Wavetronix CLK-400 User Manual

Click 100–400 Series
USER GUIDE
Click 100–400 Series
USER GUIDE
www.wavetronix.com  78 East 1700 South Provo, Utah 84606  801.734.7200
© 2014 Wavetronix LLC. All Rights Reserved.
Wavetronix, SmartSensor, Click, Command, and all associated product names and logos are trademarks of Wavetronix LLC. All other products or brand names as they appear are trademarks or registered trademarks of their respective holders.
e Company shall not be liable for any errors contained herein or for any damages arising out of or related to this document or the information contained therein, even if the Company has been advised of the possibility of such damages.
is document is intended for informational and instructional purposes only. e Company reserves the right to make changes in the specications and other information contained in this document without prior notication.
FCC Part 15 Compliance: e Wavetronix SmartSensor sensors comply with Part 15 of the Federal Communications Commission (FCC) rules which state that operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesirable operation. FCC compli­ance statements for applicable optional modules are to be found in the module specications. Unauthorized changes or modications not expressly approved by the party responsible for compliance with the FCC rules could void the user’s authority to operate this equipment.
Disclaimer: e advertised detection accuracy of the Wavetronix SmartSensor sensors is based on both external and internal testing, as outlined in each product’s specication document. Although our sensors are very accurate by industry standards, like all other sen­sor manufacturers we cannot guarantee perfection or assure that no errors will ever occur in any particular applications of our tech­nology. erefore, beyond the express Limited Warranty that accompanies each sensor sold by the company, we oer no additional representations, warranties, guarantees or remedies to our customers. It is recommended that purchasers and integrators evaluate the accuracy of each sensor to determine the acceptable margin of error for each application within their particular system(s).
WX-500-0055 04/2012
Contents
Introduction 7
Using this Manual 7
Part I Introduction to the Click Series
Chapter 1 The Power Plant 11
Connecting to a Circuit Breaker 12 • Connecting AC Surge Protection 12 • Connecting Power 13 • Wiring AC Power into the Click 201/202/204 14
Chapter 2 T-bus Basics 17
Adding a T-bus to the DIN Rail 18 • Mounting Click Devices 18 • Wiring T-buses 18
Chapter 3 Wiring the Devices 21
Working with Screw Terminal Blocks 21 • RS-485 Communi­cation 22 • RS-232 Communication 24
Chapter 4 Installing Click Supervisor 27
Installing Click Supervisor 28 • Microso .NET Framework 31
Chapter 5 Using Click Supervisor 33
Connecting to Your Computer 33 • Accessing the Communi­cation Screen 34 • Serial Communication 35 • IP Communica­tion 37 • Working with Modules 38
Part II Individual Click 100–400 Series Modules
Chapter 6 Click 100 — 16 Output Contact Closure 43
Physical Features 44 • Troubleshooting 48
Chapter 7 Click 101 — Multi-sensor to Contact Closure 49
Physical Features 51 • Installation 54 • On-device Congura­tion 54 • Computer Conguration 55
Chapter 8 Click 104 — 4-channel DIN Rail Contact Closure 61
Physical Features 62 • Installation 64 • Conguration 65 • Rotary Switch 66 • Front Panel Menu 67 • Click Supervisor 73
Chapter 9 Click 110 — 4-channel Contact Closure Eurocard 79
Physical Features 80 • Installation and Wiring 82 • Fail-safe Mode 85 • Conguration 85 • DIP Switches 86 • Front Panel Menu 92 • Click Supervisor 101
Chapter 10 Click 112/114 — Detector Rack Cards 107
Physical Features 108 • Installation and Wiring 109 • Congu­ration 111 • DIP Switches 112 • Front Panel Menu 115
Chapter 11 Click 120/121 — Relay 129
Physical Features 130 • Installation 130
Chapter 12 Click 172/174 — Contact Closure Rack Cards 133
Physical Features 134 • Installing and Wiring the Click 172/174 136 • Operation Modes 136 • Power and Congu­ration 139 • Verify Operation 141 • Fail-safe Mode 142 • Troubleshooting 143
Chapter 13 Click 200 — Lightning Surge Protector 145
Physical Features 146 • Installation 147
Chapter 14 Click 201/202/204 — AC to DC Power Supply 151
Physical Features 152 • Installation 152
Chapter 15 Click 203 — UPS/Battery 155
Physical Features 156 • Installation 157 • On-device Congu­ration 158
Chapter 16 Click 210 — AC Circuit Breaker 161
Physical Features 162 • Installation 162
Chapter 17 Click 211 — AC Outlet 163
Physical Features 164 • Installation 164
Chapter 18 Click 221 — DC Surge Protector 167
Physical Features 168 • Installation 168
Chapter 19 Click 222 — System Surge Protector 169
Physical Features 170 • Installation 171
Chapter 20 Click 223 — Dual-485 Surge Protector 175
Physical Features 176 • Installation 177
Chapter 21 Click 230 — AC Surge Protector 179
Physical Features 180 • Installation 180
Chapter 22 Click 250 — Wireless Surge Protector 183
Physical Features 184 • Installation 184
Chapter 23 Click 301 — Serial to Ethernet Converter 187
Physical Features 188 • On-device Conguration 189
Chapter 24 Click 304 — RS-232 to RS-485 Converter 207
Physical Features 208 • On-device Conguration 209 • Com­puter Conguration 210
Chapter 25 Click 330/331 — Unmanaged Switches 219
Physical Features 220 • Installation 221 • Switching Character­istics 222
Chapter 26 Click 340/341/342 — Managed Switches 225
Physical Features 226 • Installation 228
Chapter 27 Click 400 — 900 MHz Radio 229
Physical Features 230 • On-device Conguration 231 • Com­puter Conguration 233
Chapter 28 Click 421 — Serial to Bluetooth® Radio 245
Physical Features 246 • On-device Conguration 247 • Com­puter Conguration 249
Introduction
In the introduction
Using this Manual
Wavetronix Click products are a simple and cost-eective way to connect various trac components into a single, unied system. With a broad range of easy-to-use products, the Click line integrates quickly and operates in even the harshest conditions. Click devices provide the power and communication solutions needed for eective trac control and management.
e Click series is divided into ve smaller, numerically based series. Each device in a par­ticular series shares common elements, functions, etc.:
Click 100 series – Contact closure devices Click 200 series – Power and surge protection devices Click 300 series – Wired communication devices Click 400 series – Wireless communication devices Click 500 series – Customizable devices built on our Click 500 platform
is user guide covers the Click 100–400 series. For the Click 500 series, please see the Click 500 Series User Guide.
Using this Manual
is manual is divided into two parts:
Part I: Introduction to the Click Series – is part contains information common to
the Click line, beginning with basic module installation guidelines. It then covers the
8 INTRODUCTION  CLICK 100–400 SERIES USER GUIDE
Click Supervisor soware, which is used with certain Click devices for conguration. For a list of Click 100–400 series devices that use Click Supervisor, see the beginning of Chapter 4.
A few Click devices dier from what is written in the common information chapters in the way they are installed or the soware used to congure them. In the event that a Click device departs from what is written in Part I, that dierence will be noted in that device’s chapter in Part II.
Part II: Individual Click 100–400 Series Modules – is part contains a chapter for
every device (or set of devices, in some cases) in the Click 100–400 series. Each chap­ter has an introduction to the device along with a description of the device’s physical features and, when pertinent, sections on installation, conguration, troubleshooting and more.
Part I
Introduction to the Click Series
Chapter 1 – The Power Plant Chapter 2 – T-bus Basics Chapter 3 – Wiring the Devices Chapter 4 – Installing Click Supervisor Chapter 5 – Using Click Supervisor
The Power Plant 1
In this chapter
Connecting to a Circuit Breaker Connecting AC Surge Protection Connecting Power
1
Power and surge protection are provided to your devices via the Click modules that make up what is known as the power plant (see Figure 1.1). Assembling the power plant is the rst step in installing your Click devices.
Figure 1.1 – The Click Power Plant
12 CHAPTER 1  THE POWER PLANT
Note
The power plant will only be used if your cabinet is supplied with AC power. If DC is coming into your cabinet, you will need the Click 221 DC surge protector, discussed in Part II.
Connecting to a Circuit Breaker
e rst Click module you will connect is the Click 210, a circuit breaker designed to inter­rupt an electric current under overload conditions. e breaker is trip-free and can be easily reset aer a current interruption by pushing the reset button (see the Click 210 chapter for more information on this device).
To add a Click 210 circuit breaker and switch:
1 Using a rocking motion, mount the Click 210 onto the DIN rail. 2 Make sure the reset button on front of the module is pressed down before wiring. 3 Connect the black (line) wire from the terminal block or from the AC cord into one
side of the module.
4 Connect power out of the other side.
Note
It doesn’t matter which side is power in, as long as the opposite end is power out.
Connecting AC Surge Protection
e next module in the power plant is the Click 230, which provides surge protection to other modules on the DIN rail (see the Click 230 chapter for more information on this de­vice). Use these steps to include AC surge protection in your installation:
1 Using a rocking motion, mount the Click 230 onto the DIN rail next to the Click 210. 2 Connect the wire from the Click 210 to the rightmost screw terminal (terminal 5) on
the side of the Click 230 marked IN (see Figure 1.2).
3 Connect the white (neutral) and green (ground) wires from the AC terminal block or
from the AC cord into screw terminals 1 and 3, respectively, also on the side marked IN.
4 Connect the outgoing neutral and power wires to screw terminals 2 and 6, respectively,
on the side marked OUT.
CHAPTER 1  THE POWER PLANT 13
Figure 1.2 – Click 230 Screw Terminals (labels beneath terminals have been added)
Screw terminals 3 and 4 are directly bonded via the metal mounting foot of the base ele­ment to the DIN rail. ere is no need for any additional grounding between terminals 3 and 4 and the DIN rail.
Note
If you are using a Click 211 in your installation, the configuration of the power plant will dier slightly from what is listed in this chapter, starting at this point in the installation process. See the Click 211 chapter of this manual for more information.
Connecting Power
e nal component of the power plant is the AC to DC converter. e Click line features several such converters. e Click 201/202/204 are AC to DC power supplies that provide DC power to every Click product mounted on the DIN rail. e Click 201 provides 1 A, the Click 202 provides 2 A and the Click 204 provides 4 A.
e screw terminals on the top and bottom of the Click 201/202/204 can be unplugged from the module, allowing you to pre-wire power before the nal installation. e screw terminal blocks are red-keyed, allowing the block to plug back into only one specic jack.
Note
If you prefer, instead of the Click 201/202/204, you can use the Click 203, which is a combination UPS and battery. This set of modules will convert AC to DC and provide uninterrupted power to your equipment. See the Click 203 chapter in Part II of this document for more information.
14 CHAPTER 1 THE POWER PLANT
Wiring AC Power into the Click 201/202/204
Use the steps below to properly wire AC power to the top of the Click 201/202/204:
1 Using a rocking motion, mount the Click 202/202/204 to the DIN rail next to the Click
230.
2 Connect the power and neutral wires from the Click 230 into the screw terminals
marked L and N, respectively, on the side of the module marked 100–240V AC In.
Figure 1.3 – Wiring AC Power into the Click 201/202/204
Caution
Make sure power to AC mains is disconnected while wiring the AC input.
Wiring DC Power out of the Click 201/202/204
e screw terminals on the bottom of the devices are slightly dierent. e Click 202 and 204 have a single terminal block, while the Click 201 has two; it doesn’t matter which of the two terminal blocks on the 201 you wire into. Connect one wire for DC power (red is standard) to a screw terminal marked +. Connect a second wire as a ground wire (black is standard) to either of the two terminals marked – (see Figure 1.4).
Note
Do not wire into the DCOK terminal; it provides only 20 mA and should only be used to monitor the power supply.
CHAPTER 1  THE POWER PLANT 15
Figure 1.4 – Wiring DC Power out of the Click 201/202/204
Caution
An authorized electrical technician should perform installation and operation of this unit. Persons other than authorized and approved electrical technicians should NOT attempt to connect this unit to a power supply and/or trac control cabinet, as there is a serious risk of electrical shock through unsafe handling of the power source. Ex­treme caution should be used when connecting this unit to an active power supply.
T-bus Basics 2
In this chapter
Adding a T-bus to the DIN Rail Mounting Click Devices Wiring T-buses
2
Now that the power plant is complete, the next step in installing your Click modules is add­ing a T-bus to your DIN rail. A T-bus is made up of small modules called T-bus connectors that snap onto your DIN rail to provide power and communication connections to your Click devices. You can connect together as many T-bus connectors as you need to provide power and communication to all the Click devices on the rail with only a single wiring con­nection.
Wavetronix has two varieties of T-bus connectors: green connectors, which conduct both power and communication, and gray connectors, which only conduct power. Gray T-bus connectors are used when you don’t want certain devices to communicate with each other. In such a case, a gray connector placed between the two devices would prevent communica­tion while still providing power.
Note
Wavetronix removes the communication lines from the gray T-bus connectors it pro­vides. Gray T-bus connectors obtained from suppliers other than Wavetronix, how­ever, will still have communication capabilities.
18 CHAPTER 2 T-BUS BASICS
Adding a T-bus to the DIN Rail
Placing the T-bus on the DIN rail is quick and easy. To attach a T-bus connector to the rail, simply position the connector over the rail with the male connector pointing to the right. Hook one arm of the connector over one side of the DIN rail and press the other arm down over the other side until the connector snaps in place. All the T-bus connectors you connect together should be facing this direction.
To connect T-bus connectors together, simply slide them toward each other until you hear them snap into place. To disconnect T-bus connectors, use a small, thin item, like a small screwdriver, to gently pry the two modules apart.
Mounting Click Devices
To connect a Click device to the DIN rail and T-bus, simply position the device over the T­bus connector and, using the same rocking motion used to connect the devices in the power plant, snap the device onto the DIN rail.
Note
Not all Click devices use the T-bus this way. Some devices, such as the 330, 331, 340, 341, 342, and those in the power plant, snap onto the DIN rail but not onto the T-bus. For more information on how to install these devices, see the appropriate chapters in Part II of this document.
Wiring T-buses
ere are two ways to provide power to a T-bus: wiring through a Click 200 and wiring through a 5-screw terminal block.
Wiring through a Click 200
e Click 200 is a surge protection device that can be connected to a sensor. e Click 200 is unique among Click devices because it can take power and communications in through its screw terminals and send it through any T-bus it is currently mounted on.
To provide power to a T-bus through a Click 200, follow these steps (see Figure 2.1):
1 Connect a Click 200 to a DIN rail and T-bus. 2 Connect the red (+24 VDC) wire from the Click 201/202/204 into the +DC screw ter-
minal on the side of the Click 200 marked PROTECTED.
3 Connect the black (ground) wire from the Click 201/202/204 into any of the terminals
marked GND on the same screw terminal block as the red wire.
CHAPTER 2  T-BUS BASICS 19
Figure 2.1 – Wiring Power into the Click 200
Wiring through a 5-screw Terminal
If you choose not to use a Click 200, or if you have one but prefer not to wire through it, you can also connect power through a 5-screw terminal block connected to the end of the T-bus.
To provide power to a T-bus through a 5-screw terminal block, follow these steps:
1 Attach a male 5-screw terminal block to the le end of the T-bus by aligning it with the
rst connector and pushing the modules together.
2 Connect the black (ground) and red (+24 VDC) wires from the Click 201/202/204
into the top two screw terminals in the 5-screw terminal block (see Figure 2.2 for the 5-screw terminal block pinout).
Figure 2.2 – 5-screw Terminal Block Pinout
Note
To disconnect a 5-screw terminal block from a T-bus connector, use a small, thin item, such as a small screwdriver, to gently pry the two modules apart.
20 CHAPTER 2  T-BUS BASICS
Wiring out of a T-bus
Occasionally you will need to provide power and communication to devices in your cabinet that are not on a DIN rail or on a T-bus. In these cases, you can connect a female 5-screw terminal block to the right side of your T-bus and wire +DC, ground and communication from there into the device.
Wiring the Devices 3
In this chapter
Working with Screw Terminal Blocks RS-485 Communication RS-232 Communication
3
You are now ready to begin adding Click modules to your cabinet. For information on the unique features of each of the devices in the Click line, see the corresponding chapter in Part II of this document (or of the Click 500 Series User Guide).
Despite having dierent features, there are certain elements that are similar across devices. Some of these, such as DIN rail mounting and the use of a T-bus for power and communi­cation, have already been discussed. is chapter will discuss another such element: wiring communication through the screw terminals.
Working with Screw Terminal Blocks
Many Click devices feature screw terminal blocks for wiring connections. ese screw ter­minal blocks simplify wiring because they can be removed from the Click device, then wired and reinserted.
To remove a screw terminal block, insert a small, thin item, such as a small screwdriver, into the gap between the screw terminal block and the Click device (just above the screw heads) and gently pry the two apart.
Aer wiring, simply reinsert the screw terminal block and push until it snaps into place. e screw terminal blocks are red-keyed, meaning they will only plug into their specic jacks.
22 CHAPTER 3  WIRING THE DEVICES
Figure 3.1 – Removing and Wiring Screw Terminal Blocks
RS-485 Communication
Another feature that is common to many Click devices is RS-485 communication capabili­ties. RS-485 is important for Click devices because it is carried on the T-bus to all the Click devices on a given DIN rail.
Connecting RS-485 communications to the Click devices on a DIN rail can be accom­plished in two dierent ways: through a 5-screw terminal on the end of a T-bus, or through a Click module, which will then communicate with the T-bus.
Note
The steps in this section are specifically for use with a Wavetronix SmartSensor ca­ble. If you are using a dierent cable or wiring system, the colors of the wires used will be dierent.
To connect through a 5-screw terminal, follow these steps.
1 Connect the +485 (white) wire from the terminal block or cable to the middle screw
terminal on the 5-screw terminal block connector you’re using for the T-bus in question (see Figure 2.2 in the previous chapter for the pinout of the 5-screw terminal block).
2 Connect the -485 (blue) wire from the terminal block or cable to the middle screw
terminal on the 5-screw terminal block.
3 Plug the 5-screw terminal block into the T-bus.
To connect through any Click device with RS-485 ports, follow these steps:
1 Ensure that the Click device is mounted on a T-bus connector. 2 Connect the +485 (white) wire from the terminal block or cable to the terminal marked
“+485” in the screw terminal blocks (see Figure 3.2).
3 Connect the -485 (blue) wire from the terminal block or cable to the terminal marked
“-485” in the screw terminal blocks.
4 Connect the RS-485 drain wire from the terminal block or cable to a GND terminal in
the screw terminal blocks.
CHAPTER 3  WIRING THE DEVICES 23
Note
If you are using a Click 200 in your installation, it is recommended you wire RS-485 through it if you would like to connect to a Click device.
Figure 3.2 – Wiring RS-485 Communication into the Click 200
Wiring RS-485 from a Click Device
Several Click devices—such as the 104, 110, 112/114, 172/174, 200, 301 and 304—also have RJ-11 jacks for RS-485 communication with a computer or with contact closure cards. To use, simply use an RJ-11 jumper cable to connect the two devices.
Figure 3.3 – A Click Device Showing RJ-11 and DB-9 Jacks
24 CHAPTER 3 WIRING THE DEVICES
RS-232 Communication
Most Click devices also feature RS-232 communication capabilities. ese modules will convert the RS-485 communication moving to and from the T-bus to RS-232. See below for how to connect RS-232 to a laptop.
Several modules also have RS-232 screw terminals.
Note
The steps in this section are specifically for use with a Wavetronix SmartSensor ca­ble. If you are using a dierent cable or wiring system, the colors of the wires used will be dierent.
To use, follow the steps below:
1 Connect the RTS (orange) wire from the cable or terminal block to the RTS screw ter-
minal on the protected side of the Click device (see Figure 3.4).
2 Connect the CTS (brown) wire to the CTS terminal on the protected side of the Click
device.
3 Connect the TD (yellow) wire to the TD terminal on the protected side of the Click
device.
4 Connect the RD (purple) wire to the RD terminal on the protected side of the Click
device.
5 Connect the RS-232 drain wire to a GND terminal on the protected side of the screw
terminal blocks.
CHAPTER 3  WIRING THE DEVICES 25
Figure 3.4 – Wiring RS-232 Communication into the Click 200
Wiring RS-232 from a Click Device
Many Click modules feature an DB-9 jack for RS-232 communication with a laptop or other such device. To use, simply use a straight-through cable to connect the two devices.
Installing Click Supervisor 4
In this chapter
Installing Click Supervisor Microsoft .NET Framework
4
Once your Click devices are installed and wired, the next step is to install Click Supervi­sor, a computer program that will help you work with your Click modules. Most Click devices can be congured and monitored to some extent using the buttons and LEDs on the module, but certain devices can be ne-tuned using Click Supervisor. ese computer­programmable devices include the following:
Click 101 – Multi-sensor to contact closure module Click 104 – 4-channel DIN rail contact closure module Click 110 – 4-channel contact closure Eurocard Click 112/114 – Detector rack cards Click 301 – Serial to Ethernet converter Click 304 – Intelligent RS-485 to RS-232 converter Click 306 – 1-port terminal server Click 400 – Autobaud 900 MHz spread spectrum radio Click 421 – Bluetooth® to serial converter
ere are also a number of Click 500 series devices that can be congured using Click Su­pervisor; these are discussed in the Click 500 Series User Guide.
28 CHAPTER 4  INSTALLING CLICK SUPERVISOR
Note
If you are running Windows® Vista, you must run Click Supervisor in XP Service Pack 2 compatibility mode. To switch to this mode, right-click on the Click Supervisor icon and select Properties from the drop-down menu. Go to the Compatibility tab. Under Compatibility mode, click the Run this program in compatibility mode for: check­box. This will enable the drop-down menu, allowing you to select Windows XP (Ser­vice Pack 2). Hit OK.
Installing Click Supervisor
If you have a Wavetronix Install Kit, the handheld computer included in the kit comes with Click Supervisor already installed, along with sensor soware. If you don’t have an install kit, or if you want to install on a desktop computer, follow the steps below.
Click Supervisor can be run on a Windows® PC and on ahandheld computer Everything needed to install Click Supervisor is contained in the Click Supervisor Setup.exe le. e setup program can install Click Supervisor on a PC, handheld computer or both.
Note
You must have administrator rights to run the setup program.
e soware can be downloaded from the Wavetronix website at www.wavetronix.com. Af­ter downloading the setup le, double-click on it to run the Click Supervisor setup wizard (see Figure 4.1).
Figure 4.1 – Click Supervisor Setup Wizard
CHAPTER 4  INSTALLING CLICK SUPERVISOR 29
To install Click Supervisor on a handheld computer, you need to have ActiveSync (on Win­dows XP or earlier) or Windows Mobile Device Center (on Windows Vista). If you do not have these programs, they are available for download on the Microso website.
If you do not have ActiveSync or Windows Mobile Device Center installed on your com­puter, skip to the next section, titled Installing Click Supervisor on a PC.
If you do have ActiveSync or Windows Mobile Device Center installed on your computer, the setup program will detect this and the next screen that comes up will prompt you to se­lect where you want to install Click Supervisor: a PC, a Pocket PC, or both (see Figure 4.2).
Figure 4.2 – Selecting an Installation
If you select Computer, the program will go through the steps outlined in the next section, Installing Click Supervisor on a PC. If you select Pocket PC, the program will go through the steps in the section titled Installing Click Supervisor on a handheld computer. If you select both, the program will go through both installation processes, beginning with install­ing on the PC.
Note
Although the software can be installed on most handhelds, because of constantly changing handheld technologies, Wavetronix can only oer technical support on the handheld in the kit, which is a Socket Mobile 650.
Installing Click Supervisor on a PC
Follow these steps to install Click Supervisor on a PC:
1 On the screen shown in Figure 4.2, click the checkbox labeled Computer and then
select Next > >.
2 Select an installation location. e default location provided is normally “C:\Program
Files\Wavetronix.” Click Browse to choose another location (see Figure 4.3).
30 CHAPTER 4  INSTALLING CLICK SUPERVISOR
Figure 4.3 – Location to Be Installed
3 Click the Install Now button. 4 Aer Click Supervisor is installed, you can create shortcuts to the soware on the desk-
top and in the start menu using the corresponding checkboxes on the nal screen (see Figure 4.4). If no shortcuts are desired, uncheck the corresponding boxes. If you are installing on a Pocket PC at the same time, this screen will not appear until both instal­lations are complete.
Figure 4.4 – Shortcut Options
5 Click the View release notes when nished checkbox to view the Click Supervisor
release notes. e release notes contain additional information about the current ver­sion of the Click Supervisor soware. A PDF reader program such as Adobe Acrobat Reader is required to view the release notes.
6 Click Finish to complete the setup process.
Installing Click Supervisor on a Handheld Computer
Although the soware can be installed on many handheld computers, because of constantly changing handheld technologies, Wavetronix can only oer technical support on the hand­held in the kit, which is a Socket Mobile 650.
CHAPTER 4  INSTALLING CLICK SUPERVISOR 31
Use these steps to install Click Supervisor on a handheld computer:
1 Ensure that you have ActiveSync or Windows Mobile Device Center installed and that
the handheld is connected to the PC and synced.
2 On the screen shown in Figure 4.2, click the checkbox labeled Pocket PC and then
select Next > >.
3 On the next screen, click Continue > > to start the installation process (see Figure
4.5). e setup program runs the Add/Remove Programs application for Windows handheld devices. If a handheld device is connected to the computer, Add/Remove Programs will immediately begin installing Click Supervisor on the handheld device. If a device is not connected to the computer, Click Supervisor will be downloaded the next time a handheld device is connected to the computer.
Figure 4.5 – Adding Click Supervisor to a Pocket PC
4 Click OK once the download is complete.
Microsoft .NET Framework
e Click Supervisor setup program will automatically detect whether Microso .NET Compact Framework v1.1 is installed on your PC. If it is not installed, you will be prompted to install it (see Figure 4.6).
32 CHAPTER 4  INSTALLING CLICK SUPERVISOR
Figure 4.6 – Microsoft .NET Framework Prompt
Use the following steps to install Microso .NET Framework:
1 Click the Install Framework button. 2 Click the I Agree radio button when the License Agreement appears (see Figure 4.7).
Figure 4.7 – Microsoft .NET License Agreement
3 Click Install. A window will appear stating that the .NET Framework has been in-
stalled successfully.
4 Click OK and you will be returned to the Click Supervisor setup program.
Using Click Supervisor 5
In this chapter
Connecting to Your Computer Accessing the Communication Screen Serial Communication IP Communication Working with Modules
5
Once you have Click Supervisor installed on your computer, you can begin using it to con­gure and monitor your Click devices.
Connecting to Your Computer
e rst step is to connect your computer to the Click modules on your DIN rail so that Click Supervisor can see them. Click Supervisor can detect all computer-programmable devices that are connected together by either a wired or wireless connection.
You can do this one of two ways. If you are using an Ethernet connection, you must be on the same network with the Click device. Plug the Ethernet cable from your computer or switch to the RJ-45 jack on the front of the Click 301. You must use a crossover cable to connect your computer to the Click 301 via Ethernet.
If you are using a serial RS-232 connection, the computer needs to be connected by a straight-through serial cable to the DB-9 connector on the front of any one of the comput­er-programmable devices on the T-bus. See the beginning of Chapter 4 for a list of Click 100–400 series devices that can be congured using Click Supervisor.
34 CHAPTER 5  USING CLICK SUPERVISOR
Connecting the computer to another device that has a RS-232 port but is not computer­programmable, such as the Click 200, will not allow Click Supervisor to communicate with the other computer-programmable devices on the T-bus.
Accessing the Communication Screen
To connect to your devices with Click Supervisor, open the program by double-clicking on it. It will bring you to the Click Supervisor main screen (see Figure 5.1).
Figure 5.1 – Click Supervisor Main Screen
Click on Communication to access the Communication screen (see Figure 5.2). ere are two ways to connect to your Click devices: through a serial connection or an IP connection.
Figure 5.2 – Communication Screen
CHAPTER 5  USING CLICK SUPERVISOR 35
Serial Communication
e rst section on the Communication screen is Serial Communication. Here you can connect to a Click device through an RS-232 cable.
Changing Settings
Click Settings to bring up the Serial Settings screen (see Figure 5.3).
Figure 5.3 – Serial Settings Screen
COM Port – Allows you to change the serial connection port. Baud Rate – Allows you to change the baud rate or set it to auto-detect. Flow Control – Is usually only used if you are connecting your computer to an RS-232
device that requires hardware handshaking.
Parity – Allows you to set parity error checking. Stop Bits – Allows you to set the number of stop bits. Data Bits –Allows you to set the number of data bits being sent.
Note
The flow control, parity, stop bits and data bits settings should not be changed un­less you have been instructed to do so by Wavetronix Technical Services.
Click the Save as default settings checkbox to tell the soware to remember your setup. Click OK to return to the Communication screen or Cancel to exit without saving your settings.
On the Communication screen, you can see the settings reected in the Port: and Baud: entries. Port: shows the port you’ve set the program to communicate through, and Baud: shows the baud rate, as set under Settings or as automatically detected.
36 CHAPTER 5  USING CLICK SUPERVISOR
Connecting to a Device
Click Supervisor can talk to one device at a time. ere are two ways to select which module to talk to.
Follow these steps if you know the Click ID number of the device:
1 Enter the ve-digit ID number in the Click ID text eld, either by typing or by using
the arrows to the right of the box.
2 Click Connect. Aer downloading the communication le, the program will return
you to the Click Supervisor main screen.
Note
You can find the Click ID number of your device by looking at the number beneath the barcode. The ID number is the last five digits of this number. Each device on a rail must have a unique number. The number it’s been assigned should be unique, but if it is not, you can change it after connecting to the device. See that device’s chapter in Part II of this guide for more information.
Alternatively, you can connect without the ID number:
1 Leave a 0 in the Click ID text eld. Click Supervisor will look for all connected devices
on the network.
2 Click Connect. e Device Selection screen will appear (see Figure 5.4). e comput-
er-programmable devices on the network will appear as they are detected. e device list is divided into three columns: ID shows the ID number of the device, Click shows the product number of the device, and Description shows the user-dened description of the device.
Figure 5.4 – Device Selection
CHAPTER 5  USING CLICK SUPERVISOR 37
3 Click on the device you’d like to connect to and hit Select. Aer downloading the com-
munication le, the program will return you to the Click Supervisor main screen.
Note
After connecting, you may see a dialog box asking if you’d like to upgrade. Each ver­sion of Click Supervisor has the newest firmware for all the Click devices, and when it connects to a device it will check to see if the firmware in the program is newer than that in the device. If it is, you will see the dialog box. If you’d like to upgrade your device with the newest firmware, click Yes .
IP Communication
e second section on the Communication screen is IP Communication. To connect to the devices on your network, rst enter the IP address assigned to the Click 301 (or other Ethernet communication device connected to your modules), then enter the port number. e default port number for the Click 301, as well as many other such devices, is 10001. e default IP address is 172.16.0.13.
Once a connection is made, Click Supervisor will remember the information so you don’t have to type it the next time.
Connecting to a Device
As with a serial connection, you must choose which device Click Supervisor will connect to. ere are two ways to select which device to talk to.
Follow these steps if you know the Click ID number of the device:
1 Enter the ve-digit ID number in the Click ID text eld, either by typing or by using
the arrows to the right of the box.
2 Click Connect. Aer downloading the communication le, the program will return
you to the Click Supervisor main screen.
Note
You can find the Click ID number of your device by looking at the number beneath the barcode. The ID number is the last five digits of this number. Each device on a rail must have a unique number. The number it’s been assigned should be unique, but if it is not, you can change it after connecting to the device. See that device’s chapter in Part II of this guide for more information.
38 CHAPTER 5  USING CLICK SUPERVISOR
Alternatively, you can connect without the ID number:
1 Leave a 0 in the Click ID text eld. Click Supervisor will look for all connected devices
on the network.
2 Click Connect. e Device Selection screen will appear, and aer a few moments, the
list will be populated with the computer-programmable devices on the network. e list is divided into three columns: ID shows the ID number of the device, Click shows the product number of the device, and Description shows the name of the device.
3 Click on the device you’d like to connect to and hit Select. Aer downloading the com-
munication le, the program will return you to the Click Supervisor main screen.
Note
After connecting, you may see a dialog box asking if you’d like to upgrade. Each ver­sion of Click Supervisor has the newest firmware for all the Click devices, and when it connects to a device it will check to see if the firmware in the program is newer than that in the device. If it is, you will see the dialog box. If you’d like to upgrade your device with the newest firmware, click Yes .
Working with Modules
You will now be able to select Setup Click and choose a driver to start working with the device (see Figure 5.5). e drivers under Setup Click will be dierent for every device you connect to. For information on how to congure each device through Click Supervisor, see that device’s chapter in Part II or in the Click 500 Series User Guide for more information.
Figure 5.5 – Selecting a Driver
From the Select Driver screen, you can also access backups you’ve made of settings (how to save these settings is discussed in each chapter in Part II that deals with Click Supervisor).
CHAPTER 5  USING CLICK SUPERVISOR 39
To open a backup, select the Backups radio button in the lower righthand corner of the screen. All the backups currently saved in the correct folder will appear (see Figure 5.6). Select the backup you wish to open and click OK.
Figure 5.6 – Selecting a Backup
Note
The default folder to save backups in is C:\Program Files\Wavetronix\ClickHome\ Drivers\ [model number] \User. If you try to save the files elsewhere, the program will still save them in the User folder.
Aer you’ve nished conguring a device, you can connect to another one by returning to the Communication screen, closing the connection, and connecting to a dierent device.
Part II
Individual Click 100–400 Series Modules
Chapter 6 – Click 100 Chapter 7 – Click 101 Chapter 8 – Click 104 Chapter 9 – Click 110 Chapter 10 – Click 112/114 Chapter 11 – Click 120/121 Chapter 12 – Click 172/174 Chapter 13 – Click 200 Chapter 14 – Click 201/202/204 Chapter 15 – Click 203 Chapter 16 – Click 210 Chapter 17 – Click 211
Chapter 18 – Click 221 Chapter 19 – Click 222 Chapter 20 – Click 223 Chapter 21 – Click 230 Chapter 22 – Click 250 Chapter 23 – Click 301 Chapter 24 – Click 304 Chapter 25 – Click 306 Chapter 26 – Click 330/331 Chapter 27 – Click 340/341/342 Chapter 28 – Click 400 Chapter 29 – Click 421
Click 100 —
16 Output Contact Closure 6
In this chapter
Physical Features On-device Configuration Troubleshooting
6
e Click 100 is a hot-swappable contact closure module for use with the Wavetronix SmartSensor. It mounts onto a DIN rail and is connected to the SmartSensor through the Click 200 surge protection module.
Figure 6.1 – The Click 100
44 CHAPTER 6 CLICK 100
Physical Features
e Click 100 has eight primary and eight secondary contact outputs, which all share a logic ground (see Figure 6.2).
Figure 6.2 – Diagram of Click 100
Communication Port
e back of the Click 100 features a 5-position connector that plugs into a T-bus connector and provides power and RS-485 communication to the device. It also passes RS-485 com­munication from the Click 100 to all other devices on the T-bus when pressing the Mode button during conguration (see the On-device Conguration section of this chapter for more information).
Screw Terminals
e contact closure outputs are wired to a controller, data logger or BIU (Bus Interface Unit) using the pluggable screw terminals on the top and bottom of the Click 100. e top screw terminals are labeled 1–8 and represent the primary outputs. Primary 1 (P1) repre­sents the lane closest to a side-re SmartSensor and the remaining outputs represent the lanes as they sequentially get further from the sensor. For dual-loop emulation, the contact closure outputs must be wired with the primary always leading the secondary (see Figure
6.3).
CHAPTER 6  CLICK 100 45
Primary Detector
Secondary Detector
Traffic Direction
Primary
Channel
Secondary
Channel
Time
Dual-Loop Emulation System (Output Time Waveform)
Elapsed Time
(
Detection
Duration
On
Off
On
Off
Figure 6.3 – Primary and Secondary Outputs
Figure 6.4 below shows a diagram of the output signal time waveforms of the two detectors.
Indicates Speed)
Figure 6.4 – Emulation System Output Waveforms
e bottom screw terminals are also labeled 1–8 and represent the secondary outputs, with secondary one (S1) representing the lane closest to the SmartSensor. e remaining four screw terminal connections are labeled GND and are a common logic ground for all 16 contact closure outputs. You must provide a connection from the GND terminals to a logic ground to make the primary and secondary outputs operational.
e screw terminal connectors can also be unplugged from the Click 100 allowing you to pre-wire the Click 100 before nal installation.
Configuration Features
e four LEDs located right below the push-button are used to indicate operation modes, which will be discussed later in the On-device Conguration section of this chapter. Below is a list of the four LEDs:
PR (Presence) – Red PU (Pulse) – Orange
46 CHAPTER 6  CLICK 100
AC (Actuation) – Green 1L (One Loop Speed) – Ye l low
e front also has a push-button labeled Mode Switch, which is used to cycle the Click 100 through operation modes. is will be discussed in the On-device Conguration section.
LEDs
e Click 100 module has sixteen contact closure outputs. Each output represents a prima­ry or secondary channel and has a corresponding LED on the front of the Click 100 module.
e eight red LEDs on the top of the faceplate correspond to the primary outputs and the eight yellow LEDs on the bottom of the faceplate correspond to the secondary outputs.
On-device Configuration
e Click 100 can be congured using the push-button in the middle of the faceplate.
To automatically congure the Click 100, press and hold the push-button until the green LED ashes four times. e green LED and contact closure LEDs will ash during the auto­conguration process, which normally takes 5–30 seconds. e auto-conguration process matches the Click 100 with the sensor’s baud rate, loop size and loop spacing.
e rst four primary LEDs indicate the current baud rate at which the Click 100 is trying to congure. e following table shows what the dierent ashing LEDs represent:
Primary LED Baud Rate
1 9400 bps
2 19200 bps
3 38400 bps
4 57600 bps
Table 6.1 – List of Baud Rates
Note
The maximum baud rate that can be used is 57600. If the sensor’s RS-485 bus is set higher than 57600, no data will be seen on the Click 100.
e yellow LED will ash four times indicating the end of the auto-conguration process. Once the Click 100 is congured, the device will be set to Presence (PR) mode.
Press the push-button until the desired operation mode is selected.
CHAPTER 6  CLICK 100 47
Operation Modes
Press and hold the push-button to cycle through the dierent operation modes; release the button when the desired mode is reached. A quick press and release of the push-button will exit out of any mode and return the unit back to normal operation.
Table 6.2 describes the dierent operating modes. To use dual-loop emulation, you must wire both the primary and secondary outputs; to use single-loop emulation, you must only wire the primary output.
Mode LED Definition
PR (Presence) Red Outputs contact closures for single-loop or dual-loop
emulation. Dual-loop emulation will signal the radar’s speed and duration measurements. Speed is signaled as the elapsed time between the primary and second­ary outputs. Duration in the radar beam is signaled as the duration of the outputs. Single-loop emulation will simply signal the radar’s duration measurement (no speed information).
PU (Pulse) Orange Outputs contact closures for single-loop or dual-loop
emulation. Dual-loop emulation will signal the radar’s speed measurement using the time elapsed between the onset of the primary and secondary outputs, but not the radar’s duration measurement. Instead the outputs will be held active for precisely 125 millisec­onds for every vehicle detected. This fixed period of time is necessary when integrating with some systems and is often used in counting applications. Single-loop emulation will simply signal that the radar detected a vehicle (no duration or speed information).
AC (Actuation) Green Outputs contact closures for single-loop emulation.
This mode of single-loop emulation is used both with true presence and continuous passage detectors. True presence detectors signal the existence of a stopped or moving vehicle within the detector beam. Continuous passage detectors signal the existence of a moving vehicle meeting specific criteria (speed, range, ETA) within the detector beam. When a vehicle within the detector beam meets the requirements of the true presence or continuous passage detector, the associated rack card output will be closed. This is the only mode used by SmartSensor Advance. With side­fire radar sensors this mode is used for occupancy data collection.
48 CHAPTER 6  CLICK 100
1L (One Loop Speed) Yellow Outputs contact closures for single-loop emulation.
The duration of each contact closure output is based upon the speed of the detected vehicle (instead of the duration of the vehicle in the beam). The duration of each contact output is based on the formula: duration in seconds = nominal vehicle length in feet / actual speed in feet per second. The nominal vehicle length is read from the sensor when this mode is selected. To set the nominal vehicle length, use the SmartSen­sor Manager software. The nominal length in feet is entered in the default loop spacing field.
Autobaud Green (flashing) Autobauds to the connected SmartSensor; also polls
it for loop spacing. These values are saved to flash memory. While autobauding, the green and yellow LEDs will flash intermittently, as well as the 16 digital output LEDs. If the autobauding is unsuccessful, the LEDs will remain in that state indefinitely. If the auto­bauding is successful, the yellow LED will flash, then the device will return to its normal state and default to the Presence mode.
Table 6.2 – Click 100 Mode Definitions
Troubleshooting
e Click 100 conguration will fail if the communication link is lost or if another device is active on the communication link (usually the sensor’s native RS-485 port). For example, the conguration will fail if SmartSensor Manager remains actively connected and com­municating over the same link as the Click 100. To avoid this issue, connect SmartSensor Manager to the sensor’s native RS-232 port or simply shutdown SmartSensor Manager dur­ing Click 100 conguration.
If you choose to use the sensor’s native RS-232 port by connecting to the DB-9 connector on the associated Click 200, this link will become unreliable if the cable run is longer than 200 feet. Contact Wavetronix Technical Services for assistance if you would like both of the sensor’s ports to be reliable over distances greater than 200 feet.
One thing to be aware of is that the relays take ve milliseconds to open or close; they physi­cally cannot react any faster than the messages they receive.
Click 101 —
Multi-sensor to Contact Closure 7
In this chapter
Physical Features Installation On-device Configuration Computer Configuration
7
e Click 101 is a contact closure module that is capable of collecting lane-by-lane data from multiple Wavetronix SmartSensors in real time. e Click 101 device is designed to collect volume and occupancy data from all midblock stations pertaining to a signalized intersection.
Figure 7.1 – The Click 101
50 CHAPTER 7  CLICK 101
Traffic
Controller
Each side-re sensor can use its two communication ports to send real-time trac data to both cabinets for which it is collecting data (see Figure 7.2). e real-time data is used to control intersections using distributed and centralized strategies.
Note
The Click 101 data protocol used to poll sensors is supported by SmartSensor HD v1.3 or greater; likewise this protocol is supported in SmartSensor 105 v2.8 or greater.
Figure 7.2 – Each Side-fire SmartSensor Communicates with Two Trac Controllers
To collect the data at a particular intersection, the Click 101 polls each sensor for real-time lane-by-lane volume and occupancy data detected since the last polling period. Each poll­ing period typically takes a few seconds. is data is signalized to the trac controller or data logger using up to 16 contact closure outputs.
Figure 7.3 illustrates an example where the Click 101 in Cabinet A can retrieve lane-by­lane volume and occupancy data from Sensor ID 20 and 21. e data from lanes 4 and 5 of Sensor ID 20 is used to control phase 2 of the intersection, and the data from lanes 1–3 of Sensor ID 21 is used to control phase 6. e other lanes from Sensor ID 20 and 21 can be retrieved by Click 101 devices in cabinets at the adjacent arterial intersections.
CHAPTER 7  CLICK 101 51
Sensor ID 21
1
2
3
4
5
Sensor ID 20
Click! 101
Cabinet A
1
2
3
4
5
ф
2
ф
6
Figure 7.3 – The Click 101 Collects from Multiple Sensors
More sensors can be used to control all the phases at each intersection along an arterial or within a city grid. Each sensor has two dierent buers for the lane-by-lane volume and occupancy data. ere will be no loss of data on the sensor as long as each Click 101 com­municates over a dierent serial port.
During its normal polling routine, the Click 101 can collect trac data from up to ten side­re units. e normal polling routine will request new lane-by-lane volume and occupancy data every time it cycles through the list of sensors. If a sensor does not respond aer ten cycles, the Click 101 will suspend data queries to that sensor for one minute. Aer one min­ute, the Click 101 will retry data queries twice. If those queries are unsuccessful, the Click 101 will suspend queries for another minute. is feature prevents unresponsive sensors from unnecessarily slowing down the polling routine.
A Click 101 will not execute its normal polling routine if:
 It is being programmed with Click Supervisor or the push-button.  It is being used for RS-232 to RS-485 conversion.  A device connected to the RS-485 bus has sent a passcode message to temporarily
suspend polling.
Lane outputs from any one of the side-re sensors can be mapped to any of the 16 digital outputs. Mapping multiple lanes to a single output it also possible.
Physical Features
e Click 101 has 2 communication ports, 16 LEDs, 16 digital outputs and a push-button (see Figure 7.4).
52 CHAPTER 7  CLICK 101
Figure 7.4 – Diagram of the Click 101
Communication Ports
e back of the Click 101 features a 5-position connector that plugs into a T-bus connector and provides DC power and half-duplex RS-485 communication to the device. e RS-485 communication port on the T-bus allows the Click 101 to serve as the polling master on a multi-drop RS-485 bus. e sensors act as clients on the RS-485 bus, only responding to requests from the Click 101. Any devices connected to the T-bus will also have connectivity over the shared RS-485 lines; however, when a Click 101 is being used, it is expected that none of the sensors or other devices on the bus will push data. is will help avoid com­munication message collisions on the RS-485 bus.
Note
It is recommended that the sensors not be connected to the T-bus while program­ming this device with Click Supervisor.
e front of the Click 101 features a DB-9 connector for RS-232 communication. is con­nector is used for device conguration using Click Supervisor. A straight-through cable can be used to connect from this port to a computer.
CHAPTER 7  CLICK 101 53
Note
After you have completed programming the device using Click Supervisor, remove the RS-232 serial cable from the DB-9 port. This will prevent computer equipment (like docking stations) from holding the RS-232 TD line high. If the TD line is inadver­tently held high, the Click 101 will transmit on the RS-485 bus, but will not receive any data from connected sensors.
Like many of the other Click devices, the Click 101 also acts as an RS-232 to RS-485 con­verter. To disable the normal polling routine and enable serial conversion, a passcode mes­sage must rst be sent over one of the ports. SmartSensor Manager automatically sends a passcode message when a connection is made to a side-re sensor. is allows you to congure any of the sensors on the RS-485 bus via the DB-9 connector on the front of the Click 101. e normal polling routine will resume operation aer 10 seconds of inactivity on the ports. SmartSensor Manager HD sends a passcode message once every few seconds to keep the normal polling routine of the Click 101 suspended. SmartSensor Manager for the 105 sensor only sends passcode messages on some screens, so you may run into situa­tions where normal polling will resume while connected to a 105 sensor.
e passcode message can be one of those shown in Table 7.1:
C String Format Hex Byte Format
“X5/r” 0x58 0x35 0x0D
“Z1/r” 0x5A 0x31 0x0D
“Z2/r” 0x5A 0x32 0x0D
Table 7.1 – Passcode Messages that Enable Serial Conversion
LEDs
e Click 101 faceplate contains 16 LEDS. During normal polling, each LED lights up when the associated digital output is active.
If normal polling is suspended and the device is powered, the PWR (red) LED will light up and the RD (yellow) LED will activate each time data is received on a communication port. e TD (green) LED will not activate each time data is transmitted on a communication port. e green LED is used during normal polling to indicate that output 15 is active, and it is also used during manual conguration to select the autobaud conguration task.
Screw Terminals
e screw terminals labeled 1–16 on the top and bottom of the Click 101 are contact closure outputs that can be connected to a trac controller or data logger. ese digital outputs are contact closure outputs that require a logical ground connection.
54 CHAPTER 7  CLICK 101
e screw terminals labeled C1–C4 represent the common lines for each contact closure output pluggable screw terminal block (see Figure 7.4):
C1 – e common terminal for digital outputs 1–4. C2 – e common terminal for digital outputs 5–8. C3 – e common terminal for digital outputs 9–12. C4 – e common terminal for digital outputs 13–16.
Configuration Features
e lower section of the faceplate has a push-button labeled Mode Switch, which is used to initiate conguration tasks. ese tasks will be discussed in the On-device Conguration section of this chapter.
Installation
Wire the outputs of the Click 101 to a trac controller or other contact closure input. Make sure that each bank of the four outputs shares a single common wire. Tie each bank’s com­mon wire to either Logic Ground or the proper common connection.
Note
It is recommended that the sensors not be connected to the T-bus while program­ming this device with Click Supervisor.
On-device Configuration
e Click 101 can be partially congured using the Mode Switch push-button. is push­button cycles through two device conguration tasks: autobaud conguration and reset to factory defaults.
To select a task, hold the push-button down until the corresponding red or green LED turns on. Once a conguration task has nished, the Click 101 will return to normal poll­ing mode. During normal polling, the LEDs on the bottom row are used to signal contact closure outputs.
e autobaud task is initiated by holding the push-button until the green LED lights up. is task will set the polling baud rate to match that of one of the 10 possible sensor con­nections. All sensor connections must be at the same baud rate. e default baud rate of the sensors and the Click 101 is 9600 bps. However, communication modems or other devices in between the sensor and the Click 101 may dictate the baud rate.
CHAPTER 7  CLICK 101 55
Note
You will only be able to communicate properly if the Click 101 and each sensor’s RS­485 baud rate match.
To reset the module to factory defaults, hold the push-button down for 10-15 seconds until the red LED ashes. During the reset process, the rst 12 red LEDs will light up momen­tarily.
Computer Configuration
You must use Click Supervisor to customize the polling parameters, output mapping and other important settings. See Chapters 4 and 5 for instructions on how to download and install Click Supervisor and how to connect to your device using the soware.
You will usually select the Expert driver to congure a Click 101. e Expert driver does not modify Click 101 settings unless you save changes to the device. You should not connect to your device using other drivers, unless you are sure that driver has been specically de­signed for your application. Other drivers may inadvertently overwrite the settings on your module. Once you have nished conguring your device, save the settings to a backup le.
Aer you have made conguration changes on a driver and saved it to the Click device, the word “current” will appear aer that driver to indicate the driver that is currently loaded onto the device.
Note
Some settings appear on multiple drivers. Changing one of those settings on any driver and saving them to the Click device will change that setting on all other drivers.
Expert Driver
e Expert driver allows you to see all possible settings and elds, both those available in other drivers and those available only through this driver. e driver is divided into three tabs—System, Contact Closures and Diagnostics—which are then subdivided further.
e System > General tab allows you to change the settings aecting the setup of the device (see Figure 7.5 and Table 7.2).
56 CHAPTER 7  CLICK 101
Setting Description
Module
Driver
Description
Location
Serial #
Firmware Version
Subnet ID
Device ID
Table 7.2 – Expert Driver General Tab
Figure 7.5 – Expert Driver General Tab
Allows you to enter a name and description of the device.
Names the driver you are currently working with.
Shows a description of the device being configured. This is only for your information and does not aect the operation of the device.
Displays the location of the device being configured. This is only for your information and does not aect the operation of the device.
Displays the serial number of your device.
Shows the version of firmware your device currently has installed. If Click Supervisor detects a discrepancy between this version and the most current version it currently has access to, you will be prompted to upgrade when you connect to the device.
Shows the subnet ID number. This option is currently not available.
Gives the ID number of the device being configured, which is used to identify the device when you are connecting to it. By default, this number is the last five digits of the serial number, which can be found under the About tab or on the barcode sticker on the bottom of the device. It is recommended that you do not change this number unless another device on your network has the same ID number.
e System > Comm tab allows you to congure how the Click device communicates (see Figure 7.6 and Table 7.3).
CHAPTER 7  CLICK 101 57
Figure 7.6 – Expert Driver Comm Tab
Setting Description
Baud Rate
Flow Control
Parity
Stop Bits
Data Bits
Active Port
Latency
Table 7.3 – Expert Driver Comm Tab
Allows you to change the baud rate for both the RS-485 and RS-232 communication ports.
Is used for configuring hardware handshaking. This option is currently not available.
Allows you to set parity error checking.
Allows you to set the number of stop bits.
Shows you the number of data bits being sent. This option currently cannot be changed.
Indicates on which port you are communicating with one of the sen­sors on the multi-drop RS-485 bus. When you communicate to more than one sensor, the port may be dierent on each sensor. To change the connection port, you will have to physically change the connection of the communications link.
Indicates the latency between the sensor and the Click device. This option cannot be changed.
e System > Autobaud tab allows you to congure how the device autobauds (see Figure
7.7 and Table 7.4).
58 CHAPTER 7  CLICK 101
Setting Description
Command
Response
SmartSensor ID
Server/Client
Table 7.4 – Expert Driver Autobaud Tab
Figure 7.7 – Expert Driver Autobaud Tab
Allows you to set the command sent from the device during the autobaud process.
Shows the response the device is expecting from the above command.
Shows the ID number of one of the sensors with which the Click device is currently communicating. This only shows the number after you have autobauded the Click device; when the Click device is not communicating with a sensor, this option will display a 0.
This setting is not used by the Click 101.
e Contact Closures > Sensor tab allows you to change contact closure outputs and the normal polling routine (see Figure 7.8 and Table 7.5).
Figure 7.8 – Expert Driver Sensor 1 Tab
CHAPTER 7  CLICK 101 59
Setting Description
Sensor ID
Contact Closure Outputs
Table 7.5 – Expert Driver Sensor 1 Tab
The sensor’s multi-drop communication ID.
Allows you to set the Click 101 output for lanes 1-10 of each sensor. SmartSensor HD has 10 lanes per sensor; SmartSensor 105 only has 8 lane per sensor. Assignments made for Lanes 9 and 10 of a Smart­Sensor 105 unit will have no impact. Multiple lanes from one or more sensors can also be assigned to the same output.
e Contact Closures > Cong tab is located under the Sensors 9-10 tab and allows you to select the number of sensors and set the polling interval (see Figure 7.9 and Table 7.6).
Figure 7.9 – Expert Driver Config Tab
Setting Description
Number of Sensors This indicates how many of the 10 possible sensors you would like to
include in the current polling list. If you select only 1, then only sensor 1 will be polled for data. If you select 2, then only sensors 1 and 2 will be polled for data. In other words, sensors 1–X will be polled, where X is the value entered in this field.
Polling Interval (ms) The amount of time allotted for each sensor in the polling list to re-
spond. If a sensor responds more quickly, the Click 101 will continue to wait until the full time interval has expired. In other words, if you poll 8 sensors with an interval of 250 ms, you will query each sensor every 2 seconds. This two seconds represents the time required to poll all sensors on the list. This is defined as the total list poll time. The total list poll time is variable when sensors are momentarily dropped from the polling list. Unresponsive sensors are dropped from the poll list for one minute. For example, if 1 of 8 devices is not responding to requests, then the total list poll time will be 1.75 seconds (during the cycles that the unresponsive sensor is dropped from the list).
Table 7.6 – Expert Driver Config Tab
60 CHAPTER 7  CLICK 101
Under the Diagnostics tab, you can run diagnostics on your device (see Figure 7.10). Click the General button to run diagnostics on the items listed below the button. If a problem is detected, the program will display a red square next to the item in question. If no problems are detected, a green circle will appear.
Figure 7.10 – Expert Driver Diagnostics Tab
Once you have nished, use the menu bar at the top of the screen to save your settings, return to the Select Driver screen, and more.
 e Save menu allows you to save your settings. Select Save to File to save your set-
tings to a le. Selecting this will open a directory box, allowing you to name your settings le. is le will always be saved in the Wavetronix folder created when you installed Click Supervisor, under Wavetronix > ClickHome > Drivers > 101 > User. You can also select Save to Device to save your settings to your Click 101.
Note
If you do not save your settings to your Click 101, they will be lost the next time you power the device down.
 e To o l s menu contains ve options for working with your device. Reset > System
power cycles your device, while Reset > Factory Default restores your device to the settings with which it was shipped. Restore will restore the driver to the settings cur­rently saved on the Click 101, erasing any unsaved changes. Upgrade can be used to manually upgrade to the most current rmware for your device. Hex View changes the view of certain settings in the driver to hexadecimal.
 Clicking the Quit menu exits the driver and returns you to the Click Supervisor main
page.
Click 104 —
4-channel DIN Rail Contact Closure 8
In this chapter
Physical Features Installation Configuration Rotary Switch Front Panel Menu Click Supervisor
8
e Click 104 is a 4-channel contact closure module for use with sensors that use Z4 pro­tocol: HD, Advance and Matrix. It mounts on a DIN rail for power and communication.
Figure 8.1 – The Click 104
62 CHAPTER 4 CLICK 104
Physical Features
e Click 104 has the following physical features.
T-Bus
Connector
TOP
RS-232 Connector
FRONT
RS-232
+DC
-DC
+485
-485
GND
Bus 2
Control
Bus 1 Data
Click
104
Contact
Closures
3-4 1-2
Bus 1 Data
LEDs
RS-485
Mode
Switch
Rotary Switch
Outputs 1-2 Connector
Outputs 3-4 Connector
LED Indicators
RS-485
Connector
Mode Switch
Rotary Switch
Figure 8.2 – Diagram of Click 104
Communication Ports
e Click 104 has two independent serial communications buses. Bus 1, also referred to as the data bus, should be used to report vehicle data; its associated communication ports consist of two RJ-11 jacks, for RS-485, on the faceplate and one screw terminal, for RS-232, on the top of the device.
Bus 2, also referred to as the control bus, should be used for conguration. Its associated communication port is the a 5-position connector, located on the back of the Click 104, that plugs into a T-bus connector and provides power and RS-485 communication to the device. It also passes RS-485 communication from the Click 104 to all other devices on the T-bus.
Contact Closure Outputs
e contact closure outputs should be wired to a controller, data logger or BIU (Bus In­terface Unit) using the pluggable screw terminals on the bottom of the Click 104. ere are two screw terminal blocks; the one closer to the faceplate has outputs 1 and 2, and the farther one has outputs 3 and 4. Each output consists of two terminals, one + and one –.
e screw terminal connectors can also be unplugged from the Click 104 allowing you to
CHAPTER 4  CLICK 104 63
pre-wire the Click 104 before nal installation.
Rotary Switch
On the faceplate of the device is a rotary switch, numbered 0–9. is switch, which can be twisted by inserting a small screwdriver into the arrow slot, is used to congure channels.
Mode Switch
e faceplate of the Click 104 features a push-button labeled Mode Switch, which is used to cycle through and select menu and conguration options.
LEDs
e faceplate of the Click 104 has three banks of LEDs. e top bank is used for detection indication, the second bank menu indication, and the third for menu indication as well as operation states.
Channel
1 2 3 4
Menu
PWR OK TD RD
Figure 8.3 – Click 104 LEDs
e Channel LEDs are detection indicators; they consist of four red LEDs numbered 1–4, each representing a channel (see Figure 8.3). An illuminated LED indicates that the asso­ciated contact is being closed (this can mean either a vehicle detection or fail-safe mode, which will be discussed later in this chapter). ese indicators are dedicated to detection and have no other display purposes.
e menu indicator LEDs include two rows of LEDs (see Figure 8.3). e lower row con­tains Level 1 indicators, while the upper row contains Level 2 indicators. Each level consists of four LEDs numbered 1–4 (le to right). Level 1 LEDs (the multicolored row) display which menu item is active. ese Level 1 LEDs are dual-purpose, each indicating both menu selection as well as a normal operation state when not in Menu mode. e normal operation state functions include:
Red (PWR) – Indicates the presence of power to the device. Blue (OK) – Indicates proper system operation; it extinguishes during fail-safe mode. Green (TD) – Indicates serial communication transmit data (from the Click 104) on
either bus 1 (data) or bus 2 (control).
Yellow (RD) – Indicates serial communication receive data (to the Click 104) on either
64 CHAPTER 4  CLICK 104
bus 1 (data) or bus 2 (control).
Level 2 LEDs display conguration options for the menu items selected via the level 1 LEDs. All level 2 LEDs are red. ese LEDs are dedicated to menu operation, and are extinguished when the menu is not active.
Installation
1 Mount the Click 104 on a DIN rail over a T-bus connector. is connects the device’s
control bus (bus 2) to the installation’s shared communication bus; you can connect your computer to another device on this shared bus, such as the Click 305 USB con­verter, to access the Click 104 to congure it using Click Supervisor. Mounting the Click 104 on the T-bus also connects it to the power source.
2 Send detection data to the data bus (bus 1) in one of two ways. If you’re using a Smart-
Sensor Advance or Matrix, and therefore a Click 222 or 223, connect it to the Click 104 by connecting jumper cables from the RJ-11 jacks on the faceplate of the Click 222 or 223 to the RJ-11 jacks on the faceplate of the Click 104.
If you’re using a SmartSensor HD, rst set the sensor to push data on the RS-232 port. en connect wires between the TD and RD screw terminals on the protected side of the Click 200 to the TD and RD screw terminals on the Click 104.
3 If needed, daisy-chain multiple Click 104 devices together by utilizing both RJ-11 jacks
on each device’s faceplate.
Contact Closure Outputs
Part of installing the device is wiring its contact closure outputs to the trac controller (or data logger or other device). It’s recommended, however, that you not do this until the device is done being congured, to avoid sending any incorrect contact closures to the controller
ere are four contact closure outputs, for the four channels the Click 104 can handle. Each output has two screw terminals, one + and one –. e + terminals are for data, while the – are ground, or common. Each – terminal is isolated from all the other grounds; if your installation requires a common ground for each contact closure output, you’ll need to tie together the wires from those four terminals yourself.
Fail-safe Mode
e Click 104 receives datagrams from the connected SmartSensor. ese datagrams must be mapped to device outputs, as will be discussed later in this chapter. If the Click 104 does not receive a datagram describing the device’s channels for ten seconds, the device will enter fail-safe mode. In fail-safe mode, all outputs will assert a detection condition, and will con­tinue to do so until the device receives a datagram that updates the state of its congured channels. See the Click Supervisor section of this chapter for more information on how to
CHAPTER 4  CLICK 104 65
change the amount of time that must elapse without the device receiving a pertinent data­gram before the device enters fail-safe mode.
Configuration
e Click 104 can be congured in three ways: the rotary switch (which can only change one parameter), the front panel menu, and Click Supervisor.
ese three conguration methods can congure dierent sets of parameters; some of these parameters can be set using multiple conguration methods, and some of them can only be set using one particular method. Table 8.1 lists how each parameter may be accessed and congured.
Rotary Switch Front Panel Menu Click Supervisor
Baud Rate No Yes Ye s
Channel Input Map Yes Yes Yes
Autobaud No Yes No
Reset to Default No Yes Ye s
Description No No Yes
Location No No Yes
Device ID No No Yes
Fail-safe Settings No No Yes
To use this configuration option:
Table 8.1 – Click 104 Configuration Options
Hardware mode Software mode Software mode
Configuration Modes
e nal row on the table refers to conguration modes. Hardware mode means a par­ticular parameter is set by the rotary switch; Soware mode means that parameter is set by either the front panel menu or Click Supervisor. However, this is only applicable for channel input mapping, since that is the only parameter that can be set by the rotary switch.
e position of the rotary switch determines whether the device is in Hardware or Soware mode:
 If the switch is set to 0, the device is in Soware mode. is means that all parameters
are set by the front panel menu or Click Supervisor.
 If the switch is set to any other number, the device is in Hardware mode, meaning that
the channel input mapping is set by the rotary switch. If this is set, you will not be able to change the channel input mapping any other way; in Click Supervisor the option will be grayed out, and the front panel menu will only allow to view, not change, this setting. However, even when the rotary switch is set in Hardware mode, you will still be
66 CHAPTER 4  CLICK 104
able to congure all other parameters (besides channel input mapping) using the front panel menu and Click Supervisor.
Note
If any non-switch setting—that is, those that aren’t set by the rotary switch—has been set using both the front panel menu and Click Supervisor, whichever configura­tion was set most recently will take precedence.
Rotary Switch
e rotary switch is located on the lower part of the faceplate and can be used to change the channel input mapping. Remember that if you use this switch to set the channel input mapping, you won’t be able to use the soware or the front panel menu to change this particular parameter (although you will still be able to use them to change other param­eters).
Channel input mapping is the process of telling the device which incoming data channels should be mapped to which outgoing channels. As mentioned earlier, the Click 104 receives serial datagrams from a sensor to which it is connected. ese datagrams can contain many channels of detection data. Because the devices have fewer output channels than there are possible input datagram channels received from the sensor, you must use the channel input map to map the desired inputs to outputs. e Click 104 has four output channels; if you need more than this, you’ll need to use multiple devices daisy-chained together.
As shown in the table below, the outputs are mapped sequentially—that is, they can only be mapped in numerically ordered groups of four (1–4, 5–8, etc.). If you set the switch to 3, for 9–12, then input 9 would be mapped to output 1, input 10 would be mapped to out­put 2, input 11 would be mapped to output 3, and input 12 would be mapped to output 4.
Switch Channels
0 Software mode
1 1–4
2 5–8
3 9–12
4 13–16
5 17–20
6 21–24
7 25–28
8 29–32
CHAPTER 4  CLICK 104 67
9 33–36
Table 8.2 – Click 104 Rotary Switch Channel Input Map Settings
To set the switch, insert a small screwdriver into the slot and twist until the arrow is pointed at the desired number.
Front Panel Menu
e front panel of the device features a push-button and three banks of LEDs for on-device conguration and monitoring. e rst bank of LEDs, labeled Channel, displays the state of the contact closure outputs and is described in the Physical Features section.
e two lower banks of LEDs, labeled Menu, and the push-button, labeled Mode Switch, are used for navigating through Menu mode. is section will cover how to use the menu to congure the Click 104.
e lower bank of LEDs will be referred to as Level 1 and is used in selecting menu options. e upper bank will be referred to as Level 2 and is used in conguring the menu options. Level 2 LEDs only light up when a menu selection is made using the Level 1 LEDs.
1 2 3 4
Menu
Level 2
Level 1
Mode Switch
Figure 8.4 – Menu Indicator LEDs and Mode Switch
PWR
OK TD RD
Note
The LEDs in the lower bank also function as activity/status indicators. These func­tions, outlined in the Physical Features section of this chapter, are only executed when the device is not in Menu mode. In this case, the upper bank of LEDs (Level 2) remains o.
Navigating through the Menu
e mode switch push-button is used to enter Menu mode. To use the menu:
1 Press and hold the mode switch to enter Menu mode. e Level 1 LEDs will start to
68 CHAPTER 4  CLICK 104
light up to indicate that the device is cycling through all menu options (specics on these menu options, and which LEDs and LED combinations represent them, will be covered later in this section).
2 Release the mode switch when you reach the desired menu option. (Pressing and hold-
ing again will resume cycling through menu options.)
3 Quickly press and release the mode switch to select the current menu option. Once it’s
selected, the Level 2 LEDs will start to let you congure the options for the selected menu option.
4 Press and hold the mode switch to cycle through the submenu. e Level 2 LEDs will
light to indicate that the device is cycling though all conguration options (specics on these conguration options, and which LEDs and LED combinations represent them, will be covered later in this section).
5 Release the mode switch once the desired conguration option is reached. 6 Quickly press and release the mode switch to select the current conguration option.
e device will exit Menu mode, and either the selected function will run or the se­lected conguration will be set and saved to the device.
For example, the following table illustrates an example of how the mode switch and menu indicator LEDs are used in conguring the Click 104—in this case, how to autobaud bus 2.
Mode Switch Action Display State
None Normal operation
Press and hold Channel map menu option displayed
Continue holding Autobaud menu option displayed
Release Autobaud menu option displayed
Press and release Autobaud menu selected and first
configuration parameter displayed (bus 1 autobaud)
Press and hold Second configuration parameter
displayed (bus 2 autobaud)
Release Second configuration parameter
displayed
CHAPTER 4  CLICK 104 69
Menu Operation
Press and release Configuration parameter selected;
autobaud commences (will show intermediate LED states); auto­baud finishes and normal operation resumes
Table 8.3 – Menu Operation Example
Inactivity of one minute on the mode switch will exit menu mode.
Front Panel Menu Options
e following gure documents the menu and conguration options available from the front panel menu. is label is also printed on the side of the device.
e menu options are displayed on the Level 1 LEDs (multicolored) and the conguration parameters are displayed on the Level 2 LEDs (all red).
= LED O
= LED Flashing
= LED On
R B G Y
Input Mapping
Menu LEDs 1 2 3 4
Cancel
1-4
5-8
9-12
13-16
17-20
21-24
25-28
29-32
33-36
R B G Y
Autobaud
Menu LEDs
1 2 3 4
Cancel
Bus 1
Bus 2
R B G Y
Bus 1 Baud Rate
Menu LEDs
1 2 3 4
Cancel
9600
19200
38400
57600
PUSH and HOLD Mode Switch to
cycle through menus and options.
R B G Y
Reset to Default
Menu LEDs
1 2 3 4
R B G Y
Bus 2 Baud Rate
Menu LEDs
1 2 3 4
Cancel
Reset
Cancel
9600
19200
38400
57600
PUSH and
RELEASE Mode Switch to make selections.
1 minute of
inactivity exits menu.
Rotary Switch
= SW0
= 1-4
1
= 5-8
2
= 9-12
3
= 13-16
4
= 17-20
5
= 21-24
6
= 25-28
7
= 29-32
8
= 33-36
9
8
7
9
6
0
5
1
4
2
3
Figure 8.5 – Front Panel Menu Label
Channel Input Map
e rst conguration parameter that comes up when you’re cycling through the front panel menu is the channel input map. To select this parameter, release the push-button when the blue LED ashes.
70 CHAPTER 4  CLICK 104
Note
This parameter can also be changed using the rotary switch or Click Supervisor.
As mentioned earlier, the Click 104 devices receive serial datagrams from a SmartSensor. ese datagrams can contain many channels of detection data.
Because the devices have fewer output channels than there are possible input datagram chan­nels received from the sensor, you must use the channel input map to map the desired inputs to outputs. e Click 104 has four outputs and therefore must be mapped to four inputs; if you need more than four channels, you’ll need to use multiple devices daisy-chained together.
As shown in the table below, the outputs are mapped sequentially—that is, they can only be mapped in numerically ordered groups of four (1–4, 5–8, etc.). If you set the switch to 3, for 9–12, then input 9 would be mapped to output 1, input 10 would be mapped to output 2, input 11 would be mapped to output 3, and input 12 would be mapped to output 4.
Level 1 LEDs
Level 2 LEDs
Table 8.4 – Click 104 Front Panel Menu Channel Input Map Settings
Input Mapping
Cancel and exit menu
Channels 1–4
Channels 5–8
Channels 9–12
Channels 13–16
Channels 17–20
Channels 21–24
Channels 25–28
Channels 29–32
Channels 33–36
LED o LED on
See the earlier Navigating through the Menu and the Menu Operation Example sections for how to congure this parameter.
Because this parameter can also be set by the rotary switch, you may need to ensure that the switch is set to 0; if it’s not, the front panel menu will be able to display but not change the channel input mapping.
CHAPTER 4  CLICK 104 71
Autobaud
e second option that comes up when you’re cycling through the front panel menu is the autobaud function. To select this option, release the push-button when the green LED comes on solid.
Note
The autobaud function can only be accessed here, on the front panel menu.
is function initiates an autobaud on the communication buses (you will select which bus to autobaud on the Level 2 LEDs). An autobaud will stop data reporting on the selected port and attempt to communicate with the SmartSensor at all supported baud rates.
Level 1 LEDs
Level 2 LEDs
Table 8.5 – Front Panel Menu Autobaud Settings
Autobaud
Cancel and exit menu
Autobaud on bus 1
Autobaud on bus 2
LED o LED on
See the earlier Navigating through the Menu and the Menu Operation Example sections for how to congure this parameter.
As each baud rate is attempted, the Level 2 LEDs will sequence with a single LED illumi­nated from LED 1–4.
If the Click 104 is successful in communicating with a SmartSensor, it will display the baud rate found, using the same Level 2 LED pattern used in selecting the baud rate (covered in the Baud Rate section of this chapter and Table 8.6). Aer a short time of displaying the au­tobaud results, the menu will return to normal operation with the baud rate setting updated (and stored) to the baud rate detected during the autobaud process.
If the autobaud fails, all four Level 2 LEDs will light up for a few seconds, and then the menu will return to normal operation with the baud rate setting remaining unchanged.
Baud Rate (Bus 1 and 2)
e next two conguration parameters that come up in the front panel menu allow you to manually set the baud rate of the two communication buses. Bus 1 comes up rst, with the yellow LED coming on solid, then bus 2, with the yellow LED ashing.
72 CHAPTER 4  CLICK 104
Note
This parameter can also be changed using Click Supervisor.
Baud rate for bus 1
Level 1 LEDs
Level 2 LEDs
Table 8.6 – Front Panel Menu Baud Rate Settings
Baud rate for bus 2
Cancel and exit menu
9600 bps (default)
19200 bps
38400 bps
57600 bps
LED o LED on
See the earlier Navigating through the Menu and the Menu Operation Example sections for how to congure this parameter.
Reset to Default Settings
e nal option that comes up in the menu is Reset to Default Settings. To select this func­tion, release the mode switch when the red LED starts ashing.
Note
Resetting to default settings can also be done using Click Supervisor.
is function will restore all conguration settings to factory defaults, even those param­eters not congured using the front panel menu: baud rate, channel input map, description eld, location eld, and device ID.
Level 1 LEDs
Level 2 LEDs
Table 8.7 – Front Panel Menu Reset to Default Settings
Reset to Default Settings
Cancel and exit menu
Reset to default settings
LED o LED on
CHAPTER 4  CLICK 104 73
See the earlier Navigating through the Menu and the Menu Operation Example sections for how to view this parameter.
Aer the Click 104 has reset to factory defaults, it will check the rotary switch; if it is set to any option besides 0, that channel input mapping will be applied. If resetting to factory defaults doesn’t reset the channel input mapping, check the rotary switch to see if it’s aect­ing this setting.
Click Supervisor
Click Supervisor is the only way to congure non-data path type parameters such as the description, location, and device ID. See Chapters 4 and 5 of this document for instructions on how to download and install Click Supervisor and how to connect to your device using the soware.
Note
Some of the parameters mentioned below can only be configured in Click Supervisor. Others can be configured by the front panel menu and/or the rotary switch. If the ro­tary switch has been used to configure the channel input mapping, that parameter is considered to be in Hardware mode; it will be grayed out in Click Supervisor, meaning you can view but not change the setting. If you would like to set it using Click Supervi­sor, you will have to turn the rotary switch to 0.
e Click 104 can be congured using the Expert driver (see Figure 8.6).
Figure 8.6 – Selecting a Driver
Aer you have made conguration changes on the driver and saved it to the Click device, the word “current” will appear aer it to indicate the driver is currently loaded onto the device.
74 CHAPTER 4  CLICK 104
e Backups option can be used to read congurations that have previously been saved to le. See Chapter 5 for more information.
Expert Driver
e Expert driver contains two tabs, System and Diagnostics; the System tab is then sub­divided further.
e System > General tab lets you change general information about your device. e tab has the following parameters (see Figure 8.7 and Table 8.8):
Figure 8.7 – Expert Driver General Tab
Note
These parameters can only be configured using Click Supervisor.
Setting Description
Module
Driver
Description
Location
Serial Number
Allows you to enter a name and description of the device.
Names the driver you are currently working with.
Shows a description of the device being configured. This is only for your information and does not aect the operation of the device.
Displays the location of the device being configured. This is only for your information and does not aect the operation of the device.
Displays the serial number of your device. This information cannot be changed.
CHAPTER 4  CLICK 104 75
Firmware Version
Subnet ID
Device ID
Table 8.8 – Expert Driver General Tab
Shows the version of firmware your device currently has installed. If Click Supervisor detects a discrepancy between this version and the most current version it currently has access to, you will be prompted to upgrade when you connect to the device. This information cannot be changed.
Shows the subnet ID number. This option is currently not available.
Gives the ID number of the device being configured, which is used to identify the device when you are connecting to it. By default, this number is the last five digits of the serial number, which can be found under the About tab or on the barcode sticker on the bottom of the device. It is recommended that you do not change this number unless another device on your network has the same ID number.
e System > Settings tab lets you congure and view many of the parameters that are also available elsewhere on the device (see Table 8.1 earlier in this chapter for more informa­tion). e tab has the following parameters (see Figure 8.8 and Table 8.9):
Figure 8.8 – Expert Driver Settings Tab
Note
These parameters can also be configured using the front panel menu. Also, chan­nel input mapping can be set using the rotary switch; if the rotary switch is set to anything but 0, the input mapping drop-down will appear grayed out on this screen.
Setting Description
Control (T-Bus) Baud
Data (RJ11 _232) Baud
Lets you change the baud rate, in bps, of the control bus (bus 2).
Lets you change the baud rate, in bps, of the data bus (bus 1).
76 CHAPTER 4  CLICK 104
Input Mapping
Failsafe Enabled
Failsafe Timeout (Sec)
Table 8.9 – Expert Driver Settings Tab
Lets you assign input datagram channels received from the sensor to the two or four output channels on the device. The outputs are mapped sequentially—that is, they can only be mapped in numerically ordered groups of four. See Input Mapping in either the Rotary Switch or Front Panel Menu sections in this chapter for more information.
Turns on and o fail-safe mode. For more information on what this mode is, see the Fail-safe Mode section earlier in this chapter.
Lets you select what length of time, in seconds, the device can go without receiving datagrams describing the device’s channels before it goes into fail-safe mode. The default is 10 seconds.
Under the Diagnostics tab, you can run diagnostics on your device (see Figure 8.9).
Figure 8.9 – Expert Driver Diagnostics Tab
Click the General button to run diagnostics on the items listed below the button. If a prob­lem is detected, the program will display a red square next to the item in question. If no problems are detected, a green circle will appear.
Click Failsafe Status to check whether any of the channels are in fail-safe mode. If a fail-safe condition is detected, a red square will be displayed below the button. If no problems are detected, a green circle will appear.
Once you have nished, use the menu bar at the top of the screen to save your settings, return to the Select Driver screen, and more.
 e Save menu allows you to save your settings. Select Save to File to save your settings
to a le. Selecting this will open a directory box, allowing you to name your settings le. is le will always be saved in the Wavetronix folder created when you installed Click Supervisor, under Wavetronix > ClickHome > Drivers > 104 > User. You can also select Save to Device to save your settings to your Click 104.
CHAPTER 4  CLICK 104 77
Note
If you do not save your settings to your Click 104, they will be lost the next time you power the device down.
 e To o l s menu contains ve options for working with your device. Reset > System
power cycles your device, while Reset > Factory Default restores your device to the settings with which it was shipped. Restore will restore the driver to the settings cur­rently saved on the Click 104, erasing any unsaved changes. Upgrade can be used to manually upgrade to the most current rmware for your device. Hex View changes the view of certain settings in the driver to hexadecimal.
 Clicking the Quit menu exits the driver and returns you to the Click Supervisor main
page.
Once you have nished, click Save on the menu bar to save your settings.
Click 110 —
4-channel Contact Closure Eurocard 9
In this chapter
Physical Features Installation and Wiring Operation Configuration
9
e Click 110 is used to report vehicle data to a MIDAS outstation when used with Wa­vetronix SmartSensors. is card plugs directly into an outstation and reports four channels of detection. Because the Click 110 has two independent serial buses, it can be congured without interfering with data reporting.
Figure 9.1 – The Click 110
80 CHAPTER 9 CLICK 110
Physical Features
e following sections describe the physical features of the Click 110 card.
Figure 9.2 – Diagram of the Click 110
Communication Ports
e Click 110 contains two independent serial communications ports. Each port is made up of two RJ-11 connectors, which make it simple to daisy-chain multiple Click 110 cards together and create a RS-485 bus. e two RJ-11 RS-485 data buses can be connected to a SmartSensor through a Click 200 surge protection module, or through a serial data con­verter.
Typically, one bus is used to report vehicle data, and the other is used for conguration. As both buses are identical it does not matter which is used for data or conguration. Alterna­tively, a single bus could be used for both data and conguration, but data reporting would be temporarily halted during conguration. During this time, the Click 110 will enter fail­safe mode if vehicle data is not reported for ten seconds.
LEDs
e faceplate of the Click 110 has four banks of LEDs. e top bank is used for detection in­dication, the second bank for fault indication, the third for menu indication, and the fourth for menu indication as well as operation states.
CHAPTER 9  CLICK 110 81
Detection
1 2 3 4
Fault
Menu
1 2 3 4
PWR MF TD RD
Figure 9.3 – Click 110 LEDs
e detection indicator LEDs consist of four red LEDs numbered 1–4, each representing a channel (see Figure 9.3). An illuminated LED indicates the presence of a vehicle. ese indicators are dedicated to detection and have no other display purposes.
e fault indicator LEDs consist of four dual-color (green / yellow) LEDs numbered 1–4, each representing the channel with the corresponding number (see Figure 9.3).
Illuminated green LED – Indicates a no-fault condition. Illuminated yellow LED – Indicates a fault condition which has existed for less than
one minute.
Extinguished LED – Indicates a fault condition which has existed for more than one
minute.
e menu indicator LEDs include two rows of LEDs (see Figure 9.3). e lower row con­tains Level 1 indicators, while the upper row contains Level 2 indicators. Each level consists of four LEDs numbered 1–4 (le to right). Level 1 LEDs display which menu is active. ese Level 1 LEDs are dual-purpose, each indicating both menu selection as well as a normal operation state when not in Menu mode. e normal operation state functions include:
Red (PWR) – Indicates the presence of power to the device. Blue (MF) – Illuminates when the master fault output is in the no-fault condition. e
LED is extinguished in the fault condition.
Green (TD) – Indicates serial communication transmit data (from the Click 110) on
either RS-485 bus 1 or RS-485 bus 2.
Yellow (RD) – Indicates serial communication receive data (to the Click 110) on either
RS-485 bus 1 or RS-485 bus 2.
Level 2 LEDs display conguration options. All level 2 LEDs are red. ese LEDs are dedi­cated to menu operation, and are extinguished when the menu is not active.
82 CHAPTER 9  CLICK 110
Push-buttons
e faceplate of the Click 110 features two push-buttons. e upper push-button, labeled Mode Switch, is used to cycle through and select menu and conguration options.
e lower push-button, labeled Reset, will reboot the Click 110. e Click 110 can be re­booted in any of three ways: via the reset switch, from the outstation via the 64 way DIN 41612, or by power cycling the device. A reboot is the only way to clear a latched fault con­dition. To reboot using the reset switch, simply press and release the push-button.
DIP Switches
Just behind the faceplate of the Click 110, on the circuit board, is a set of DIP switches. ese switches are used to congure the Click 110 in Hardware mode. All settings, with the exception of Outstation mode and disabling fault latching, are also congurable via Soware mode (front panel menu, or Click Supervisor). See the DIP Switches section of this chapter for more information.
Installation and Wiring
Use the following steps to install and wire Click 110 devices:
1 If you’re using hardware conguration, set all DIP switches before installing Click 110
devices (this will be covered in the DIP Switches section of this chapter).
2 Insert the cards into the rack. 3 Daisy-chain together all the cards you intend to use in your installation, using short
RJ-11 jumper cables.
4 Connect the rst Click 110 card to the SmartSensor via a surge protector, such as the
Click 200, 222, or 223, and a 60" RJ-11 patch cord.
For your information, this guide includes the pinout for the 64-pin backplane connector on the the back of the Click 110. However, the pins behave dierently depending on which Outstation mode the device is set to, Peek or Siemens (for more on Outstation mode, see the DIP Switches section of this chapter); the dierences all relate to the fault outputs and whether they are normally opened or normally closed.
For this reason, there are two pinout tables on the following pages. e rst is the pinout when the Click 110 is set to Peek; the second is when it’s set to Siemens.
Note
The pins that change between the two tables will be highlighted in light gray for ease of comparison.
CHAPTER 9  CLICK 110 83
Description Pin
Channel 1 fault, normally closed B1
Channel 1 common B2
Channel 1 fault common B3
Master fault, normally closed B4
No connection B5
No connection B6
No connection B7
Channel 2, normally closed B8
No connection B9
Channel 2, normally open B10
No connection B11
No connection B12
No connection B13
Chassis ground B14
Channel 3 fault, normally closed B15
Channel 3 common B16
Channel 3 fault common B17
No connection B18
No connection B19
No connection B20
No connection B21
Channel 4, normally closed B22
No connection B23
Channel 4, normally open B24
No connection B25
No connection B26
No connection B27
No connection B28
No connection B29
+DC (12–24 VDC) B30
No connection B31
-DC (common) B32
Pin Description
A1
A1 Channel 1, normally closed
A2 No connection
A3 Channel 1, normally open
A4 No connection
A5 No connection
A6 No connection
A7 Master fault, normally open
A8 Channel 2 fault, normally closed
A9 Channel 2 common
A10 Channel 2 fault common
A11 Master fault common
A12 No connection
A13 No connection
A14 No connection
A15 Channel 3, normally closed
A16 No connection
A17 Channel 3, normally open
A18 No connection
A19 No connection
A20 No connection
A21 No connection
A22 Channel 4 fault, normally closed
A23 Channel 4 common
A24 Channel 4 fault common
A25 No connection
A26 No connection
A27 No connection
A28 No connection
A29 Reset
A30 No connection
A31 No connection
A32 No connection
Figure 9.4 – Click 110 Pinout with Peek Outstation
84 CHAPTER 9  CLICK 110
Description Pin
Channel 1 fault, normally open B1
Channel 1 common B2
Channel 1 fault common B3
Master fault, normally open B4
No connection B5
No connection B6
No connection B7
Channel 2, normally closed B8
No connection B9
Channel 2, normally open B10
No connection B11
No connection B12
No connection B13
Chassis ground B14
Channel 3 fault, normally open B15
Channel 3 common B16
Channel 3 fault common B17
No connection B18
No connection B19
No connection B20
No connection B21
Channel 4, normally closed B22
No connection B23
Channel 4, normally open B24
No connection B25
No connection B26
No connection B27
No connection B28
No connection B29
+DC (12–24 VDC) B30
No connection B31
-DC (common) B32
Pin Description
A1
A1 Channel 1, normally closed
A2 No connection
A3 Channel 1, normally open
A4 No connection
A5 No connection
A6 No connection
A7 Master fault, normally closed
A8 Channel 2 fault, normally open
A9 Channel 2 common
A10 Channel 2 fault common
A11 Master fault common
A12 No connection
A13 No connection
A14 No connection
A15 Channel 3, normally closed
A16 No connection
A17 Channel 3, normally open
A18 No connection
A19 No connection
A20 No connection
A21 No connection
A22 Channel 4 fault, normally open
A23 Channel 4 common
A24 Channel 4 fault common
A25 No connection
A26 No connection
A27 No connection
A28 No connection
A29 Reset
A30 No connection
A31 No connection
A32 No connection
Figure 9.5 – Click 110 Pinout with Siemens Outstation
CHAPTER 9  CLICK 110 85
Preparing the SmartSensor
In addition to wiring the SmartSensor to the Click 110, you must also make sure that the SmartSensor is congured correctly. Because the Click 110 device receives serial datagrams from the sensor, the sensor must be congured to report data properly for each application. is includes conguring the sensor for the following:
 Dual-loop speed trap or one-loop conguration  Predened pulse duration, or pulse duration emulating a given loop size  Z4 protocol  Physical loop spacing to emulate
Fail-safe Mode
e Click 110 receives datagrams from the connected SmartSensor. ese datagrams must be mapped to device outputs (covered in the next section). If the Click 110 does not receive a datagram containing a channel that is mapped to its outputs for ten seconds, the device will enter fail-safe mode.
In fail-safe mode, all enabled outputs will assert a detection and fault condition. e master fault output will also assert. How the device gets out of fail-safe mode is determined by the fault latch conguration option, which will be covered at the end of the DIP Switches sec­tion of this chapter.
Configuration
e Click 110 can be congured in three ways: DIP switches, the front panel menu, and Click Supervisor.
ese three dierent conguration methods can congure dierent sets of options; some of these parameters can be set using multiple conguration methods, and some of them can only be set using one particular method. Table 9.1 lists how each parameter may be accessed and congured.
DIP Switch Front Panel Menu Click Supervisor
Baud Rate Yes Ye s Yes
Channel Enable Yes Yes Yes
Channel Input Map Yes Yes Yes
Fault Latch Disable Yes Read-only Read-only
Outstation Mode Yes Read-only Read-only
Autobaud No Yes No
Reset to Default No Yes Ye s
Description No No Yes
86 CHAPTER 9  CLICK 110
Location No No Yes
Device ID No No Yes
Fault Status No Fault Indicators Read-only
To use this configuration feature:
Table 9.1 – Click 110 Configuration Options
e nal row on the table refers to conguration modes. e DIP switches can be used to choose between Hardware and Soware modes. If the switches are set to Hardware mode, the DIP switches will be used to change conguration options. If the switches are set to So­ware mode, the front panel menu and Click Supervisor will be used to change conguration options. is will be discussed in greater detail in the DIP Switches section of this chapter.
Hardware Configu­ration Mode
Software Configu­ration Mode
Software Configu­ration Mode
Note
Any setting which has been configured via the DIP switches will be read-only in Click Supervisor and the front panel menu.
DIP Switches
e DIP switches are located on the circuit board behind the faceplate. e side of the face­plate contains information on conguring using the DIP switches, as shown in Figure 9.6.
CHAPTER 9  CLICK 110 87
Figure 9.6 – Click 110 DIP Switches
e Click 110 features three DIP switches labeled S1, S2 and S3 on the label and in the pic­ture above. (e fourth switch, labeled S4, is currently not used.) Each DIP switch is used to congure one or two dierent settings, for a total of six dierent congurable parameters:
 Bus 1 baud rate  Bus 2 baud rate  Channel enable  Channel input map  Outstation mode  Fault latch
Each parameter (except fault latch and outstation mode) has a way to pick between Hard­ware/Soware modes. If Soware mode is selected, the parameter must be congured using the front panel menu or Click Supervisor. If Hardware mode is selected, the parameter can be congured using the switches. In this case, the setting can be viewed but not changed via Click Supervisor and the front panel menu.
Baud Rate
e baud rates for the two RS-485 buses, bus 1 and bus 2 (see the faceplate of the device for which RJ-11 jacks are for each bus), may be independently congured using the switches on the rst DIP switch, labeled S1.
88 CHAPTER 9  CLICK 110
Note
This parameter can also be changed using the front panel menu or Click Supervisor.
e switch patterns for the two parameters are identical, but bus 1 is congured using switches 1–4 (S1:1–4) while bus 2 is congured using switches 5–8 (S1:5–8).
S1: Bus 1 Baud Rate
1 2 3 4 Value
O Software mode
On O O O 9600 bps
On O O On 19200 bps
On O On O 38400 bps
On O On On 57600 bps
On On O O 9600 bps
On On Off On 9600 bps
On On On O 9600 bps
On On On On 9600 bps
Table 9.2 – DIP Switch Baud Rate Settings for Bus 1 (left) and Bus 2 (right)
5 6 7 8 Value
O Software mode
On O O O 9600 bps
On O O On 19200 bps
On O On O 38400 bps
On O On On 57600 bps
On On O O 9600 bps
On On Off On 9600 bps
On On On O 9600 bps
On On On On 9600 bps
S2: Bus 2 Baud Rate
As these tables show, if the switches are in any conguration besides the ones laid out in the rst few rows of these tables, that bus will default to 9600 bps.
If switch 1/5 is on (up), Hardware mode is selected, meaning the baud rate can be cong­ured using the DIP switches (as shown in Table 9.2 above), and Click Supervisor and the front panel menu will be able to display the current setting, but not change it. (Dashes in the table above indicate that the other three switches don’t aect Soware mode selection.) If switch 1/5 is o (down), Soware mode is selected and Click Supervisor and the front panel menu will be able to both display and change the current setting.
Channel Enable
e next parameter that can be congured is which of the output channels are enabled. Enabling output channels is located on the second DIP switch, labeled S2, and is controlled with switches 4–8 (S2:4–8).
Note
This can also be changed using the front panel menu or Click Supervisor.
CHAPTER 9  CLICK 110 89
A disabled output will never enter the detection state, and will never indicate a fault condi­tion. Any combination of outputs can be enabled. Due to limited space on the faceplate side label, not all combinations of enabled and disabled channels are listed. A complete table is shown below.
S2: Channel Enable
4 5 6 7 8 Channel
O Software mode
On O O O O All o
On O O O On Channel 4 on
On O O On O Channel 3 on
On O O On On Channels 3 and 4 on
On O On O O Channel 2 on
On O On O On Channels 2 and 4 on
On O On On O Channels 4 and 3 on
On O On On On Channels 2, 3, and 4 on
On On O O O Channel 1 on
On On O O On Channels 1 and 4 on
On On O On O Channels 1 and 3 on
On On O On On Channels 1, 3, and 4 on
On On On O O Channels 1 and 2 on
On On On O On Channels 1, 2, and 4 on
On On On On O Channels 1, 2, and 3 on
On On On On On Channels 1, 2, 3, and 4 on
Table 9.3 – DIP Switch Channel Enable Settings
If switch 4 (S2:4) is on (up), Hardware mode is selected, meaning the channels can be en­abled using the DIP switches (as shown in Table 9.3 above), and Click Supervisor and the front panel menu will be able to display the current setting, but not change it. (Dashes in the table above indicate that the other three switches don’t aect Soware mode selection.)
If switch 4 is o (down), Soware mode is selected and Click Supervisor and the front panel menu will be able to both display and change the current setting.
Channel Input Map
e next set of switches is used in mapping channel inputs. Mapping input datagram chan­nels to output channels is congured on the third DIP switch, labeled S3, using switches 1–4 (S3:1–4).
90 CHAPTER 9  CLICK 110
Note
This parameter can also be changed using the front panel menu or Click Supervisor.
As mentioned earlier, the Click 110 device receives serial datagrams from a SmartSensor. ese datagrams can contain many channels of detection data.
Because the Click 110 has four output channels, only four input datagram channels, re­ceived from the sensor, can be output by each device. (If you need more than four channels, consider using multiple devices.) As shown in the table below, the outputs are mapped sequentially—that is, they can only be mapped in numerically ordered groups of four (1–4, 5–8, etc.). If you chose, for example, 17–20, then input 17 would be mapped to output 1, input 18 would be mapped to output 2, input 19 would be mapped to output 3, and input 20 would be mapped to output 4.
If fewer than four outputs are required, any contact closure output can be disabled. A dis­abled output will never enter the detection state, and will never indicate a fault condition. Depending on whether each channel is enabled or disabled, the input mapped to it will also be enabled or disabled.
S3: Channel Input Map
1 2 3 4 Channel
O Software mode
On O O O 1–4
On O O On 5–8
On O On O 9–12
On O On On 13–16
On On O O 17–20
On On O On 21–24
On On On O 25–28
On On On On 29–32
Table 9.4 – DIP Switch Channel Input Map Settings
If switch 1 (S3:1) is on (up), Hardware mode is selected, meaning the inputs can be mapped using the DIP switches (as shown in Table 9.4 above), and Click Supervisor and the front panel menu will be able to display the current setting, but not change it. (Dashes in the table above indicate that the other three switches don’t aect Soware mode selection.)
If switch 1 is o (down), Soware mode is selected and Click Supervisor and the front panel menu will be able to both display and change the current setting.
CHAPTER 9  CLICK 110 91
Outstation Mode
Also on this switch is the outstation mode. is is congured on the third DIP switch, la­beled S3, using switch 6 (S3:6).
Note
This parameter can only be changed using the DIP switches.
e Click 110 can be used with two brands of outstations, Peek and Siemens. Because of dierences in the way these two operate, you need to use switch 6 on the S3 DIP switch to tell the Click 110 with which outstation it is going to be used.
If S3:6 is o (down), the Click 110 is set to work with a Peek brand outstation. If S3:6 is on (up), the Click 110 is set to work with a Siemens brand outstation.
S3: Outstation Mode
6 State
O Peek
On Siemens
Table 9.5 – DIP Switch Outstation Mode Settings
Note
In Peek mode the Isolated fault output channels are N/C; in Siemens mode they are N/O. The Master Fault output relay is also opposite when switching between the two modes. Refer to the pinout table earlier in this chapter for more information.
Because Outstation mode can only be changed using the DIP switches (though it can be viewed elsewhere), there is no option for selecting Hardware or Soware conguration modes.
Fault Latch
e last option that can be congured on the DIP switches is fault latching. is is cong­ured on the third DIP switch, labeled S3, using switch 8 (S3:8).
Note
This parameter can only be changed using the DIP switches.
92 CHAPTER 9  CLICK 110
Fault latching involves how the Click 110 reacts when the ow of data from the connected SmartSensor is interrupted. As mentioned in the Fail-safe Mode section above, if the Click 110 does not receive a datagram containing a channel that is mapped to its outputs for ten seconds, the device will enter fail-safe mode.
In fail-safe mode, all enabled outputs will assert a detection and fault condition. e master fault output will also assert. As long as the ow of data is reestablished within one minute, the device will exit the mode and continue normal operation. How the device reacts when data ow is not reestablished is determined by whether fault latch is enabled or disabled.
If S3:8 is on (up), fault latching is disabled. is means that if the Click 110 starts to receive data again at any point aer the one-minute mark, the device will exit fail-safe mode and continue normal operation. If S3:8 is o (down), fault latching is enabled. In this case, if the fault condition has existed for more than one minute, normal mode can only be restored by rebooting (front panel reset switch, power cycle, or remote reset via outstation), even if the device has started to receive data again.
S3: Fault Latch
8 State
O Enable
On Disable
Table 9.6 – DIP Switch Fault Latch Settings
Because fault latching can only be changed using the DIP switches, there is no need (and no option) for selecting Hardware or Soware conguration modes.
Front Panel Menu
e front panel of the device features two push-buttons and four banks of LEDs for on­device conguration and monitoring. e rst two banks of LEDs, labeled Detection and Fault, and the lower push-button, labeled Reset, are for basic monitoring and conguration and are explained in the Physical Features section.
e two lower banks of LEDs, labeled Menu, and the rst push-button, labeled Mode Switch, are used for navigating through Menu mode. is section will cover how to use these features and the menu to congure the Click 110.
e lower bank of LEDs will be referred to as Level 1 and is used is selecting menu options. e upper bank will be referred to as Level 2 and is used in conguring the menu options.
CHAPTER 9  CLICK 110 93
Menu
Level 2
Level 1
Mode Switch
Figure 9.7 – Menu Indicator LEDs and Mode Switch
1 2 3 4
PWR MF TD RD
Note
The LEDs in the lower bank also function as activity/status indicators. These func­tions, outlined in the Physical Features section of this chapter, are only executed when the device is not in Menu mode. In this case, the upper bank of LEDs (Level 2) remains o.
Navigating through the Menu
e mode switch push-button is used to enter Menu mode. To use the menu:
1 Press and hold the mode switch to enter Menu mode. e Level 1 LEDs will start to
light up to indicate that the device is cycling through all menu options (specics on these menu options, and which LEDs and LED combinations represent them, will be covered later in this section).
2 Release the mode switch when you reach the desired menu option. (Pressing and hold-
ing again will resume cycling through menu options.)
3 Quickly press and release the mode switch to select the current menu option. Once it’s
selected, the Level 2 LEDs will start to let you congure the options for the selected menu option.
4 Press and hold the mode switch to cycle through the submenu. e Level 2 LEDs will
light up to indicate that the device is cycling though all conguration options (specif­ics on these conguration options, and which LEDs and LED combinations represent them, will be covered later in this section).
5 Release the mode switch once the desired conguration option is reached. 6 Quickly press and release the mode switch to select the current conguration option.
e device will exit Menu mode, and either the selected function will run or the se­lected conguration will be set and saved to the device.
Inactivity of one minute on the mode switch will exit menu mode and resume normal operation.
e following table illustrates an example of how the mode switch and menu indicator LEDs are used in conguring the Click 110—in this case, how to autobaud bus 2.
94 CHAPTER 9  CLICK 110
Mode Switch Action Display State
None Normal operation
Press and hold Channel map menu option displayed
Continue holding Autobaud menu option displayed
Release Autobaud menu option displayed
Press and release Autobaud menu selected and first
configuration parameter displayed (bus 1 autobaud)
Press and hold Second configuration parameter
displayed (bus 2 autobaud)
Release Second configuration parameter
displayed (bus 2 autobaud)
Press and release Configuration parameter selected
and normal operation resumes
Table 9.7 – Menu Operation Example
Front Panel Menu Options
e following gure documents the menu and conguration options available from the front panel menu. is label is also printed on the side of the Click 110 (on the opposite side from the DIP switches).
CHAPTER 9  CLICK 110 95
Level 1
Using the Mode Switch to
View or Modify Conguration
Level 2 LEDs
Level 1 LEDs
• Press and hold Mode Switch to cycle through options
• Press and release Mode Switch to select option
Level 1
LEDs
Level 1
LEDs
Level 1
LEDs
Level 2
LEDs
NOTE: If a settings DIP switch is not set to SW Cong, then the current setting is displayed but cannot be modied using the Mode Switch.
Menu
1 2 3 4
Channel Input Map
Autobaud Settings
Baud Rate Setting for Bus 1
Baud Rate Setting for Bus 2
Channel Enable
Fault Latch
Outstation Support Settings
Reset to Default Settings
Cancel and Exit Menu
Channel Input Map
Channels 1 - 4
Channels 5 - 8
Channels 9 - 12
Channels 13 - 16
Channels 17 - 20
Channels 21 - 24
Channels 25 - 28
Channels 29 - 32
Cancel and Exit Menu
Autobaud Settings
Perform Autobaud on Bus 1
Perform Autobaud on Bus 2
Cancel and Exit Menu
Figure 9.8 – Front Panel Menu Label
On
Blinking
Off
LEDs
Level 2
LEDs
Level 1
LEDs
Level 2
LEDs
Channel: 1 2 3 4
Level 1
LEDs
Level 2
LEDs
Level 1
LEDs
Level 2
LEDs
Level 1
LEDs
Level 2
LEDs
Level 1
LEDs
Level 2
LEDs
Baud Rate Setting for Bus 1
Baud Rate = 9600 (default)
Baud Rate = 19200
Baud Rate = 38400
Baud Rate = 57600
Baud Rate = 115200
Cancel and Exit Menu
Baud Rate Setting for Bus 2
Baud Rate = 9600 (default)
Baud Rate = 19200
Baud Rate = 38400
Baud Rate = 57600
Baud Rate = 115200
Cancel and Exit Menu
Channel Enable
All Channels Disabled
Enable Channel 1
Enable Channel 2
Enable Channel 3
Enable Channel 4
Cancel and Exit Menu
Fault Latch
Fault Latch Enabled (default)
Fault Latch Disabled
Outstation Support Settings
Peek Outstation Support (default)
Siemens Outstation Support
Reset to Default Settings
Reset to Default Settings
Cancel and Exit Menu
(default)
As shown above, the menu options are displayed on the Level 1 LEDs and the conguration parameters are displayed on the Level 2 LEDs.
If a conguration parameter has been set using the DIP switches (meaning that parameter is currently set to Hardware mode), you cannot change it using the front panel menu. Aer selecting that particular menu option from the Level 1 LEDs, the Level 2 LEDs will display the conguration option set in the DIP switches and will not allow you to switch from that option. e only way to exit at this point is to press the push-button once.
Channel Input Map
e rst conguration parameter that comes up when you’re cycling through the front panel menu is the channel input map. To select this parameter, release the push-button when the yellow LED comes on solid.
96 CHAPTER 9  CLICK 110
Note
This parameter can also be changed using the DIP switches or Click Supervisor.
As mentioned earlier, the Click 110 device receives serial datagrams from a SmartSensor. ese datagrams can contain many channels of detection data. Because the Click 110 has four output channels, only four input datagram channels, received from the sensor, can be output by each device. (If you need more than four channels, consider using multiple devices.) As shown in the table below, the outputs are mapped sequentially—that is, they can only be mapped in numerically ordered groups of four (1–4, 5–8, etc.). If you chose, for example, 17–20, then input 17 would be mapped to output 1, input 18 would be mapped to output 2, input 19 would be mapped to output 3, and input 20 would be mapped to output 4.
If fewer than four outputs are required, any contact closure output can be disabled (covered later in this section). A disabled output will never enter the detection state, and will never indicate a fault condition. Depending on whether each channel is enabled or disabled, the input mapped to it will also be enabled or disabled.
Level 1 LEDs
Level 2 LEDs
Table 9.8 – Front Panel Menu Channel Input Map Settings
Input Mapping
Channels 1–4
Channels 5–8
Channels 9–12
Channels 13–16
Channels 17–20
Channels 21–24
Channels 25–28
Channels 29–32
Cancel and exit menu
LED o LED on
See the earlier Navigating through the Menu and the Menu Operation Example sections for how to congure this parameter.
Because this parameter can also be set by the DIP switches, you may need to ensure that the DIP switches are set to Soware conguration mode; if they are set to Hardware, the front panel menu will be able to display but not change these settings.
CHAPTER 9  CLICK 110 97
Autobaud
e second option that comes up when you’re cycling through the front panel menu is the autobaud function. is option is indicated by the green LED coming on solid.
Note
The autobaud function can only be accessed here, on the front panel menu.
is function initiates an autobaud on the RS-485 buses (you will select which bus to auto­baud on the Level 2 LEDs). An autobaud will stop data reporting on the selected port and attempt to communicate with the SmartSensor at all supported baud rates.
Level 1 LEDs
Level 2 LEDs
Table 9.9 – Front Panel Menu Autobaud Settings
Autobaud
Autobaud on bus 1
Autobaud on bus 2
Cancel and exit menu
LED o LED on
See the earlier Navigating through the Menu and the Menu Operation Example sections for how to congure this parameter.
As each baud rate is attempted, the Level 2 LEDs will sequence with a single LED illumi­nated from LED 1–4.
If the Click 110 is successful in communicating with a SmartSensor, it will display the baud rate found, using the same Level 2 LED system used in selecting the baud rate (covered in the Baud Rate section of this chapter and Table 9.10). Aer a short time of displaying the autobaud results, the menu will return to normal operation.
If the autobaud fails, all four Level 2 LEDs will ash once, and then the menu will return to normal operation.
Note
If the baud rate of either of the RS-485 buses was configured using the DIP switches (so that parameter is set to Hardware mode), the Level 2 LED configuration options for that bus will not be displayed (the LED option will never come on). If both RS-485 buses are configured using the DIP switches, the Level 1 LED menu option for auto­baud will not be displayed (the green LED option will never come on).
98 CHAPTER 9  CLICK 110
Baud Rate (Bus 1 and 2)
e next two conguration parameters that come up in the front panel menu allow you to manually set the baud rate of the two RS-485 buses. Bus 1 comes up rst, with the green and yellow LEDs coming on together; bus 2 comes up second, with the blue LED glowing solid.
Note
This parameter can also be changed using the DIP switches or Click Supervisor.
Level 1 LEDs
Level 2 LEDs
Table 9.10 – Front Panel Menu Baud Rate Settings
Baud rate for bus 1
Baud rate for bus 2
9600 bps (default)
19200 bps
38400 bps
57600 bps
Cancel and exit menu
LED o LED on
See the earlier Navigating through the Menu and the Menu Operation Example sections for how to congure this parameter.
Because this parameter can also be set by the DIP switches, you may need to ensure that the DIP switches are set to Soware conguration mode; if they are set to Hardware, the front panel menu will be able to display but not change these settings.
Channel Enable
e next congurable parameter is enabling output channels. To select this parameter, re­lease the push-button when the blue and yellow LEDs come on.
Note
This parameter can also be changed using the DIP switches or Click Supervisor.
A disabled output will never enter the detection state, and will never indicate a fault condi­tion. Any combination of outputs can be enabled. Due to limited space on the side label,
CHAPTER 9  CLICK 110 99
not all combinations of enabled and disabled channels are listed. A complete table is shown bel ow.
Level 1 LEDs
Level 2 LEDs
Channel Enable
All o (default)
Channel 4 on
Channel 3 on
Channels 3 and 4 on
Channel 2 on
Channels 2 and 4 on
Channels 2 and 3 on
Channels 2, 3, and 4 on
Channel 1 on
Channels 1 and 4 on
Channels 1 and 3 on
Channels 1, 3, and 4 on
Channels 1 and 2 on
Channels 1, 2, and 4 on
Table 9.11 – Front Panel Menu Channel Enable Settings
Channels 1, 2, and 3 on
Channels 1, 2, 3, and 4 on
Cancel and exit menu
LED o LED on
Note
If you are configuring the device with the front panel menu, it’s vital that you set up your enabled channels; if you don’t, as you can see in the table, it will default to all channels being disabled and the device will not work.
See the earlier Navigating through the Menu and the Menu Operation Example sections for how to congure this parameter.
Loading...