Water Pressure Reducing Valves*
Sizes: 11⁄4" – 2" (32 – 50mm)
Series N45B Water Pressure Reducing Valves are designed to reduce incoming water pressure to a sensible level to protect plumbing system components and reduce water consumption. This series is suitable for water supply pressures up to 300psi (20.7 bar) and may be adjusted from 25 – 75psi (172 – 517 kPa). The standard setting is 50psi (345 kPa). All parts are quickly and easily serviceable without removing the valve from the line. The standard bypass feature permits the flow of water back through the valve into the main when pressures, due to thermal expansion on the outlet side of the valve, exceed the pressure in the main supply.
Features
•  Double union inlet & outlet connections 
•  Integral stainless steel strainer
•  Thermoplastic seat & cage
•  Bronze body construction
•  Serviceable in line
•  Bypass feature controls thermal expansion pressure**
•  Sealed spring cage on all models for accessible outdoor or pit installations
Models
N45B NPT threaded female inlet x NPT female outlet N4 5BU NPT threaded union inlet x NPT female outlet N4 5BU-S Solder union inlet x NPT female outlet N45BDU   Double Union – NPT threaded union female inlet 
and outlet
N45BDU-S  Double Union – Solder union inlet and outlet
Specifications
A Water Pressure Reducing Valve and strainer shall be installed on the water service pipe near its entrance to the building where supply main pressure exceeds 60psi (413 kPa) to reduce it to 50psi (345 kPa) or lower. Provision shall be made to permit the bypass flow of water back through the valve into the main when pressures, due to thermal expansion on the outlet side of the valve, exceed the pressure in the main supply. Pressure reducing valves with built-in bypass check valves and integral strainer will be acceptable. Approved valves shall comply with ASSE 1003. Valve shall be a Watts Regulator Company Series N45B.
* A water saving test program concluded that reducing the supply pressure from
80 – 50psi (551 – 345 kPa) resulted in a water savings of 30%.
** NOTE: The bypass feature will not prevent the pressure relief valve from opening
on the hot water supply system with pressure above 150psi (10.3 bar).
Series N45BDU – 2" (50mm) size shown
Integral Stainless Steel Strainer
Thermoplastic Seat
Reinforced Diaphragm
Threaded or solder ends
Thermal Expansion Bypass
Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with­out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.
Materials
2"
1 1/4"
1 1/2"
Body:   Bronze 
Seat: Thermoplastic Cage: Thermoplastic
Integral Strainer:  Stainless steel
Diaphragm:  Reinforced EPDM
Valve Disc:  Elastomer
Capacity
kPa psi
0 0
34 5
Pressure – Temperature
Temperature Range: 33˚F – 180˚F (0.5˚C – 82˚C)
Maximum Working Pressure: 300psi (20.7 bar)
Adjustable Reduced Pressure Range: 25 – 75psi (172 – 517 kPa) Standard Reduced Pressure Setting: 50psi (345 kPa)
Standards
Meets requirements of ASSE Standard 1003; (ANSI A112.26.2); CSA  Standard B356; and listed by IAPMO. City of Los Angeles.
Options
G Gauge tapping GG Gauge tapping and 160psi (11 bar) gauge
Dimensions – Weights
AN - NONE
BN - NONE
69 10
103 15
Pressure Drop
138 20
172 25
0 10 20 30 40 50 60 70 80 90 100 110 gpm 0 38 76 114 152 190 228 266 304 342 380 418 lpm
(50mm)
(40mm)
(32mm)
Flow
C
Max.
ET - NPT ENGAGEMENT FOR TIGHT JOINT
D
BT = NPT BS = sweat
SIzE (DN) DIMENSIONS WEIGHT
A
in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in mm in mm in. mm lbs. kgs.
11⁄4 32 83⁄8 213 715⁄16 201 513⁄16 148 43⁄8 111 41⁄8 105 31⁄16 78 87⁄8 225 17⁄16 36 11⁄16 17 1 25 31⁄4 82 6.5 2.9
1
1
2 40 83⁄8 213 83⁄16 207 513⁄16 148 49⁄16 115 47⁄16 112 31⁄4 83 87⁄8 225 15⁄8 41 11⁄16 17 11⁄8 28 31⁄4 82 8 3.6
T As AN BT Bs BN C  D  ET ES G
2 50 9 228 9
A Watts Water Technologies Company
ES-N45B-L 1210 © 2012 Watts
AT = NPT AS = sweat
1
4 235 63⁄8 162 5 126 51⁄16 129 311⁄16 93 87⁄8 225 17⁄8 47 11⁄16 17 13⁄8 34 311⁄16 93 9 4.1
G
USA: Tel. (978) 688-1811 • Fax: (978) 794-1848 • www.watts.com
Canada: Tel. (905) 332-4090 • Fax: (905) 332-7068 • www.wattscanada.ca
ES - FEMALE SWEAT SOCKET DEPTH
Loading...