Watts S1114-2 User Manual

R
RATE-OF-FLOW VALVE with PRESSURE REDUCING FEATURE
01/05
Stainless Series
S1114-2 or S61114-2 (Angle)
Operation
The flow control action of the valve is controlled by a normally open, differential control pilot designed to: 1) Open (allowing fluid out of the main valve cover chamber) when the differential pressure across the orifice plate is below it’s adjustable set point, and, 2) Close (allowing fluid to fill the main valve cover chamber) when the differential pressure across the orifice plate is above it’s adjustable set point. A decrease in differential pressure causes the valve to modulate towards an open position, increasing flow rate. An increase in differential pressure causes the valve to modulate towards a closed position, decreasing flow rate.
The pressure reducing action of the valve is controlled by a normally open, pressure reducing pilot designed to: 1) Open (allowing fluid out of the main valve cover chamber) when downstream pressure is below the adjustable setpoint, and 2) Close (allowing fluid to fill the main valve cover chamber) when downstream pressure is above the adjustable setpoint. A decrease in downstream pressure causes the valve to modulate toward an open position, raising downstream pressure. An increase in downstream pressure causes the valve to modulate toward a closed position, lowering downstream pressure.
S114-2 or S6114-2 (Globe)
The Orifice Plate Assembly should be installed three to five pipe diameters downstream of the Rate­of-Flow Valve, and field connected with 3/8” minimum copper tubing in accordance with factory piping schematic. Please specify desired flow rate prior to ordering.
8550 Hansen Road Houston, Texas 77075 (Ph) 713.943.0688 (Fx) 713.944.9445 www.wattsacv.com
R
RATE-OF-FLOW VALVE with PRESSURE REDUCING FEATURE
01/05
Stainless Series
S1114-2 or S61114-2 (Angle)
Installation Guidelines
S114-2 or S6114-2 (Globe)
Prior to installation, flush line to remove debris.
Install valve horizontally “in line” (cover facing UP), so flow arrow matches flow through the line. Avoid
installing valves 6” or large vertically. Consult factory prior to ordering if installation is other than described.
Install inlet and outlet isolation valves. NOTE: When using butterfly valves, insure disc does not contact control valve. Damage or improper valve seating may occur.
Provide adequate clearance for valve servicing and maintenance.
Install pressure gauges to monitor valve inlet and outlet pressure.
Install Orifice Plate Assembly (provided) 3 to 5 pipe diameters downstream of the Rate-of-Flow Valve
with the sensing connections offset from top of pipeline to avoid air accumulation. The Orifice Plate Assembly should not be installed next to a butterfly valve.
Connect Orifice Plate Assembly to Rate-of-Flow Pilot using 3/8” diameter minimum copper tubing (field installed) in accordance with factory piping schematic.
Other Watts ACV Rate-of-Flow Control Valves
S114 / S6114 Rate-of-Flow Control Valve S114-1 / S6114-1 Rate-of-Flow Control Valve with Solenoid (On-Off) Feature S114-3 / S6114-3 Rate-of-Flow Control Valve with Hydraulic Check Feature S114-8 / S6114-8 Rate-of-Flow Control Valve with Pressure Sustaining Feature
8550 Hansen Road Houston, Texas 77075 (Ph) 713.943.0688 (Fx) 713.944.9445 www.wattsacv.com