You are required to thoroughly read all installation instructions and
product safety information before beginning the installation of this product. FAILURE TO COMPLY WITH PROPER INSTALLATION AND
MAINTENANCE INSTRUCTIONS COULD RESULT IN PRODUCT
FAILURE WHICH CAN CAUSE PROPERTY DAMAGE, PERSONAL
INJURY AND/OR DEATH. Watts is not responsible for damages result-
ing from improper installation and/or maintenance.
Local building or plumbing codes may require modifications to the
information provided. You are required to consult the local building and
plumbing codes prior to installation. If this information is not consistent
with local building or plumbing codes, the local codes should be followed.
Installation Instructions
Installation should be in accordance with acceptable plumbing practices. Flush all pipes thoroughly before installation. Installation and field
adjustment are responsibility of the installer and shall be carried out per
following installation instructions.
1. Valves are to be installed as close to building inlet supply as possible
to prevent/minimize pressure fluctuations.
2. Valve body can be installed in multiple positions, see below. Make
sure that the union nuts and tailpieces are tightened securely if you
are using checkstops.
3. Connect inlets and outlet and check for leaks.
!
4. CAUTION: When N170-M3 or LFN170-M3 supplies tempered
water to self-closing and/or solenoid valves, provide a shock absorber on the discharge line.
5. Before use, check discharge temperature. Reset if necessary
Temperature Adjustment
1. Turn off recirculation pump (if one is in the system).
2. Open enough fixtures to meet the minimum flow requirement of the
valve.
3. Loosen the lock nut. Turn temperature adjustment screw clockwise
to decrease or counterclockwise to increase outlet temperature.
NOTE: Please allow valve temperature to stabilize in before making
your next adjustment. Watts recommends that a temperature gauge is
installed on the tempered line and be checked at least monthly under
normal flow conditions. The gauge must be installed at least 6 ft. away
from the tempering valve.
4. When desired temperature is set, tighten the lock nut. Turn recirculation pump back on. Close open fixtures.
FRONT OUTLET
WARNING
!
Watts Hot Water Master Tempering Valves cannot be used for
tempering water temperature at fixtures. Severe bodily injury (i.e.,
scalding or chilling) and/or death may result depending upon system
water pressure changes and/or supply water temperature changes.
ASSE standard 1016, 1069 or 1070 listed devices such as Watts
Series MMV, LFMMV, USG, LFUSG, L111 or LFL111 valves should be
used at fixtures to prevent possible injury.
The Watts Hot Water Tempering Valves are designed to be installed at
or near the boiler or water heater. They are not designed to compensate
for system pressure fluctuations and should not be used where ASSE
standard 1016, 1069 or 1070 devices are required. These Watts valves
should never be used to provide “anti-scald” or “anti-chill” service.
WARNING
!
Need for Periodic Inspection: Periodic inspection by a licensed
contractor is recommended. Corrosive water conditions, temperatures over 210°F, unauthorized adjustments or repair could render
the valve ineffective for service intended. Regular checking and
cleaning of the valves internal components and checkstops helps
to assure maximum life and proper product function. Frequency of
cleaning depends upon local water conditions.
LFN170-M3
BACK OUTLETTOP OUTLET
IS-N170-M3
N170-M3 CSUT
Basic Installation
To Fixture
To Model
L111, LFL111, MMV or LFMMV
From Cold Supply
Thermometer
Tempered 140°F *†
ATTENTION INSTALLER: After installation,
please leave this Instruction Sheet for
occupant’s information.
Temperature
Adjusting Screw
Lock Nut
Cold
† N170-M3
or LFN170-M3
Cold
Tempering
Valve
Shutoff Valves
(on both hot
and cold inlets)
Minimum Flow Requirements to
for N170-M3 or LFN170-M3 Series
Valve Size gpm
3
⁄4" thru 2" (20-50mm) 3 to 7 (11 to 26.5 lpm)
Check Valves
(on both hot and
cold inlets)
Maintain Set Temperature
Storage
Tank
180°F
8" to 12"
Drain
CSA/ASME T&P Valve
ASME Pressure
Relief Valve
Water Heater
or
Hot Water Boiler
Hot
Water
NOTE: Heat trap is recommended.
† Valves listed to ASSE Standard 1016, 1069
or 1070, such as the Watts L111, LFL111,
USG, LFUSG, MMV, or LFMMV should be
used at point of delivery.
Specifications
• Maximum Operating Pressure ............................. 125 psig (861 kPa)
• Maximum Hot Water Temperature .......................... 200°F (93°C)
• Minimum Hot Water Supply Temperature ..................... 5°F (3°C) Above Set-Point*
Series N170-M3 and LFN170-M3
Hot Water Master Tempering Valves
Installation Instructions for
A Two Temperature Recirculating Hot Water Supply System
Recirculation System 1
WATTS CSA/ASME
Temperature &
Pressure Relief Valve
Hot Water Supply
DrainTube
Water
Heater
or
Boiler
WATTS
Series N170-M3†
or LFN170-M3
Thermometer
WATTS
Ball
Valve
Series
MMV
WATTS
Check
Valves
Tempered Water Supply
To Fixture
Cold Water Supply
To MMV, USG-B, L111 or
LFL111 then to fixtures
Cold Water
Supply
WATTS
Check
Valves
Aquastat
Circulator
Recirculation Loop
3
Series N170-M3 and LFN170-M3
Hot Water Master Tempering Valves Continued
Installation Instructions for
A Two Temperature Recirculating Hot Water Supply System
IMPORTANT: Valve must be installed
trapped as shown. (See reverse side for rec-
ommended minimum gpm flow requirements.)
The sketch illustrates a two-temperature (180°F
and 140°F) hot water supply system with
a Series N170-M3 and LFN170-M3 valve
and recirculating line for maintaining approxi-mate fixture water temperatures in the mains.
Because very little hot water is required to maintain the low temperature in the mains (usually
140°F), a relatively small capacity recirculator
can generally be specified. The minimum flow
requirements must be maintained between 3-7
gpm. Providing the heat loss from the piping
is not too great (long runs of hot water piping
should be insulated) standard circulators are
usually adequate. However, each installation
should be evaluated for its own recirculation
requirements of gpm and pipe resistance.
NOTE: Recirculating control aquastat must
be set at least 5°F to 10°F lower than the
temperature setting of the Series N170-M3 or
LFN170-M3 valve, otherwise the recirculator will
run continually. Aquastat must be used to maintain water to fixtures at a desired temperature
and to eliminate temperature override during no
draw periods.
† Valves listed to ASSE Standard 1016, 1069 or
1070 such as the Watts L111, LFL111, USG,
LFUSG, MMV or LFMMV should be used at
point of delivery.
Recirculation System 2
Typical Two Temperature System with High
Temperature Hot Water Recirculation Line
To MMV, LFMMV,
USG, LFUSG, L111
or LFL111 then to
fixtures
Thermometer
Aquastat
WATTS
Circulator
Hot Water Return
Aquastat
Circulator
Check
Valves
Cold Water Supply
Watts
Series
N170-M3†
WATTS Check
Valve
To Fixture
Cold Water Supply
MMV
High
Temperature
Hot Water
Tempered Water 140°
Shut
Off
Valve
WATTS Series 600
Check Valves
Note: Water Heaters may be direct or indirect fired.
8”-12”
HeatTrap†
Water
Heater
or Boiler
WATTS CSA/ASME
Temperature &
Pressure Relief Valve
Drain Tube
Limited Warranty: Watts Regulator Co. (the “Company”) warrants each product to be free from defects in material and workmanship under normal usage for a period of one year from the date of
original shipment. In the event of such defects within the warranty period, the Company will, at its option, replace or recondition the product without charge.
THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY WARRANTY GIVEN BY THE COMPANY WITH RESPECT TO THE PRODUCT. THE COMPANY MAKES NO OTHER
WARRANTIES, EXPRESS OR IMPLIED. THE COMPANY HEREBY SPECIFICALLY DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE IMPLIED
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
The remedy described in the first paragraph of this warranty shall constitute the sole and exclusive remedy for breach of warranty, and the Company shall not be responsible for any incidental, special
or consequential damages, including without limitation, lost profits or the cost of repairing or replacing other property which is damaged if this product does not work properly, other costs resulting
from labor charges, delays, vandalism, negligence, fouling caused by foreign material, damage from adverse water conditions, chemical, or any other circumstances over which the Company has no
control. This warranty shall be invalidated by any abuse, misuse, misapplication, improper installation or improper maintenance or alteration of the product.
Some States do not allow limitations on how long an implied warranty lasts, and some States do not allow the exclusion or limitation of incidental or consequential damages. Therefore the above
limitations may not apply to you. This Limited Warranty gives you specific legal rights, and you may have other rights that vary from State to State. You should consult applicable state laws to
determine your rights. SO FAR AS IS CONSISTENT WITH APPLICABLE STATE LAW, ANY IMPLIED WARRANTIES THAT MAY NOT BE DISCLAIMED, INCLUDING THE IMPLIED WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED IN DURATION TO ONE YEAR FROM THE DATE OF ORIGINAL SHIPMENT.