Watts S500, S1500 User Manual

Stainless Steel Series Basic Valves
ES-ACV-S500-S1500
Job Name
Job Location
Engineer
Approval
–––––––––––––––––––––––––––––––––––––––––––
–––––––––––––––––––––––––––––––––––––––––
–––––––––––––––––––––––––––––––––––––––––––––
–––––––––––––––––––––––––––––––––––––––––––––
S500 / S1500
Full Port Stainless Steel Dual Chamber Basic Valve
The Watts ACV Models S500 and S1500 are full port, dual chamber basic valves that incorporate a one-piece disc and dia­phragm assembly. This assembly is the only moving part within the valve, allowing it to open or close as commanded by the pilot control system.
When pressure is applied to the upper diaphragm chamber and released from the lower diaphragm chamber, the valve travels to a closed position. When pressure is applied to the lower diaphragm chamber and released from the upper diaphragm chamber the valve travels to a full open position. When pressure is balanced between the upper and lower diaphragm chambers, the valve will hold an intermediate position until commanded to modulate open or closed by the pilot control system.
The Stainless Steel design offers superior corrosion resistance, as well as a lightweight alternative to conventional heavy iron valves. Stainless Steel construction reduces corrosion, reducing diaphragm wear and the frequency and labor costs associated with traditional maintenance repairs.
Model S500: Globe Pattern Dual Chamber Basic Valve Model S1500: Angle Pattern Dual Chamber Basic Valve
Contractor
Approval
––––––––––––––––––––––––––––––––––––––––––––
Contractor’s P.O. No.
Representative
––––––––––––––––––––––––––––––––––––––––
S500 (Globe) S1500 (Angle)
C
A
B
––––––––––––––––––––––––––––––––––
I
H
J
H
F G
D
E
Dimensions
Valve Size Globe 150# Globe 300# Cover To Center Angle 150# Angle 300# Angle 150# Angle 300# Port Size Port Size Port Size Shipping
A B C D E F G H I J
in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm lbs. kgs.
4 100 15 381 15
6 150 20 508 21 533 18
8 200 25
10 250 29
12 300 34 864 35
16 400 41
3
8 645 263⁄8 670 2113⁄16 554 123⁄4 324 131⁄4 337 8 203 81⁄2 216 1 25 1 251⁄2 13 240 109
3
4 756 311⁄8 791 233⁄8 594 147⁄8 378 159⁄16 395 85⁄8 219 95⁄16 237 1 25 11⁄4 321⁄2 13 397 180
3
8 1051 431⁄2 1105 35 889 2013⁄16 529 215⁄8 549 1511⁄16 398 161⁄2 419 1 25 11⁄2 38 1 25 925 420
Standard Materials
Body, Cover & 304L Stainless Steel (standard)
5
8 397 141⁄4 362 71⁄2 191 77⁄8 200 5 127 55⁄16 1351⁄2 133⁄4 191⁄2 13 87 39
1
2 902 295⁄16 744 17 432 173⁄4 451 133⁄4 349 141⁄2 368 1 25 11⁄4 32 1 25 480 217
7
16 468 10 254 101⁄2 267 6 152 61⁄2 1651⁄2 133⁄4 191⁄2 13 178 81
Operating Pressure
150 Flanged = 250psi (17.2 bar)
Flanges: 316L Stainless Steel (optional)
Trim: 316 Stainless Steel
Elastomers: Buna-N (standard)
EPDM
®
Viton
Stem, Nut & Spring: Stainless Steel
Viton® is a registered trademark of DuPont Dow Elastomers.
Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with­out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.
Operating Temperature
Buna-N: 160°F (71°C) Maximum
EPDM: 300°F (140°F) Maximum
®
Viton
: 250°F (121°C) Maximum
Weights*
*Estimated in lbs.
S500 / S1500 — Full Port Stainless Steel Dual Chamber Basic Valve
Flow Data - ACV S500 (Globe) / S1500 (Angle)
Valve Size - Inches 4 6 8 10 12 16
Maximum Continuous
Flow Rate Gpm (Water)
Maximum Intermittent
Flow Rate Gpm (Water)
CV Factor GPM (Globe) 210 460 790 1260 1725 2940
CV Factor GPM (Angle) 250 561 990 1590 2500 4200
Maximum continuous flow based on velocity of 20 ft. per second. Maximum intermittent flow based on velocity of 25 ft. per second. The Cv Factor of a value is the flow rate in US GPM at 60°F that will cause a 1psi drop in pressure. The factors stated are based upon a fully open valve. Cv factor can be used in the following equations to determine Flow (Q) and Pressure Drop (∆P):
Q (Flow) = Cv√∆P ∆P (Pressure Drop) = (Q/Cv)
800 1850 3100 5000 7000 11100
1000 2300 4000 6250 8900 14100
2
Estimated
Headloss
100
80
60
40
30
20
10
8
6
4
Pressure Drop (psi)
3
2
Angle
Globe
2 4 6 8 10 20 40 60 80 100 200 500 1000 2000 5000 10000 20000
4
4
6
8
6
8
10
10
12
12
16
16
Flow Rate - Gallons per minute (Water)
Valve Cover Chamber Capacity
Valve Size - Inches 4 6 8 10 12 16
fluid oz. 22 70
U.S. Gal 1-1/4 2-1/2 4 9-1/2
Valve Travel
Valve Size - Inches 4 6 8 10 12 16
Travel - Inches 1 1-1/2 2 2-1/2 3 4
A Watts Water Technologies Company
ES-ACV-S500-S1500 1219 © 2012 Watts
USA: Tel. (713) 943-0688 • (713) 944-9445 • www.watts.com
Loading...