Watts Radiant SubRay Installation Manual

Page 1
Installation
Installation
Manual
Manual
44..0
0
4.0
Page 2
2 SubRay Installation Manual
Benefits of the SubRay® System
SubRay is a safe, practical, and easy way to install radiant
See the Watts Radiant Product Catalog or visit us on the Web at www.wattsradiant.com for an entire list of hydronic and electric radiant heating/snowmelting equipment.
Features of the SubRay System
• FAST — Quick and easy installation.
• CLEAN — No messy silicone needed.
• BIGGER ZONES — Twice the flow-rate of 5/16” PEX.
• SILENT — Silent floating RadiantPEX
• THIN — Less than 5/8” thick (with 3/8” RadiantPEX).
• THREE PIPES — 3/8” and 1/2” RadiantPEX, and 3/8” Onix.
®
/Onix™ design.
• COMFORTABLE — The best heat there is.
• FLEXIBLE
• LIGHTWEIGHT — Easy-to-carry parts.
• QUALITY — High quality, 7-ply, Douglas Fir, boat grade plywood
and cabinet grade Group 1 Baltic Birch that meets the specs of all wood flooring manufacturers.
• ECONOMICAL — Does not require constant circulation. Uses standard pipes and fittings.
— Accommodates odd-sized rooms.
Tools Required
• Saw
• Flat-blade screwdriver
• Hammer
• Rubber mallet
• Tape measure
• RadiantPEX Unwinder or Onix Unwinder
• Radiant Tubing Cutter
• Chalk line
FREE Design
Call 1-800-276-2419 for free design assistance on any SubRay installation.
(NYSE WTS)
4500 E. Progress Place Springfield, MO 65803-8816 800-276-2419 (USA and Canada) 417-864-6108 (phone) 417-864-8161 (fax) www.wattsradiant.com
Page 3
Quality Construction
European Baltic Birch is kiln dried, won’t splinter or crack, and holds nails and screws better than any construction­grade plywood. Sleepers are made from a high quality, 7-ply, Douglas Fir, boat grade ply wood that is finished and sanded on both sides. Both Birch and Douglas Fir compnents are made of multiple thin laminations for dimensional stability. Order 15 mm components for use with 3/8” RadiantPEX; order 18 mm components for 1/2” RadiantPEX and 3/8” Onix piped systems. All SubRay products are made of either Baltic Birch or Douglas Fir.
Note: Ends of 15-mm Birch parts are color-coded red;
18-mm parts are color-coded blue.
SubRay Component and Accessory List
Header Sticks (Fig. 1). Header Sticks hold radiant pipe at each end of the room and spaces it on 8” centers. When installing hardwood strip floor­ing, you must run header sticks parallel to the flooring at both ends of the room. If using other flooring types, run header sticks along both short sides of the room.
SubRay Installation Manual 3
Fig. 1. Header Sticks.
Fig. 2. Sleepers.
Sleepers (Fig. 2).
Sleepers are 6” wide and are installed 2” apart. They sup­port the finish floor and provide a radiant channel for the pip­ing to be safely installed. Allow about 30 Sleepers per 100 sq. ft. of floor.
Grippers (Fig. 3). Grippers are used to hold RadiantPEX where it enters or exits the floor so that the pipe will not rub against floor penetrations. Allow two for each RadiantPEX circuit. Not needed for Onix installations.
Radiant Tape (Fig. 4). Radiant Tape is applied to the bottom of each radiant chan­nel to reflect the radiant energy upward to the floor. Use a tape dispenser; allow one roll for every 240 sq. ft.
Aluminum Conduction Rolls (Fig. 5). Aluminum Conduction Rolls are installed over the top of the Sleepers, and help disperse the heat more evenly. Use one roll for each 70 sq. ft. of floor.
Corner Sweeps (Fig. 6). Corner Sweeps help RadiantPEX make a 90° turn. Most simple rectangular rooms will need two sweeps per pipe cir­cuit; most cut up complex rooms will need 5–15 sweeps per circuit. Not needed for Onix installations.
Fig. 3. Grippers.
Fig. 5.
Aluminum Conduction Roll.
Fig. 4. 2” Radiant Tape.
Fig. 6. Corner Sweep.
C-Covers (Fig. 7). C-Covers are heavy steel “U” guards that protect pipe from nails, and are used to support tile backer board. Most com­monly they are used to protect supply/return lines that run parallel to strip flooring.
Fig. 7. C-Cover.
Page 4
4 SubRay Installation Manual
Manifolds (Figs. 8 and 9).
Manifolds distribute hot water to the radiant circuits in the floor. Manifolds are installed as pairs. We suggest using manifolds with shut off and/or individual circuit balancing valves. Manifolds can be installed in walls, under frame floors, in utility closets, mechanical rooms, inside cabinets, or in any other accessible spot.
Zones
Zones are areas controlled by a shared thermostat or other control. A zone may be one room or several rooms, but all the radiant heating circuits for a zone will usually originate and return to a single manifold location.
Radiant Tubing (Figs. 10 and 11). Radiant Tubing transfers hot water or glycol/water through the radiant channels in a SubRay system. The red-coded 15-mm SubRay system is designed for 3/8" ASTM Watts Radiant RadiantPEX radiant tubing. The blue-coded 18-mm SubRay system is designed for use with both Watts Radiant 1/2" RadiantPEX, or 3/8" Onix radiant tubing.
Fig. 10. Onix radiant hose.
Fig. 11. RadiantPEX tubing.
Fig. 8. Watts Stainless Steel
manifolds with circuit balancing and circuit flow indicators.
Fig. 9. Manifold Box.
The SubRay Radiant System Installs Fast and Easy.
Fig. 12. Installing the SubRay 862 Radiant System.
(a). Lay out Header Sticks and 6" Sleepers. (b). Lay down 2" aluminized tape in the radiant channels. (c). Use a screwdriver to pop up the removable Header Plate. (d). Take the slack out of the RadiantPEX in the radiant channel. Then
push the tube into the header groove.
(e). Tap the Header Plate in place with a rubber hammer or step on it. (f). Put in a screw in the hole provided. (g). Lay the aluminum conduction roll over the wood and tube.
(b)
(c)
(d)
(e)
(g)
(a)
(f)
Page 5
SubRay Installation Manual 5
Fig. 13. Run your tubing to the far corner of the room and build your SubRay floor back to the manifolds.
Recommended.
Fig. 15. Building your SubRay floor to the center of the room.
Not Recommended!
Fig. 14. Building your SubRay floor from the manifolds.
Not Recommended!
Important SubRay Design Requirements
1. SubRay components are not structural, and
must be installed on top of structurally sound subfloors or slabs.
2. Unless you protect the pipe with C-Covers or nail-
guards, do not install SubRay piping immediately next to walls, in doorways, thresholds, or areas where you might expect nails to be driven by flooring, trim, or carpet installers. Be sure to allow for a perimeter strip around the edge of the room.
3. Locate manifolds as close to the area to be
heated as you can. Supply and return manifolds can be installed under floors, or in walls, but make sure they are accessible.
4. Avoid running supply/return lines or manifolds in
exterior walls. Freeze damage may result.
5. Hardwood floors can be installed directly over the
SubRay system. Other floor finishes will require a mini­mum 1/4", 3/8", or 1/2" plywood to be installed over the SubRay components. Read this manual’s directions for your particular floor covering before proceeding. This will ensure your finish floor heights will match.
6. Ask Watts Radiant or its professional reps to
perform a RadiantWorks™heat loss calculation to ensure the boiler, pumps and system design meet the structure’s heat load. This will include a list of radiant pipe, manifolds, SubRay components and other materi­als required for each zone. After you have done a few jobs you will probably feel comfortable doing your own take-offs.
Planning the Installation
Planning Your Tubing Layout
Here’s a good rule of thumb: Once you have located your supply and return manifolds, run your tubing circuit to the far corner of the room and then build your SubRay floor back to the manifolds. This is especially important when you have a manifold above the SubRay floor and there are multiple circuits of tubing in the zone. Figure 13 shows this design practice, and if you plan accordingly you can always get back to your manifold from any place in the room. Figures 14 and 15 are not recommended because if you build your SubRay floor from the manifold or toward the middle of the room, you will not have the space to return the end of the tubing circuit(s) back to the manifold location.
Page 6
6 SubRay Installation Manual
Manifold and Circuit Selection
Using 3/8" Onix or RadiantPEX, most contractors will run 200' circuits, although longer lengths are possible. Using standard 8" spacing, and allowing for manifold connections, a single 200' circuit will heat about 125 sq. ft.
Using 1/2" RadiantPEX, most contractors will run 300' circuits, which can heat about 200 sq. ft. Therefore, if you are heating a 375 sq. ft. room, you could select (3) 200' circuits, or (2) 300' circuits. You’ll need to select a supply/return manifold set with the correct number of branches to ser vice the circuits you’re using for each zone. Remember that you’ll need to use red-coded 15-mm SubRay components if you’re using 3/8" RadiantPEX, and blue-coded 18-mm compo­nents if you’re using 1/2" RadiantPEX or 3/8" Onix. We recommend Header Sticks if you’re using Onix, but you won’t need to secure the removable Header Plate as shown in Fig. 12e. See Watts Radiant’s RadiantPEX or Onix Radiant Design and Installation manuals for more information regarding tubing and manifold selection.
Note: We suggest using manifolds with individual circuit shut-off valves on both supply and return circuits. If your circuits are cut to special lengths, you should use balancing valves if any circuit within a single zone is more than 10% longer than the shortest circuit in that zone.
Manifold Location
The location of the manifolds can change the pipe layout, so this section of the manual gives you some ideas regarding manifold placement. Remember that manifolds must be accessible. The radiant tubing in the floor begins and ends at the manifolds, so piping access from the manifolds to the radiant floor is key. Although there are many possible ways to install mani­folds we will show you three popular methods.
Manifold Below the Floor
In Fig. 16 the radiant tubing enters the floor at one end of the room and exits at the other end. The mani­folds may be located under the floor, or at some remote location. You can run one, two, or more circuits in the same room using this method. Wherever you enter/exit the floor, cut a minimum 2"–3" long slot so that the radiant pipe will make a gentle upward bend, and not kink, where it enters the floor. Use a Gripper at each entry/exit slot to firmly hold the pipe in place, if you are using RadiantPEX (Fig. 16).
Fig. 16. Loop configuration with manifolds below the floor (manifolds not shown).
Manifolds Above the Floor
Manifolds may be installed in wall cavities, under vanities, in mechanical closets, or adjoining rooms. In Fig. 17 you’ll see a manifold in the wall, near a room corner.
Tubing in Wall Studs
This approach keeps your floor layout very simple, and is useful if you can run radiant piping through the walls. The radiant tubing leaves the supply manifold, runs through the wall studs and then to the far corner of
Fig. 17. Loop configuration with manifolds above the floor with radiant tubing running through adjacent studs.
Pipe enters floor
Gripper location
Gripper location
Pipe exits floor
Stud wall (overhead view)
Manifolds
Page 7
SubRay Installation Manual 7
Manifolds
Fig. 18. Loop configuration with manifolds above the floor and tubing in radiant channels.
the room. Then build your SubRay floor back to the return manifold.
Don’t run piping through exterior walls, unless frost­proofed with antifreeze. Cover the piping where it enters/exits the wall with nail plates to protect it against tack strips and trim nails.
Tubing in the Floor Only
You may not have the option of running piping through a wall, so locate your supply/return manifolds and cut a slot or drill a hole in the wall base plate to form an entry point for the radiant tubing. Install nail plates as needed to protect tubing from base trim and carpet tack strips. Form a radiant pathway for the tubing by installing a sec­ond sleeper, just after the perimeter sleeper strip on the left wall. Run the radiant tubing up this pathway (Fig. 18) along the left wall. If you are installing hardwood strip flooring you will want to install a protective C-Cover over the tubing because hardwood flooring will be running lengthwise over this pathway. Run your radiant channel to the far end of the room and build your Subray floor back to the return manifold. (See also Fig. 35.)
Installation Steps
How to Begin
1. Select the two opposing walls of the room that the
Header Sticks will be installed next to (labeled Wall A and Wall B in Fig. 19). Headers Sticks are normally installed on the two short walls of a rectangular room. If you are installing strip hardwood, the Header Sticks must be installed parallel to (running with) the flooring. Each Header Stick is 42" long and will hold three pipe bends. The radiant circuits begin at the manifold and are installed to run back and forth between the two sets of Header Sticks.
2. Screw or nail standard SubRay 6" Sleepers in a
continuous strip along the two Header Stick walls (A/B) (see Fig. 19).
Fig. 19. Planning the SubRay layout.
Direction of hardwood strip flooring (if used)
Wall A
Wall B
Manifolds
Page 8
8 SubRay Installation Manual
Installing Perimeter Strips and Header Sticks
3. Measure the width of the room, between the two
walls that do not have Header Sticks (labeled Wall C and Wall D in Fig. 20). Take this width (in inches) to Appendix B (page 20) and see which width of perimeter strips matches with your room width. In the example, a 120"-wide room (see span wall width in Appendix B, Fig. 43, page 20) will require 7" perimeter strips along walls C and D. Rip up SubRay Sleepers as needed to make up correct width and install the perimeter strips along walls C and D.
Fig. 20. Installing Perimeter Strips and Header Sticks. Fig. 22. Installing Sleepers and Radiant Tape.
Fig. 21. Detail of corner for Onix
installation without Corner Sweep. Due to its greater flexibility, Onix does not require Corner Sweeps.
4. Fasten down the Header Sticks along the Header
Stick walls (A,B), add Corner Sweeps (see Fig. 20) as needed. Corner Sweeps are not needed for Onix tubing; see Fig. 21 for detail. Note: Fasten the removable Header Plate only after radiant tubing is installed.
Important Note: Look ahead to Fig. 22 and see
how the Header Stick on wall B will always be offset by one radiant channel (8") compared to the Header Stick on wall A.
Installing Sleepers and Radiant Tape
5. Fill in Sleepers as shown in Fig. 22, maintaining
a 2" space between the Sleepers.
Note: Spacing of Sleepers is based on the Header
Sticks. It is recommended that a chalk line be made between the opposing Header Sticks for the first Sleeper and for every third or fourth Sleeper afterward to make sure that the Sleepers are installed with the 2" spacing between them (see Fig. 22). Do not
use
Grippers as spacers.
6. Lay in radiant Reflective Tape in the 2" space.
Wall C
Wall A
Wall D
Wall C
Chalk line
Wall A
Wall D
Corner Sweep
Sleepers
Wall B
Manifolds
Wall B
Manifolds
Perimeter Strip
Channel
Perimeter Strip
Channel
Header Stick
Page 9
SubRay Installation Manual 9
Wall C
Fig. 23. Installing Radiant Tubing. Fig. 25. Installing Aluminum Conduction Layer.
Running Radiant Tubing
7. Beginning at the manifolds, run the radiant tubing
in the radiant channels (see Fig. 23). Try to avoid field splices. Use Grippers where RadiantPEX enters or leaves the floor, as necessary.
8. Cover vulnerable areas of radiant tubing with
C-Covers (Figs. 7 and 23) or nail guards as needed. Use C-Covers anywhere radiant tubing is running parallel to hardwood strip flooring. Because Onix is slightly thicker than PEX, C-Covers over Onix may need to be secured by driving roofing nails between the C-Cover and the Sleepers (see Fig. 24).
9. When the piping in each zone is installed, connect
it to the manifolds. Use a Watts Radiant pressure test kit, or equivalent, to pressurize each SubRay zone to
100 psi or as local codes require. If possible, pressurize the system for 24 hours before rolling out the Aluminum Conduction Rolls. You must pressurize the system for a minimum of 24 hours before covering it with a perma­nent floor. After a 24-hour initial test, the system should experience no more than a 10% loss of pressure.
Maintain a pressure in the system continuously until the finish floor is installed and the base trim is installed. Check the system frequently while other tradespeople are working on the job to minimize the chance of con­cealed damage. Read the Watts Radiant RadiantPEX or Onix manuals for essential pressure test procedures and cautions before pressure testing. If a leak is sus­pected, check all connections and locations of possible pipe damage before retesting the system. If you are not sure how to proceed, please call Watts Radiant or your local technical support person for advice.
Installing Aluminum Conduction Layer
10. Roll out the first Aluminum Conduction Roll (see
Fig. 25). Leave the Header Sticks exposed if you will be nailing a finish floor down and need to see where the radiant pipe is installed.
Fig. 24. Securing C-Covers over Onix radiant tubing.
Wall A
Aluminum Conduction Roll
Wall D
C-Cover
C-Cover
Wall B
Roofing Nails
(driven between Sleepers and C-Cover)
C-Cover
(over Onix)
Sleeper Sleeper
Plywood Subfloor
C-Cover
C-Cover
Page 10
Fig. 26. Installing hardwood flooring.
11. Roll out the rest of the rolls, but leave a 1/2"
gap between them, so that you will be able to clearly see where the pipes are located underneath.
Installing Finish Flooring
12. After consulting the section(s) of this manual
that apply to your finish flooring, cover the SubRay System with the correct subfinish and finish flooring materials (Fig. 26), as outlined in this manual and required by the finish flooring manufacturer.
10 SubRay Installation Manual
Fig. 27. A Watts Radiant HydroControl maintains control over the water temperature entering the SubRay zone.
Insulation
Adequate insulation will reduce fuel bills and increase comfort. When SubRay is installed over a frame floor, it is highly desirable to insulate under the floor, unless it is physically impossible. If the lower floor is heated, you should use a minimum R-13 batt under the floor. If the area below is unheated, then use a R-19 to R-38 batt under the floor. See following figures for illustrations of various ways to insulate under floors.
If SubRay is installed over a new slab, the slab, espe­cially the slab perimeter, should be insulated to at least
the standards of the local building code, although most builders will add additional insulation. If installed over an old slab, 1" to 3" of perimeter insulation should be retrofitted.
If it is impossible to insulate under the floor consult
with Watts Radiant before proceeding.
Operating Guidelines
The SubRay system does not require costly or com­plex constant circulation systems to maintain even floor temperatures. You may wish to use a Watts Radiant dual-sensing stat that measures both air and floor temperature, an outdoor reset system, or other control option. Consult with your Watts Radiant representative for technical assistance.
For maximum comfort, ASHRAE Guidelines suggest that floor surface temperatures should not exceed 85°F in most living areas. Most floors will warm to between 75° and 80° to meet the heat loss, perhaps more during cold weather, or where a building is not well insulated.
Some types of finished flooring are made of glues, laminates, or polymers that may react adversely to higher temperatures. When in doubt, check with the flooring manufacturer regarding temperature limits for their materials.
The water and surface temperatures can be con­trolled with a combination of Watts dual-sensing stats (air/floor), preassembled HydroControl®Panels (see Fig. 27) or other combinations. Always use the lowest temperature necessary to maintain comfort. Do not allow inlet water temperatures to exceed 160°F.
Hardwood Flooring
Aluminum Conduction Roll
Page 11
SubRay Installation Manual 11
Fig. 28. Hardwood over SubRay system, over slab.
SubRay Installation and Floor Surfaces
Natural Hardwood Flooring
Preparation of Slab. Secure Sleepers and Header
Sticks to the underlying slab on 8" centers. Concrete nails may spall some concrete, and cause rocking. If so, use concrete screws or bolts (see Appendix A for details). We recommend you predrill the Sleepers before drilling into the concrete. The slab must have a vapor barrier installed underneath it to prevent ground mois­ture from coming up into the floor. If the slab is less than six months old, or contains residual moisture, it must first be aged or heated to drive out the moisture. Tape down a 2' x 2' square of plastic over a section of the slab and wait 24 hours. If there is no moisture pres­ent on the plastic sheet after this test, the concrete is suitably dry for a wood floor to be installed over it. If in doubt as to moisture content of the slab, or if installing over an existing older slab; you must install a thick (eight mil or better) vapor barrier over the slab. Overlap and tape the edges of the barrier to prevent residual concrete moisture from damaging the wood flooring.
The slab beneath must be insulated according to local code and practices. In a retrofit of an existing slab, it may not be possible to insulate the slab. See your Watts Radiant representative for additional design and installation concepts if you cannot insulate the slab.
Aluminum
Conduction
Roll
Sleepers
Radiant Tubing
Radiant
Tape
Vapor Barrier
Slab
Extruded Polystyrene Insulation
Hardwood Flooring
Preparation of Subfloor. Secure Sleepers and Header
Sticks to the underlying subfloor on 6" to 8" centers. Preferentially use screws. Do not install a vapor barrier over a subfloor if the space below is unconditioned, as this could trap moisture in the floor.
Wood Selection. Use only kiln-dried 3/4"-thick
hardwood flooring. Widths up to 3-1/4" are acceptable. The wood must be site tested to ensure that its moisture content does not exceed 8% when installed. Follow all installation recommendations of the wood flooring manu­facturer and the National Oak Flooring Manufacturer’s Association.
Special Considerations. Hardwood strip flooring can
be installed directly over the SubRay aluminum conduc­tion layer. Stagger all joints; if a length of flooring ends over the 2" radiant channel, it is not necessary to trim it so that it ends over a sleeper. Hardwood strips can easily span this channel.
When you install hardwood strips parallel to a radiant channel, such as for a supply/return line, cover the radi­ant channel with a C-Cover. The C-Cover protects the tub­ing underneath from nails and staples. Use adhesive, instead of nails, to hold down the flooring installed directly over the C-Cover.
If drywalling or painting after the flooring is installed, provide suitable ventilation to prevent wood from absorb­ing excess moisture.
Additional Sources of Information. Contact The Hardwood Council at www.hardwoodcouncil.com or The National Oak Flooring Manufacturer’s Association at www.nofma.org or call 901-526-5016.
Fig. 29. Hardwood over SubRay system, over frame floor.
Aluminum
Conduction
Roll
Sleepers Radiant
Tubing
Subfloor
Hardwood Flooring
Insulation
Radiant
Tape
Page 12
12 SubRay Installation Manual
Tile, Ceramic, and Stone
Preparation of Slab. Secure Sleepers and Header
Sticks to the underlying slab on 6" to 8" centers. Concrete nails may spall some concrete, and cause rocking. If so, use concrete screws or bolts. We recom­mend predrilling the Sleepers before drilling into the concrete. The slab must have a vapor barrier installed underneath to prevent ground moisture from coming up into the floor. If installing over an existing older slab, lay a thick (8 mil or better) vapor over the slab to keep ground moisture out. Overlap and tape the edges of the barrier to prevent residual concrete moisture from coming up.
The slab beneath must be insulated according to local code and practices. When retrofitting over an exist­ing slab, it may not be possible to insulate to modern practices. See your Watts Radiant representative for additional design and installation concepts if you cannot insulate the slab. Always consult with your Watts Radiant representative for a design analysis when installing over an existing slab.
Preparation of Subfloor. Secure Sleepers and Header Sticks to the underlying subfloor on 6" to 8" centers. Preferentially use screws. Insulate under the subfloor according to local standards for radiant floors, or con­sult with Watts Radiant. A subfloor must be designed to hold the weight of the flooring without excessive deflec­tion or bending of the floor. Generally, subfloor deflec­tion must not exceed L/360 when the floor is exposed to the combined design dead and live loads.
General Guidelines. All tile floors should be installed according to the guidelines of the TCA or ANSI specifica­tions. The following steps are illustrative, and provided for general guidance only. Local codes, customs, or good engineering or contractor experience may dictate other procedures. Consult with Watts Radiant for further advice or suggestions.
Bridge the Channel. Tile, ceramic, or stone flooring will not bridge the two inch wide radiant channel where the radiant tubing is installed. There are at least three ways you can proceed.
1. Some installers will fill the radiant channel with
“mud,” and cover the Sleepers, channels, and Header Sticks with the aluminum conduction roll. Leave 1/2" gaps between the rolls for radiant channel visibility, and screw down cement board (TCA Guideline) or plywood over the aluminum (not illustrated).
2. Where keeping the floor height to a minimum is
important, fill the radiant channels using C-Covers, and then roll out the aluminum. Screw down the cement board (TCA Guideline) or plywood over the SubRay assembly, covering the aluminum sheet (see Fig. 30).
3. A third choice is to roll out the aluminum over the
Sleepers, and then bridge over the radiant channels with
Fig. 30. Tile over SubRay system, over frame floor.
Thinset
Thinset
Backerboard
C-Covers
Sleepers
Radiant Tubing
Subfloor
Tile
Fig. 31. Tile over SubRay system, over frame floor.
Thinset
Thinset
Backerboard
Second Sheet Plywood
Aluminum Conduction Roll
Sleepers
Radiant Tubing
Insulation
Insulation
Subfloor
Tile
Radiant
Tape
Radiant
Tape
Page 13
SubRay Installation Manual 13
3/8" plywood. Screw the second sheet of plywood down carefully to avoid damaging the radiant tubing. If you are following TCA/ANSI practice of installing tile backerboard over plywood, you’ll need to snap chalk lines on the ply­wood. Use these chalk lines to mark the Header Sticks and radiant channel locations, so that you can safely screw the cement board over the plywood (Fig. 31).
Caution: Cementious adhesives used in thinset or
mortar could cause the aluminum to surface oxidize, breaking the bond between the aluminum and tile/stone directly above. Use screws on 6" to 8" centers to mechanically fasten the overlay sheets to the subfloor and SubRay materials.
The recommended fastener is a corrosion-resistant 1-1/4" No. 8 by .323" head diameter ribbed screw with countersunk head. The screw must be long enough to reach through the SubRay materials to the bottom of the supporting subfloor.
Install Tile or Stone Floor.
Caution: Always cover the aluminum conduction
sheet with cement board or plywood before setting tile or stone. Do not apply thinset or mortar directly to the aluminum sheet.
Using a 1/4" notched trowel, apply a layer of latex or acrylic modified thinset mortar (complying with ANSI A118.4) to the surface of the cement board or plywood. Alternatively use thickset mortar as local custom or codes may require.
Caution: The system must always be pressurized dur­ing construction. Check the pressure gauges frequently while you are using screws or nails near the radiant tub­ing. Use approved Watts Radiant field splices as needed.
Consult with thinset or mortar supplier before applying heat. Most cementious materials will require at least 7 to 28 days to reach design strength. Premature applica­tion of heat will cause weakening of thinset and mortar.
Carpet
If properly designed, most combinations of carpet and pad may be installed over a SubRay radiant floor. Due to the insulating value of carpet and pad, all SubRay installations should be designed by an authorized Watts Radiant representative using the latest version of RadiantWorks®, Watts Radiant’s design software.
RadiantWorks software calculates the heat loss of each zone based on the specific building design and local climate. The software calculates the insulating value of the floor coverings to determine the required radiant fluid temperature. If necessary, RadiantWorks will tell the designer if supplemental sources of heat may be required. In most cases the radiant system is capable of satisfying the heat load.
After laying out the SubRay components and installing the radiant tubing, roll out the aluminum conduction roll.
Leave a 1/2" space between each roll so that the floor­ing contractor can see where the radiant channels are located. Screw or nail a minimum of 3/8" plywood, or equivalent structural subflooring product, over the SubRay components. Observe care near the Header Sticks (see Fig. 32).
Always maintain a minimum 3" perimeter strip around the room. This perimeter strip should not have any radi­ant tubing installed in it, unless the tubing is protected against nails and carpet tack strips. If any tubing runs from one room to another, the threshold area should have nail guards installed to protect the tubing against tack strips.
Caution: The system must always be pressurized during construction. Check the pressure gauges on your manifold test kit frequently anytime you are using screws or nails near the radiant tubing, and for at least 24 hours afterward. Use approved Watts Radiant field splices if the tubing is damaged.
According to industry guidelines, the radiant system should be designed so that the surface of the carpet does not exceed 85°F.
Advice about carpet installation is available at the Carpet and Rug Institute in Dalton, Georgia. Call 706-428-2106 or contact the Institute at www.carpet­rug.com.
Fig. 32. Carpet over SubRay system, over frame floor.
Plywood
Sleepers
Aluminum
Conduction
Roll
Radiant Tubing
Subfloor
Insulation
Carpet
Radiant
Tape
Page 14
14 SubRay Installation Manual
Pergo®Laminate
Installation Requirements. Pergo floors can be in-
stalled over a SubRay system, as long as the following Pergo requirements are observed. All SubRay installa­tions should be designed by an authorized Watts Radiant representative using the latest version of RadiantWorks, Watts Radiant’s design software.
Preparation of Slab. Secure Sleepers and Header
Sticks to the underlying slab on 8" centers. Concrete nails may spall some concrete, and cause rocking. If so, use concrete screws or bolts (see Appendix A). We recommend you predrill the Sleepers before drilling into the concrete. The slab must have a vapor barrier installed underneath it to prevent ground moisture from coming up into the floor. If the slab is less than 6 months old, or contains residual moisture, it must first be aged or heated to drive out the moisture. Tape down a 2' x 2' square of plastic over a section of the slab and wait 24 hours. If there is no moisture present on the plastic sheet after this test, the concrete is suitably dry for the finish flooring to be installed over it. If in doubt as to moisture content of the slab, or if installing over an existing older slab, you must install a thick (eight mil or better) vapor over the slab. Overlap and tape the edges of the barrier to prevent residual concrete moisture from damaging the flooring.
The slab beneath must be insulated according to local code and practices. In a retrofit of an existing slab, it may not be possible to insulate the slab. See your Watts Radiant representative for additional design and installa­tion concepts if you cannot insulate the slab. Always con­sult with your Watts Radiant representative for a design analysis when installing over an existing slab.
Preparation of Subfloor. Secure Sleepers and Header Sticks to the underlying subfloor on 6" to 8" centers. Preferentially use screws. Do not install a vapor barrier over a subfloor if the space below is unconditioned, as this could trap moisture in the floor. Always insulate under the subfloor in accordance with local codes. If in doubt as to the recommended insulation, consult with Watts Radiant for design assistance.
RadiantWorks software calculates the heat loss of each zone based on the specific building design and local climate. The software calculates the insulating value of the floor coverings to determine the required radiant fluid temperature. If necessary, RadiantWorks will tell the designer if supplemental sources of heat may be required. In most cases the radiant system is capable of satisfying the heat load.
After laying out the SubRay components and installing the radiant tubing; roll out the aluminum conduction roll. Leave a 1/2" space between each roll so that the floor­ing contractor can see where the radiant channels are located. Screw or nail a minimum of 1/2" plywood over
the SubRay components. Observe care near the Header Sticks.
Always maintain a minimum 3" perimeter strip around the room. This perimeter strip should not have any radi­ant tubing installed in it unless the tubing is protected against trim nails/staples and possible future carpet tack strips. If any tubing runs from one room to another, the threshold area should have nail guards installed to protect the tubing against possible future tack strips.
Caution: The system must always be pressurized during construction. Check the pressure gauges on your manifold test kit frequently anytime you are using screws or nails near the radiant tubing, and for at least 24 hours afterward. Use approved Watts Radiant field splices if the tubing is damaged.
According to Pergo guidelines, the radiant system should be designed so that the surface of the Pergo flooring does not exceed 84°F. A Watts Radiant DualTemp thermostat is available with this floor limit feature.
Advice about Pergo specifications and installation instructions is available at www.pergo.com.
Wilsonart
®
Installation Requirements. Wilsonart floors can be installed over a SubRay system, as long as the Wilsonart requirements are observed. All SubRay installation should be designed by an authorized Watts Radiant representative using the latest version of RadiantWorks, Watts Radiant’s design software.
Preparation of Slab. Secure Sleepers and Header Sticks to the underlying slab on 8" centers. Concrete nails may spall some concrete, and cause rocking. If so,
Fig. 33. Pergo over SubRay system, over frame floor.
Sleepers
Radiant Tubing
Pergo
1/2" Plywood
Aluminum
Conduction
Roll
Insulation
Subfloor
Radiant
Tape
Page 15
SubRay Installation Manual 15
use concrete screws or bolts (see Appendix A). We recommend you predrill the Sleepers before drilling into the concrete. The slab must have a vapor barrier installed underneath it to prevent ground moisture from coming up into the floor. If the slab is less than 6 months old, or contains residual moisture, it must first be aged or heated to drive out the moisture. Tape down a 2' x 2' square of plastic over a section of the slab and wait 24 hours. If there is no moisture present on the plastic sheet after this test, the concrete is suitably dry for the finish flooring to be installed over it. If in doubt as to moisture content of the slab, or if installing over an existing older slab, you must install a thick (8 mil or better) vapor over the slab. Overlap and tape the edges of the barrier to prevent residual concrete moisture from damaging the flooring.
The slab beneath must be insulated according to local code and practices. In a retrofit of an existing slab, it may not be possible to insulate the slab. See your Watts Radiant representative for additional design and installa­tion concepts if you cannot insulate the slab. Always consult with your Watts Radiant representative for a design analysis when installing over an existing slab.
Preparation of Subfloor. Secure Sleepers and Header Sticks to the underlying subfloor on 6" to 8" centers. Preferentially use screws. Do not install a vapor barrier over a subfloor if the space below is unconditioned, as this could trap moisture in the floor. Always insulate under the subfloor in accordance with local codes. If in doubt as to the recommended insulation, consult with Watts Radiant for design assistance.
Fig. 34. Wilsonart over SubRay system, over frame floor.
Sleepers
Radiant Tubing
Wilsonart
1/2" Plywood
Aluminum
Conduction
Roll
Insulation
Subfloor
Radiant
Tape
RadiantWorks software calculates the heat loss of each zone based on the specific building design and local climate. The software calculates the insulating value of the floor coverings to determine the required radiant fluid temperature. If necessary, RadiantWorks will tell the designer if supplemental sources of heat may be required. In most cases the radiant system is capable of satisfying the heat load.
After laying out the SubRay components and installing the radiant tubing; roll out the aluminum conduction roll. Leave a 1/2" space between each sheet so that the flooring contractor can see where the radiant channels are located. Screw or nail a minimum of 1/4" plywood over the SubRay components. Observe care near the Header Sticks.
Always maintain a minimum 3" perimeter strip around the room. This perimeter strip should not have any radi­ant tubing installed in it, unless the tubing is protected against trim nails/staples, and possible future carpet tack strips. If any tubing runs from one room to another, the threshold area should have nail guards installed to protect the tubing against possible future tack strips.
Caution: The system must always be pressurized during construction. Check the pressure gauges on your manifold test kit frequently anytime you are using screws or nails near the radiant tubing, and for at least 24 hours afterward. Use approved Watts Radiant field splices if the tubing is damaged.
According to Wilsonart guidelines, the radiant system should be installed so that the surface of the Wilsonart flooring does not exceed 84°F. A Watts Radiant DualTemp thermostat is available with this floor limit feature.
Advice about Wilsonart specifications and installation instructions is available at www.wilsonart.com, or call 1-800-710-8846.
Other Flooring Options
Other flooring options may be heated with a SubRay system. Consult with Watts Radiant and the flooring manufacturer for written application instructions before proceeding. Some vinyl floors are very temperature sensitive and may fade when exposed to normal floor warming conditions.
Watts Radiant can make no representations regarding color stability of all vinyl floors. We suggest you consult with the flooring manufacturer to verify that their product is temperature stable.
The use of a Watts Radiant DualTemp thermostat pro­vides for a safe and easy way to limit the floor surface temperature. Simply dial in the maximum floor tempera­ture you want and this control will not permit your floor to rise above the limit you have programmed.
Page 16
Fig. 35. SubRay system alternate layout: bathroom
16 SubRay Installation Manual
Header Stick
C-Covers (optional)
Supply/Return Manifolds
Place tubing as close as possible to face of cabinet.
Corner Sweep
Sleepers
Perimeter Strip
Bath Layout
1 circuit of tubing, 130' long
Page 17
SubRay Installation Manual 17
Fig. 36. SubRay layout: room with circular wall.
Fig. 37. SubRay layout: room with bay window.
Sleeper
Header Stick
(cut to accommodate
curve of the wall)
C-Cover
(optional)
Sleepers
Perimeter Strip
Tubing enters zone
from manifold
below floor
Tubing returns to manifold below floor
C-Cover (optional)
Perimeter Strip
C-Cover (optional)
Header Stick
Corner Sweep
Header Stick
(cut to accommodate
curve of the wall)
C-Cover (optional)
Supply/Return Manifolds
Circular Wall Layout
3 circuits of tubing, 150' long
Bay Window Layout
3 circuits of tubing, 160' long
Page 18
18 SubRay Installation Manual
Fig. 38. SubRay layout: three rooms with central manifold.
Supply/Return
Manifolds
Fill in this area with scrap Sleeper cut-offs.
Corner Sweep
Corner Sweep
Sleepers
C-Covers
(optional)
Header Sticks
Perimeter Strip
Corner Sweep
Header Sticks
Perimeter Strip
Three-room Layout
2 circuits of tubing, 160' long
Page 19
SubRay Installation Manual 19
Attaching the SubRay Components to Concrete
Fig. 39. If you need to secure the Header Sticks or Sleepers to a concrete slab, first lay out your compo­nents so you have a very good idea of where they will be permanently fastened. Use a hammer drill with a 3/16" carbide tipped masonry bit to drill a 1-3/4" deep hole through the Sleeper and into the concrete.
Fig. 40. Place a 1-1/2" Powers Mush Head Spike (or equivalent) in the hole and use a hammer to drive the spike so the head is flush or below the surface of the wood. Locate Spikes as needed along the Sleepers and Header Sticks. The Spikes are permanent and cannot be removed without destroying the wood, so plan your work carefully.
Fig. 41. You can also secure SubRay Sleepers and Header Sticks to a concrete slab using a powder actuated nailer. Be sure to use facial and ear protection when using this device.
Fig. 42. When you must trim a SubRay Header Stick, cut it along line indicated by the circle to preserve the 2" radiant channel. For more detailed information
on properly cutting Header Sticks, see page 23.
Appendix A
10"
Page 20
20 SubRay Installation Manual
3" 3.5" 4" 4.5" 5" 5.5" 6" 6.5" 7" 7.5" 8" 8.5" 9" 9.5" 10" 10.5"
48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95
96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297 298 299 300 301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 328 329 330 331 332 333 334 335 336 337 338 339 340 341 342 343 344 345 346 347 348 349 350 351 352 353 354 355 356 357 358 359 360 361 362 363 364 365 366 367 368 369 370 371 372 373 374 375 376 377 378 379 380 381 382 383 384 385 386 387 388 389 390 391 392 393 394 395 396 397 398 399 400 401 402 403 404 405 406 407 408 409 410 411 412 413 414 415 416 417 418 419 420 421 422 423 424 425 426 427 428 429 430 431 432 433 434 435 436 437 438 439 440 441 442 443 444 445 446 447 448 449 450 451 452 453 454 455 456 457 458 459 460 461 462 463 464 465 466 467 468 469 470 471 472 473 474 475 476 477 478 479 480 481 482 483 484 485 486 487 488 489 490 491 492 493 494 495 496 497 498 499 500 501 502 503 504 505 506 507 508 509 510 511 512 513 514 515 516 517 518 519 520 521 522 523 524 525 526 527
Rip Perimeter Strips to this width for two sides of the room, according to room width.
Width of Span Wall (inches)
120"
Use standard 6" Perimeter Strips behind Header Sticks. See chart for other Perimeter Strip widths.
Example: When width of room equals 120" (see chart at left for 120" width), look at top of chart to see Perimeter Strip width (7") for non-Header Stick walls.
Fig. 43. How to center Header Sticks.
Appendix B
Selecting Perimeter Strip Widths to Center Header Sticks to Room
6" Perimeter Strips
7" Perimeter Strips
7" Perimeter Strips
6" Perimeter Strips
Header Sticks
Page 21
SubRay Installation Manual 21
Appendix C
SubRay Materials Estimating Guide
Introduction: Before using this quick SubRay material estimating sheet, read the SubRay design manual. Actual quantities of Header Sticks and Sweeps may vary, especially for complex or irregular rooms. The amount of Sleepers, Tape, Grippers, and Aluminum Rolls relates directly to room size.
The SubRay 862 system uses tubing on 8" centers, so 1' of tubing will heat .67 sq. ft. of floor. Typical lengths for 3/8" tubing are 200’ and for 1/2" tubing 300'.
Fill in the blanks to calculate your material requirements. See the Watts Radiant website for a simple automated SubRay quoting system.
If using 3/8" RadiantPEX order 15 mm (coded red) wood parts and channels. If you are using 1/2" RadiantPEX or 3/8" Onix order 18 mm (coded blue) wood parts and channels.
Room Area
Calculate the room area (length x width) in square feet (sq. ft.) and enter below.
L ________ x W ________ = ________ sq. ft.
Example: 20' x 40' room = 800 sq. ft.
Radiant Tubing
Divide room area by .67 to get feet of tubing.
_________ sq. ft./.67 = ________ total feet of radiant tubing.
Example: 800 sq. ft./.67 = 1194 ft. of tubing.
Radiant Circuits
Divide feet of radiant tubing by typical circuit length. We suggest 200' for 3/8" tubing, and 300' for 1/2" tubing. Round the result up to the next largest whole number.
________ ft. of tubing/200 = _______ circuits of 3/8" tubing.
________ ft. of tubing/300 = _______ circuits of 1/2" tubing.
Example: 1194 ft. tubing/200 = 5.97 circuits of 3/8" tubing. Round this up to 6 circuits, each averaging about 199 ft.
Figuring Notes:
Page 22
22 SubRay Installation Manual
Appendix C (continued)
SubRay Materials Estimating Guide
Header Sticks
Add the lengths of the two opposing walls along which the Header Sticks will be installed. Normally, these are the two short walls in the room, but the finished orientation of a hardwood floor may dictate otherwise. See page 5 for example.
_______ Wall A + _______ Wall B = ________ Total Header Wall Length.
Example: 20' + 20' = 40' of Header Wall Length (HWL).
Divide this total by 3.5 to get the number of Header Sticks you’ll need. Round up to the next largest number.
________ (HWL)/3.5 = ________ Number of Header Sticks.
Example: 40/3.5 = 11.4. Order 12 Header Sticks.
Sleepers
Take the room area and divide by 3.3 to get the number of Sleepers.
________ (area)/3.3 = ________ Number of Sleepers.
Example: 800 sq. ft./3.3 = 242 Sleepers
Corner Sweeps (not needed for Onix installations)
Multiply number of radiant circuits in room by four for rectangular rooms. Multiply number of radiant circuits in room by twelve for complex rooms.
________ (circuits) x ________ = ________ Sweeps Needed.
Example: A square room with 6 circuits will need 6 x 4 = 24 Corner Sweeps.
Rolls of Radiant Tape
Divide room area by 240 and round up to next largest number.
_______ (area)/240 = _______ Number of Radiant Tape Rolls.
Example: 800/240 = 3.33. Order 4 Radiant Tape Rolls.
Figuring Notes:
Page 23
SubRay Installation Manual 23
Appendix C (continued)
SubRay Materials Estimating Guide
Grippers (not needed for Onix installations)
Multiply the number of radiant circuits by two.
______ Radiant Circuits x 2 = ______ number of Grippers.
Example: 6 circuits x 2 = 12. Order 12 Grippers.
Aluminum Conduction Rolls
Divide room area by 70 and round up to next largest number.
_______ room area/70 = ______ Number of Aluminum Rolls.
Example: 800/70 = 11.4. Order 12 Rolls of Aluminum.
C-Covers
For most hardwood floors order enough C-Covers to run the length of the room.
Divide room length by 4 to get number of C-Covers.
______ room length/4 = ______ number of C-Covers.
Example: The room is 40' long. 40/4 = 10. Order 10 C-Covers.
Note: Many projects may not need C-Covers. See Manual to see if you need them.
Header Stick cutting detail:
Figuring Notes:
42"
10"10"10"
CUT
CUT
CUT
CUT
Page 24
Proud Members Of:
Charter Member:
4500 E. Progress Place Springfield, MO 65803-8816 417-864-6108
Radiant Panel Association
417-864-8161 f a x 800-276-2419 (u s a and c a n a d a ) www.wattsradiant.com
© Copyright 2004-2008 Watts Radiant, Inc. SubRay Installation Manual 4.0 LIT#SR862MAN0308 Effective 03/01/2008