SubRay Installation Manual 13
3/8" plywood. Screw the second sheet of plywood down
carefully to avoid damaging the radiant tubing. If you are
following TCA/ANSI practice of installing tile backerboard
over plywood, you’ll need to snap chalk lines on the plywood. Use these chalk lines to mark the Header Sticks
and radiant channel locations, so that you can safely
screw the cement board over the plywood (Fig. 31).
Caution: Cementious adhesives used in thinset or
mortar could cause the aluminum to surface oxidize,
breaking the bond between the aluminum and tile/stone
directly above. Use screws on 6" to 8" centers to
mechanically fasten the overlay sheets to the subfloor
and SubRay materials.
The recommended fastener is a corrosion-resistant
1-1/4" No. 8 by .323" head diameter ribbed screw with
countersunk head. The screw must be long enough to
reach through the SubRay materials to the bottom of the
supporting subfloor.
Install Tile or Stone Floor.
Caution: Always cover the aluminum conduction
sheet with cement board or plywood before setting tile
or stone. Do not apply thinset or mortar directly to the
aluminum sheet.
Using a 1/4" notched trowel, apply a layer of latex or
acrylic modified thinset mortar (complying with ANSI
A118.4) to the surface of the cement board or plywood.
Alternatively use thickset mortar as local custom or
codes may require.
Caution: The system must always be pressurized during construction. Check the pressure gauges frequently
while you are using screws or nails near the radiant tubing. Use approved Watts Radiant field splices as needed.
Consult with thinset or mortar supplier before applying
heat. Most cementious materials will require at least 7
to 28 days to reach design strength. Premature application of heat will cause weakening of thinset and mortar.
Carpet
If properly designed, most combinations of carpet
and pad may be installed over a SubRay radiant floor.
Due to the insulating value of carpet and pad, all SubRay
installations should be designed by an authorized
Watts Radiant representative using the latest version
of RadiantWorks®, Watts Radiant’s design software.
RadiantWorks software calculates the heat loss of
each zone based on the specific building design and
local climate. The software calculates the insulating
value of the floor coverings to determine the required
radiant fluid temperature. If necessary, RadiantWorks will
tell the designer if supplemental sources of heat may be
required. In most cases the radiant system is capable of
satisfying the heat load.
After laying out the SubRay components and installing
the radiant tubing, roll out the aluminum conduction roll.
Leave a 1/2" space between each roll so that the flooring contractor can see where the radiant channels are
located. Screw or nail a minimum of 3/8" plywood, or
equivalent structural subflooring product, over the
SubRay components. Observe care near the Header
Sticks (see Fig. 32).
Always maintain a minimum 3" perimeter strip around
the room. This perimeter strip should not have any radiant tubing installed in it, unless the tubing is protected
against nails and carpet tack strips. If any tubing runs
from one room to another, the threshold area should
have nail guards installed to protect the tubing against
tack strips.
Caution: The system must always be pressurized
during construction. Check the pressure gauges on
your manifold test kit frequently anytime you are using
screws or nails near the radiant tubing, and for at least
24 hours afterward. Use approved Watts Radiant field
splices if the tubing is damaged.
According to industry guidelines, the radiant system
should be designed so that the surface of the carpet
does not exceed 85°F.
Advice about carpet installation is available at
the Carpet and Rug Institute in Dalton, Georgia. Call
706-428-2106 or contact the Institute at www.carpetrug.com.
Fig. 32. Carpet over SubRay system, over frame floor.
Plywood
Sleepers
Aluminum
Conduction
Roll
Radiant
Tubing
Subfloor
Insulation
Carpet
Radiant
Tape