For Residential, Commercial and Institutional Applications
ES-LFMMV
Job Name
Job Location
Engineer
Approval
––––––––––––––––––––––––––––––––––––––––––––
––––––––––––––––––––––––––––––––––––––––––
–––––––––––––––––––––––––––––––––––––––––––––
–––––––––––––––––––––––––––––––––––––––––––––
LEAD FREE
*
Contractor
Approval
Contractor’s P.O. No.
Representative
Triple Listed!
ASSE 1017,
ASSE 1069 & ASSE 1070
Series LFMMV
Thermostatic Mixing Valves
Sizes: 1⁄2" – 1" (15 – 25mm)
Series LFMMV Thermostatic Mixing Valves maintain and limit mixed
hot water to a desired, selectable temperature. The LFMMV series
can be set to any temperature between 80°F and 120°F with flow
rates as low as 0.5 gpm and as high as 12 gpm (refer to capacity chart on back). This mixing valve series is listed under ASSE
1017 for valves used in hot water source applications, ASSE 1069
for single-pipe, tempered water applications and ASSE 1070 for
valves used in individual or multiple fixture applications and also
listed IAPMO cUPC. The LFMMVs feature Lead Free* construction
to comply with Lead Free* installation requirements.
The LFMMV-M1 uses a double throttling design to control both the
hot and cold water supply to the mixed outlet. The superior flow
characteristics of this valve provide accurate temperature control
(±3°F) with low pressure drop across the rated flow range. As an
added feature, the LFMMV-M1 series incorporates integral inlet filter
washers and check valves in both the hot and cold water inlets to
protect against cross flow.
The LFMMV-M1 is available with either union thread (-UT), union solder
(-US), CPVC (-CPVC ) Quick-Connect (-QC) or PEX (-PEX) end connectors.
Features
• Lead Free* cast copper silicon alloy body construction
• Solid wax hydraulic principle thermostat assures dependable
mixing of hot and cold water
• Thermostat controls both hot and cold water
• Solder, threaded, PEX or CPVC, Quick-Connect end connection
models available
• Adjustment cap with locking feature
• ASSE 1017 listed
• ASSE 1069 listed
• ASSE 1070 listed
• IAPMO cUPC listed
• Integral filter washers and check v alves
Specifications
A Thermostatic Mixing Valve shall be installed on the hot water supply
to fixture. The valve shall be ASSE 1017, ASSE 1069, ASSE 1070 and
IAPMO cUPC listed. It shall have a Lead Free* cast copper silicon alloy
body. Lead Free* thermostatic valves shall comply with state codes and
standards, where applicable, requiring reduced lead content. The valve
shall include integral filter washers and check valves and an adjustment
cap with locking feature. The valve shall be provided with solder (-US),
threaded (-UT), CPVC, (-CPVC) Quick Connect (-QC) or PEX (-PEX)
union connections. The valve shall be a Watts Series LFMMV-M1.
* The wetted surface of this product contacted by consumable water
contains less than 0.25% of lead by weight.
––––––––––––––––––––––––––––––––––––––––––––
––––––––––––––––––––––––––––––––––––––––––––––
–––––––––––––––––––––––––––––––––––
–––––––––––––––––––––––––––––––––––––––––
LFMMV-QC-M1
LFMMV-US-M1
Applications
The LFMMV-M1 Thermostatic Mixing Valves are ideal for supplying sinks, baths, showers or lavatories with tempered water. The
LFMMV-M1 valves can be used in residential, commercial and
institutional environments. These thermostatically modulated mixing
valves can be used anywhere preset water temperature is required
for point-of-use installations such as in homes, schools, restaurants,
hospitals, beauty salons, and public restrooms. The LFMMV-M1 is
provided with an adjustment cap that includes a locking feature.
The LFMMV-M1 valves should be used prior to the fixture to reduce
the hot water supply to a safe temperature.
!
WARNING
When used in an ASSE 1017 application at the hot water source,
the Watts Thermostatic Mixing Valve Series LFMMV cannot
be used by itself to control final temperature at fixtures where
ASSE Standard 1016 or ASSE Standard 1070 listed devices are
required. Such use may result in severe bodily injury (i.e. scalding or chilling) and/or death. ASSE Standard 1016, ASSE 1069
or ASSE Standard 1070 listed devices, such as Watts Series
LFUSG, LFL111 or LFMMV, should be used at point-of-use to
prevent possible injury. Consult all product manuals, and instruction guides before installing any referenced product.
Recirculation systems should recirculate water at temperatures
over 140°F to reduce the risk of bacterial growth in the piping.
This valve should not be used at the hot water source in recirculation systems.
!
WARNING
Water temperatures in excess 110ºF (43ºC) are dangerous and
may cause scalding, severe injury or death! This valve can be
adjusted to deliver water at temperatures exceeding 110ºF
(43ºC). Consequently, when used in an ASSE 1016, ASSE 1069
or ASSE 1070 application, the installer must check the mixed
water outlet temperature at the point of use and adjust the Watts
Thermostatic Mixing Valve Series LFMMV to ensure delivery
of water at a safe temperature not exceeding 110ºF (43ºC).
Mechanical valves are not fail-safe. Due to the effects of various
water conditions, periodic verification of outlet water temperature
is required.
Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.
Materials
Body: Lead Free* cast copper silicon alloy
Disc: Stainless steel
Thermostat Assembly: Copper
O-rings: Buna-N; EPDM
Pistons: Polysulfone (PSU)
Springs: Stainless Steel
Pressure –– Temperature –– Flow Rate
Minimum Supply Pressure Static: 30psi (207 kPa)
Inlet Temperatures: hot inlet, 120°F – 180°F (49°C – 82°C),
cold inlet, 39°F – 85°F (4°C – 29°C)
Hot Water Inlet to Outlet Differential Temperature: 5°F (3°C)
above set point
Temperature Out: Field range: 80°F – 120°F (27°C – 49°C), adjust-
able. Accurate within ±3°F (1.7°C)
Maximum Temperature: 200°F (93°C)
Maximum Pressure: 150psi (1034 kPa)
Minimum Flow: 0.5 gpm (1.9 lpm) @ 0.8psi (0.55 kPa)
Maximum Flow: 20 gpm (76 lpm) @ 125psi (862 kPa)
†
†
Maximum Pressure Differential between Hot & Cold Water Supplies:
25%
Listing: ASSE 1017, ASSE 1069, ASSE 1070 and IAPMO cUPC
†
When tested in accordance with ASSE 1017, ASSE 1069 & ASSE 1070.
Dimensions — Weights
A
Capacity**
kpa psi
345 50
276 40
207 30
138 20
Pressure Drop
69 10
0
0 2 4 6 8 10 12 14 gpm
7.6 15 23 30 38 46 53 lpm
Flow curves are for reference. Actual flows may vary
depending on system temperatures and/or pressures.
**Flow curve with integral inlet filters and check valves
Basic Construction
LOCKING
ADJUSTMENT CAP
ADAPTER
O-RING
CHECK MODULE
BODY
TAILPIECE
INLET
FILTER
WASHER
UNION NUT
FIBER WASHER
Flow
BUTTON HEAD SCREW
STEM ASSEMBLY
BONNET ASSEMBLY
O-RING
SPRING
THERMOSTAT
FUNNEL
FILTER WASHER
O-RING
PLUNGER
SEAT
Hot
Water
Inlet
B
Cold
Water
Inlet
THREAD
(UT)
SWEAT
(US)
CPVCPEX
QUICK-CONNECT
QC
C
Mixed Outlet
SIZE (DN) MODEL DIMENSIONS WEIGHT
A B C D
in. mm in. mm in. mm. in. mm in. mm lbs. kg.
1⁄2 15 47⁄8 124 57⁄16 137 33⁄16 80 5⁄8 16 1.8 0.8
3
⁄4 20 MMV-UT-M1 47⁄8 124 57⁄16 137 33⁄16 80 5⁄8 16 2.4 1.1
1 25 5
1
⁄2 15 413⁄16 123 53⁄8 137 31⁄8 80 5⁄8 15 1.7 0.8
3
⁄4 20 MMV-US-M1 55⁄16 135 55⁄8 143 33⁄8 86 7⁄8 22 2.3 1.0
1 25 5
1
⁄2 15 51⁄4 133 59⁄16 142 35⁄16 85 13⁄16 21 1.8 0.8
3
⁄4 20 MMV-PEX-M1 51⁄2 140 511⁄16 145 37⁄16 88 15⁄16 24 2.5 1.1
1 25 5
1
⁄2 15 43⁄4 121 55⁄16 136 31⁄16 79 9⁄16 14 1.6 0.7
3
⁄4 20 MMV-CPVC-M1 51⁄4 133 59⁄16 142 35⁄16 85 13⁄16 21 2.2 1.0
1 25 5
1
⁄2 15 65⁄8 168 61⁄4 159
3
⁄4 20 615⁄16 177 67⁄16 163 43⁄16 106 111⁄16 42 2.8 1.3
1 25 7
LFMMV-UT-M1
LFMMV-US-M1
LFMMV-PEX- M1
LFMMV-CPVC-M1
LFMMV-QC-M1
5
⁄16 135 55⁄8 143 33⁄8 86 3⁄4 20 3.0 1.4
13
⁄16 148 57⁄8 149 35⁄8 92 11⁄8 28 2.9 1.3
7
⁄8 149 57⁄8 150 35⁄8 93 11⁄8 29 3.1 1.4
11
⁄16 144 513⁄16 147 39⁄16 90 1 26 2.6 1.2
1
⁄8 181 61⁄2 165 41⁄4 108 13⁄4 44 3.5 1.6
D
D
4 102 11⁄2 38 2.1 0.9
D
D
D
A Watts Water Technologies Company
USA: Tel: (978) 688-1811 • Fax: (978) 794-1848 • www.watts.com
Canada: Tel: (905) 332-4090 • Fax: (905) 332-7068 • www.watts.ca
ES-LFMMV 1324 © 2013 Watts