Watts SAN89 User Manual

Gauge Glass Cut-offs
No. N89S No. N89D
Instructions for Installing
No. N89S, N89D - Low water cut-off.
Note: Install carefully and line up so that the top of switch box is reason-
ably level.
1. Remove gauge glass and cocks from boiler.
2. Install the 1⁄2" tee, with long and short nipples, on the float chamber by
3. Insert long nipple into lower gauge glass tapping in boiler. Swing the entire
float chamber until the nipple is made up tight. The cut-off must be level. Fig. 3.
4. Screw the nipple which is in the tee carrying the tubing connector into the
upper gauge glass tipping and pull up tight. Install compression coupling in top float chamber tapping. Fig. 4.
5. Hold tube bend in position, Fig. 5, and mark tube on level with top of hex
on compression coupling. Cut off tube at this mark.
6. Slide ring and nut over end of tube. Slide end of tube into compression cou-
pling in float chamber. Tighten both couplings.
7. Install drain valve in bottom float chamber tapping. Fig. 6.
8. Re-install gauge cocks in the end of the tees and replace the gauge glass.
Fig 6.
NOTE: Open the drain valve at least once every month or more often dur­ing boiler operation to flush out sediment from the float chamber. This must be done to insure FULL boiler PROTECTION
Single Switch Assembly (See Page 4) (Replaces former No. 89S and No. 89A)
"DUAL" (two) Switch Assembly (See Page 3) (Replaces former No. 89D and No. DT89A)
Maximum Steam Pressure 15 lbs.
.
Fig. 1
IS-N89
Fig. 2
Fig. 3
Flared Connection
Compression Coupling
Fig. 4
Cut tube on Level with Top of Hex.
Standard switch entirely suitable for millivolt service on self-energized control circuits of gas fired heating installations.
Fig. 5
Top of Box Must Be Level
Fig. 6
Built-in Cut-offs
No. N93S, N193S, N101S
with Single Switch Assembly. (See Page 4)
No. N93D, N193, N101D
with "DUAL" (Two) Switch Assembly. (See Page 3)
This line of cut-offs was designed for boilers where a 21⁄2" pipe tapping is provided for the low water cut-off and where space is limited by the boiler jacket. For boilers that do not have this tapping, use WATTS No. N89S, N89D which is made for gauge glass connection.
Special Notice
Before leaving the job, it is recommended that the installation of the cut-off be checked under actual working conditions; this will reveal any installation irregularities.
To check, turn on switch to burner and if water in boiler is at or above the water line, the cut-off will allow the burner to start. Now lower the water line by draining off water from the boiler; if the cut-off is wired and installed correctly, the burner will shut off when the water level drops to approximately
3
8" below the normal water line.
Float chamber should be flushed at least once every month or more often to remove any accumulated sediment by opening drain valve where installed or removing drain plug.
Instructions for Installing
No. N93S, N193S, N93D, N193D
Attach cut-off to the boiler by screwing into the 21⁄2" tapping provided, make up tight with the "TOP" marking uppermost and the adjacent flat edge of the square flange is exactly level. Before installing No. N93S, N93D, be sure that there is a minimum distance of 2
1
4" between the inside of the boiler shell and any wall or other protrusion inside the boil­er. (See Figure 1.) Maximum Steam Pressure 15 lbs.
Fig.1
Insertion
Length
1
2
4"
N93 Only
Marked Top
Level
N93 N193
No. N101S, N101D
Attach cut-off to boiler as in Fig. 2 using a 21⁄2" close or space nipple to suit installation requirements. Make up tight with float chamber lev­elled in position shown. Attach drain valve. Maximum Steam Pressure 15 lbs.
No. N50S, N50D, N501S, N501D
Watts Series N50 and N501 are designed with a heavier float and bel­lows construction for protection of hot water space heating boilers against emergency low water conditions. Float chamber has 1" female top and bottom connections, for equalizing pipe connection. (See Figure 3). Maximum Boiler Pressure 50 lbs. @ 250°F.
For installation of N501, see Figure 2.
Inside Boiler Shell
Boiler
Fig. 2
Supply
Fig. 3
Drain Valve
Cut-off Line
1
2
2" Nipple
Equalizing
No. N50
Drain Plug
N101 N501
Pipe
Equalizing
Pipe
Wiring Diagrams For Low Water Cut-offs No. N89D, N101D, N93D, N193D, N50D, N501D with "Dual" (Two) Switch Assembly
For independent line voltage burner service and for low (or high) voltage alarm, feed valve or pump starter service. Alarm, feed valve or pump starter switch actuates just bbeeffoorree
the burner switch cuts the firing.
HI or LO
LINE
()
Voltage
HI or LO
Voltage
Service Switch
Closed Circuit
Burner Switch Closed Circuit
When Used For
When Used For PILOT DUTY
BURNER SWITCH and
ACCESSORY CIRCUITS
HI or LO
LINE
Burner
Load
Alarm Feed
Valve or Pump
Starter
CommonCommon
Norm
Norm
TOP
Open
Norm
Open
Norm
Closed
Closed
For loads in excess of ratings or when a 3-phase burner motor is used, use either switch as pilot to operate a relay or magnetic starter as shown under "Pilot Duty" above for burner switch.
Incoming leads must be suitable for temperature rise of 90°C (194°F).
LINE
()
Voltage
HI or LO
Voltage
Service Switch
Closed Circuit
Burner Switch Closed Circuit
Alarm Feed
Valve or
Pump Starter
CommonCommon
Norm
Norm
TOP
Open
Norm
Open
Norm
Closed
Closed
Relay
LINE
Line
(Burner)
1
AC
2 H.P. 1 Phase 110-120 volts
1 H.P. 1 Phase 220-240 volts
Pilot Duty AC 15 Amps. 120, 240 volts DC1⁄2 Amps. 120 volts
Motor Duty
1
2 H.P. 1 Phase 100-120 volts
AC
1 H.P. 1 Phase 220-240 volts
472 V.A. 120 volts
AC
768 V.A. 240 volts
Motor Duty
Pilot Duty
Alarm Circuit AC 15 Amps. 120, 240 volts DC1⁄2 Amps. 120 volts
WARNING: DO NOT CONNECT TO AN ELECTRICAL LOAD IN EXCESS OF THE RATED
Switch cuts off burner or stoker when water line drops approximately 3⁄8" below center line. Switch alarm circuit when used is closed just before burner cuts off.
CAUTION:"This switch mechanism is factory set for optimum performance, alteration may cause the
valve to malfunction and will invalidate the warranty.
CAPACITY OF THE SWITCH.
ALWAYS CHECK THE CUT-OFF LEVEL BEFORE LEAVING THE JOB.
Wiring Diagrams
No. N89S, N101S, N93S, N193S, N50S, N501S with Single Switch Assembly For Burner Service with Single Pole, Single Throw Switch
When Used For BURNER SWITCH When Used For PILOT DUTY
LINE
TOP
Line
(Burner)
Burner Switch Closed Circuit
Common
For loads in excess of ratings or when a 3-phase burner motor is used, use switch as pilot to operate a relay or magnetic starter as shown under "Pilot Duty" above for burner switch. Incoming leads must be suitable for a temperature rise of 90°C (194°F).
1
AC
2 H.P. 1 Phase 110-120 volts
1 H.P. 1 Phase 220-240 volts
Float and Switch Assemblies Interchangeable in Low Water Cut-offs
Open
Norm
Motor Duty
Norm
Closed
Burner Switch Closed Circuit
AC
AC
LINE
TOP
Open
Norm
Common
1
2 H.P. 1 Phase 110-120 volts
1 H.P. 1 Phase 220-240 volts
472 V.A. 120 volts 768 V.A. 240 volts
Norm
Closed
Motor Duty
Pilot Duty
Line
(Burner)
Watts float and switch assemblies are furnished to provide a complete new low water cut-off, less the float
chamber, and are recommended for field servicing of such units. They can be quickly installed with­out changing existing piping and eliminate the possibility of disturbing factory adjustments. The complete one piece unit not only facilitates installation but also assures the user of receiving latest, up to date con­struction.
SAN89D - Complete assembly facilitates maintenance and inventory, by being interchangeable in all previous Series 89, 101, 93 and 193. Maximum Steam Pressure 15 lbs.
SAN89S - Same as above, but furnished with single switch assembly.
SAN50D - Complete assembly facilitates servicing by being interchangeable in all
previous Series 50 and 501. Maximum Boiler Pressure 50 lbs.
SAN50S - Same as above, but furnished with single switch assembly. Standardly furnished with "Dual" switch assembly unless single switch assembly type num­ber is specified.
When required for manual reset models, specify SAN50SM.
Limited Warranty: Watts Regulator Co. (the “Company”) warrants each product to be free from defects in material and workmanship under normal usage for a period of one year from the date of original shipment. In the event of such defects within the warranty period, the Company will, at its option, replace or recondition the product without charge.
THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY WARRANTY GIVEN BY THE COMPANY WITH RESPECT TO THE PRODUCT. THE COMPANY MAKES NO OTHER WARRANTIES, EXPRESS OR IMPLIED. THE COMPANY HEREBY SPECIFICALLY DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
The remedy described in the first paragraph of this warranty shall constitute the sole and exclusive remedy for breach of warranty, and the Company shall not be responsible for any incidental, special or consequential damages, including without limitation, lost profits or the cost of repairing or replacing other property which is damaged if this product does not work properly, other costs resulting from labor charges, delays, vandalism, negligence, fouling caused by foreign material, damage from adverse water conditions, chemical, or any other circumstances over which the Company has no control. This warranty shall be invalidated by any abuse, misuse, misapplication, improper installation or improper maintenance or alteration of the product. Some States do not allow limitations on how long an implied warranty lasts, and some States do not allow the exclusion or limitation of incidental or consequential damages. Therefore the above limitations may not apply to you. This Limited Warranty gives you specific legal rights, and you may have other rights that vary from State to State. You should consult applicable state laws to determine your rights.
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED IN DURATION TO ONE YEAR FROM THE DATE OF ORIGINAL SHIPMENT.
SO FAR AS IS CONSISTENT WITH APPLICABLE STATE LAW, ANY IMPLIED WARRANTIES THAT MAY NOT BE DISCLAIMED, INCLUDING THE IMPLIED WARRANTIES OF
SAN89D or SAN89S
SAN50D or SAN50S
Water Safety & Flow Control Products
Canada: 5435 North Service Rd., Burlington, ONT. L7L 5H7; www.wattscanada.ca
USA: 815 Chestnut St., No. Andover, MA 01845-6098; www.watts.com
IS-N89 0829 EDP# 1910095 © Watts, 2008
Loading...