, and responding to alarm
conditions.
Rev. B - 1/97
3-3
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Configuration
Command-Line Format
The general syntax of a command line consists of a basic command keyword
followed by additional keywords and operands that qualify the command
keyword:
BASIC_KEYWORD KEYWORD_1 … KEYWORD_n operand; comment
The command-line format and syntax is based upon the following :
❚Separators: Each keyword or operand must be separated by a separator
character—a space or a TAB character. Extra space characters between two
command elements are treated as one space character.
❚Order: The basic command keyword must be the first word of the command.
All operands that relate to a keyword must immediately follow that
keyword in the prescribed order. Keywords relating to another keyword
must follow that keyword.
❚Comments: In a case where the command line is part of a file that is sent to
the remote interface, you can add comments to a command line by appending
a semicolon character (;) to the end of the command line, followed by the
text of the comment. The command interpreter ignores the semicolon and
any characters following it except <Return>.
❚Length: The maximum keyword length is 15 characters. The maximum
command-line length is 250 characters, including comment text, separator
characters, and <Return>. Any command that exceeds this length is
rejected with an appropriate error message.
❚Short forms of keywords: You can save keystrokes when typing commands
by abbreviating a keyword to the first four characters of the keyword.
❚Case: Commands are not sensitive to case. You can enter keywords as all
upper-case characters, all lower-case characters, or as any combination.
❚Choosing from a list of options: The notation
{ x1 | x2 | ... | xn }
showing numbers or terms separated by vertical bars indicates that you can
select one of the elements in the listed set of x1 to xn. For example, in the set
of options:
{ 0 | 133 | 266 | 399 | 533}
you can choose any one of the listed values.
3-4
Rev. B - 1/97
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Configuration
❚Choosing from a range of numbers: The notation
{n1 .. n2}
indicates that you can specify a number within the range of numbers shown
in the active command context, for example, given the range {0 .. 24}, you
would specify a single number from 0 to 24.
❚Special keystroke sequences:
Press <Ctrl>+R to repeat the previous command.
Press <Esc> to clear the command line and start a new command.
Command Responses
Commands that contain errors or that request information from the unit receive
responses. Commands that set parameters receive a response of "OK" only
when they contain no errors. The following keywords are:
OKIndicates that a command to change system
configuration settings was received correctly and
executed.
SYNTAX ERRORIf an entry error is entered, the unit responds with a list
of valid choices.
Setting Administrative Parameters
The AirLink Pro T1/E1 Rack Mount administrative parameters include the
following:
❚Site Name
❚Date and Time
❚Password
Site Name
The site name identifies the role or location of the specified AirLink Pro T1.
This parameter is optional and can be a description of up to 60 alphanumeric
characters.
To set the site name for the local AirLink Pro T1/E1 Rack Mount, type the
following command at the AirLink Pro T1/E1 Rack Mount prompt:
Rev. B - 1/97
3-5
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Configuration
AIRLINK PRO T1/E1> set site name name
where name is any convenient description of up to 60 alphanumeric characters.
For example, to set the site name of the local AirLink Pro T1/E1 Rack Mount to
Sunnyvale 2, type the following command at the AirLink Pro T1/E1 Rack Mount
prompt:
AIRLINK PRO T1/E1> set site name Sunnyvale 2
To set the site name of the remote AirLink Pro T1/E1 Rack Mount, use the
command:
AIRLINK PRO T1/E1> remote set site name name
Date and Time
The date and time in system operations provides a reference in time-stamping
status, performance and alarm information.
To set the date for the local AirLink Pro T1/E1 Rack Mount, type the following
command at the AirLink Pro T1 prompt:
AIRLINK PRO T1/E1> set date date
The operand date is the calendar date, and takes the form mm/dd/yy, where
mm is a number from 1 to 12, dd is a number from 1 to 31, and yy is the last two
digits of the current year.
For example, to set the date of the local AirLink Pro T1/E1 Rack Mount, type
the following command at the AirLink Pro T1/E1 Rack Mount prompt:
AIRLINK PRO T1/E1> set date 9/30/94
To set the date of the remote unit, use the command:
AIRLINK PRO T1/E1> remote set date date
To set the time for the local unit, type the following command at the AirLink
Pro T1/E1 Rack Mount prompt:
AIRLINK PRO T1/E1> set time time
The operand time is a 24-hour clock value that takes the form hh:mm:ss,
where hh is a number from 0 to 23, representing the hour, mm is a number from 0
to 59 representing the minute, and ss is a number from 0 to 59, representing the
second. Seconds are optional; if you do not enter a value for seconds, the system
assumes a setting of 00 seconds.
3-6
Rev. B - 1/97
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Configuration
For example, to set the time of the local AirLink Pro T1/E1 Rack Mount, type
the following command at the AirLink Pro T1/E1 Rack Mount prompt:
AIRLINK PRO T1/E1> set time 10:35:00
To set the time of the remote unit, use the command:
AIRLINK PRO T1/E1> remote set time time
For outdoor use, print (AU) in the Site name when the Access Unit is installed.
NOTEThe additional time required to access the remote end of the link is a fraction of a second
and need not be taken into account.
Password
The password is required when the unit is powered on, or after the operator logs
off the system and wants to enter it again. The operator must provide the
correct password to use the GET, SET, QUERY, RESET, TEST and REMOTE
commands.
When the unit is prepared for shipment, it is configured with a null password
as a default. To gain access to the system the first time, press <Return> in
response to the login prompt for the password.
To protect the system, you should change the password at the earliest
opportunity. The new password should be noted and stored in a safe place. After
changing the password, you should test the new password by logging out and in
again.
NOTEIf you are unable to use your password or forget your password, contact Cylink Customer
Service for assistance.
A password can be any convenient combination of up to 16 alphanumeric
characters from the set a-z, A-Z, and 0-9. The Password is case sensitive.
To set or change the password for the local unit, type the following command at
the AirLink Pro T1/E1 Rack Mount prompt:
AIRLINK PRO T1/E1> set password
The system prompts you to enter the old password, prompts you to enter the new
password, and then prompts you to enter the new password again, for
confirmation. If the second instance of the new password matches the first
Rev. B - 1/97
3-7
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Configuration
instance of the new password, the new password is accepted. A password can be
any convenient combination of up to 16 alphanumeric characters.
For example, the local AirLink Pro T1/E1 Rack Mount is new and currently has
no password. To set the password to 1Awombat, type the following commands
at the AirLink Pro T1/E1 Rack Mount prompt:
AIRLINK PRO T1> set password
Old Password: <Return>
New Password: 1Awombat
Retype New Password: 1Awombat
Setting T1/E1 Line Parameters
The AirLink Pro T1/E1 Rack Mount line interface parameters include:
❚Coding
❚Equalization
Coding
You might change values for either or both of these configuration parameters
depending on your applications.
The AirLink Pro T1 supports both Alternate Mark Inversion (AMI) and Bipolar
8-Zero Substitution (B8ZS)line coding The E1 supports both the HDB3 and the
AMI. To set the coding for the local AirLink Pro T1/E1 Rack Mount, type the
following command at the AirLink Pro T1 prompt:
AIRLINK PRO T1/E1> set coding operand
where operand is AMI , B8ZS or HDB3. If you do not specify a value, the system
assumes the default value: B8ZSor HDB3.
For example, to set the coding for the local AirLink Pro T1/E1 Rack Mount to
AMI, type the following command at the AirLink Pro T1 prompt:
AIRLINK PRO T1/E1> set coding ami
To set the coding of the remote AirLink Pro T1/E1 Rack Mount, type:
AIRLINK PRO T1/E1> remote set coding operand
3-8
Rev. B - 1/97
T1 Equalization
The length in feet from the DSX point.
To set the equalization for the local unit, type the following command at the
AirLink Pro T1 prompt:
where operand is one of the following: 0, 133, 266, 399, or 533.
If you do not specify a value, the system assumes the default value: 0. For
example, to set the equalization for the local unit to 133, type the following
command at the AirLink Pro T1/E1 Rack Mount prompt:
To set the equalization of the remote AirLink Pro T1/E1 Rack Mount, use the
command:
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Configuration
AIRLINK PRO T1/E1> set equalization operand
AIRLINK PRO T1/E1> set equalization 133
AIRLINK PRO T1/E1> remote set equalization operand
The equalization distance is the total of the cable length from the AirLink Pro
T1/E1 Rack Mount. If there is no physical cross-connect, use half the distance to
the DTE (multiplexer, PBX, router, etc.).
High Density Bipolar 3 (HDB3) E1 (default)
Alternate Mark Inversion (AMI)
T1 Equalization 0(feet)(default)
133
266
399
533
Rev. B - 1/97
3-9
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Configuration
Setting Link Parameters
The AirLink Pro T1/E1 Rack Mount Link parameters include the following:
❚Application
❚Burst Mode
❚PN Code
❚RF Power
❚Order Wire Type
❚Interface Type (E1 only)
Depending upon your application, you will need to set or change values for one
or more of these configuration parameters.
NOTEThese are service-affecting configuration parameters. Changing any of these parameter
values disrupts the radio link for the time it takes to set compatible parameter values for
both ends of the link. Do the remote change always first so that the radio link can be
regained by making changes to the local unit. If you make the local changes first and lose
the radio link, you might be forced to go to the remote site in order to reconfigure the
remote unit and reinstate operation.
Application
Application refers to the role the unit plays in either a point-to-point link
(master/slave) or in a hub scheme involving primary and secondary masters.
Your choice of application determines the timing (external versus internal)
relationship between the AirLink Pro T1/E1 Rack Mount units:
1.Primary master at a hub
2.Secondary Master at a hub
3.Master unit at a repeater site
4.Master unit in a point-to-point link
5.Slave unit at a repeater site
6.Slave unit in a point-to-point link
3-10
7.Secondary Master in a protected link
Rev. B - 1/97
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Configuration
8.Backup Master at a hub
To set the application for the local AirLink Pro T1/E1 Rack Mount, type the
following command at the AirLink Pro T1/E1 Rack Mount prompt:
AIRLINK PRO T1/E1> set application operand
where operand is a number in the range 1 to 6. If you do not specify a value, the
system assumes the default value: 4 (master unit in a point-to-point link). For
example, to set the application for the local AirLink Pro T1/E1 Rack Mount to 1
(primary master at a hub), type the following command at the AirLink Pro
T1/E1 Rack Mount prompt:
AIRLINK PRO T1/E1> set application 1
To set the application of the remote AirLink Pro T1/E1 Rack Mount, use the
command:
AIRLINK PRO T1/E1> remote set application operand
All units are shipped from the factory configured as master units in a point-topoint link . You must configure one of the units in the pair as a slave so that the
system alignment procedures can be performed. Use your application plan to
determines how each unit will be configured.
The following sections describe the use of these applications in point-to-point
links, hubs, and repeaters.
Point-to-Point Link (Applications 4 and 6)
In a point-to-point link (Fig. 3-1), where one AirLink Pro T1/E1 Rack Mount
pair operates independently of any other pair, the burst synchronization timing
signal is derived from the internal clock of the designated master unit, and the
slave unit derives its synchronization from the received RF signal.
The master unit would be configured as a master unit in a point-to-point link
(application 4), while the unit at the other end would be configured as a slave
unit in a point-to-point link (application 6).
Rev. B - 1/97
3-11
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Configuration
Figure 3-1
Point-to-Point Link
Hub Application (Different Paths) (Applications 1, 2, and 8)
In a hub, where more than one AirLink Pro T1/E1 Rack Mount master unit is
located at a central site (Figure 3-2), one of the master units must be configured
as the primary master at the hub (application 1), providing burst
synchronization, while a second unit is selected as the backup hub master
(application 8). All other units at the hub are designated as secondary mastersat the hub (application 2).
The primary master supplies burst sync as long as it is operating properly.
Should the primary fail, the backup master will provide burst sync to all other
secondary masters. The externally timed secondary masters are daisy-chained
through their burst synchronization wire pairs to the internally timed primary
master so that all of the units “talk” and “listen” in a synchronized manner
(Refer to Chapter 2, Figure 2-12).
3-12
Rev. B - 1/97
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Configuration
Figure 3-2
Hub Application Different paths
Hub Application (Same Path) (Application 7)
This example involves the use of antenna pairs configured to take advantage of
fixed horizontal and vertical wave polarization. Wave polarization is
achieved by mounting the antenna pair so that the feedhorns of both antennas
are aligned either vertically or horizontally (per manufacturer’s instructions).
By using antenna polarization, you can locate two AirLink Pro T1/E1 Rack
Mount pairs at the same sites and use the same wave path without conflict (see
Figure 3-3). In this application, the primary master provides burst sync to the
secondary master and the two units are connected to a AirLink Pro T1/E1 Rack
Mount protection switch (Application 7).
When the Primary master fails, the link does not break because the secondary
master transfers to its own internal burst sync.
Rev. B - 1/97
3-13
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Configuration
Figure 3-3
Hub Application Same Path
Repeater (Applications 3 and 5)
In a repeater, the two AirLink Pro T1/E1 Rack Mount units that form the crossover point between the previous segment of the entire repeater link and the next
segment of the repeater link are referred to as the repeater site (Figure 3-4).
3-14
Figure 3-4
AirLink Pro T1/E1 Rack Mount Two Part Repeater Link
In this case, the slave unit of the previous segment of the repeater link is
configured as the slave unit at a repeater site (application 5), while the master
unit of the next segment of the repeater link is configured as the master unit at arepeater site (application 3). The burst synchronization signal pair of the
slave unit at the repeater site is wired to the burst synchronization signal pair
Rev. B - 1/97
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Configuration
of the master unit at the repeater site so that the slave at the repeater site
provides the burst synchronization signal for the master unit of the next
segment of the link.
Repeater Variations
If other AirLink Pro T1/E1 Rack Mount units are located at the repeater site,
the repeater site is treated as a hybrid hub, where the added units are wired to
the burst synchronization signal pairs of the slave at the repeater site and
synchronize their transmit bursts to the burst synchronization signal from the
slave at the repeater site. These units can be configured as either secondarymasters at a hub (application 2) or as master units at a repeater site
(application 5).
If the entire repeater link is set up as a point-to-point link, the AirLink Pro
T1/E1 Rack Mount unit that serves as the near-end unit in the entire repeater
link can be configured as a master unit in a point-to-point link (application 4).
The AirLink Pro T1 unit that serves as the far-end unit for the entire repeater
link is configured as a slave unit in a point-to-point link (application 6).
If the entire repeater link originates from a hub, the AirLink Pro T1/E1 Rack
Mount unit that serves as the near-end unit in the entire repeater link can be
configured as either a primary master at a hub (application 1) or a secondarymaster at a hub (application 2). The AirLink Pro T1/E1 Rack Mount unit that
serves as the far-end unit for the entire repeater link is configured as a slaveunit in a point-to-point link (application 6).
Burst Mode
Burst Mode describes the transmit timing relationship between the master unit
and the slave unit. In Normal mode, the master unit initiates burst timing and
the slave unit times its responses to the timing from the master. The master unit
transmits for a time, then listens for a time; the slave waits until the master
unit is listening, then transmits. In Test mode, the master transmits a constant
RF using the QRSS data pattern; the slave only listens.
NOTETest mode should only be used for alignment and testing under the direction of Cylink
personnel. In ordinary operation, the unit should be set for Normal operation.
To set the burst mode for the local AirLink Pro T1/E1 Rack Mount, type the
following command at the AirLink Pro T1/E1 Rack Mount prompt:
AIRLINK PRO T1/E1> set burst mode operand
Rev. B - 1/97
3-15
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Configuration
where operand is either Normal or Test. If you do not specify a value, the
system assumes the default value: Normal.
For example, to set the burst mode for the local AirLink Pro T1 to Normal, type
the following command at the AirLink Pro T1/E1 Rack Mount prompt:
AIRLINK PRO T1/E1> set burst mode normal
To set the burst mode of the remote AirLink Pro T1, use the command:
AIRLINK PRO T1/E1> remote set burst mode operand
WARNINGIf the burst mode of the remote unit is changed from Normal to Test, it cannot be
restored to Normal from the local unit.
PN Code
The AirLink Pro T1/E1 Rack Mount has a set of pseudo-random noise (PN)
codes. Each code number corresponds to a subset of long binary code words. These
code words are substituted for each bit in the T1 data stream. This substitution
is the basic principle of the direct-sequence spread spectrum modulation
scheme used in the AirLink Pro T1/E1 Rack Mount.
No PN code is “better” or “worse” than another. Using a different code
separates the AirLink Pro T1/E1 Rack Mount and the desired incoming signal
from undesired signals from other AirLink Pro T1/E1 Rack Mount paths.
The master unit and the slave unit of a AirLink Pro T1/E1 Rack Mount pair must
be set to the same PN code (pseudo-random noise code). The setting is then
stored in the protected system configuration memory of both units in the pair.
To set the PN code for the local unit, type the following command at the
AirLink Pro T1/E1 Rack Mount prompt:
AIRLINK PRO T1/E1> set pn code operand
where operand is a number from 1 to 8. If you do not specify a value, the system
assumes the default value: 1. For example, to set the PN code for the local
AirLink Pro T1 to 4, type the following command at the AirLink Pro T1 prompt:
AIRLINK PRO T1/E1> set pn code 4
3-16
Rev. B - 1/97
To set the PN code of the remote unit, use the command:
AIRLINK PRO T1/E1> remote set pn code operand
RF Power Level
When there are a number of AirLink Pro T1/E1 Rack Mount pairs in a hub
arrangement, the received signal levels are dependent on the distances to the
remote sites. Adjust the transmit power level to minimize cross-channel
interference and ensure that the received levels at the hub are of equal power.
To set the RF power for the local AirLink Pro T1/E1 Rack Mount, type the
following command at the AirLink Pro T1/E1 Rack Mount prompt:
AIRLINK PRO T1/E1> set rf power operand
where operand is a number from -4 to 20.
If you do not specify a value, the system assumes the default value: 0 (dBm).
For example, to set the RF power level for the local AirLink Pro T1/E1 Rack
Mount to -1, type the following command at the AirLink Pro T1/E1 Rack Mount
prompt:
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Configuration
AIRLINK PRO T1/E1> set rf power -1
To set the RF power for the remote unit, type the following command at the
AirLink Pro T1/E1 Rack Mount prompt:
AIRLINK PRO T1/E1> remote set rf power operand
Order Wire Type
The type of order wire interface (2 or 4) is selected from the command line
interface configuration screen. The interface must be the same at both ends of
the link.
To set the order wire interface for the local unit, type:
AIRLINK PRO T1/E1> Set orderwire 2W
To set the order wire for the remote unit, type the following command at the
AirLink Pro T1/E1 Rack Mount prompt:
AIRLINK PRO T1/E1> remote set orderwire 2W
Rev. B - 1/97
3-17
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Configuration
Interface Type (E1 Only)
Set the interface operand on the E1, where the operand is balanced or
unbalanced.
Setting Alarm Control Parameters
The alarm control parameters of the AirLink Pro T1/E1 Rack Mount include:
❚Alarm reporting
❚Alarm level
❚1-hour Errored Seconds (ES) threshold
❚1-hour Unavailable Seconds (UAS) threshold
❚24-hour ES threshold
❚24-hour UAS threshold
❚Receive (Rx) power
❚Transmit (Tx) power
The following sections describe how to set values for these parameters.
Alarm Reporting
This parameter determines whether alarms are displayed as they happen or
are held until you query for them. When an alarm event occurs, an alarm
message is inserted in the event queue and the Major or Minor indicator is
illuminated and the alarm relay contacts are de-energized: the NO contact is
closed; the NC contact is opened.
The Major Alarm LED is red and indicates that there is one or more of the
following events has occurred: transmit power below threshold, synthesizer
loss of lock, transmitter failure, DTE input loss, radio sync loss, loss of primary
burst sync (single sync bus), loss of primary and backup burst sync (dual sync bus).
The minor Alarm LED is yellow and indicates that one or more of the following
events has occurred: rcv input level below threshold, unit has been placed in a
test mode, ES threshold exceeded, UAS threshold exceeded, loss of primary or
backup burst sync (dual sync mode).
3-18
Rev. B - 1/97
Alarm Level
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Configuration
To set the alarm reporting priority for the local unit, type the following
command at the AirLink Pro T1/E1 Rack Mount prompt:
AIRLINK PRO T1/E1> set alarm reporting operand
where operand is either Request or Immediate. If you do not specify a value,
the system assumes the default value: Immediate. For example, to set the
alarm reporting priority for the local unit to Request, type the following
command at the AirLink Pro T1 prompt:
AIRLINK PRO T1/E1> set alarm reporting request
To set the alarm reporting priority of the remote unit, type:
AIRLINK PRO T1/E1> remote set alarm reporting operand
The alarm level parameter sets the severity level for reporting alarms: Status,
Advisory, Alarm, and Fault. The status messages are the least severe; fault
messages the most severe.
If you set the alarm level at Status, the system reports all four levels. If you set
the alarm level at Fault, the system only reports fault events (refer to
Appendix A for alarm messages).
To set the alarm level for the local unit, type the following command at the
AirLink Pro T1/ E1 Rack Mount prompt:
AIRLINK PRO T1/E1> set alarm level operand
where operand is one of the following: Status, Advisory, Alarm or Fault. If
you do not specify a value, the system assumes the default value: Status.
For example, to set the alarm level for the local unit to Alarm, type the
following command at the AirLink Pro T1/E1 Rack Mount prompt:
AIRLINK PRO T1/E1> set alarm level Alarm
To set the alarm level of the remote AirLink Pro T1/E1 Rack Mount, type:
AIRLINK PRO T1/E1> remote set alarm level operand
Rev. B - 1/97
3-19
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Configuration
1-Hour Errored Seconds Threshold
This parameter sets the number of errored seconds (ES) events that must occur in
a one-hour interval before an entry is inserted in the Alarm queue. The 1-hour
ES threshold is compared to the number of errored seconds in the past hour. If
the 1-hour ES count is greater than the threshold value, the unit inserts a
message in the alarm log.
To set the 1-hour ES threshold for the local radio unit, type the following
command at the AirLink Pro T1/E1 Rack Mount prompt:
AIRLINK PRO T1/E1> set threshold 1_hr es operand
where operand is a number from 1 to 999. If you do not specify a value, the
system assumes the default value: 1. For example, to set the 1-hour ES
threshold for the local unit to 15, type the following command at the AirLink
Pro T1/E1 Rack Mount prompt:
AIRLINK PRO T1/E1> set threshold 1_hr es 15
To set the 1-hour ES threshold of the remote unit, type:
AIRLINK PRO T1/E1> remote set threshold 1_hr es operand
1-Hour Unavailable Seconds Threshold
This parameter sets the number of unavailable seconds (UAS) events that must
occur in a one-hour interval before an entry is inserted in the Alarm queue. The
1-hour UAS threshold is compared to the number of unavailable seconds in the
past hour. If the 1-hour UAS count is greater than the threshold value, the unit
inserts a message in the alarm log.
To set the 1-hour UAS threshold for the local radio unit, type the following
command at the AirLink Pro T1/E1 Rack Mount prompt:
AIRLINK PRO T1/E1> set threshold 1_hr uas operand
where operand is a number from 1 to 99. If you do not specify a value, the system
assumes the default value: 1. For example, to set the local unit’s 1-hour UAS
threshold to 15, type the following command at the AirLink Pro T1/E1 Rack
Mount prompt:
AIRLINK PRO T1/E1> set threshold 1_hr uas 15
3-20
To set the 1-hour UAS threshold of the remote unit, use the command:
Rev. B - 1/97
AIRLINK PRO T1/E1> remote set threshold 1_hr uas operand
24-Hour Errored Seconds Threshold
This parameter sets the number of errored seconds (ES) events that must occur in
a 24-hour interval before an entry is inserted in the Alarm queue. The 24-hour
ES threshold is compared to the number of errored seconds in the past 24 hours.
If the 24-hour ES count is greater than the threshold value, the unit inserts a
message in the alarm log.
To set the 24-hour ES threshold for the local unit, type the following command
at the AirLink Pro T1/E1 Rack Mount prompt:
AIRLINK PRO T1/E1> set threshold 24_hr es operand
where operand is a number from 1 to 999. If you do not specify a value, the
system assumes the default value: 1. For example, to set the 24-hour ES
threshold for the local radio unit to 15, type the following command at the
AirLink Pro T1/E1 Rack Mount prompt:
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Configuration
AIRLINK PRO T1/E1> set threshold 24_hr es 15
To set the 24-hour ES threshold of the remote unit, use the command:
AIRLINK PRO T1/E1> remote set threshold 24_hr es operand
24-Hour Unavailable Seconds Threshold
This parameter sets the number of unavailable seconds (UAS) events that must
occur in a 24-hour interval before an entry is inserted in the Alarm queue. The
24-hour UAS threshold is compared to the number of unavailable seconds in the
past 24 hours. If the 24-hour UAS count is greater than the threshold value, the
unit inserts a message in the alarm log.
To set the 24-hour UAS threshold for the local unit, type the following
command at the AirLink Pro T1/E1 Rack Mount prompt:
AIRLINK PRO T1/E1> set threshold 24_hr uas operand
where operand is a number from 1 to 99. If you do not specify a value, the system
assumes the default value: 1. For example, to set the local unit’s 24-hour UAS
threshold to 15, type the following command at the AirLink Pro T1/E1 Rack
Mount prompt:
Rev. B - 1/97
AIRLINK PRO T1/E1> set threshold 24_hr uas 15
3-21
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Configuration
To set the 24-hour UAS threshold of the remote unit, use the command:
AIRLINK PRO T1/E1> remote set threshold 24_hr uas operand
Receive (Rx) PowerThreshold
This parameter sets the minimum receive power level before an entry is
inserted in the event queue. This threshold should be set approximately 10 dB
below the receive power level to allow for occasional fading.
To set the Rx power threshold for the local unit, type the following command at
the AirLink Pro T1/E1 Rack Mount prompt:
AIRLINK PRO T1/E1> set threshold rx power operand
where operand is a number from -80 to -40 (dBm). If you do not specify a value,
the system assumes the default value: -75. For example, to set the Rx power
threshold for the local unit to -45 dBm, type the following command at the
AirLink Pro T1/E1 Rack Mount prompt:
AIRLINK PRO T1/E1> set threshold rx power -45
To set the Rx power threshold of the remote unit, use the command:
AIRLINK PRO T1/E1> remote set threshold rx power operand
Transmit (Tx) Power Threshold
This parameter sets the minimum transmit power level before an entry is
inserted in the event queue. This threshold should be set approximately 6 dB
below the transmit power level.
To set the Tx power threshold for the local unit, type the following command at
the AirLink Pro T1/E1 Rack Mount prompt:
AIRLINK PRO T1/E1> set threshold tx power operand
where operand is a number from -10 to 20 (dBm). If you do not specify a value,
the system assumes the default value: -6 (dBm). For example, to set the Tx
power threshold for the local AirLink Pro T1 to 10 dBm, type the following
command at the AirLink Pro T1/E1 Rack Mount prompt:
AIRLINK PRO T1/E1> set threshold tx power 10
3-22
To set the Tx power threshold of the remote radio unit, use the command:
Rev. B - 1/97
AIRLINK PRO T1/E1> remote set threshold tx power operand
Setting Modem Parameters
Introduction
TheAirLink Pro T1/E1 Rack Mount ASCII terminal and Network Management
ports are EIA/TIA-232 interfaces that allow terminal devices or personal
computers to control and monitor AirLink Pro T1/E1 Rack Mount operation at
either end of a point-to-point link. Each EIA/TIA-232 connection can be either
a direct connection (device to port), or an indirect connection (device to modem to
port) for dial-up operation.
The Network Management (Modem) Port is available only on the Access Unit,
and uses a different physical port from the Terminal port. However, when the
network management port is connected (and dialed-up, in the case of a modem
link), commands issued from that port, along with the responses from the
terminal port, are duplicated at the Network Management port.
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Configuration
The modem support may be configured to work in any of these five modes:
DISABLEDThe port is completely disabled and it will not
respond to user commands or connection
indications from the modem.
DEDICATEDThe port behaves exactly as the Terminal
port; all commands and responses taking place
on that port are duplicated on the modem port.
ANSWERThe modem port remains idle (does not respond
to user commands) until it receives a dial-in
indication from the modem.
DIALOUT ONLYThe modem port is used only for dialing-out to
report alarms.
DIALOUT/ANSWERCombines the functionality of the ANSWER
and DIAL-OUT modes.
After the completion of a dial-out, a connection announcement is printed at the
remote end. This announcement identifies the unit type, the site name as
configured by the user, the date and time, plus a copy of the alarm text message.
Rev. B - 1/97
3-23
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Configuration
For example:
>>> AIRLINK-T1> Sunnyvale Engineering Unit 1
12 APR 95 14:33:59 Receive Power Below Threshold
NOTEThe particular alarm message chosen is the highest-priority alarm condition in effect when
dialing commences.
Connection and Configuration
The unit is shipped with a default configuration of DISABLED and 9600 bps.
Any changes to the default values can be made using the command line
interface. To change the settings, use the command line interface. Each of the
configuration items is stored in the configuration database. In addition, the
state of the connection is maintained so that recovery from a power failure will
re-initiate the connection.
Multidrop configuration (multiple units sharing a modem) is supported only by
the use of an external port-sharing device.
Modem Setup Procedures
A pair of Hayes-compatible “external” modems, 1200 bps or higher is required.
Configure each modem according to the following procedure. Note that not all
so-called smart modems are identical. Please check your modem user’s manual.
Configuring the Modem
1.To reset modem to its factory defaults (for most modems):
a. Connect the modem to a terminal using a standard EIA/TIA-232 modem
cable.
b. Wait one second then type +++ on the terminal. Pause one second again
and then type AT&F<RETURN>.
c.Cycle power on the modem.
2.Configure the modem to ignore DTR, by typing AT&D<RETURN>, or
selecting a DIP switch on some modems.
3.Configure the modem to ignore RTS, by typing AT&K0<RETURN> (Hayes
compatible modems), or AT&H0<RETURN> (US Robotics modems), or by
selecting a DIP switch on some modems.
3-24
Rev. B - 1/97
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Configuration
4.Configure the modem for error correction, if the modem is so equipped
(newer modems). This is generally the factory default, but can be invoked
by typing AT&Q5<RETURN> on Hayes compatible modems, or
AT&M4<RETURN> on US Robotics modems.
5.Set the number of rings you want the modem to answer on, by typing
ATS0=X<RETURN> where x is a digit from 1 to 9 (the number of rings), or
0 (zero) for no answer.
6.Save the new configuration in the modem’s non-volatile memory by typing
AT&W<RETURN>.
7.Cycle power on the modem.
Connecting the Modem
Connect the modem at the AirLink Pro T1/E1 Rack Mount end as follows:
1.Configure the AirLink Pro T1/E1 modem port speed by issuing the
following command at the Terminal port SET MODEM RATE XXXX
<RETURN>where XXXX is the speed in bits per second, for instance 1200,
2400, 4800, or 9600.
2.Connect the unit’s modem port to the modem using a standard EIA/TIA-232
modem cable, with a 9-pin male DB-9 connector at the unit end and an
appropriate connector (typically male DB-25) at the modem end.
3.Connect the modem’s phone port to the phone line using an appropriate
cable (usually supplied with the modem).
Connecting the Modem to the Remote Terminal
Connect the modem to the remote terminal as follows:
1.Connect the terminal’s modem port to the modem using a standard
EIA/TIA-232 modem cable.
2.Connect the modem’s phone port to the phone line using an appropriate
cable (usually supplied with the modem).
Rev. B - 1/97
3-25
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Configuration
Testing the Modem Link
1.Issue the following commands at the Terminal port:
Table 3-2
Terminal Commands of the Modem (Port) Interface
CommandDefinition
SET DIAL LEVEL FAULT <RETURN>Prevents dialing of most alarms while the link
testing
SET ALARM HOLDOFF 600 <RETURN>Prevents any alarms from being dialed for at least
10 minutes
SET MODEM MODE BOTH <RETURN>Enables dial-in and dial-out
SET DIAL TONE <RETURN>TONE (touch-tone) or PULSE (rotary)
SET PHONE 1 XXX-XXXX <RETURN> XXX-XXXX is the remote modem phone number
SET PHONE 2 XXX-XXXX <RETURN>Optional backup phone number
GET MODEM <RETURN>To view and verify the modem configuration
CONNECT 1Manually dial the phone number programmed by
the SET PHONE 1 command above
Functions
2.Type characters at the terminal port; they should appear on the terminal
connected to the remote modem. Type characters at the remote terminal.
They should appear on the local terminal.
3.Type DISCONNECT <RETURN> on the unit’s terminal to terminate the
manual dial-out connection. The modem link is now operational.
Port Duplication
During a manual connection (dial-in or dial-out), the modem and Command Line
Interface (CLI) ports appear as one at the character level. Any character typed
by either party is echoed on both terminals and entered into the ensuing
command. For example, if the CLI port user types "GET" and the modem port
user types "<blank>CONFIG" and presses RETURN, both users will see "GET
CONFIG" and the GET CONFIG screen.
3-26
Rev. B - 1/97
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Configuration
Login
When first dialing in, the remote user is not required to enter a password if the
local user is already logged in.
Auto Answer Function
If Auto Answer mode is selected, the unit sends an automatic answering
command to the modem to answer incoming calls after a designated number of
rings. Otherwise, the modem will be configured not to answer.
Events
Events are defined in the AirLink Pro T1/E1 Rack Mount as Faults, Alarms,
Advisories, or Status Messages. These are the four levels of severity, with
Faults being the highest. The user may select a dial-out threshold as one of
these levels by issuing the SET DIAL LEVEL command, in much the same way
as selecting the event reporting level with the SET ALARM LEVEL command.
The Dial-out function will dial out when there is a condition at or above that
level. For proper operation, the dial-out severity level must be equal to or
greater than the event queuing level.
Dialout Function
During an event, the modem is directed to dial the telephone number(s) in the
configuration database and send a brief descriptive announcement. The
connection is then terminated. Up to two numbers can be selected; a primary
number that will always be dialed first, and a backup number in case the unit
cannot reach the primary number. Also, the unit will make repeated attempts
to dial if the first attempt is unsuccessful.
Operation
There are two user-configurable thresholds for alarms. An alarm threshold
establishes the point when the unit begins to dial-out. In addition, to prevent
excessive dialing in the presence of repetitive events, a dial holdoff time is
defined.
Alarm Holdoff Time (0 - 600 seconds; default = 10)
One or more events must persist between 0 - 600 seconds before a dial-out
attempt is made. When set to zero, the unit dials out immediately.
One qualifying event must be present although Alarm Holdoff does not require
the same condition for the entire interval.
Rev. B - 1/97
3-27
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Configuration
Events are alternately declared and cleared for cyclical alarm conditions and
must be declared between 2 - 1000 counts during the period defined by Alarm
Holdoff Time. The event does not have to be the same one each time. Dial-out
is not attempted until the end of the alarm holdoff time, even if the Repeat
Count is reached before then.
Dial Holdoff Time (0 - 5000 minutes; default = 10)
Dial Holdoff Time is the length of time to wait between successive dial-outs
when alarms are repetitive. This alarm timer operates independently of the
alarm holdoff time and repeat alarm count. After a dial-out, any persistent or
repeated alarm conditions will wait until the end of the dial holdoff time.
When the interval value is set to zero, there will be a minimum 10 seconds
between the last time the local modem hung up and the next attempt (in
conformance with EIA-602).
Dial Holdoff does not apply in the case of failure to connect; instead, the Dial
Retry time is applied.
If any of the above parameters is changed, or if the event queue is reset with
the RESET ALARMS command, the holdoff counters and timers will be
reinitialized. This is to prevent spurious dial-outs.
Repeat Dialing and Prioritization
During dial-out, an alarm text message is sent according to a prioritization
scheme (the highest-severity alarm condition in effect is sent first). If there
are multiple alarms present at that level, the text is for the first-occurring
event.
Although Radio Sync Loss and Receive Power Below Threshold are both at the
level of ALARM, Radio Sync Loss takes priority over Receive Power Below
Threshold, for dial-out purposes. (Both are at the ALARM level for SET
ALARM THRESHOLD and SET DIAL THRESHOLD.)
Alarm conditions of a persistent nature, that do not clear themselves, will
result in repeated dial-outs. Alarms of this class include all the conditions at
the ALARM and FAULT levels, such as Radio Sync Loss and Receive Signal
Level Below Threshold. One-time events, such as Errored-second threshold
exceeded, and fault-cleared conditions, result in only a single dial-out.
3-28
Rev. B - 1/97
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Configuration
Telephone Numbers and Dial Format
The primary telephone number is the first number dialed. Ringing will continue
for a user-specified period (default is 30 seconds) before giving up as
unanswered. When the connection to the primary telephone number is not
successful, then the secondary number is attempted.
If neither the primary nor the secondary number is successful, then the AirLinkT1 waits for a Dial Retry period before retrying. In this case, an advisory event
is logged stating the reason for the failed dial-out. In addition, if the unit is
unable to communicate with the modem, it will continuously retry (no holdoff
period is imposed), and log an advisory. Only one advisory message of each
type will be logged per dialing session (from the first failed attempt until dialout is successful) in order to prevent the event queue from becoming flooded with
dial-out failures. No busy or no-answer advisory event will cause a dial-out.
The telephone numbers are entered as 40 characters, including the "ATDT"
prefix. If there is no primary number, the secondary number is never attempted.
The following characters may be used in the telephone number fields:
0-9Dial numbers
, (comma)Pause 1 second each before processing next char
(to wait for second dial tone after dialing '9')
!Flash (0.5 second ON-HOOK signal)
@causes the modem to wait 30 seconds for one or more rings
followed by 5 seconds of silence before processing the next
character. This is used when the system being called does not
provide a dial tone.
# # key on touch-tone telephone keypad
** key on touch-tone telephone keypad
- (dash)No meaning; provided for user convenience
( )No meaning; provided for user convenience
' 'Blank spaces are ignored.
User-Directed Connections
To troubleshoot, enter the command to dial a specific telephone number and
hold the connection. The syntax for this command is:
CONNECT 1
Rev. B - 1/97
CONNECT 2
3-29
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Configuration
CONNECT telephone-number
When the parameter is given as 1 or 2, the unit will dial the stored primary or
backup phone number respectively. Otherwise, the modem will dial the
number supplied on the command line. The telephone number must follow the
syntax of the configured telephone numbers.
CONNECT does not automatically retry upon dial-out failure; this is strictly a
manual operation. To redial, use the control-R key to repeat the last command.
When this command is used, the connection remains in effect until the user
issues a DISCONNECT command, the remote modem hangs up, or (if
configured), a Connection Timeout timer expires.
Manual or automatic connections can be terminated immediately by using the
following command:
DISCONNECT
This immediately hangs up the telephone connection and returns the dial-out
function to IDLE. RTS is returned to its configured state and DTR is released.
DISCONNECT also abandons any dial-out attempt in progress but does NOT
prevent future dial-outs. For this reason, the mode should be set to DISABLED
before performing any maintenance functions.
RS-232 Modem Port Interface
Data Rate and Port Parameters
The Data Rate is part of the port configuration. The available rates are 1200,
2400, 4800, and 9600 bits per second.
So-called "smart modems" of the type commonly in use, "auto-baud" or adjust
their RS-232 bit rate to that of the DTE.
Before using an unknown modem, it is a good idea to reset its configuration to the
factory defaults, then configure the three-wire operation if desired. For most
modems, this can be accomplished by issuing the following commands:
AT&F<RETURN>Reset to factory defaults
AT&K0<RETURN>Ignore RTS
AT&D0<RETURN>Ignore DTR
The remaining unchanging port parameters are:
1 start bit
1 stop bit
3-30
Rev. B - 1/97
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Configuration
8 data bits
no parity
Protocol Modems
Protocol modems support MNP or other data compression. Since protocol
modems introduce unneeded complications for flow control, and the AirLink Pro
T1/E1 Rack Mount modem data rate needs are modest, such protocols should be
turned off. However, error correction should be enabled if available; it will
prevent garbage characters from appearing on the remote terminal when the
unit hangs up the modem. This option is normally enabled by factory default on
modems equipped with it.
RTS Control
RTS Control allows the Request-To-Send (RTS) line to be set to Continuous or
Switched. When set to Continuous, the RTS is asserted at all times. When set
to Switched, the RTS line is asserted.
The unit will wait a reasonable time (so the unit does not hang) for the modem
to release the CTS line before reasserting the RTS line to begin any future
transmit cycles. The Switched mode is used with modem sharing devices.
When the DTR line is needed for modem sharing devices, it can be configured to
perform the modem enable function. If the DTR line is configured for a modem
sharing device, it will perform the same as the RTS line and the response will
come from the CTS line.
Responses
All numeric responses are followed by <CR> (ASCII 13 decimal). All “word”
responses are followed by <CR> and <LF> (ASCII 10 decimal).
Rev. B - 1/97
3-31
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Configuration
Table 3-3
Modem Response Definitions
Modem ResponseDefinition
0 (zero)Numeric version of "OK"
OKSuccessful execution of non-dial command
CONNECT[XXXX] carrier detected; XXXX = numeric bit rate
RINGRinging detected
NO CARRIERNo connection established, or connection lost
ERRORError in command line
NO DIALTONENo dial tone present
BUSYBusy signal
NO ANSWER5 seconds of silence not detected if '@' dial modifier was used.
3-32
Rev. B - 1/97
User Interface Additions
Table 3-4
Modem Commands
ParameterSpecification
SET ALARM HOLDOFF0-600 (seconds)
SET ANSWER TIMEOUT0-99 (seconds)
SET CONNECTION TIMEOUT0 - 43200 (seconds; 0 means no time-out)
SET DIAL{TONE | PULSE}
SET DIAL HOLDOFF0-5000 (minutes, repeat dial holdoff)
SET DIAL LEVEL{FAULT | ALARM | ADVISORY | STATUS}
SET DIAL RETRY15-3600 (seconds)
SET MODEM MODE{DISABLED | DEDICATED DIAL_OUT | ANSWER | BOTH}
SET MODEM RATE{1200 | 2400 | 4800 | 9600}
SET MODEM RTS{SWITCHED | CONTINUOUS}
SET MODEM CTS{OBEY | IGNORE}
SET MODEM DTR{SWITCHED | CONTINUOUS}
SET MODEM VOLUME{OFF | LOW | MEDIUM | HIGH}
SET MODEM XOFF{OBEY | IGNORE}
SET PHONE 1(XXX) XXX-XXXX
SET PHONE 2(XXX) XXX-XXXX
SET REPEAT COUNT0-99
SET RINGCOUNT0-9
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Configuration
Rev. B - 1/97
The GET MODEM command retrieves all of the Modem Command parameters.
This command produces a screen displaying all of the settings, the dial-out
status, and the date and time. In addition, all the SET and GET commands are
available via the REMOTE prefix.
This is the period of time between the onset of the first alarm condition, and
the unit dialing out to report the alarm. During this period, an alarm condition
must have existed continuously, or a minimum number of events must have
occurred. The minimum number of events is defined by Repeat Count. The alarm
events must be all be at or above the severity level, as defined by Dial Level.
To set this value, type the command:
SET ALARM HOLDOFF XXX <RETURN>
where XXX is the time period in (0 - 600) seconds. The default is 10.
Repeat Count
The number of alarm events occurring at or above the Dial Level, during the
Alarm Holdoff period, before an Alarm Dialout is initiated.
To set this value, type the command:
SET REPEAT COUNT XX <RETURN>
where XX is the number of (2 - 1000) events. The default is 10.
Dial Level
The severity level that alarm events must be to contribute to an Alarm Dialout.
To set this level, type the command:
The period of time between alarm dial-outs. This time period is independent of
the alarm holdoff and dial retry time periods. To set this value, type the
command:
SET DIAL HOLDOFF XXX <RETURN>
where XXX is the period in (1 - 5000) minutes. The default is 1.
Dial Format
Rev. B - 1/97
To set the Dial format to TONE or PULSE, type:
SET DIAL TONE <RETURN>
3-35
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Configuration
or
SET DIAL PULSE <RETURN>
The default setting is TONE.
Dial Retry
If the unit dials an alarm and reaches a busy or no answer signal, the unit will
dial a second number if one is specified. Both numbers are dialed before a
holdoff period is imposed. There is no automatic retry when the unit is
configured for manual dialing.
To set the holdoff period before the unit dials the first number again, type the
command:
SET DIAL RETRY XXX <RETURN>
where XXX is the period in (15 - 3600) seconds. The default is 60.
Modem (Enabling) Mode
This is the modem operation mode that is described in the section Using the
Network Management (Modem) Port. To set this mode, type the command:
This is the bit rate of the modem port. To set this parameter, type the
command:
SET MODEM RATE {1200 | 2400 | 4800 | 9600}
The default is 9600.
Modem RTS Mode
This mode governs whether the modem port RTS line is permanently asserted,
or switched on only when the port is sending characters. The RTS line is not
needed for use with smart modems. To change the mode, type the following
command:
3-36
SET MODEM RTS {SWITCHED | CONTINUOUS}
The default mode is CONTINUOUS.
Rev. B - 1/97
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Configuration
Modem DTR Mode
This governs whether the modem port DTR line is permanently asserted or
switched on only when the port is sending characters. The DTR line is not
needed for use with smart modems. To change the mode, type the following
command:
SET MODEM DTR {SWITCHED | CONTINUOUS}
The default mode is CONTINUOUS.
Phone Numbers 1 and 2
Phone number 1 is the phone number that the unit will dial first when trying to
send out an alarm message. The phone number must be specified if a dial-out
mode is chosen. Phone number 2 is an optional second phone number that the
unit will dial if Phone number 1 is busy or does not answer.
To set phone numbers, type the command:
SET PHONE 1 XXX-XXXX <RETURN>
or
SET PHONE 2 XXX-XXXX <RETURN>
where XXX-XXXX is the phone number. Any string of up to 20 characters is
acceptable, provided the modem can interpret it. This string is preceded by the
letters ATDT or ATDP depending on whether tone or pulse dialing is selected.
Any special dialing prefixes should precede the number entered here, such as
“9," for dialing out from a PBX, or any special sequences for disabling Call
Waiting. For example:
SET PHONE 1 9, 555-5555 <RETURN>
Ring Count
This mode determines the number of rings the modem at the unit end will
answer. In order to use this command, the modem must be connected to the unit
and preferably be on hook. To set this value, type the command:
SET RINGCOUNT X <RETURN>
where X is the number of ( 0 - 9) rings. Zero (0) means Do Not Answer. The
default is 1.
Rev. B - 1/97
3-37
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Configuration
Answer Timeout
For dialing out, this is the time period after that the unit will declare a noanswer condition, and if a second phone number is defined, attempt that number.
To set this value, type the command:
SET ANSWER TIMEOUT XX <RETURN>
where XX is the period in (0 to 99) seconds. The default is 30 seconds. This can
be adjusted depending on the number of rings that the remote modem is
programmed to answer.
Connection Timeout
This mode determines the time period the unit will terminate a manual
connection, either dial-in or dial-out. To set this value, type the command:
SET CONNECTION TIMEOUT XXXX <RETURN>
where XXXX is the time period in (0 - 43200) seconds. The default value is 3600
(one hour). A value of zero means that no time-out will be applied and the
modem link will remain connected indefinitely.
Getting AirLink Pro T1/E1 Rack Mount Configuration
Information
The GET command keyword requests configuration-related information from the
AirLink Pro T1/E1 Rack Mount. Use the REMOTE command keyword to request
configuration-related information from the far-end AirLink Pro T1/E1 Rack
Mount on the following:
❚Configuration parameter settings
❚Threshold settings
❚Hardware and software revision levels
Configuration Parameter Settings
To list the current configuration parameter settings, type the following
command at the AirLink Pro T1/E1 Rack Mount prompt:
3-38
AIRLINK PRO T1/E1> get configuration
Rev. B - 1/97
The system displays a list of information similar to the following:
AIRLINK PRO T1/E1> get configuration
Site Name: Cylink Sunnyvale 2
To list the hardware and software revision information, type the following
command at the AirLink Pro T1/E1 Rack Mount prompt:
AIRLINK PRO T1/E1> get revision
The system displays a similar list:
AIRLINK PRO T1/E1> get revision
Rev. B - 1/97
Site Name: sunnyvale 2
Digital Assembly: 14501-010
3-39
AirLink Pro T1/E1 Rack Mount Installer’s Guide
Configuration
Digital List: 1
Digital Issue: A
Digital S/N: 001
FPGA Rev: 14496-0100
Software Rev: 1.00
IF Assembly: 13559-020-03
IF List: 1
IF Issue: A
IF S/N: 001
Top Assembly: 14413-010-00
Top Assembly:S/N: 00000000
OK
Command Keywords and Operands
In addition to the SET and GET command keywords, the terminal user interface
provides command keywords that monitor status, performance, and alarms, to
initiate QRSS and loop tests, and reset alarm and test counters.
The command keywords are described in Appendix C, Commands.
3-40
Rev. B - 1/97
C
HAPTER
HAPTER
C
Operations and Maintenance
Operations and Maintenance
This chapter contains information on the operation and maintenance
of the AirLink Pro T1/E1 Rack Mount procedures for monitoring the
alarm queue, and describes how the AirLink Pro T1/E1 Rack Mount
responds to particular alarm conditions.
AirLink Pro T1/E1 Rack MountInstaller’s Guide
Operations and Maintenance
Overview
This chapter focuses on monitoring system operation by querying for status,
performance, and alarm information through the terminal user interface. This
chapter also includes descriptions of the LEDs on the AirLink Pro T1/E1 Rack
Mount digital module. Finally, this chapter describes the diagnostic tests and
procedures used to isolate and resolve errors occurring during radio unit
operation.
Programmed Configuration Parameters
AirLink Pro T1/E1 Rack Mount operation is governed by user-selectable
configuration and control parameters that reside in the non-volatile memory of
the unit. These parameters are displayed and controlled through a terminal
device that can access both the local and remote unit. When power is lost and
then restored, the system reconfigures itself from its protected configuration
database.
A long-life lithium battery protects all system configuration settings during
power losses. The battery is part of the non-volatile memory/real-time clock
circuitry on the digital module in the AirLink Pro T1 and has a 10-year storage
life (in the absence of power to the AirLink Pro T1/E1 Rack Mount).
CAUTIONThe component containing the lithium battery is NOT a customer-replaceable part. Do not
expose the lithium battery cell by opening the component. Do not attempt to recharge the
battery. Do not dispose of the component by fire. The lithium battery could explode if
mistreated.
Refer to Chapter 3, Configuration, for more information on changing
configuration parameter settings.
Acquiring Status Information
Each AirLink Pro T1/E1 Rack Mount system maintains an internal database of
status and performance information that it uses, in part, to derive the events
that are stored in the event queue. The status information categories include:
❚T1 DTE Input Loss
4-2
❚Radio Synchronization Loss
Rev. B - 1/97
❚Burst Synchronization Loss
❚Test in Progress
❚DTE Alarm Indicator Signal (AIS)
❚RF Alarm Indicator Signal (AIS)
❚Transmit module failure
❚Receive power level
❚Transmit power level
❚Temperature
All this information is available from both the local and the remote AirLink
Pro T1/E1 Rack Mount units.
Viewing Status Information
Airlink Pro T1/E1 Rack Mount Installer’s Guide
Operations and Maintenance
To view the status information for the local unit, type the following command
at the AirLink Pro T1/E1 Rack Mount prompt:
AIRLINK PRO T1/E1> query status
The system displays a list of status information similar to the following:
AIRLINK PRO T1/E1> query status
Site Name: Sunnyvale 2
DTE Loss: NO
Radio Sync Loss: NO
Burst Sync Loss: N/A
Test in Progress: FE Radio Remote Loop
DTE AIS: OFF
RF AIS: OFF
Tx Fail: NO
Rx Power: -60.5 dBm
Tx Power: 12.0 dBm
Temperature: 5 C
The significance of these information categories is explained in the following
sections.
Rev. B - 1/97
4-3
AirLink Pro T1/E1 Rack MountInstaller’s Guide
Operations and Maintenance
Site Name
The site name identifies the role or location of the specified AirLink Pro T1/E1
Rack Mount. In the previous example, “Sunnyvale 2” is the site name. This
parameter is optional and can be any convenient description up to 60
alphanumeric characters.
When using the Dial Out Alarm feature, it is important to have a descriptive
name because the Site Name is part of the specific alarm report.
It might also be useful to put AU in a site name when an Access Unit is at the
site.
T1/E1 DTE Input Loss
Indicates whether the T1/E1 signal on the cable from the DTE has been lost.
The T1/E1 input loss detector monitors the T1 or E1 input signal from the DTE
and declares DTE input loss when it detects 175 ±75 continuous zeros in the T1 or
E1 bit stream.
When the controller detects T1/E1 input signal loss, it instructs the transmitter
to send all ones toward the radio, updates the status reporting database, and
turns on the Signal Loss indicators in the AirLink Pro T1/E1 Rack Mount. In the
absence of a T1/E1 input signal, the unit switches to internal clocking.
Radio Synchronization Loss
Indicates whether radio synchronization has been lost. An action similar to
the DTE input loss occurs for radio synchronziation loss. See the previous
paragraph referring to the controller detecting signal loss.
Burst Synchronization Loss
Indicates whether burst synchronization has been lost. An action similar to the
DTE input loss occurs for burst synchronziation loss. See the paragraph referring
to the controller detecting signal loss under the heading DTE Input Loss.
Test in Progress
When a test is active, query status identifies the test by name. Only one test
can be run at a time. If you attempt to start up a second test while a test is
running, the system terminates the first test and inserts an event message in the
event queue.
4-4
Rev. B - 1/97
Airlink Pro T1/E1 Rack Mount Installer’s Guide
Operations and Maintenance
DTE Alarm Indication Signal (AIS)
DTE AIS is declared when Radio Sync Loss (RSL) is detected, or when there is
an active loop test that does not involve this DTE connection. The AirLink Pro
T1/E1 Rack Mount sends an unframed, all-ones signal toward the DTE. This
condition is cleared after RSL ceases or the loop test is terminated. For more
information on AIS conditions, refer to “Carrier Failure Alarms” in “Acquiring
Alarm Information”, later in this chapter.
RF Alarm Indication Signal (AIS)
RF AIS is declared when LOS is detected, or when there is an active loop test
that does not involve this connection. The AirLink Pro T1/E1 Rack Mount sends
an unframed, all-ones signal toward the remote AirLink Pro T1/E1 Rack Mount,
which passes it on to the remote DTE. This condition is cleared after LOS ceases
or the loop test is terminated. For more information on AIS conditions, refer to
“Carrier Failure Alarms” in “Acquiring Alarm Information” in this chapter.
Transmit Module Failure
Indicates whether service affecting a hardware failure has occurred.
Receive Power Level
A measurement, in dBm, representing the current receive power level for the
unit.
Transmit Power Level
A measurement, in dBm, representing the current transmit power level for the
unit.
Temperature
The temperature (in degrees Celsius) detected at the RF module in the AirLink
Pro T1/E1 Rack Mount.
Acquiring Alarm Information
As alarm events occur, they are signaled through indicators on the AirLink Pro
T1/E1 Rack Mount and are entered in the event queue. For a complete list of
events causing an alarm state, refer to the section “The Event Queue” in this
chapter.
Rev. B - 1/97
4-5
AirLink Pro T1/E1 Rack MountInstaller’s Guide
Operations and Maintenance
While indicators provide an observable indication of alarm conditions and
other behavior, the information available through the terminal connected to
the system is easier to access and interpret.
The Event Queue
When an alarm is detected, a message is entered into the AirLink Pro T1/E1
Rack Mount event queue. The event queue is a chronological list of up to 256
events. An alarm event is defined as the declaration of an alarm condition or
the clearing of an alarm condition. The event queue logs the cause and time of
individual alarm events as they occur.
Events Causing an Alarm State
The following events cause an alarm state in the AirLink Pro T1/E1 Rack Mount
and insert an alarm entry in the event queue:
• Receive level below the threshold
• Transmit level below the threshold
• T1 input signal loss
• Error count exceeds the threshold
• Synthesizer loss of lock
• Radio sync loss
• Transmit burst sync loss
Carrier Failure Alarms
The AirLink Pro T1/E1 Rack Mount responds to a carrier failure differently
than devices in a conventional network scheme.
In a conventional network scheme (Figure 4-1), if a cable breaks and disrupts
the network signal, the device immediately downstream from the break detects
the loss of signal and enters a red alarm state.
In the red alarm state, the device sends an unframed, all-ones Alarm Indication
Signal (AIS)—also known as a “blue” signal—toward its downstream neighbor
and a Remote Alarm Indication (RAI), or “yellow “signal back towards its
upstream neighbor.
4-6
Rev. B - 1/97
Airlink Pro T1/E1 Rack Mount Installer’s Guide
Operations and Maintenance
Figure 4-1
Conventional Carrier Failure Response
If the microwave signal is lost between two AirLink Pro T1/E1 units
(Figure 4-2), both AirLink Pro T1/E1 units enter the local alarm state and send
an unframed, all-ones AIS (blue alarm) back toward its neighboring network
device. When the RF signal is regained, the AirLink Pro T1/E1 will come out of
the alarm state in about 10 ms.
Rev. B - 1/97
Figure 4-2
AirLink Pro T1 Carrier Failure Response
If one of the three AirLink Pro T1/E1 Rack Mount loopback tests is active, AIS
is sent toward that portion of the link that has been excluded by the loop, so
the location and direction of the AIS depends upon which loopback test is
active. For more information about AIS and loopback tests, refer to “Loopback
Tests” in “Diagnostic Tools,” in this chapter.
Note that the other equipment in the network can take action upon receiving
alarm signals and might or might not restore service when the alarm clears.
Viewing the Event Queue
To view the event queue for the local unit, type the following command at the
AirLink Pro T1/E1 Rack Mount prompt:
4-7
AirLink Pro T1/E1 Rack MountInstaller’s Guide
Operations and Maintenance
AIRLINK PRO T1/E1> query alarms
The system displays a list of alarm information similar to the following:
AIRLINK PRO T1/E1> query alarms
8: 8001: 20 SEP 1995 15:11:32 QRSS Test Started
7: C006: 20 SEP 1995 15:11:31 All Tests Cleared
6: 8007: 20 SEP 1995 15:09:50 FE Remote Loop Test Started
5: C006: 20 SEP 1995 15:09:50 All Tests Cleared
4: C006: 20 SEP 1995 15:07:51 All Tests Cleared
3: 8001: 20 SEP 1995 15:06:22 QRSS Test Started
2: C006: 20 SEP 1995 15:06:22 All Tests Cleared
1: C000: 20 SEP 1995 14:59:22 Event queue Cleared
NOTECentral office equipment, such as PBXs, and routers usually take some action when
receiving AIS, and might or might not automatically restore service after AIS is cleared.
When the signal is regained, it will halt AIS within 10 milliseconds.
When the event queue contains alarm messages, the most recent message with
the most recent time and date displays at the top of the list.
When there are more messages than will fit on one screen, you can page through
the messages by pressing <Return> to go forward one screen, or <B><Return> to
go back one screen. Press <Q> to exit (quit) the event queue display.
To view the event queue of the remote unit, use the command:
AIRLINK PRO T1/E1> remote query alarms
Resetting the Event Queue
To reset the event queue for the local unit, type the following command:
AIRLINK PRO T1/E1> reset alarms
The system prompts you to confirm the event queue reset request:
AIRLINK PRO T1/E1> reset alarms
Reset alarms: Are you sure? (Y/N)
When you enter y (yes) to confirm the request, the system clears the event
queue. If you enter n (no) or just press <Return>, the system ignores the event
queue reset request. If you query the event queue at this point, you should see
only one event, Alarm Queue Reset.
4-8
Rev. B - 1/97
The size of the Alarm Queue is 256 lines. No more alarms are logged when the
action is full.
AirLink Pro T1/E1 Rack Mount Indicators
The AirLink Pro T1/E1 Rack Mount has five front-panel indicators. These
indicators (LEDs) are duplicated on the rear panel. Refer to Figure 4-3 and 4-4.
Airlink Pro T1/E1 Rack Mount Installer’s Guide
Operations and Maintenance
Figure 4-3
Front Panel Indicators
Figure 4-4
Rear Panel Indicators
Rev. B - 1/97
4-9
AirLink Pro T1/E1 Rack MountInstaller’s Guide
Operations and Maintenance
Table 4-1
Visual Indicators
NameColorFunction
PowerGreenIndicates that primary power is applied to the
Major AlarmRedWhen ON, indicates that one or more of the
Minor AlarmYellowWhen ON, indicates that one or more of the
Sync SourceGreenWhen ON, indicates that this unit is a source of
T1/E1 SIG LossRedWhen ON, indicates the T1/E1 input signal from
equipment and the power supply is working.
following events has occurred.
-Transmit Power below threshold
-Synthesizer Loss of Lock (equipment failure)
-Transmitter Failure
- DTE Input Loss
- Radio Sync Loss
- Loss of primary burst sync (single sync bus)
- Loss of primary and backup burst sync (dual
sync bus)
following events has occurred.
- RCV Input Level Below Threshold
- Unit has been placed in a test mode
- ES threshold exceeded
- UAS threshold exceeded
- Loss of primary or backup burst sync (dual
sync mode)
burst sync for other AirLinks.
the DTE has been lost or all zeros.
Acquiring Performance Information
Each AirLink Pro T1/E1 Rack Mount system maintains an internal database of
status and performance information that it uses, in part, to derive the events
that are stored in the event queue. The performance information categories
include:
❚Quasi-Random Signal Sequence Bit Error Rate (QRSS BER)
❚Errored Second (ES) counts (1-hour and 24-hour)
❚Unavailable Second (UAS) counts (1-hour and 24-hour)
4-10
Rev. B - 1/97
❚Receive Signal Quality (RSQ)
The AirLink Pro T1/E1 Rack Mount uses a Cyclic Redundancy Check (CRC)
error-checking system that constantly monitors the link error performance. The
CRC calculation is only performed on the T1/E1 payload. The CRC sequence is a
16-bit sequence that is appended to the end of the burst. The receiver on the
other end uses the same CRC-16 algorithm to perform the check on the received
burst and then compares the result. If the two checks do not match, the system
declares a CRC-16 error and increments the CRC-16 counter. Whether errored or
not, the CRC-16 sequence is removed and the payload is passed through to the
DSX-1 interface.
Viewing Performance Information
To view the performance information for the local unit, type the following
command at the AirLink Pro T1/E1 Rack Mount prompt:
AIRLINK PRO T1/E1> query performance
Airlink Pro T1/E1 Rack Mount Installer’s Guide
Operations and Maintenance
The system displays a list of performance information similar to the following:
The following sections contain significance information about these categories.
QRSS BER
When the QRSS test is active, the Quasi-Random Signal Sequence Bit Error
Rate (QRSS BER) is the count of QRSS bit errors detected. The error counter
normally used to count CRC-16 errors is used instead to count QRSS bit errors.
When the QRSS test is active, the count of ES and UAS errors is suspended and
the existing values held, unaffected by the QRSS test. These counts are
reactivated when the QRSS test is terminated.
The results of the QRSS BER calculation are displayed in one of the following
forms:
Rev. B - 1/97
unavailableWhen QRSS test is not selected, the word unavailable is
displayed.
4-11
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.