Watts PWR4021 User Manual

Installation, Operation and Maintenance Manual
Commercial Reverse Osmosis Systems Series PWR4021
PURE WATER
!
CAUTION: Please read the entire manual before proceed­ing with the installation and startup. Your failure to follow any attached instructions or operating parameters may lead to the product’s failure, which can cause property damage and/or personal injury.
• Do not use where the water is microbiologically unsafe.
• Pretreatment must be sufficient to eliminate chemicals that
would attack the membrane materials.
• Always turn off the unit, shut off the feed water, and discon-
nect the electrical power when working on the unit.
• Never allow the pump to run dry.
• Never start the pump with the reject valve closed.
• Never allow the unit to freeze or operate with a feed water
temperature above 100°F.
Save manual for future reference.
Please refer to Section 6 of this manual for operating parameters according to your specific feed water Silt Density Index (SDI). For all other settings according to your specific feed water quality, please contact your Watts representative. A chemical analysis of the feed water should be conducted prior to the initial sizing and selection of this system.
Notes
Changes in operating variables are beyond the control of Watts. The end user is responsible for the safe operation of this equipment. The suitability of the product water for any specific application is the responsibility of the end user.
Successful long-term performance of an RO system depends on proper operation and maintenance of the system. This includes the initial system startup and operational startups and shutdowns. Prevention of fouling or scaling of the membranes is not only a mat­ter of system design, but also a matter of proper operation. Record keeping and data normalization are required in order to know the actual system performance and to enable corrective measures when necessary. Complete and accurate records are also required in case of a system performance warranty claim.
Changes in the operating parameters of an RO system can be caused by changes in the feed water or can be a sign of trouble. Maintaining an operation and maintenance log is crucial in diagnos­ing and preventing system problems. For your reference, a typical log sheet is included in this manual.
Table Of Contents
I. Introduction
A. Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
B. RO Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
C. Pre-treatment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
II. Controls, Indicators, and Components
A. General System Component Identification – Figure #1 . . . . . . 3
B. Controller Drawing – Figure #2 . . . . . . . . . . . . . . . . . . . . . . . . 4
III. Operation
A. Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
B. Plumbing Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
C. Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
D. Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
E. Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
F. Operation and Maintenance Log . . . . . . . . . . . . . . . . . . . . . . 10
G. Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-13
IV. Replacement Parts List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
V. Membrane Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
VI. Appendix
Flow Rate Guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Temperature Correction Factors . . . . . . . . . . . . . . . . . . . . . . . . 14
Electrical Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
IOM-WQ-PWR4021
Series PWR4021
Note: Do not use with water that is microbiologically unsafe or
of unknown quality without adequate disinfection before or after the system.
I. Introduction
The separation of dissolved solids and water using RO membranes is a pressure driven temperature dependent process. The membrane material is designed to be as permeable to water as possible while maintaining the ability to reject dissolved solids.
The main system design parameters require the following:
• Internal flows across the membrane surface must be high enough to prevent settling of fine suspended solids on the membrane surface.
• The concentration of each dissolved ionic species must not exceed the limits of solubility anywhere in the system.
• Pre-treatment must be sufficient to eliminate chemicals that would attack the membrane materials.
A. Specifications
PWR40213023 PWR40213033 PWR40213043 PWR40213053 PWR40213063
Productivity (gallons per day / gallons per minute) Maximum production based on standard membranes and feed water of 25°C, SDI < 3, 1000 ppm TDS, and pH 8. Individual membrane productivity may vary (± 15%).
Quality (typical membrane percent rejection) Based on membrane manufactures specifications, overall system percent rejection may be less.
Recovery without reject recycle 29 % 39 % 50 % 57 % 62 % Recovery with reject recycle (adjustable) 50 % 50 % 75 % 75 % 75 % Membrane Size 4 x 40 4 x 40 4 x 40 4 x 40 4 x 40 Number Of Membranes Per Vessel 1 1 1 1 1 Pressure Vessel Array 1:1 1:1:1 1:1:1:1 1:1:1:1:1 1:1:1:1:1:1 Number Of Membranes 2 3 4 5 6 Prefilter (system ships with one 5 micron cartridge) 20" BB 20" BB 20" BB 20" BB 20" BB Feed Water Connection 1" NPT 1" NPT 1" NPT 1" NPT 1" NPT Product Water Connection Reject Water Connection Feed Water Required (feed water required will be less if reject recycle is used) 9 gpm 10 gpm 10 gpm 12 gpm 13 gpm Feed Water Pressure (minimum) 20psi 20psi 20psi 20psi 20psi Drain Required 9 gpm 10 gpm 10 gpm 12 gpm 12 gpm Electrical Requirement 230 VAC, 3-ph, 60 Hz (other voltages available) 15 amps 15 amps 15 amps 15 amps 15 amps TEFC Motor (horse power) 5 5 5 5 5 Dimensions L x W x H (inches) 60 x 18 x 56 60 x 18 x 56 60 x 18 x 56 60 x 18 x 56 60 x 18 x 56 Shipping Weight (estimated pounds) 400 500 600 700 800
3600 / 2.5 5400 / 3.75 7200 / 5.0 9000 / 6.25 10800 / 7.5
98 % 98 % 98 % 98 % 98 %
3
4" NPT
3
4" NPT
3
4" NPT
3
4" NPT
3
4" NPT
3
4" NPT
3
4" NPT
3
4" NPT
3
4" NPT
3
4" NPT
B. RO Overview
Reverse osmosis systems utilize semipermeable membrane ele­ments to separate the feed water into two streams. The pressurized feed water is separated into purified (product) water and concentrate (reject) water. The impurities contained in the feed water are carried to drain by the reject water. It is critical to maintain adequate reject flow in order to prevent membrane scaling and/or fouling.
RO Membrane
Feed Water Product Water
Reject Water
2
C. Pretreatment
The RO feed water must be pretreated in order to prevent mem­brane damage and/or fouling. Proper pretreatment is essential for reliable operation of any RO system.
Pretreatment requirements vary depending on the nature of the feed water. Pretreatment equipment is sold separately. The most common forms of pretreatment are described below.
Media Filter - Used to remove large suspended solids (sediment) from the feed water. Backwashing the media removes the trapped particles. Backwash can be initiated by time or differential pressure.
Water Softener - Used to remove calcium and magnesium from the feed water in order to prevent hardness scaling. The potential for hardness scaling is predicted by the Langelier Saturation Index (LSI). The LSI should be zero or negative throughout the unit unless approved anti-scalents are used. Softening is the preferred method of controlling hardness scale.
Carbon Filter - Used to remove chlorine and organics from the feed water. Free chlorine will cause rapid irreversible damage to the membranes.
The residual free chlorine present in most municipal water supplies will damage the thin film composite structure of the membranes used in this unit. Carbon filtration or sodium bisulfite injection should be used to completely remove the free chlorine residual.
Chemical Injection - Typically used to feed antiscalant, coagulant, or bisulfite into the feed water or to adjust the feed water pH.
Prefilter Cartridge - Used to remove smaller suspended solids and trap any particles that may be generated by the other pretreatment. The cartridge(s) should be replaced when the pressure drop across the housing increases 5 - 10 psig over the clean cartridge pressure drop. The effect of suspended solids is measured by the silt density index (SDI) test. An SDI of five (5) or less is specified by most mem­brane manufacturers and three (3) or less is recommended.
Iron & Manganese - Iron should be removed to less than 0.1 ppm. Manganese should be removed to less than 0.05 ppm. Special me­dia filters and/or chemical treatment is commonly used.
pH - The pH is often lowered to reduce the scaling potential.
Silica: Reported on the analysis as SiO2. Silica forms a coating on
membrane surfaces when the concentration exceeds its solubility. Additionally, the solubility is highly pH and temperature dependent. Silica fouling can be prevented with chemical injection and/or reduc­ing the recovery.
II. Controls, Indicators, and
Components
A. General System Component Identification
A Controller - Controls the operation of the system and displays
the product water quality. This system uses the micro-electronic based CI-1000 controller.
B Reject Control Valve - Controls the amount of reject flow. A
separate reject recycle water control valve is included to regulate waste water recovery.
C Pump Discharge Valve - Used to throttle the pump.
D Prefilter Pressure Gauges - Indicates the inlet and outlet pres-
sure of the prefilter. The difference between these two gauges is the prefilter differential pressure.
E Pump Discharge Pressure Gauge - Indicates the pump dis-
charge pressure.
F Reject Pressure Gauge - Indicates the reject pressure.
G Reject Flow Meter - Indicates the reject flow rate in gallons per
minute (gpm). A reject recycle flow meter is also included.
H Product Flow Meter - Indicates the product flow rate in gallons
per minute (gpm).
I Prefilter Housing - Contains the RO prefilter.
J Automatic Inlet Valve - Opens when pump is on and closes
when the pump is off.
K Low-pressure Switch - Sends a signal to the controller if the
pump suction pressure is low.
L RO Feed Pump - Pressurizes the RO feed water.
M RO Membrane Vessels - Contains the RO membranes.
(See Figure 1)
Separate motor starter
enclosure used only with
CI 1000 controller.
Figure 1
Figure 1
3
B. Controller Drawing
Figure 2
CI-1000 Controller
4
III.Operation
A. Installation
1. The water supply should be sufficient to provide a minimum of 20 psig pressure at the design feed flow.
2. Proper pretreatment must be determined and installed prior to the RO system.
3. A fused high voltage disconnect switch located within 10 feet of the unit is recommended. This disconnect is not provided with the RO system.
4. Responsibility for meeting local electrical and plumbing codes lies with the owner /operator.
5. Install indoors in an area protected from freezing. Space al­lowances for the removal of the membranes from the pressure vessels should be provided. This system requires 42" minimum clear space on each side.
B. Plumbing Connections
Note: It is the responsibility of the end user to ensure that the installation is done according to local codes and regulations.
1. Connect the pretreated feed water line to the inlet side of the prefilter housing. (Figure # 1 item # 1) A feed water shutoff valve should be located within 10 feet of the system.
2. Temporarily connect the outlet of the product water flow meter to drain. (Figure # 1 item # 2) The product water line should never be restricted. Membrane and/or system damage may oc­cur if the product line is blocked.
3. Connect the outlet of the reject water flow meter to a drain. (Fig­ure # 1 item # 3) The reject drain line should never be restricted. Membrane and/or system damage may occur if the reject drain line is blocked. An air gap must be located between the end of the drain line and the drain. The use of a standpipe or other open drain satisfies most state and local codes and allows for visual inspection and sampling.
C. Electrical
Note: It is the responsibility of the end user to ensure that the installation is done according to local codes and regulations.
1. A safety switch or fused disconnect should be installed within 10 feet of the system.
2. Verify that the disconnect switch is de-energized using a voltme­ter.
3. Connect the outlet of the disconnect switch to the terminals on top of the motor starter (Figure # 2). Attach the power supply ground to the chassis ground. It may be necessary to drill a hole in the enclosure and install a water tight strain relief or conduit connector. The hole size and location must be determined by the installer. Check the pump motor nameplate for the amper­age draw at various voltages to determine the wire size required.
4. Do not apply power to the RO unit at this time.
D. Startup
1. Verify that the pretreatment equipment is installed and working properly. Verify that no free chlorine is present in the feed water.
2. Verify that the on/off switch is in the off position.
3. Verify that the pump discharge valve (Figure # 1 item C) is open.
4. Install a 20" five micron filter cartridge in the prefilter housing. (Figure #1 item I)
5. Open the reject control valve completely (Figure # 1 item B) by turning it counterclockwise. Close the reject recycle control valve completely if the reject recycle option is included.
6. Open the feed water shutoff valve installed in step III-B-1 above.
7. Manually open the inlet solenoid valve (figure #1 item J) by turn­ing the white lever located near the valve outlet.
8. Water will flow through the system and to drain through the reject flow meter (figure # 1 item G).
9. Manually close the inlet solenoid valve after the air has been purged from the system, or after 10 minutes, whichever occurs first.
10. Close the pump discharge valve half way. (Figure # 1 item C)
11. Engage the safety switch or disconnect (installed in step III-C-1 above) to apply electrical power to the RO system.
12. On the CI-1000 controller, put the key switch in the on position and press the start / stop button to turn the pump on. Press the start / stop button again when the pump turns on to turn the pump off and look at the motor fan as the pump stops to determine if the pump rotation is correct. There is a 10 second delay before the pump starts. See the controller section for more details. The fan should rotate in the direction of the rotation arrow located on the pump. Continue with the startup if the pump is rotating in the proper direction. If the pump is rotating backwards, change the rotation by disconnecting the power and reversing any two of the wires on the power inlet. Verify proper pump rotation before continuing.
13. Turn the system on.
14. Adjust the reject control valve(s) (figure # 1 item B) and the pump discharge valve (Figure # 1 item C) until the desired flows are achieved. Closing the reject valve increases the product flow and decreases the reject flow. Opening the pump discharge valve increases both the reject flow and the product flow. See the flow rate guidelines and temperature correction table in the appendix to determine the flow rates for different operating temperatures.
15. Allow the product water to flow to drain for 30 minutes.
16. Turn off the system and connect the product line to the point of use. (Figure # 1 item # 2) The product water line should never be restricted. Membrane and/or system damage may occur if the product line is blocked.
17. Restart the system and record the initial operating data using the log sheet in the next section.
Note: See the controller section of this manual for more installation and operation information
5
Note: It is very important to vent the mechanical seal during startup. Failure to vent the seal may result in premature seal failure.
Vented Priming Plug
Drain Plug
Back off needle valve to vent air. Retighten to 25 in.­lbs. when vent port runs a steady stream of water.
E. Controllers
The controller for this system is the CI 1000 controller. This is a microprocessor-based controller with a product water conductivity meter. A separate manual for this controller begins on the next page.
6
Reverse Osmosis Controller
Operations and Maintenance Model #CI-1000
Introduction
The CI-1000 Reverse Osmosis Controller is designed to control and monitor the operating parameters of a reverse osmosis water puri­fication system. Information is displayed on a back-lit liquid crystal display, and on individual light-emitting diodes (LEDs). Functions and controls are operated through snap-dome switches (see Figure 2).
Features
Temperature Compensated Conductivity Monitor
Water Temperature Monitor
Three Modes of Operation: Stand-by, Tank Feed, and Direct Feed
Pretreatment Interlock
Tank Full Shutdown
Inlet Valve Control
Pump Control
Low Feed Pressure Sensing with Automatic Reset
Autoflush with Adjustable Flush Time
Diverter Valve Output
Specifications
Power Requirements: The controller can operate with a power
source of 115 or 230 VAC single phase. A multi-function power inlet is used to select the proper input voltage.
Fuse: 1 amp 250 volt slow blow, located inside the power inlet receptacle.
Environment: The controller can operate at a temperature from 0° to 60° C (32° to 140°F). Relative humidity must not exceed 95 percent.
Conductivity Monitor: The conductivity monitor measures the prod­uct water quality and displays this information in micro-mhos/cm. The display is temperature compensated to 25°C (770°F).
Outputs
Inlet Solenoid: A 24 VAC output is provided to power the inlet
solenoid. This output always energizes 12 seconds before the pump turns on, and de-energizes 12 seconds after the pump turns off.
Flush Valve: A 24 VAC output is provided to power the optional reject solenoid valve. This output will energize during the flush cycle. This is an optional accessory.
Motor Starter: A 24 VAC output is included to provide controlled pump operation. This output powers the coil of the magnetic starter relay. This output is energized depending on other operating param­eters.
Auxiliary Output: A 24 VAC output that energizes under certain con­ditions, depending upon the mode selected for it in the configuration. This output is intended to power a relay or some other low current device. The maximum current available is one ampere. Two modes are selectable for this output:
Diverter: Output energizes when the product quality is below
the set point. The diverter valve is not included with the system.
Alarm: Output energizes for final detection of low-pressure
conditions and low water quality conditions. No alarm hardware is included with the system.
Inputs
WARNING: All the inputs described below are dry contacts. Do not apply voltage to these contacts or permanent damage to the controller will result.
Conductivity Probe: There are four inputs for the conductivity probe, two for the thermistor and two for the conductivity. Only probes with a cell constant of 1.0 and a thermistor with a nominal resistance value of 20K at 25' C will work with this controller.
Low-pressure Switch: This is a dry contact that signals the system to shut down if the pump suction pressure falls below the desired value. This is a normally open contact. When a circuit is not com­plete between the two terminals, the system will operate. If contact is made between the two terminals, the system will shut down. The LCD display and a LED will indicate when the system is shut down due to low-pressure. The controller can be programmed to automati­cally restart. This is described in Section III, Operation.
Tank Level: This is a dry contact that signals the system to shut down when the storage tank is full. This contact is normally closed. When a circuit is complete between the two terminals the system will operate. If contact is broken between the two terminals, the system will shut down if it is operating in the tank feed mode. A LED will indicate when the tank is full. The system will restart itself when the contact is closed. The switch for this function in not provided with the controller.
Pretreatment Interlock: This is a dry contact that signals the system to shut down when a pretreatment device is not functioning, or re­generating. This could be used on a water softener, multi media filter, chemical feed pump, differential pressure switch, etc. This contact is normally open. When a circuit is not complete between the two ter­minals the system will operate. If the contact is= closed the system will shut down. A LED will indicate when the system is shut down due to pretreatment interlock. The system will restart itself when the contact is opened.
Mode Descriptions
The stand-by mode is intended to place the system in a temporary non-operational mode. When the system is placed in this mode it will operate for the amount of time set for the flush cycle. If the flush time is set for zero the system will operate for one minute. After this cycle is complete the pump will turn off and the inlet valve will close. The system will repeat this cycle once every hour. When the system is flushing, the amount of time remaining in the flush cycle will be indicated on the last line of the display. When the system is idle, the amount of time remaining until the next flush will be indicated. When the pump is running, the reject valve and diverter valve outputs are energized.
The tank feed mode is intended to be used when the system is feeding a storage tank. When in this mode the system will shut down when the tank level switch (not provided) has an open contact. The flush cycle is also enabled in this mode. If the autoflush option has been included on the system, the controller will activate the flush cycle when the system is turned on and once every hour. When the system is flushing, the amount of time remaining in the flush cycle will be indicated on the last line of the display. When the system is not flushing the amount of time until the next flush will be indicated. The system will still flush every hour even if the tank is full. During a full tank condition the system is essentially in standby. When the system is flushing, the diverter valve output is energized. If the flush time is set for zero the system will not flush when the tank is full.
The direct feed mode is intended to be used when the system is feeding a distribution loop or another piece of equipment. In this mode the system will not flush and the tank level switch is disre­garded. When the system is in this mode, the total number of hours the system has been operated will be indicated on the last line of the display.
7
Controls (see Figure 2)
NOTE: Refer to Section III, Operation for detailed instructions on operating the controls .
Start / Stop Button: This button turns the system on and off.
Select Button: This button is used to select a function or parameter
so that it can be reviewed or changed.
Up Arrow. This button increases the value of, or advances to the next option of, the function selected.
Down Arrow. This button decreases the value of, or advances to the next option of, the function selected.
Accept Button: Pressing this button causes the controller to store current values or options in memory.
Alarm Reset Button: This button is used to reset the system after a shut down due to; low-pressure or overload.
Key Switch: This switch which serves as a master power switch. When the system is turned on the key may not be removed. If the system is turned off the key may be removed.
Indicators (see Figure 2)
Multi Function Display: This is a back-lit liquid crystal display. It provides information to the operator regarding water quality, system options, etc.
There are six individual LED's to indicate the following conditions:
(See Front View drawing)
On: Indicates when the system is on.
Overload: Indicates that the system has shut down due to an over-
load condition on one of the outputs.
Low Quality: Indicates that the quality of the water is below the setpoint.
Tank Full: Indicates when the system is shut down due to a full stor­age tank. The system will only shut down in the tank feed mode
Pretreatment Interlock: Indicates when the system is shut down due to external pretreatment equipment.
Low-pressure: Indicates that the system has shut down due to low pump feed pressure.
Configuration Screen
Press the SELECT button to view the configuration screen. The software revision level is displayed in the upper right corner of this screen. While the configuration screen is displayed, the SELECT button moves the highlight cursor to the next field. The up and down arrows change the value of the highlighted field. The ACCEPT button saves all of the values and brings up the timer screen. The RESET button discards all changes and brings up the timer screen. If no input is detected for a continuous 30 seconds, the controller will discard all changes and return to the operation screen. An asterisk appears next to a field whenever the value of the field equals the value stored in memory. The configuration screen contains the fol­lowing field with their options:
Mode: (direct feed, tank feed, and standby)
Low Quality: (2-200 micromhos) This is the set point for the diverter
valve. When the product water conductivity is equal to or greater than value selected, the diverter valve output will be energized and the low quality LED will turn on.
Autostart: (on/off) if “on” is selected, the system will automatically restart after a power loss. If "off" is selected, the unit will not restart after a power loss.
Low-pressure Retry: (0-10) This is the number of times the system will attempt to restart after a low-pressure shutdown.
Low-pressure Delay: (15-90 seconds in 15 second increments) This is the amount of time between attempts to restart after a low­pressure shutdown.
Autoflush: (0-10 minutes) This is the length of the flush cycle. The system will flush for this amount of time every hour in tank feed and standby modes.
Inlet Delay Time: (10,30,60,120,300,600 seconds) This is the amount of time that the inlet valve stays open after the pump turns off.
Auxiliary Output Mode: This selects whether the auxiliary output should be used for a diverter valve (default) or an alarm output. Noted in the configuration menu as “Aux. Out”
Low Water Quality Alarm Delay: (0,5,10,30,60, 120,300,600 sec­onds) This selects the delay between the detection of a low quality water condition and the activation of the auxiliary output. This only applies if the auxiliary output is configured as an alarm output. Noted in the menu as “L/Q Alarm Delay”
Operation
The key switch must be in the ON position (see Figure 2).
Contrast Adjustment
Press the up or down arrow when the home screen is displayed to increase or decrease the contrast of the display.
Operation Screen
When the Start/Stop button is pressed the inlet valve will open. After a 12 second delay the pump will start. The system will operate according to the information stored in memory. The product water conductivity is displayed in the large numbers at the top center of the display. The temperature is displayed as degrees Celsius in the top right corner of the display. The mode of operation is displayed below the product water quality. Flush time information or pump run hours are displayed on the bottom of the display.
Timer Screen
Pressing either the ACCEPT or the RESET button from the configu­ration screen brings up the timer screen. The controller has three timers (hour meters). Two are user resetable and one is not. All of these timers count up when the pump is running. The two user rese­table meters are labeled PREFILTER and MEMBRANE. Pressing the reset button when either of these timers are highlighted will reset the timer to zero. The SELECT button moves the highlight cursor to the next timer. Press Accept while the membrane meter is highlighted to exit and return to the operation screen.
Calibration Screen
This screen is used to calibrate the conductivity and temperature. Press ACCEPT and RESET at the same time to bring up this screen. The temperature and conductivity fields on the last two lines of the display can be adjusted using the up and down arrows. Use the arrow keys to input the correct temperature and then press the ACCEPT button. The conductivity will now be highlighted. Use the arrow keys to input the correct conductivity and press the ACCEPT button. Always calibrate the temperature first. (Note: the new values are only saved when the ACCEPT button is pressed while the field is highlighted.) When the desired values are entered press the RESET button to return to the operation screen. You can only enter the cali­bration screen if the conductivity and temperature readings
8
Pop-Up Screens
Under certain circumstances a pop-up screen may be displayed. These look like a window that partially blocks out the screen behind it. The conditions that display pop-up screens are:
Low Inlet Pressure
Pretreatment Interlock
Overload Conditions
Trying to calibrate if the temperature and/or conductivity is not stable.
Service and Maintenance
The CI-1000 Reverse Osmosis Controller is designed for ease of maintenance and minimum service. Since the highest quality of electronic semiconductor components are used in this design, it is not likely that circuit malfunctions or failures will occur. It is our recommendation that service be limited to identifying malfunctions at the board level and that component level troubleshooting be referred to the factory.
Field failures that most frequently occur are:
- Improper or broken wiring connections
- Incorrect wiring of the motor starter
- Improper grounding
- Cable run is too long
- Water in connectors
- Dirty probes
- Defective probes
Troubleshooting
DESCRIPTION OF PROBLEM POSSIBLE CAUSE OR SOLUTION
System shuts down on low-pressure but pressure is okay. 1. Check the pressure switch set point
Pressing the Start/Stop button does not turn the system on. 1. Verify that the key switch is on
Conductivity monitor does not display the proper reading. 1. Calibrate the controller
Erratic conductivity display 1. Conductivity probe wiring may be too close to high voltage lines.
2. Possible short in wiring to pressure switch
3. Defective pressure switch
4. Orifice in pressure switch may be plugged
2. Verify that the circular connector on the bottom of the controller is attached
3. Check the fuse in the power inlet
2. Check the wiring to the conductivity probe
3. Clean the conductivity probe
4. Replace the conductivity probe
2. Check for moisture in the connection between the probe and the lead wire.
9
REMARKS
PRE FILTER
PRE FILTER
FEED WATER
FEED WATER
FEED WATER
OUTLET
PRESSURE
INLET PRESSURE
CHLORINE LEVEL
HARDNESS
TEMP
PPM
FEED TDS PPM PRODUCT TDS
REJECT
PRESSURE
PRESSURE
DISCHARGE
REJECT GPM PUMP
GPM
DATE PRODUCT
F. PWR4021 Operation and Maintenance Log
10
Note: Change the prefilter when the differential pressure increases by 5 - 10 psi over the clean differential pressure.
Clean the RO membrane(s) when the product flow drops by 15% or more. (See appendix)
G. PWR4021 Troubleshooting
RO Membrane Troubleshooting Guide
SYMPTOMS
SALT PASSAGE PERMEATE FLOW PRESSURE DROP LOCATION POSSIBLE CAUSES VERIFICATION CORRECTIVE ACTION
Normal to increased Decreased Normal to increased Predominantly
first stage
Normal to increased Decreased Normal to increased Predominantly
first stage
Increased Decreased Increased Predominantly
last stage
Normal to moderate increase
Decreased or mod-
Decreased Normal to moderate
increase
Can occur in any stage
Decreased Normal All stages Organic fouling Destructive testing, e.g. IR
erately increased
Increased Increased Decreased Most severe in
the first stage
Increased Increased Decreased Most severe in
the first stage
Increased Normal to increased Decreased At random O-ring leaks, End or side
Increased Normal to low Decreased All stages Conversion too high. Check flows and pressures
Metal oxide Analysis of metal ions in
cleaning solution.
Colloidal fouling SDI measurement of feed/
X-ray diffraction analysis of cleaning sol. residue.
Scaling (CaSO
4, SiO2)
BaSO
4, CaSO3,
Analysis of metal ions in cleaning sol. Check LSI of reject. Calculate maximum solubility for CaSO
2 in reject analysis.
SiO
4, BaSO4,
Biological fouling Bacteria count in permeate
and reject. Slime in pipes and vessels.
reflection analysis.
Chlorine oxidant attack Chlorine analysis of feed.
Destructive element test.
Abrasion of membrane by crystalline material
Microscopic solids analysis of feed. Destructive ele­ment test.
Probe test. Vacuum test.
seal glue leaks.
Colloidal material passage.
against design guidelines
Improved pretreatment to remove met­als. Cleaning with acid cleaners.
Optimize pretreatment system for colloid removal. Clean with high pH, anionic detergent formulation.
Increase acid addition and scale inhibitor for CaSO
3 and CaSO4. Reduce
recovery. Clean with an acid formula­tion for CaCO
3, CaSO4 and BaSO4.
Shock dosage of sodium bisulfite. Continuous feed of low conc. bisulfite at reduced pH. Peracetic acid steriliza­tion. Clean with alkaline anionic sur­factant. Chlorine dosage upstream with dechlorination. Replace cartridge filters.
Optimization of pretreatment system (e.g. coagulation process.) Resin/ activated carbon treatment. Clean with high pH detergent.
Check chlorine feed equipment and dechlorination equipment.
Improved pretreatment. Check all filters for media leakage.
Replace O-rings. Repair or replace elements.
Reduce conversion rate. Calibrate sensors. Increase analysis and data collection.
11
Motor Troubleshooting Chart
PROBLEM POSSIBLE CAUSE CORRECTIVE ACTION
Motor fails to start Blown fuses Replace fuses with proper type and rating
Overload trips Check and rest overload in starter. Improper power supply Check to see that power supplied agrees with motor nameplate and load factor. Open circuit in winding or control switch Indicated by humming sound when switch is closed. Mechanical failure Check to see if motor and drive turn freely. Check bearing and lubrication. Short circuited stator Indicated by blown fuses. Motor must be rewound. Poor stator coil connection Remove end bells, locate with test lamp. Rotor defective Look for broken bars or end ring. Motor may be overloaded Reduce load.
Motor Stalls One phase connection Check lines for open phase.
Wrong application Change type or size. Consult manufacturer. Overload motor Reduce load. Low motor voltage See that nameplate voltage is maintained. Check connection.
Open circuit Fuses blown, check overload relay, stator and push buttons. Motor runs and then dies down Power failure Check for loose connections to line, to fuses and to control. Motor does not come up to speed Not applied properly Consult supplier for proper type.
Voltage too low at motor terminals because of line drop. Use higher voltage on transformer terminals or reduce load. Check connections. Check
Broken rotor bars or loose rotor. Look for cracks near the rings. A new rotor may be required as repairs are usually temporary. Motor takes too long to accelerate Open primary circuit Locate fault with testing device and repair.
Excess loading Reduce load.
Poor circuit Check for high resistance.
Defective squirrel cage rotor Replace with new rotor.
Applied voltage too low Get power company to increase power tap. Wrong rotation Wrong sequence of phases Reverse connections at motor or at switchboard. Motor overheats while running
under load
Motor vibrates after correcting have been made
Unbalanced line current on polyphase motors during normal operation
Scraping noise Fan rubbing air shield Remove interference.
Noisy operation Airgap not uniform Check and correct bracket fits or bearing.
Hot bearings general Bent or sprung shaft Straighten or replace shaft.
Hot bearings ball Insufficient grease Maintain proper quantity of grease in bearing.
These instructions do not cover all details or variations in equipment nor provide for every possible condition to be met in connection with installation, operation or maintenance. Chart courtesy of Marathon Electric.
Overloaded Reduce load.
Frame or bracket vents may be clogged with dirt and
prevent proper ventilation of motor.
Motor may have one phase open Check to make sure that all leads are well connected.
Grounded could Locate and repair.
Unbalanced terminal voltage Check for faulty leads, connections and transformers.
Motor misaligned Realign
Weak support Strengthen base.
Coupling out of balance Balance coupling.
Driven equipment unbalanced Rebalance driven equipment.
Defective ball bearing Replace bearing.
Bearing not in line Line properly.
Balancing weights shifted Rebalance motor.
Polyphase motor running single phase Check for open circuit.
Excessive end play Adjust bearing or add washer.
Unequal terminal volts Check leads and connections
Single phase operation Check for open contacts
Fan striking insulation Clear fan.
Loose on bedplate Tighten holding bolts.
Rotor unbalance Rebalance.
Excessive belt pull Decrease belt tension.
Pulleys too far away Move pulley closer to motor bearing.
Pulley diameter too small Use larger pulleys.
Misalignment Correct by realignment of drive.
Deterioration of grease, or lubricant contaminated Remove old grease, wash bearings thoroughly in kerosene and replace with new grease.
Excess lubricant Reduce quantity of grease: bearing should not be more than ½ filled.
Overloaded bearing Check alignment, side and end thrust.
Broken ball or rough races Replace bearing: first clean housing thoroughly.
conductors for proper size.
Open vent holes and check for a continuous stream of air from the motor.
12
RO System Troubleshooting
PROBLEM CORRECTIVE ACTION
General
High Product Water TDS
Membrane expanded. Replace membrane. Membrane attack by chlorine Carbon pre-filter may be exhausted. Replace with a new cartridge. Clogged pre-filter-creates pressure drop and low reject flow. Replace pre-filter cartridge. Feed pressure too low. Feed pressure must be at least 20 psi. Insufficiently flushed post-filter cartridge. Flush post-filter with pure water. Brine seal on membrane leaks. Determine if seal or O-ring is bad. Replace as needed.
No Product Water or Not Enough Product Water
Feed water shut off. Turn on feed water. Low feed pressure. Feed pressure must be at least 20 psi. Consider booster pump. Pre-filter cartridge clogged. Replace pre-filter cartridge. Membrane fouled. Determine and correct cause; replace membrane. Product check valve stuck. Replace check valve fitting. Low pump discharge pressure Open pump discharge valve, replace pump Membrane fouled. Determine and correct cause; replace or clean membrane. Product check valve stuck. Clean or replace check valve. Low pump discharge pressure Adjust reject valve or replace pump
IV. Replacement Parts List
A list of common replacement parts is provided below. All of these parts are not used on every system and all of the parts are not listed. Contact you dealer for replacement parts assistance.
ITEM NUMBER DESCRIPTION
1 Pre filter housing 20" Big Blue 2 RO Membrane Pressure Vessels 4" x 40" SS 3 Pressure Gauge, 2", 0-100psi, Dry 4 Pressure Gauge, 2 5 Flow Meter 1-10 gpm (product) 6 Flow Meter 1-10 gpm (reject) 7 Motor Starter Contactor, 16 amps, 24 volt coil 8 Overload Relay 8 - 14 amps
9 Overload Relay 6 - 8.5 amps 10 Pump & Motor CR2-180U 5hp, 3-Phase 11 Low-pressure Switch, 6.5psi 12 Inlet Solenoid Valve, 1", 24 volt coil 13 Watts 4 x 40 RO Membranes 14 CI 1000 Controller 15 Conductivity Probe 16 Autoflush Solenoid Valve,
1
2", 0-400psi, LF
1
2", Brass, 24 volt coil.
V. Membrane Replacement
1. Turn off the system and close the feed water shutoff valve.
2. Disconnect the membrane feed hoses by loosing the brass fit­tings between the end of the hoses and the pressure vessel end caps.
3. Remove the retaining “U” pins from the pressure vessels.
4. Push the old membrane out of the vessel in the direction of the feed flow. (See flow arrows on the right side of figure #1)
5. Record the serial numbers of the new membranes.
6. Lightly lubricate the brine seals on the new membranes with clean water.
7. Install the new membranes in the direction of flow with the brine seal end going in last.
8. Lightly lubricate the end cap internal and external O-rings with glycerin.
9. Install the end caps and secure them with the “U” pins.
10. Install the membrane feed hoses.
11. Verify that all retaining “U” pins are installed.
12. Follow the start up procedure in section III-D.
Flow Direction
13
Membrane
Brine
Seal
VI. Appendix
The following tables are intended as a guide to determining the flow rates for the PWR4021 series RO systems. All flows are in gallons per minute (GPM).
Nominal flows for systems with reject recycle and a feed water Silt Density Index less than 3.
MODEL NUMBER PWR40213023 PWR40213033 PWR40213043 PWR40213053 PWR40213063
Product 2.5 3.75 5 6.25 7.5 Reject 2.5 3.75 1.7 2.1 2.5 Reject Recycle 3.6 2.2 3.3 2.6 2.1
Nominal flows for systems with reject recycle and a feed water Silt Density Index of 3 to less than 5.
MODEL NUMBER PWR40213023 PWR40213033 PWR40213043 PWR40213053 PWR40213063
Product 2.3 3.5 4.3 5.2 6.3 Reject 2.3 3.5 1.4 1.7 2.1 Reject Recycle 4.3 3 3.9 3.1 2.3
Temperature Correction Factors
°C °F CORRECTION FACTOR
30 86 1.16 29 84.2 1.13 28 82.4 1.09 27 80.6 1.06 26 78.8 1.03 25 77 1.00 24 75.2 0.97 23 73.4 0.94 22 71.6 0.92 21 69.8 0.89 20 68 0.86 19 66.2 0.84 18 64.4 0.81 17 62.6 0.79 16 60.8 0.77 15 59 0.74 14 57.2 0.72 13 55.4 0.70 12 53.6 0.68 11 51.8 0.66 10 50 0.64
9 48.2 0.62 8 46.4 0.61 7 44.6 0.59 6 42.8 0.57 5 41 0.55
Multiply the nominal product flow at 25° C by the temperature correction factor to determine the flow at various other temperatures.
14
CI-1000 Controller
15
LIMITED WARRANTY: Certain Watts Pure Water products come with a limited warranty from Watts Regulator Co. Other products may have no warranty or are covered by the original manufacturer’s warranty only. For specific product warranty information, please visit www.watts.com or the published literature that comes with your product. Any remedies stated in such warranties are exclusive and are the only remedies for breach of warranty. EXCEPT FOR THE APPLICABLE PRODUCT WARRANTY, IF ANY, WATTS MAKES NO OTHER WARRANTIES, EXPRESS OR IMPLIED. TO THE FULLEST EXTENT
PERMITTED BY APPLICABLE LAW, WATTS HEREBY SPECIFICALLY DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, AND IN NO EVENT SHALL WATTS BE LIABLE, IN CONTRACT, TORT, STRICT LIABILITY OR UNDER ANY OTHER LEGAL THEORY, FOR INCIDENTAL, INDIRECT, SPECIAL OR CONSEQUENTIAL DAMAGES, INCLUDING, WITHOUT LIMITATION, LOST PROFITS OR PROPERTY DAMAGE, REGARDLESS OF WHETHER IT WAS INFORMED ABOUT THE POSSIBILITY OF SUCH DAMAGES.
A Watts Wat er Techno logies Company
USA: North Andover, MA • Tel. (800) 224-1299 • www.watts.com
Canada: Burlington, ON • Tel. (888) 208-8927 • www.wattscanada.ca
IOM-WQ-PWR4021 1105 EDP# 2915864 © 2011 Watts
Loading...