Specifications
The Solenoid Control Valve shall be a pilot operated diaphragm valve designed to open fully or close driptight as commanded by a 3-Way Solenoid Pilot. The valve shall have provisions for manual operation in
the event of power outage. Solenoid voltage shall be _________ and enclosure shall be NEMA 4 General
Purpose. The main valve shall (open / close) when the solenoid is energized.
The main valve shall be a hydraulically operated, single diaphragm actuated, globe or angle pattern valve.
Y-pattern valves shall not be permitted. The valve shall contain a disc and diaphragm assembly that forms
a sealed chamber below the valve cover, separating operating pressure from line pressure. The diaphragm
shall be constructed of nylon reinforced Buna-N, and shall not seal directly against the valve seat and shall
be fully supported by the valve body and cover. Rolling diaphragm construction will not be allowed and there
shall be no pistons operating the main valve or any pilot controls.
The main valve body shall be fabricated 304L with Class D zinc plated steel flanges, utilizing stainless
steel seal welds allowing the entire flow path to be stainless steel. External steel components shall be fully
primed and painted with a stainless steel paint to prevent surface corrosion. The valve cover and all internal
components shall be fabricated 304L Stainless Steel, and the main valve trim and throttling components
(cover bearing, valve seat and disc guide) shall be Stainless Steel.
S113-6 or S6113-6 (Globe)
The disc and diaphragm assembly shall contain a Buna-N synthetic rubber disc with a rectangular crosssection that is securely retained on 3-1/2 sides by a disc retainer and disc guide. Diaphragm assemblies
utilizing bolts or cap screws for component retention will not be permitted.
The exposed portion of the seat disc shall contact the valve seat and seal drip-tight. The disc and diaphragm
assembly must be guided by two separate bearings, one installed in the valve cover and one concentrically
located within the valve seat, to avoid deflection and assure positive disc-to-seat contact. Center guided
valves will not be permitted. All necessary repairs shall be made from the top of the valve while the body
remains in line.
The pilot control system shall contain a 3-Way Solenoid Pilot with screw type Manual Operator, 3-Way
Accelerator Pilot, separate Adjustable Opening and Closing Speed Controls, an external Y-Strainer and
Isolation Ball Valves on all body connections. The pilot control system shall utilize copper tubing and brass
fittings.
The valve shall be Watts ACV Model S113-6 / S6113-6 (Globe) or S1113-6 / S61113-6 (Angle) Solenoid OnOff Control Valve.