PUMP CONTROL VALVE with MECHANICAL CHECK FEATURE
01/05
Stainless Series
S1513-5 or S61513-5 (Angle)
Specifications
The main valve shall be a hydraulically operated, single diaphragm actuated, globe or angle pattern valve. Y-pattern valves shall not be permitted. The valve shall contain a disc and diaphragm assembly that forms two separate sealed chambers: 1) between the diaphragm and the valve cover, and 2) between the diaphragm and the power chamber. The diaphragm shall be constructed of nylon reinforced Buna-N, and shall not seal directly against the valve seat and shall be fully supported by the power chamber. Rolling diaphragm construction will not be allowed and there shall be no pistons operating the main valve or any pilot controls.
The main valve body shall be fabricated 304L with Class D zinc plated steel flanges, utilizing stainless steel seal welds allowing the entire flow path to be stainless steel. External steel components shall be fully primed and painted with a stainless steel paint to prevent surface corrosion. The valve cover and all internal components shall be fabricated 304L Stainless Steel, and the main valve trim and throttling components (cover bearing, power chamber bearing, valve seat and disc guide) shall be Stainless Steel.
S513-5 or S6513-5 (Globe)
The disc and diaphragm assembly shall contain a Buna-N synthetic rubber disc with a rectangular cross­section that is securely retained on 3-1/2 sides by a disc retainer and disc guide. It shall utilize a two-piece telescoping stem design that allows the lower portion of the disc and diaphragm assembly to act independently from the upper portion, regardless of valve position. The lower portion of the disc and diaphragm assembly shall act as a mechanical check feature that closes, preventing reverse flow, the moment flow ceases.
The exposed portion of the seat disc shall contact the valve seat and seal drip-tight. The disc and diaphragm assembly must be guided by two separate bearings, one installed in the valve cover and one concentrically located within the power chamber, to avoid deflection and assure positive disc-to-seat contact. Center guided valves will not be permitted. All necessary repairs shall be made from the top of the valve while the body remains in line.
The pilot control system shall be designed with a “shuttle-supply” to utilize the highest source of available pressure (upstream or downstream) to operate the valve. It shall contain a 4-Way Solenoid Pilot with a lever type Manual Operator, Single Limit Switch, separate Adjustable Opening and Closing Speed Controls, (2) Check Valves, (2) Y-Strainers and Isolation Ball Valves on all body connections. The pilot control system shall utilize copper tubing and brass fittings.
The valve shall be Watts ACV Model S513-5 / S6513-5 (Globe) or S1513-5 / S61513-5 (Angle) Pump Control Valve.
8550 Hansen Road Houston, Texas 77075 (Ph) 713.943.0688 (Fx) 713.944.9445 www.wattsacv.com