Watts LFN170 CSUT User Manual [en, es, fr]

ENGLISH INSTRUCTIONS
Series N170-M3 and LFN170-M3
Hot Water Master Tempering Valves
WARNING
!
You are required to thoroughly read all installation instructions and product safety information before beginning the installation of this prod­uct. FAILURE TO COMPLY WITH PROPER INSTALLATION AND
MAINTENANCE INSTRUCTIONS COULD RESULT IN PRODUCT FAILURE WHICH CAN CAUSE PROPERTY DAMAGE, PERSONAL INJURY AND/OR DEATH. Watts is not responsible for damages result-
ing from improper installation and/or maintenance.
Local building or plumbing codes may require modifications to the information provided. You are required to consult the local building and plumbing codes prior to installation. If this information is not consistent with local building or plumbing codes, the local codes should be fol­lowed.
Installation Instructions
Installation should be in accordance with acceptable plumbing prac­tices. Flush all pipes thoroughly before installation. Installation and field adjustment are responsibility of the installer and shall be carried out per following installation instructions.
1. Valves are to be installed as close to building inlet supply as possible to prevent/minimize pressure fluctuations.
2. Valve body can be installed in multiple positions, see below. Make sure that the union nuts and tailpieces are tightened securely if you are using checkstops.
3. Connect inlets and outlet and check for leaks.
!
4. CAUTION: When N170-M3 or LFN170-M3 supplies tempered water to self-closing and/or solenoid valves, provide a shock absorb­er on the discharge line.
5. Before use, check discharge temperature. Reset if necessary
Temperature Adjustment
1. Turn off recirculation pump (if one is in the system).
2. Open enough fixtures to meet the minimum flow requirement of the valve.
3. Loosen the lock nut. Turn temperature adjustment screw clockwise to decrease or counterclockwise to increase outlet temperature.
NOTE: Please allow valve temperature to stabilize in before making your next adjustment. Watts recommends that a temperature gauge is installed on the tempered line and be checked at least monthly under normal flow conditions. The gauge must be installed at least 6 ft. away from the tempering valve.
4. When desired temperature is set, tighten the lock nut. Turn recircu­lation pump back on. Close open fixtures.
FRONT OUTLET
WARNING
!
Watts Hot Water Master Tempering Valves cannot be used for tempering water temperature at fixtures. Severe bodily injury (i.e., scalding or chilling) and/or death may result depending upon system water pressure changes and/or supply water temperature changes. ASSE standard 1016, 1069 or 1070 listed devices such as Watts Series MMV, LFMMV, USG, LFUSG, L111 or LFL111 valves should be used at fixtures to prevent possible injury.
The Watts Hot Water Tempering Valves are designed to be installed at or near the boiler or water heater. They are not designed to compensate for system pressure fluctuations and should not be used where ASSE standard 1016, 1069 or 1070 devices are required. These Watts valves should never be used to provide “anti-scald” or “anti-chill” service.
WARNING
!
Need for Periodic Inspection: Periodic inspection by a licensed contractor is recommended. Corrosive water conditions, tempera­tures over 210°F, unauthorized adjustments or repair could render the valve ineffective for service intended. Regular checking and cleaning of the valves internal components and checkstops helps to assure maximum life and proper product function. Frequency of cleaning depends upon local water conditions.
LFN170-M3
BACK OUTLET TOP OUTLET
IS-N170-M3
N170-M3 CSUT
Basic Installation
To Fixture
To Model
L111, LFL111, MMV or LFMMV
From Cold Supply
Thermometer
Tempered 140°F *†
ATTENTION INSTALLER: After installation,
please leave this Instruction Sheet for
occupant’s information.
Temperature
Adjusting Screw
Lock Nut
Cold
† N170-M3
or LFN170-M3
Cold
Tempering
Valve
Shutoff Valves (on both hot and cold inlets)
Minimum Flow Requirements to
for N170-M3 or LFN170-M3 Series
Valve Size gpm
3
⁄4" thru 2" (20-50mm) 3 to 7 (11 to 26.5 lpm)
Check Valves
(on both hot and
cold inlets)
Maintain Set Temperature
Storage
Tank
180°F
8" to 12"
Drain
CSA/ASME T&P Valve
ASME Pressure
Relief Valve
Water Heater
or
Hot Water Boiler
Hot
Water
NOTE: Heat trap is recommended.
† Valves listed to ASSE Standard 1016, 1069 or 1070, such as the Watts L111, LFL111, USG, LFUSG, MMV, or LFMMV should be used at point of delivery.
Specifications
• Maximum Operating Pressure ............................. 125 psig (861 kPa)
• Maximum Hot Water Temperature .......................... 200°F (93°C)
• Minimum Hot Water Supply Temperature ..................... 5°F (3°C) Above Set-Point*
• Temperature Adjustment Range** ........................... 90 - 180°F (32 - 82°C)
• Hot Water Inlet Temperature Range ......................... 120 - 180°F (42 - 82°C)
• Cold Water Inlet Temperature Range ........................ 40 - 80°F (4 - 27°C)
• Listing ................................................ ASSE 1017, IAPMO CUPC
• Approval Standards ..................................... ASSE 1017, CSA B125.3
* With Equal Pressure ** Low limit can not be less than the cold water temperature. For best operation, hot water should be at least 5°F (3°C)
above desire set point.
Actuator
Cold
Water
2
Capacity
Model Inlet / Outlet (NPT)
3
/4" N170-M3
3
/4" LFN170-M3
1" N170-M3
1" LFN170-M3
"
1
1
/4
N170-M3
"
1
1
/4
LFN170-M3
"
1
1
/2
N170-M3
"
1
1
/2
LFN170-M3
2" N170-M3
2" LFN170-M3
Model Inlet / Outlet (NPT)
3
/4" N170-M3 CSUT
3
/4" LFN170-M3 CSUT
1" N170-M3 CSUT
1" LFN170-M3 CSUT
"
1
1
/4
N170-M3 CSUT
"
1
1
/4
LF170-M3 CSUT
"
1
1
/2
N170-M3 CSUT
"
1
1
/2
LFN170-M3 CSUT
2" N170-M3 CSUT
2" LFN170-M3 CSUT
3
/4 x 3/4"
1 x 1"
1
1-
/4 x 1-1/4"
1
1-
/2 x 1-1/2"
2 x 1-
3
/4 x 3/4"
3
/4 x 1"
1
1-
/4 x 1-1/4"
1
1-
/4 x 1-1/2"
1
1-
1
/2 x 2"
/4 x 2"
Flow Capacity at 50-50 mixed Less Checkstops
Pressure Drop Across Valve
Min. Flow
to ASSE 1017
3 gpm
11 lpm 57 lpm 79 lpm 114 lpm 140 lpm 170 lpm 197 lpm
4 gpm
15 lpm 87 lpm 121 lpm 170 lpm 212 lpm 257 lpm 299 lpm
4 gpm
15 lpm 121 lpm 170 lpm 238 lpm 288 lpm 360 lpm 416 lpm
5 gpm
19 lpm 134 lpm 185 lpm 265 lpm 326 lpm 397 lpm 458 lpm
7 gpm
26 lpm 159 lpm 223 lpm 314 lpm 386 lpm 473 lpm 545 lpm
C
V
6.70
10.13
14.16
15.65
18.63
5psi 10psi 20psi 30psi 45psi 60psi
(34 kPa) (69 kPa) (138 kPa) (207 kPa) (310 kPa) (414 kPa)
15 gpm 21 gpm 30 gpm 37 gpm 45 gpm 52 gpm
23 gpm 32 gpm 45 gpm 56 gpm 68 gpm 79 gpm
32 gpm 45 gpm 63 gpm 76 gpm 95 gpm 110 gpm
35 gpm 49 gpm 70 gpm 86 gpm 105 gpm 121 gpm
42 gpm 59 gpm 83 gpm 102 gpm 125 gpm 144 gpm
Flow Capacity at 50-50 mixed with Checkstops
Pressure Drop Across Valve
Min. Flow
to ASSE 1017
3 gpm
11 lpm 53 lpm 76 lpm 106 lpm 129 lpm 159 lpm 182 lpm
4 gpm
15 lpm 79 lpm 114 lpm 163 lpm 197 lpm 242 lpm 280 lpm
4 gpm
15 lpm 114 lpm 159 lpm 227 lpm 280 lpm 341 lpm 394 lpm
5 gpm
19 lpm 125 lpm 128 lpm 254 lpm 310 lpm 379 lpm 435 lpm
7 gpm
26 lpm 151 lpm 216 lpm 303 lpm 371 lpm 454 lpm 526 lpm
C
V
6.26
9.54
13.42
14.90
17.89
5psi 10psi 20psi 30psi 45psi 60psi
(34 kPa) (69 kPa) (138 kPa) (207 kPa) (310 kPa) (414 kPa)
14 gpm 20 gpm 28 gpm 34 gpm 42 gpm 48 gpm
21 gpm 30 gpm 43 gpm 52 gpm 64 gpm 74 gpm
30 gpm 42 gpm 60 gpm 74 gpm 90 gpm 104 gpm
33 gpm 47 gpm 67 gpm 82 gpm 100 gpm 115 gpm
40 gpm 57 gpm 80 gpm 98 gpm 120 gpm 139 gpm
Series N170-M3 and LFN170-M3 Hot Water Master Tempering Valves
Installation Instructions for A Two Temperature Recirculating Hot Water Supply System
Recirculation System 1
WATTS CSA/ASME Temperature & Pressure Relief Valve
Hot Water Supply
DrainTube
Water
Heater
or
Boiler
WATTS
Series N170-M3†
or LFN170-M3
Thermometer
WATTS Ball Valve
Series
MMV
WATTS
Check Valves
Tempered Water Supply
To Fixture
Cold Water Supply
To MMV, USG-B, L111 or
LFL111 then to fixtures
Cold Water
Supply
WATTS Check Valves
Aquastat
Circulator
Recirculation Loop
3
Series N170-M3 and LFN170-M3 Hot Water Master Tempering Valves Continued
Installation Instructions for A Two Temperature Recirculating Hot Water Supply System
IMPORTANT: Valve must be installed trapped as shown. (See reverse side for rec-
ommended minimum gpm flow requirements.)
The sketch illustrates a two-temperature (180°F and 140°F) hot water supply system with a Series N170-M3 and LFN170-M3 valve and recirculating line for maintaining approxi- mate fixture water temperatures in the mains. Because very little hot water is required to main­tain the low temperature in the mains (usually 140°F), a relatively small capacity recirculator can generally be specified. The minimum flow requirements must be maintained between 3-7 gpm. Providing the heat loss from the piping is not too great (long runs of hot water piping should be insulated) standard circulators are usually adequate. However, each installation should be evaluated for its own recirculation requirements of gpm and pipe resistance.
NOTE: Recirculating control aquastat must be set at least 5°F to 10°F lower than the temperature setting of the Series N170-M3 or LFN170-M3 valve, otherwise the recirculator will run continually. Aquastat must be used to main­tain water to fixtures at a desired temperature and to eliminate temperature override during no draw periods.
† Valves listed to ASSE Standard 1016, 1069 or
1070 such as the Watts L111, LFL111, USG, LFUSG, MMV or LFMMV should be used at point of delivery.
Recirculation System 2
Typical Two Temperature System with High
Temperature Hot Water Recirculation Line
To MMV, LFMMV, USG, LFUSG, L111 or LFL111 then to
fixtures
Thermometer
Aquastat
WATTS
Circulator
Hot Water Return
Aquastat
Circulator
Check Valves
Cold Water Supply
Watts Series
N170-M3†
WATTS Check
Valve
To Fixture
Cold Water Supply
MMV
High Temperature Hot Water
Tempered Water 140°
Shut
Off
Valve
WATTS Series 600
Check Valves
Note: Water Heaters may be direct or indirect fired.
8”-12”
HeatTrap†
Water Heater
or Boiler
WATTS CSA/ASME Temperature & Pressure Relief Valve
Drain Tube
Limited Warranty: Watts Regulator Co. (the “Company”) warrants each product to be free from defects in material and workmanship under normal usage for a period of one year from the date of
original shipment. In the event of such defects within the warranty period, the Company will, at its option, replace or recondition the product without charge.
THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY WARRANTY GIVEN BY THE COMPANY WITH RESPECT TO THE PRODUCT. THE COMPANY MAKES NO OTHER WARRANTIES, EXPRESS OR IMPLIED. THE COMPANY HEREBY SPECIFICALLY DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
The remedy described in the first paragraph of this warranty shall constitute the sole and exclusive remedy for breach of warranty, and the Company shall not be responsible for any incidental, special or consequential damages, including without limitation, lost profits or the cost of repairing or replacing other property which is damaged if this product does not work properly, other costs resulting from labor charges, delays, vandalism, negligence, fouling caused by foreign material, damage from adverse water conditions, chemical, or any other circumstances over which the Company has no control. This warranty shall be invalidated by any abuse, misuse, misapplication, improper installation or improper maintenance or alteration of the product. Some States do not allow limitations on how long an implied warranty lasts, and some States do not allow the exclusion or limitation of incidental or consequential damages. Therefore the above limitations may not apply to you. This Limited Warranty gives you specific legal rights, and you may have other rights that vary from State to State. You should consult applicable state laws to determine your rights. SO FAR AS IS CONSISTENT WITH APPLICABLE STATE LAW, ANY IMPLIED WARRANTIES THAT MAY NOT BE DISCLAIMED, INCLUDING THE IMPLIED WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED IN DURATION TO ONE YEAR FROM THE DATE OF ORIGINAL SHIPMENT.
A Watts Water Technologies Company
USA: Tel: (978) 688-1811 • Fax: (978) 794-1848 • www.watts.com
Canada: Tel: (905) 332-4090 • Fax: (905) 332-7068 • www.wattscanada.ca
IS-N170-M3 1209 EDP# 2915044 © 2012 Watts
Loading...
+ 8 hidden pages