Watts QTSTMMAX-2S-1M, QTSTMMAX-3S-1M, QTSTMMAX-3S-10M, QTSTMMAX-2L-10M, QTSTMMAX-3L-10M Installation, Operation And Maintenance Manual

...
Page 1
IOM-HS-QTSteamMax
Installation, Operation and Maintenance Manual
QTTM Steam MaxTM Models: QTSTMMAX-2S-10M, QTSTMMAX-3S-10M,
QTSTMMAX-2S-1M, QTSTMMAX-3S-1M, QTSTMMAX-2L-10M, QTSTMMAX-3L-10M, QTSTMMAX-4L-10M, QTSTMMAX-2L-1M, QTSTMMAX-3L-1M, QTSTMMAX-4L-1M, QTSTMMAX-2L-1M-P, QTSTMMAX-3L-1M-P, QTSTMMAX-4L-1M-P
Tested and certified by WQA against NSF/ANSI Standard 42 for the reduction of claims specified on the performance data sheet & NSF/ANSI 372 for "lead free" compliance.
!
WARNING
Read this Manual BEFORE using this equipment. Failure to read and follow all safety and use information
can result in death, serious personal injury, property damage, or damage to the equipment.
Keep this Manual for future reference.
!
WARNING
You are required to consult the local building and plumbing codes prior to installation. If the information in this manual is not consistent with local building or plumbing codes, the local codes should be followed. Inquire with governing authorities for additional local requirements.
QTSTMMAX-4L-1M
Table of Contents
System Specications .................................2
Replacement Filters ...................................2
Notice to Installers ....................................3
Installation Precautions ................................3
Operation ..........................................3
Installation ..........................................3
Maintenance ........................................4
Filter Cartridge Replacement Procedure ...................4
Replacement Parts List ................................4
System Drawings ....................................4
Limited Warranty .....................................8
!
WARNING
Do not use with water that is microbiologically unsafe or of unknown quality without adequate disinfection before or after the system.
Page 2
System Specications
Maximum Pressure: Steam Max Models: QTSTMMAX-3S-1M, QTSTMMAX-3L-1M, QTSTMMAX-4L-1M - 90psi (6.2 bar)
All Other Systems - 100psi (6.8 bar) Minimum Pressure:
All Systems - 20psi (1.4 bar) Maximum Temperature: 100°F (38°C)
Minimum Temperature: 40°F (4.4°C) Feed Water Quality: pH 6.5 to 8.5 Hardness (maximum for systems containing OneFlow*) 75 grains
(1282 ppm CaCO3) Chlorine < 2ppm Iron (maximum) 0.3 mg/l Manganese (maximum) 0.05 mg/l Copper (for systems containing OneFlow): None allowed Oil & H2S- None allowed Polyphosphate (for systems containing OneFlow)- None allowed Silica (maximum for systems containing OneFlow) 10 ppm For all other feed water quality requirements abide by the current
USEPA Safe Drinking Water Act standards. Inlet/Outlet Connections: * QT Steam Max models that contain OneFlow
QTSTMMAX-2S-1M, QTSTMMAX-3S-1M, QTSTMMAX-2L-1M, QTSTMMAX-3L-1M, QTSTMMAX-4L-1M
Maximum Flow Rate:
System Model Flow Rate Chlorine Capacity
QTSTMMAX-2S-10M 1.5 GPM
QTSTMMAX-3S-10M 3 GPM
QTSTMMAX-2S-1M 1.5 GPM
QTSTMMAX-3S-1M 3 GPM
QTSTMMAX-2L-10M 1.5 GPM
QTSTMMAX-3L-10M 3 GPM
QTSTMMAX-4L-10M 4.5 GPM
QTSTMMAX-2L-1M 1.5 GPM
QTSTMMAX-3L-1M 3 GPM
QTSTMMAX-4L-1M 4.5 GPM
QTSTMMAX-2L-1M-P 1.5 GPM
QTSTMMAX-3L-1M-P 3 GPM
QTSTMMAX-4L-1M-P 4.5 GPM
The QT Steam Max line is available in different congurations depending upon ltration and ow requirements.
1
2" (15mm) NPT
System Flow Rate & Capacity
(5.7 LPM)
(11.4 LPM)
(5.7 LPM)
(11.4 LPM)
(5.7 LPM)
(11.4 LPM)
(17.1 LPM)
(5.7 LPM)
(11.4 LPM)
(17.1 LPM)
(5.7 LPM)
(11.4 LPM)
(17.1 LPM)
®
Media:
15,000 Gallons
30,000 Gallons
15,000 Gallons
30,000 Gallons
22,000 Gallons
44,000 Gallons
66,000 Gallons
22,000 Gallons
44,000 Gallons
66,000 Gallons
22,000 Gallons
44,000 Gallons
66,000 Gallons
Replacement Filters
System Replacement Filters
System Model Filter Ordering Code Frequency Description
QTSTMMAX-2S-10M HSR-L-SED-5M 6 Months 20" 5 Micron Sediment Pre Filter
QTSM15 6 Months
QTSTMMAX-3S-10M HSR-L-SED-5M 6 Months 20" 5 Micron Sediment Pre Filter
QTSM15 6 Months
QTSTMMAX-2S-1M HSR-L-SED-5M 6 Months 20" 5 Micron Sediment Pre Filter
QTSMX15 6 Months 15" QT 1 Micron Carbon Block
DOR-OF120RM 12 Months 20" OneFlow Anti-Scale Cartridge
QTSTMMAX-3S-1M HSR-L-SED-5M 6 Months 20" 5 Micron Sediment Pre Filter
QTSMX15 6 Months 15" QT 1 Micron Carbon Block (2)
DOR-OF140RM 12 Months 20" OneFlow Anti-Scale Cartridge
QTSTMMAX-2L-10M HSR-L-SED-5M 6 Months 20" 5 Micron Sediment Pre Filter
QTSM20 6 Months
QTSTMMAX-3L-10M HSR-L-SED-5M 6 Months 20" 5 Micron Sediment Pre Filter
QTSM20 6 Months
QTSTMMAX-4L-10M HSR-L-SED-5M 6 Months 20" 5 Micron Sediment Pre Filter
QTSM20 6 Months
QTSTMMAX-2L-1M HSR-L-SED-5M 6 Months 20" 5 Micron Sediment Pre Filter
QTSMX20 6 Months 20" QT 0.5 Micron Carbon Block
DOR-OF120RM 12 Months 20" OneFlow Anti-Scale Cartridge
QTSTMMAX-3L-1M HSR-L-SED-5M 6 Months 20" 5 Micron Sediment Pre Filter
QTSMX20 6 Months 20" QT 0.5 Micron Carbon Block (2)
DOR-OF140RM 12 Months 20" OneFlow Anti-Scale Cartridge
QTSTMMAX-4L-1M HSR-L-SED-5M 6 Months 20" 5 Micron Sediment Pre Filter
QTSMX20 6 Months 20" QT 0.5 Micron Carbon Block (3)
OFTWHRM 12 Months 20" OneFlow Anti-Scale Cartridge
QTSTMMAX-2L-1M-P HSR-L-SED-5M 6 Months 20" 5 Micron Sediment Pre Filter
QTSMX20 6 Months 20" QT 0.5 Micron Carbon Block
STMAXR-S-ACSC 6 Months 10" Phosphate Scale Control
QTSTMMAX-3L-1M-P HSR-L-SED-5M 6 Months
QTSMX20 6 Months 20" QT 0.5 Micron Carbon Block (2)
STMAXR-S-ACSC 6 Months 10" Phosphate Scale Control
QTSTMMAX-4L-1M-P HSR-L-SED-5M 6 Months
QTSMX20 6 Months 20" QT 0.5 Micron Carbon Block (3)
STMAXR-S-ACSC 6 Months 10" Phosphate Scale Control
NOTICE
Filter cartridges should be changed at end of filter life, due to lack of filtering performance, or whenever a 15 psi pressure drop or greater is experienced during normal operation, whichever comes first.
For all replacement filters and components contact your authorized Hydro-Safe Foodservice representative.
NOTICE
Cartridge capacities are estimates and may be less depending on incoming water quality.
15" QT 1 Micron Carbon Block with Phosphate Scale Control
15" QT 1 Micron Carbon Block with Phosphate Scale Control (2)
20" QT 1 Micron Carbon Block with Phosphate Scale Control
20" QT 1 Micron Carbon Block with Phosphate Scale Control (2)
20" QT 1 Micron Carbon Block with Phosphate Scale Control (3)
20" 5 Micron Sediment Pre Filter
20" 5 Micron Sediment Pre Filter
2
Page 3
Notice to Installers
• Connect the system to cold water supply only. Water Temperature
cannot exceed 100°F (38°C).
• System must be installed in a vertical, upright and level position.
• Do not use with water that is microbiologically unsafe or of
unknown water quality.
• Notice to user/owner/operator: Please retain this manual for future
reference for parts, maintenance, or troubleshooting.
• It is recommended that all personnel responsible for operation and
maintenance of this product read the precautions, maintenance, and operation sections of this manual.
Installation Precautions
• Do not install system on line pressure above the rated pressure as
noted in System Specications above.
• Do not install the system on a hot water line. Failure to limit the
water temperature to 100°F (38°C) can result in housing failure and property damage.
• Do not connect the system backwards with the feed water line
connected to the outlet.
• Do not use liquid pipe thread compounds for threaded connections. Use Teon
• Do not solder plumbing connections that are attached to the housings or inlet/outlet ttings. System damage may occur due to high temperature.
• Do not allow the system to freeze. Turn off water supply and drain
the system if temperature falls below 32°F (0°C).
• Do not install system in direct sunlight or where the system will be
exposed to harsh chemicals or may be subjected to being hit by moving equipment, carts, mops, or any other item that may cause damage.
• Allow 3" (76mm) minimum clearance under the housings for lter
replacement.
• If water hammer is evident, install water hammer arrestors before
the system.
• Do not over tighten tting connections.
• Always back up valves and ttings with a wrench when installing
ttings to avoid over tightening or loosening existing ttings.
• Do not install the unit behind equipment where it may be difcult to
access the system for future lter replacements.
Position the system in a suitable location. The direction of ow through the system is left to right. Keep this in mind when determin­ing installation locations. Do not mount the system near any source of heat. Also do not mount this system over anything that may be adversely affected by water.
®
tape only.
OneFlow Application Practices
Note: Systems using OneFlow technology prevent hard water scale formation inside the plumbing system at inuent hardness levels of 75 grains per gallon of calcium carbonate and less. Due to variances in water chemistry certain aesthetic conditions external of the plumbing system may not be attained. OneFlow is designed for the treatment of potable water that meets the requirements of the current USEPA Safe Drinking Water Act. The addition of soaps, chemicals, or cleaners, before or after OneFlow treatment, may reverse its anti-scale treatment effects and/or create water with a heavy residue or spotting potential. Any ad­verse conditions caused by the addition of soaps, chemicals, or cleaners are the sole responsibility of the end user. New copper lines need to be passivized before placing unit into service. Copper usually originates from new copper plumbing upstream of the OneFlow system. All new copper plumbing before the system should be allowed to passivate by operat­ing under normal conditions for a period of 4 weeks prior to starting the system up. This will allow the copper surfaces to be fully ushed and develop a natural protective surface. To further minimize any problem with excess copper, avoid applying excess ux on the inner surfaces of the pipe and use a low-corrosivity water soluble ux listed under the ASTM B813 standard. OneFlow is not designed for use on closed loop systems.
Operation
With sufcient pressure, operation of this system is completely auto­matic. Dependable operation involves only monitoring system pres­sure differential, periodic lter changes, and service documentation.
Installation
NOTICE
There is some light eld assembly required for this system. Be­fore beginning the installation of this system, please make sure all components are present. Compare the contents of this box to the system drawings located at the end of this manual. As illustrated by the drawings, some models have separate remote lter housings. These drawings will be referenced in the installa­tion instruction steps.
1. Turn off all equipment to be fed by the system, locate the water supply shutoff valve and turn it off.
2. Apply Teon tape to the threads of the inlet and outlet valve
assemblies and pressure gauges (if supplied for your model). DO NOT USE PASTE TYPE THREAD SEALANT. Thread the inlet and outlet valve assemblies into the inlet and outlet ports of the system as shown on the system drawings in this manual. Install the pressure gauges, if applicable, into the gauge ports as indicated by the system drawings in this manual.
DO NOT OVER TIGHTEN THESE FITTINGS INTO
THE FILTER HEADS. When installing ttings onto this system,
back any existing receiving ttings with a wrench to prevent tting movement. Use a wrench to tighten gauges into their connection ports. Do not twist on gauge case.
3. Install the lters into the lter manifold. Make sure all plastic
4. Anchor the system on a wall stud or suitable mounting material
spanning wall studs. System must be vertical, upright and level. If applicable, mount the remote lter housing at this time. The mounting hardware used must be selected and installed so that the system is rmly pressed against the mounting surface. The system mounting hardware must keep the system from moving during routine service and operation.
5. Run a suitable line from the tap water source to the inlet ball
DO NOT OVERTIGHTEN CONNECTION FITTING INTO BALL VALVE.
6. Select the appropriate size tubing for the equipment being fed,
NOTICE
wrapping and protective plastic caps have been removed from the lters prior to their installation. Insert the prelter into its blue canister. Make sure the blue canister's oring is properly inserted into its oring groove. Thread the housing onto the head with standard clockwise rotation (when viewed from below). Hand tighten the blue housing (See the system drawings in this manual for proper lter placement). Then install the QT style lter cartridges. To install these lters, push them into the heads and give them a quarter twist (clockwise when viewed from below). When the lter is completely inserted, the cartridge label will be front centered.
valve on the left side of the system. Brace the inlet ball valve on the system with a wrench when connecting the feed water line.
NOTICE
and connect it to the outlet ball valve of the system.
NOTICE
DO NOT OVERTIGHTEN CONNECTION FITTING INTO BALL VALVE.
7. Install the ¼" (8mm) tubing into the Quick-Connect tting on the outlet of the system and hold it over a drain. Open the drain valve.
8. Once all inlet and outlet piping has been completed, check and make sure all lter housing(s) are tight, slowly open the inlet valve and allow all air to purge from the system from the Slowly close the operating pressure, and check for leaks.
3
1
4" (8mm)
1
1
4" (8mm) drain valve, allow the system to reach
4" tubing.
Page 4
9. If no leaks are present, open the 1⁄4" (8mm) drain line again and allow it to run to drain for 5 minutes to ush the system. Then close the valve.
10. Open the outlet water valve and check for leaks.
11. Record the start up date and pressure gauge values in system maintenance log.
Teflon® is a registered trademark of E.I. DuPont de Nemours & Company.
NOTICE
Overtightening components can damage the system causing water damage and/or system failure.
Maintenance
Routine maintenance of this system involves periodic lter changes.
Filter cartridges should be changed at end of lter life, due to lack of ltering performance, or whenever a 15 psi pressure drop or greater is experienced during normal operation, whichever comes rst.
Filter Cartridge Replacement Procedure
!
WARNING
Determine whether all equipment connected to the system must be turned off prior to shutting off water supply from lters.
1. If required, turn off downstream equipment.
2. Turn OFF water to the system by closing the inlet and outlet ball valves.
3. Open the ¼" drain valve on the outlet of the system to relieve pressure in the housings.
4. Remove all lters. The blue lter housings unscrew to the left when viewed from underneath. They have a standard right hand thread. The QT style lters are removed by rotating them 1/4 turn to the left and then gently pulling down.
5. Clean inside of blue housing sump(s) with warm water. If desired, disinfect housing using a teaspoon of household bleach. Add to lter bowl and ll with water. Let stand 5 minutes and then discard and rinse.
6. Insert new QT style lters into the manifold assembly. Push up
and twist each QT cartridge 1/4 turn to the right to properly install it into the manifold assembly. When making the 1/4 turn, the cartridge label should come to a stop facing you.
7. Insert a new prelter and, if applicable, the remote lter cartridge into the blue lter housing(s). Check O-ring for damage and replace if damaged or distorted. Make certain the O-ring is properly positioned and reinstall the lter housing. Tighten housings hand tight. OneFlow is always the last lter in the system.
Do not overtighten lter housing, overtightening may damage O-ring(s), cause water leaks, or affect system performance.
8. Slightly open the inlet ball valve and fully open the ¼" drain valve. Once full ow of water ows from the drain port, slowly open the inlet valve to the full open position. Allow water to ush to drain for 5 minutes.
9. Slowly close the drain valve and check the system for leaks.
10. Slowly open the outlet valve to restore water ow to downstream equipment.
11. Record lter change date in system maintenance log.
Replacement Parts
Description Ordering Code
Filter Head 3/8" Top In/Out Quick Connect HSR-QTHD-QC38
Manifold Head First Stage With Oring Inlet HSR-QTMHF-OR
Manifold Head Middle Stage HSR-QTMHM
Manifold Head Last Stage HSR-QTMHL
Manifold Head Only Stage With Oring Inlet HSR-QTMHS-OR
Ball Valve 1/2 NPT Brass HSR-BV1/2
20" Slimline Prefilter Housing with Gauge Port HSR-20HSPF-12
10" Slimline Remote Housing HSR-10HS
20" Slimline Remote Housing HSR-20HS
20" Full Flow Remote Filter Housing HSR-20BHS
Slimline O-Ring HSR-RING-S
Full Flow O-Ring HSR-RING-B
Ball Valve 1/4" NPT Plastic HSR-BV1/4P
Inlet Bottom Mount Pressure Gauge HSR-GAUGE
Outlet Bottom Mount Pressure Gauge HSR-GAUGE-BKM
QTSTMMAX-2L-10M
15.733
26.08
5.56
4
Page 5
QTSTMMAX-2L-1M
15.73
5.56
QTSTMMAX-2L-1M-P
26.08
QTSTMMAX-2S-1M
15.73
4.47
4.47
25.21
5.56
15.73
26.08
QTSTMMAX-2S-10M
15.73
5.56
4.47
14.69
5.56
25.70
QTSTMMAX-3L-1M
20.30
26.08
28.35
7.22
25.21
8.01
5.56
25.70
QTSTMMAX-3L-10M
26.08
20.30
5.56
5
Page 6
QTSTMMAX-3L-1M-P
8.01
20.30
5.56
QTSTMMAX-3S-1M
20.30
7.22
8.01
5.56
26.08
QTSTMMAX-3S-10M
25.70
20.30
4.47
14.69
5.56
25.70
QTSTMMAX-4L-1M-P
26.08
24.73
28.35
5.56
4.47
14.69
QTSTMMAX-4L-1M
24.73
7.22
26.08
28.35
NOTICE
Allow 3" (76mm) of clearance at bottom of system for removal of filter bowls for filter cartridge replacement
QTSTMMAX-4L-10M
5.56
26.08
24.73
5.56
6
Page 7
Notes
7
Page 8
WARNING: This product contains chemicals known to the State of California to cause cancer and birth defects or other reproductive harm.
For more information: www.watts.com/prop65
LIMITED WARRANTY: Watts Regulator Co. (the “Company”) warrants each QT Steam Max water ltration line system, excluding lters and water treatment cartridges, to be free from defects in material and
workmanship under normal usage for a period of ve years from the date of original shipment. The Company warrants all lters and water treatment cartridges to be free from defects in material and workmanship under normal usage for a period of one year from the date of original shipment. In the event of such defects within the warranty period, the Company will, at its option, replace or recondition the product without charge. THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY WARRANTY GIVEN BY THE COMPANY WITH RESPECT TO THE PRODUCT. THE COMPANY MAKES NO OTHER WARRANTIES, EXPRESS OR IMPLIED. THE COMPANY HEREBY SPECIFICALLY DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. The remedy described in the first paragraph of this Limited Warranty shall constitute the sole and exclusive remedy for breach of warranty, and the Company shall not be responsible for any incidental, special or consequential damages, including without limitation, lost profits or the cost of repairing or replacing other property which is damaged if this product does not work properly, other costs resulting from labor charges, delays, vandalism, negligence, fouling caused by foreign material, damage from adverse water conditions, chemical, or any other circumstances over which the Company has no control. This warranty shall be invalidated by any abuse, misuse, misapplication, improper installation or improper maintenance or alteration of the product. Some States do not allow limitations on how long an implied warranty lasts, and some States do not allow the exclusion or limitation of incidental or consequential damages. Therefore the above limitations may not apply to you. This Limited Warranty gives you specific legal rights, and you may have other rights that vary from State to State. You should consult applicable state laws to determine your rights. SO FAR AS IS CONSISTENT WITH APPLICABLE STATE LAW, ANY IMPLIED WARRANTIES THAT MAY NOT BE DISCLAIMED, INCLUDING THE IMPLIED
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED IN DURATION TO ONE YEAR FROM THE DATE OF ORIGINAL SHIPMENT.
A Watts Water Technologies Company
IOM-HS-QTSteamMax 1335 X0FHSQTSMIOM © 2013 Watts