A minimum of 25 lbs of water pressure is required for regeneration valve to operate effectively.
Electrical Facilities
An uninterrupted alternating current (A/C) supply is required. Make sure:
•Voltage supply is compatible with unit before installation.
•Current supply is always hot and cannot be turned off with another switch.
Existing Plumbing
Condition of existing plumbing should be free from lime and iron buildup. Replace piping that has heavy lime
and/or iron build-up. If piping is clogged with iron, install a separate iron filter unit ahead of the water softener.
Location of Softener and Drain
Locate the softener close to a clean working drain and connect according to local plumbing codes.
Bypass Valves
Always provide for the installation of a bypass valve if unit is not equipped with one.
7. Solder joints near the drain must be done before connecting
the Drain Line Flow Control fitting (DLFC). Leave at least 6" (152
mm) between the DLFC and solder joints when soldering pipes
that are connected on the DLFC. Failure to do this could cause
interior damage to DLFC.
®
8. Use only Teflon
9. Be sure the floor under the salt storage tank is clean, level, and
strong enough to support the system..
10. Place approximately 1" (25 mm) of water above the grid plate. If
a grid is not utilized, fill to the top of the air check in the salt tank.
Do not add salt to the brine tank at this time.
11. Place the system in Bypass.
— Turn on the main water supply.
— Open a cold soft water tap nearby and let water run a few
minutes or until the system is free of foreign material (usually
solder) resulting from the installation.
12. Place the bypass In Service position and let water flow into the
mineral tank.
Electrical
13. Make all electrical connections according to codes. Plug the
valve into an approved power source. Do not insert meter cable
into the meter yet.
14. Tank one has control valve and tank two has adapter. See Figure
1, page 4.
15. Look on the right side of the control valve, it has indicators
showing which position the control valve is in during Regeneration and which tank is In Service.
— Figure 3, page 6 shows the valve In Service position with tank
one supplying conditioned water and tank two on standby.
NOTE: Make sure the meter cable is not inserted in the me-
Teflon® is a registered trademark of E.I. Dupont de Nemours & Company.
5
Model 9000/9100/9500
rapid rinse
brine rinse
backwash
tank one
Figure 3
brine fill
stand-by
tank two
: Control Valve Position Indicators
Figure 4
16. Cycle timer into backwash position. Turn manual knob so that
the micro switch rides on the first set of pins.
— In this position the tank's switch (lower piston) and the control
valve moves to the backwash position (upper piston).
— Wait until the positioning of upper and lower pistons stops
before advancing the timer further. If advanced too fast the
control will not home into the In Service position (it will not
advance to any other position). To correct this, rotate the
manual knob back to In Service and start again into backwash.
17. Plug the unit back in with all the air backwashed, slowly cycle
the timer to the brine position; rapid rinse; and brine tank refill.
Wait for the control drive motor to position itself in each cycle
and stop, before advancing on to the next position.
: Timer
18. Once back in the In Service position, cycle the control valve
again into the backwash position. The tanks switch again, and
air head backwashes out of the other tank. Once the system
reaches the backwash position unplug it again. Allow the system
to remain in the backwash position until all air is purged from the
system. When all air is gone no air will come out of the drain line.
Then plug the unit back in.
Proceed to regeneration cycle program setting procedure. Cycle
the control back to the In Service position. Leave the timer in
theopenposition.DONOTinsertmetercableyet.
6
Model 9000/9100/9500
pin
storage
NOTE:
Two motors are available:
1/15 RPM has 82 minute Regeneration Time.
1/30 RPM has 164 minute Regeneration Time. See
Figure 5
: Program Wheel
Figure 5
.
7
Model 9000/9100/9500
Regeneration Cycle Program Setting Procedure
Setting the Regeneration Cycle Program
The Regeneration cycle program on the water conditioner is preset at the factory. However, portions of the cycle or
program time may be lengthened or shortened for local conditions or system design.
1. Expose cycle program wheel by grasping timer in lower right hand corner and pulling. This releases snap
retainer and swings timer to the left
NOTE:
2. Remove the program wheel by grasping program wheel and squeezing protruding lugs towards center. Lift
program wheel off timer.
— Switch arms may require movement to facilitate removal.
3. Return timer to closed position by engaging snap retainer in back plate.
— Make certain all electrical wires locate above snap retainer post.
Meter cable
must
be removed from meter dome before opening timer.
Changing Length of the Backwash Time
The program wheel in
group of pins starting at zero determines the length of time the unit backwashes.
Example:
— The number of pins multiplied by two equals minutes of backwash.
If there are six pins in this section, the time of backwash is 12 minutes (2 minutes per pin). To
change the length of backwash time, add or remove pins as required.
Figure 5
is In Service position. Looking at the numbered side of the program wheel, the
Changing Length of Brine and Rinse Time
The group of holes between the last pin in the backwash section and the second group of pins determines the
length of time that a unit will brine and rinse (2 minutes per hole).
To change the length of brine and rinse time, add or remove pins in the rapid rinse group of pins to increase or
decrease the number of holes in the brine and rinse section.
— The number of holes multiplied by two equals minutes of brine and rinse.
Changing Length Of Rapid Rinse
The second group of pins on the program wheel determines the length of time the water conditioner rapid rinses (2
minutes per pin). To change the length of rapid rinse time, add or remove pins at the higher numbered end of this
section as required.
— The number of pins multiplied by two equals minutes of rapid rinse.
NOTE:
Program wheels with 0–82 minute cycle times, use one minute per pin or hole to set Regeneration
times. The layout of pins and holes on the program wheel follow the same procedure as on this page.
Changing Length of Brine Tank Refill Time
The second group of holes on the program wheel determines the length of time the water conditioner refills the
brine tank (2 minutes per hole).
To change the length of refill time, move the two pins at the end of the second group of holes as required.
The Regeneration cycle is complete when the two pin set at end of the brine tank refill section trips the outer
micro-switch. The program wheel, however, continues to rotate until the inner micro-switch drops into the notch on
the program wheel.
8
Model 9000/9100/9500
Time Brine Refill and Meter Setting Procedure
Programming
1. The control valve is set at the factory for backwash; brine and slow rinse; rapid rinse and brine tank fill times.
Change any of these times by repositioning the pins and holes or adding more pins.
NOTE:
2. The control valve has a separate brine tank fill cycle.
— Calculate the desired salt setting using the brine line flow control rate of refill (in gpm) multiplied by the
Example:
NOTE:
3. Setting the gallon wheel.
Knowing the amount of resin in each tank and the salt setting per Regeneration, calculate the gallons
available, using the following capacities as a guide:
Two speed timer motors are available
1/15 RPM has 82 minute Regeneration Time and each pin or hole equals one minute.
1/30 RPM has 164 minute Regeneration Time and each pin or hole equals two minutes.
timer setting. Then, using one gallon of fresh water dissolving approximately 3 lbs salt, calculate the refill
time.
A desired 30 lbs salt setting:
The unit has a 1.0 gpm refill rate so a 10 gallon fill is required.
Set the timer refill section at 10 minutes.
There must always be two pins at the end of a refill time to stop the fill cycle.
With the Regeneration times set, place timer back to its original position, making sure the lower right
hand corner snaps back into the backplate and the meter cable slides through the backplate and does
not bind.
10 gallons x 3 lbs/gals = 30 lbs salt
10 minutes x 1.0 gpm = 10 gallon fill
(capacity per ft
compensated hardness of H
NOTE:
Example:
DO NOT SET THIS FIGURE - GO TO STEP 4
— Because the control valve regenerates with soft water from the other tank, subtract the water used for
Based on tank size:
More resin increases capacity, less resin decreases capacity.
More salt increases capacity, less salt decreases capacity.
tank diameter=16"
compensated hardness=35 grains per gal (tested sample)
3
resin (based on flow rate)
ft
lbs of salt=8
capacity per ft
(24,000 x 4 ft
Regeneration. Take each Regeneration cycle and calculate the water used.
3
3
of resin per tank)
35 grains
3
x ft3 of resin per tank)
O
2
=4
=24,000
= 2740 gallons available before regeneration
= gallons available
9
Model 9000/9100/9500
Example:
Unit is set for a 16" diameter tank with 4 ft3 of resin and salted at 8 lbs. per ft3, 7 gpm backwash,
#3 injector, 1.0 gpm brine refill, and 60 psi and timer set for
rinse, 10 min. rapid rinse, 10 min. brine tank fill.
10 min. backwash, 60 min. brine and
Backwash
Brine and Rinse
Rapid Rinse
Brine Tank Fill
With the 2740 gallons available calculated in Step 3, subtract the Regeneration water used from the
total water available.
2740 gallons available- 210 gallons used =2530 gallons
4. Set meter wheel at approximately 2530 gallons. Lift the inner dial of the meter program wheel so that you can
rotate it freely. Position the white dot opposite the 2530 gallon setting.
NOTE:
5. Insert meter cable into meter.
6. Check bypass.
There is a slight delay between the time the meter zeros out and the cycle starts. Units using the:
1/15 RPM motor, 82 minute Regeneration Time has a 9
1/30 RPM motor, 180 minute Regeneration Time has an 18
This delay period is not critical on residential equipment. However, take this factor into consideration
for commercial applications by subtracting continuous flows for 9 minutes or 18 minutes from water
available.
10 minutes x 7.0 gpm =70.0 gallons
60 minutes x 1.0 gpm =60.0 gallons
10 minutes x 7.0 gpm =70.0 gallons
10 minutes x 1.0 gpm =10.0 gallons
12A160022-12brine line flow control assembly, 0.125 gpm
60022-25brine line flow control assembly, 0.250 gpm
60022-50brine line flow control assembly, 0.500 gpm
60022-100brine line flow control assembly, 1.00 gpm
12B160350brine valve assembly
13161419distributor adapter kit, 1.05"
injectornumberDLFCnumberBLFCnumber
red #000Blank0Blank0
white #1011.210.251
blue #2021.520.502
yellow #3032.0 31.003
green #4042.44
3.0 5
3.56
4.0 7
5.08
7.0 9
Not Shown
1412763seal and space stuffer tool
1513061spacer puller tool
1613759DLFC retainer tool
16
9100SecondTankAssembly
1
2
3
Figure 29
9100SecondTankAssembly
Item QuantIty Part number DescrIPtIon
1 1 60425-12 plastic tube assembly, 9100, up to 12" tanks
60425-16 plastic tube assembly, 9100, up to 16" tanks
2 1 14865 second tank adapter assembly, 9100
3 1 61419 distributors adapter kit, 9100, 1.05"
17
9000/9100/9500 MeterAssemblies
9100MeterAssembly
Figure 31
18
9100MeterAssembly
Item QuantIty Part number DescrIPtIon
11 60086 3/4" meter assembly, standard range
60087 3/4" meter assembly, extended range
1A 1 14038 meter cap assembly, standard range
1C 15150 meter cap assembly, extended range
1D 1 15218 meter cap assembly, brass standard range
15218NP
1E 15237 meter cap assembly, brass extended range
15237NP
2 1 13509 impeller
13509-01 impeller, hot water
4 1 60389 1" meter assembly, standard range
60389NP 1" meter assembly, standard range
60390 1" meter assembly, extended range
60390NP
606121" meter assembly, standard range, hot water
4A 1 15078 1" adapter coupling
7 60460 meter checker kit, standard range
860461 meter checker kit, extended range
meter cap assembly, brass nickel-plated
standard range
meter cap assembly, brass nickel-plated
extended range
1. Softener fails to regenerate.A. Electrical service to unit has been
B. Timer is defective.
2. Hard water.A. Bypass valve is open.
B. No salt in brine tank.
C. Injector screen plugged.
D. Insufficient water flowing into brine
E. Hot water tank hardness.
F. Leak at distributor tube.
G. Internal valve leak.
3. Unit used too much salt.A. Improper salt setting.
B. Excessive water in brine tank.
4. Loss of water pressure.A. Iron buildup in line to water
B. Iron buildup in water conditioner.
C. Inlet of control plugged due to
interrupted.
tank.
conditioner.
foreign material broken loose from
pipe by recent work done on
plumbing system.
A. Assure permanent electrical
service (check fuse, plug, pull
chain or switch).
B. Replace timer.
A. Close bypass valve.
B. Add Salt to brine tank and maintain
salt level above water level.
C. Clean injector screen.
D. Check brine tank fill time and clean
brine line flow control if plugged.
E. Repeated flushing of the hot water
tank is required.
F. Make sure distributor tube is not
cracked. Check O-Ring and tube
pilot.
D. Replace seals and spacers and/or
piston.
A. Check salt usage and salt setting.
B. See Problem No. 7.
A. Clean line to water conditioner.
B. Clean control and add mineral
cleaner to mineral bed. Increase
frequency of regeneration and/or
backwash time.
C. Remove pistons and clean control.
5. Loss of mineral through drain line.A. Air in water system.
B. Drain line flow control too large.
6. Iron in conditioned water.A. Fouled mineral bed.A. Check backwash, brine draw and
7. Excessive water in brine tank.A. Plugged drain line flow control.
B. Plugged injector system.
C. Timer not cycling.
D. Foreign material in brine valve.
E. Foreign material in brine line flow
control.
F. Power loss during brine fill.
A. Assure that well system has
proper air eliminator control.
Check for dry well condition.
B. Check to ensure drain line flow
control is sized properly for your
mineral tank.
brine tank fill. Increase frequency
of regeneration.
A. Check flow control.
B. Clean injector and screen.
C. Replace timer.
D. Replace brine valve seat and clean
valve.
E. Clean brine line flow control.
F. Check power source.
26
Model 9000/9100/9500
PROBLEMCAUSECORRECTION
8. Softener fails to draw brine.A. Drain line flow control is plugged.
9. Control cycles continuously.A. Broken or shorted switch.A. Determine if switch or timer is
10. Drain flows continuously. A. Valve is not programming correctly.
General Service Hints
Problem: Softener delivers hard water
PROBLEMCAUSECORRECTION
B. Injector is plugged.
C. Injector screen plugged.
D. Line pressure is too low.
E. Internal Control Leak
B. Foreign material in control.
C. Internal control leak.
A. Clean drain line flow control.
B. Clean injector.
C. Clean screen.
D. Increase line pressure to
25 psi min.
E. Change seals, spacers and piston
assembly.
faulty and replace it, or replace
complete power head.
A. Check timer program and positioning
of control. Replace power head
assembly if not positioning properly.
B. Remove power head assembly and
inspect bore, remove foreign
material and check control in various
regeneration positions.
C. Replace seals and piston assembly.
Softener delivers hard water.Reserve capacity has been exceeded. Check salt dosage requirements and
reset program wheel to provide additional reserve.
Program wheel is not rotating with
meter output.
Meter is not measuring flow.Check output by observing rotation of
Pull cable out of meter cover and rotate
manually. Program wheel must move
without binding and cycle actuator must
start the cycle before the clutch
releases.
small gear on front of timer
(Note: Program wheel must not be
against regeneration stop for this check)
Each tooth is approximately 75 gallons
on 1-1/2″ installations. If not performing
properly, replace meter.
27
Model 9000/9100/9500
Mechanical Timer Valve Wiring
TM - TIMER MOTOR
VDM - VALVE DRIVE MOTOR
SW1 - TIMER HOMING SWITCH
SW2 - TIMER PROGRAM SWITCH
SW3 - VALVE HOMING SWITCH
SW4 - VALVE PROGRAM SWITCH
THCAM - TIMER HOMING CAM
TPCAM - TIMER PROGRAM CAM
Figure 46
28
Model 9000/9100/9500
9100 Control Dimensions
Figure 50
29
Model 9000/9100/9500
9100
Figure 53:9100
Meter Flow Data
30
Model 9000/9100/9500
InjectorFlow Data
9000/9100
InjectorFlowData
9100
Figure 55:9000/9100—1600 Series Injectors
31
LImIteD Warranty: Certain Watts Pure Water products come with a limited warranty from Watts Regulator Co. Other products may have no warranty or are covered by the original manufacturer’s
warranty only. For specic product warranty information, please visit www.watts.com or the published literature that comes with your product. Any remedies stated in such warranties are exclusive and
are the only remedies for breach of warranty. eXcePt For tHe aPPLIcabLe ProDuct Warranty, IF any, Watts maKes no otHer WarrantIes, eXPress or ImPLIeD. to tHe FuLLest eXtent
PermItteD by aPPLIcabLe LaW, Watts Hereby sPecIFIcaLLy DIscLaIms aLL otHer WarrantIes, eXPress or ImPLIeD, IncLuDInG but not LImIteD to tHe ImPLIeD WarrantIes oF
mercHantabILIty anD FItness For a PartIcuLar PurPose, anD In no eVent sHaLL Watts be LIabLe, In contract, tort, strIct LIabILIty or unDer any otHer LeGaL tHeory, For
IncIDentaL, InDIrect, sPecIaL or conseQuentIaL DamaGes, IncLuDInG, WItHout LImItatIon, Lost ProFIts or ProPerty DamaGe, reGarDLess oF WHetHer It Was InFormeD about
tHe PossIbILIty oF sucH DamaGes.