Please read all instructions, identify all components and read all warnings prior to beginning the installation of this product.
This product is intended to prevent catastrophic water damage in the event of a water heater leak.
Please Note: During an emergency operating condition, the temperature and pressure relief valve installed on your water heater can
discharge an excessive amount of water. It is designed to protect your home or business from the potential danger of explosion. Upon
detection of this discharged water, the FloodSafe® Water Detector Shutoff shuts off both the supply of water and the source of power
(gas, oil or electricity) to the water heater, preventing a very dangerous situation.
The FloodSafe® Water Detector Shutoff also contains an audible & visual alarm and contacts for monitored alarm systems. It is a resettable device and can be tested at any time to ensure proper operation.
Parts Included
Control UnitPower Cutout ModulePower Supply
Water Detector Pad
Important Note: Thermostat wiring is required and must be supplied by the installer.
Water DamPower Cutout Cable & Pocket Screwdriver
Planning Your Installation:
The Water Detector Shutoff should be installed within 6 to 12 inches of the water heater on the cold water inlet supply pipe.
The Control Unit, which houses the circuitry for the operation of the valve, contains interlocking connectors for the Water Detector Pad,
the Power Supply and remote alarm and the Power Cutout Module. The cables provided should not be cut or extended; therefore,
remote installation is not recommended.
The Water Detector Pad supplied with the Water Detector Shutoff should be located as close to the water heater as possible. It is not
necessary to remove the cover of the Control Unit to install the interconnecting cables.
Flooring Surface:
Dirt flooring – A metal or plastic drain pan must be installed under the water heater. Position the Water Detector Pad inside the
drain pan.
Cement floor – Install the Water Dam provided with the Water Detector Shutoff installation kit around the outside diameter of the
water heater. Position the Water Detector Pad inside the Water Dam.
Attic installation – A metal or plastic drain pan must be installed under the water heater. Position the Water Detector Pad inside
the drain pan.
Please be certain to follow all local codes when installing this device.
Installation Instructions:
a. Turn off all electrical power to the water heater.
b. Turn off the water supply to the water heater.
c. Drain water from the water heater so that the cold water supply piping is free of water.
d. Close the drain valve after draining water.
Figure 1Figure 2
1. Install the Control Unit on the cold water supply piping with the arrow on the valve pointing in the direction of fl ow, towards the
water heater. Figure 1
CAUTION: Do not apply heat directly to the valve body!
Pre-solder the adapter fi ttings that will be used to connect piping to the valve. Use caution when soldering to avoid damage
to the valve cover and internal components.
2. After soldering the piping to the fi ttings, apply thread sealant to the adapter fi ttings and thread the adapters with attached piping
into the valve body. Figure 2
3. Install and solder the piping to the supply and to the inlet of the water heater.
4. Install the Water Detector Pad under the water heater with the green circuit board down. The Water Detector Pad must lie fl at on
the fl oor or in a drain pan. Route the connecting cable to the Control Unit and insert the interlocking connector to the circuit board.
Figure 4Figure 5Figure 5a
Figure 3
Figure 6
Figure 3
Note: It is not necessary to remove the cover of the Control Unit to install the interconnecting cables. To remove an interlocking cable, use the supplied Pocket Screwdriver to depress the tab on the cable while pulling cable from its socket. Figure 4
Important: Interconnecting wires must not touch or be in close proximity to any fl ame or hot surface.
a. If no drain pan exists, install the Water Dam around the perimeter of the water heater. The Water Dam can be cut so that it fi ts
approximately 1 to 2 inches outside the diameter of the water heater and includes the area where the Temperature and Pressure
safety relief drain tube terminates.
b. Install the plastic connector supplied with the Water Dam into both ends of the Water Dam so that no gap exists between the
ends. Figure 5 and Figure 5a
5. Install the Power Cutout Module, Figure 6, to the water heater as indicated below.
Oil Fired Water Heater Installation (for Spark Ignition Water Heater Installation, see page 3)
NOTE: Be certain to disconnect the circuit breaker/fuse that supplies power to the oil burner. A warning label should be applied to the
1. Mount the Power Cutout Module Figure 10, as close to the oil burner as possible.
2. Remove the jumper from the TT terminals of the oil burner relay shown in Figure 7.
panel with a warning against restoring power while work is in process.
2
Figure 7Figure 8
T2
T1
Oil Burner
Primary
Relay
Remove Jumper to T T Terminals
R1
R2 C
NCNO
To T T terminals on Oil Burner Relay
To Control Unit
POWER CUTOUT MODULE
Electronic Control
SPARK
Before
Pilot Electrode
Assembly
Electronic Control
SPARK
After
To Power
Cutout Module
Terminal
CNO
Pilot Electrode
Assembly
R1
R2C
NCNO
To Electronic Control
To Control Unit
To Pilot Electrode
Assembly
POWER CUTOUT MODULE
NC
NO
R1
R2
T2T1
POWER
CUTOUT
MODULE
OIL BURNER
PRIMARY RELAY
TO
CONTROL
UNIT
C
Figure 9
3. Using two conductor thermostat cable (supplied by the installer) install the spade terminals to one side of the cable and fasten terminals to the other side of the cable. Connect the cable from the Power Cutout Module Terminal C (common) and NO (normally open) to
the TT terminals on the Oil burner Primary Relay as indicated in Figures 8 and 9. Install the connecting cable Figure 15 to the Power
Cutout Module terminals R1 and R2. Route the connecting cable to the Control Unit and insert the interlocking connector end to the
circuit board.
4. Proceed to Step 5 to continue installation
Figure 10
Figure 11
Figure 12
Spark Ignition Water Heater Installation (for Oil Fired Water Heater Installation, see page 2)
NOTE: Be certain to disconnect the circuit breaker/fuse that supplies power to the water heater. A warning label should be applied to
the panel with a warning against restoring power while work is in process.
1. Mount the Power Cutout Module as close to the electronic control module as possible.
2. Remove the wire from the Electronic Control “SPARK” terminal that goes to the Pilot Electrode Assembly from Electronic Control as
shown in Figure 11.
3. Using two-conductor thermostat cable, install the spade terminals to one side of the cable and then fasten terminals to the other
side of the cable. Connect the cable from the Power Cutout Module Figure 14 Terminal C (common) to the SPARK terminal of the
Electronic Control and NO (normally open) to the Pilot Electrode Assembly as indicated in Diagram 2, Figures 12 and 13. Note: We
have made every effort to provide all of the hardware required for a complete installation. However, the terminal connections used to
connect the Pilot Electrode Assembly to the Electronic Control vary by manufacturer, although we have included several connectors
used by leading manufacturers with your WDS, your specific mating connectors may not be included. If the required connector is
not included, it may be purchased locally at any electronic supply store. Install the Connecting Cable Figure 15 to the Power Cutout
Module terminals and R1 and R2, route the Connecting Cable to the Control Unit and insert the interlocking connector end to the
circuit board.
4. Proceed to Step 5 to continue installation.
Figure 13
Figure 14 Figure 15
3
Installation Continued
5. Remove the green circuit board terminal strip from the Control Unit by pulling straight out on the terminal strip. Figure 16
6. Install wiring (The wire is installer supplied. Thermostat wire is acceptable.) between the green circuit board connector and the
Power Supply, observing polarity, as shown on both the Power Supply and the control panel. [+ to + and – to –] Figure 17
Maximum run of thermostat wire; 18 gauge – 75 feet; 20 gauge – 50 feet; 22 gauge – 35 feet.
Note: If remote alarm detection is desired, connection to the alarm circuit can be made using the normally open contacts provided on
the terminal strip. These contacts are rated for 150mA. Do not exceed this amp range or damage to the Control Unit can occur.
Exceeding the current rating will void the warranty. Figure 18
IMPORTANT! – Do not insert the Power Supply into the 120 VAC outlet until the installation is complete.
Figure 16Figure 17
Figure 18
7. Insert the green circuit board connector into the Control Unit. Figure 19
8. Check the position of the valve reset located on the front of the Control Unit. The slots should indicate the valve is in the open
position. The 11 o’clock position is the open position. Figure 20 open position; Figure 21 closed position.
9. Turn on the water supply and check for leaks.
10. Insert the Power Supply into a suitable 120 VAC outlet. The status lamp on the Control Unit will be green.
IMPORTANT! – The outlet must be powered at all times; it must not be controlled by a switch.
11. Turn on the electricity to the water heater. The water heater should operate normally.
Figure 19Figure 20
Figure 21
4
Test the System Prior to Leaving the Installation:
1. Place enough water in the drain pan or Water Dam to actuate the Water Detector Shutoff.
2. Upon actuation, the following should take place:
a. Power to the water heater should shut off immediately.
b. The water supply to the water heater should shut off immediately. The valve position indicator on the Control Unit should indi-
cate that the valve is in the closed position.
c. The green indicating lamp on the Control Unit should turn to red.
An audible alarm should sound, and if connected, the remote alarm should be actuated. The audible alarm can be silenced by
pressing the black silence button on the Control Unit.
3. If all of the above functions take place, the unit can be reset.
To Reset the Control Unit:
1. Remove the Water Detector Pad from the drain pan or Water Dam and wipe the moisture from the green circuit board.
2. Wipe any water from the drain pan or Water Dam.
3. Reposition the Water Detector Pad on the floor or in the drain pan.
4. Turn the valve position indicator on the Control Unit to the open position.
The Water Detector Shutoff is now set to operate in the event of water heater leakage.
Note:
Please note that the Floodsafe® Water Detector Shutoff will not operate as intended without power. A battery back up is available
to allow operation for 36 to 48 hours in the event of a power outage.
Power
Supply
Water Dam
Power Cutout
Module
Detector Pad
Water
Control
Unit
Power
Supply
Control
Unit
Power Cutout
Module
Water
Detector Pad
Water Dam
Oil FiredSpark Ignition
5
Loading...
+ 11 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.