Watts S1115-7 User Manual

R
PRESSURE REDUCING VALVE with SURGE CONTROL FEATURE
01/05
Stainless Series
S1115-7 or S61115-7 (Angle)
Operation
If downstream pressure suddenly becomes greater than the desired regulated setpoint, the normally closed surge control pilot opens and rapidly admits higher inlet pressure into the valve cover, increasing rate of valve closure. Normal pressure reducing operation resumes when downstream pressure decreases below the desired regulated setpoint.
S115-7 or S6115-7 (Globe)
Installation Guidelines
Prior to installation, flush line to remove debris.
Install valve horizontally “in line” (cover facing UP), so flow arrow matches flow through the line. Avoid
installing valves 6” and larger vertically. Consult factory prior to ordering if installation is other than described.
Install inlet and outlet isolation valves. NOTE: When using butterfly valves, insure disc does not contact control valve. Damage or improper valve seating may occur.
Provide adequate clearance for valve servicing and maintenance.
Install pressure gauges to monitor valve inlet and outlet pressure.
If installation is subjected to very low flow or potentially static conditions, it is recommended a pressure
relief valve (1/2” minimum) be installed downstream of the Pressure Reducing Valve for additional system protection.
Other Watts ACV Pressure Reducing Control Valves
S115 / S6115 Pressure Reducing Valve S115-2 / S6115-2 Pressure Reducing and Sustaining Valve S115-3 / S6115-3 Pressure Reducing Valve with Hydraulic Check Feature S115-4 / S6115-4 Pressure Reducing Valve with Solenoid (On-Off) Feature S115-11 / S6115-11 Pressure Reducing and Sustaining Valve with Hydraulic Check Feature S115-43 / S1115-43 Pressure Reducing and Sustaining Valve with Surge Control Feature S115-58 / S6115-58 Pressure Reducing Valve with Return Flow Feature S115-74 / S6115-74 Pressure Reducing Valve with Low Flow By-Pass
8550 Hansen Road Houston, Texas 77075 (Ph) 713.943.0688 (Fx) 713.944.9445 www.wattsacv.com
Loading...