• Throttles to reduce high upstream pressure to
constant lower downstream pressure
P/L
(AOS)
3
X
• Reducing setpoint is adjustable
2
Standard Components
1 – Main Valve (Single Chamber)
2 – Pressure Reducing Control
3 – Fixed Orifice
Options & Accessories
Y/FC
FLOW
CLOSES VALVE
OPENS VALVE
XX
1
○ X – Isolation Cocks○ FC – Flo-Clean Strainer ○ Y – Y-Strainer (Replaces Flo-Clean)○ ACS – Adjustable Closing Speed
(Replaces Fixed Orice)
○ AOS – Adjustable Opening Speed○ P – Position Indicator○ L – Limit Switch
(2)
(1)
(3)
(3)
(1)
Standard 3" & Smaller
(2)
Standard 4" & Larger
(3)
Optional All Sizes
(2)
(3)
(1)
Operations
The Watts ACV Pressure Reducing Control Valve is designed to automatically reduce a uctuating higher
upstream pressure to a constant lower downstream pressure regardless of varying ow rates. It is controlled by a normally open, pressure reducing pilot designed to: 1) Open (allowing uid out of the main
valve cover chamber) when downstream pressure is below the adjustable setpoint, and 2) Close (allowing
uid to ll the main valve cover chamber) when downstream pressure is above the adjustable setpoint. A
decrease in downstream pressure causes the valve to modulate toward an open position, raising down-
stream pressure. An increase in downstream pressure causes the valve to modulate toward a closed
position, lowering downstream pressure.
*The wetted surface of this product contacted by consumable
water contains less than 0.25% of lead by weight.
Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.
Maximum Continuous (GPM)9513021030048580018503100500070008500111 0 0
Maximum Intermittent (GPM)11 91612653905901000230040006250890010800 14100
Minimum Continuous (GPM)
Maximum continuous ow based on velocity of 20 ft. per second.
Maximum intermittent ow based on velocity of 25 ft. per second.
Minimum continuous ow based on velocity of 1 ft. per second.
NOTE: The above chart is a suggested guide. Inlet pressure, outlet pressure, minumum, normal and maximum ow rates should
be considered for speci c valve sizing. Contact Watts ACV for details.
Cavitation Chart
After selecting the valve size, locate inlet and outlet pressures on this chart. If the intersection point falls
in the shaded area, cavitation can occur. Operation of valves continually in the cavitation zone should be
avoided. Consult Watts ACV for alternatives.
LFM1115 (Angle)
INLET PRESSURE - PSI
300
280
260
240
220
200
180
160
140
120
100
80
60
CAVITATION ZONE
40
20
010 20405060708090
30
OUTLET PRESSURE - PSI
130 140120110100
3
Page 4
Mustang series
Cross-Sectional Detail
Main Valve
LFM115 (Globe)
LFM1115 (Angle)
1
2
3
4
5
6
7
10
11
12
13
14
15
16
8
9
17
ITEMDESCRIPTIONMATERIAL
1CoverASTM A536 65-45-12 Epoxy Coated Ductile Iron
2Cover BearingASTM A276 304 Stainless Steel
3Shaft / StemASTM A276 304 Stainless Steel
4StudASTM A570 Gr.33 Zinc Plated Steel
5Cover NutASTM A570 Gr.33 Zinc Plated Steel
6Diaphragm*Buna-N (Nitrile)
7Body ASTM A536 65-45-12 Epoxy Coated Ductile Iron
8Seat Disc*Buna-N (Nitrile)
9Seat RingASTM A743 CF8M (316) Stainless Steel
10SpringASTM A276 302 Stainless Steel
11Stem NutASTM A276 304 Stainless Steel
12Spring Washer ASTM A276 304 Stainless Steel
13Diaphragm WasherASTM A536 65-45-12 Epoxy Coated Ductile Iron
14Disc RetainerASTM A536 65-45-12 Epoxy Coated Ductile Iron
15Spacer Washer*Fiber*
16Disc GuideASTM A743 CF8M (316) Stainless Steel
17Seat Gasket*Buna-N (Nitrile)
* Contained in Main Valve Repair Kit
4
Page 5
Mustang series
Controls and Accessories
Model LFCP-15
Pressure Reducing Pilot
LFM115 (Globe)
LFM1115 (Angle)
1
2
3
4
5
6
7
8
10
11
12
13
14
15
v
16
Front View Side View
ITEM
NUMBER
1Adjusting Screw
2Jam Nut
3Spring Housing
4Spring
5Cap Screw
6Body
7Seat
8O-Ring*
9Bottom Cap
10Spring Guide
DESCRIPTION
9
ITEM
NUMBER
11Nut
12Belleville Washer
13Diaphragm Washer
14Diaphragm *
15Yoke
16Disc and Retainer Assembly*
DESCRIPTION
* Included in Repair Kit
5
Page 6
LFM115 (Globe)
Mustang series
Installations
• Prior to installation, ush line to remove debris.
• Install valve horizontally “in line” (cover facing up), so ow arrow matches ow through the line. Avoid installing valves 6" and larger vertically. Consult factory prior to ordering if installation is other than
described.
• Install inlet and outlet isolation valves.
NOTICE
When using buttery valves, insure disc does not contact control valve. Damage or improper valve seating
may occur.
• Provide adequate clearance for valve servicing and maintenance.
• Install pressure gauges to monitor valve inlet and outlet pressure.
• If installation is subjected to very low ow or potentially static conditions, it is recommended a pressure
relief valve (1/2" minimum) be installed downstream of the Pressure Reducing Valve for additional system
protection.
Start-Up
Proper Automatic Control Valve startup requires bringing the valve into service in a controlled manner. All
adjustments to control pilots and speed controls should be made slowly, allowing the valve to respond and
the system to stabilize.
NOTICE
Control Valves should be set-up in a dynamic (flowing) condition for proper start-up. Provisions for
flow must be made to insure proper settings.
LFM1115 (Angle)
1. Close upstream and downstream valves to isolate the valve from line pressure. Release spring tension on Pressure Reducing Control by turning adjustment screw out (counterclockwise), decreas-
ing setpoint. Open all Isolation Ball Valves, if so equipped. If valve is fitted with adjustable speed
controls, turn needle(s) in (clockwise) until seated, and return out (counterclockwise) 11/2 to 21/2
turns. These are approximate settings, and should be fine tuned to suit system requirements after
pressure adjustments have been made.
2. Slowly open upstream isolation valve to allow controlled filling of the valve. Vent entrapped air by
carefully loosening control tubing or pipe plug at the highest point possible. If valve is equipped
with a Position Indicator, open Air Bleed Petcock to vent air. Water will be milky in appearance and
will begin to clear as air is vented. Carefully loosen enough cover screws on control pilot(s) to vent
entrapped air. Retighten when water vents clearly.
3. Setting Reducing Control: Slowly open downstream isolation valve. Gradually turn adjustment
screw on the Pressure Reducing Control in (clockwise) to raise downstream pressure. Allow valve
and system to stabilize. Observe inlet and outlet pressure gauges. Continue to adjust as needed,
pausing approximately every 11/2 turns, allowing valve and system to stabilize. Turning adjustment
screw clockwise raises outlet pressure. Turning adjustment screw counterclockwise lowers outlet
pressure. When desired downstream pressure is reached, tighten locknut on adjustment screw.
4. Fine tune Speed Controls to suit system requirements. Adjust Closing Speed Control (if equipped)
clockwise for slower closure, and counterclockwise for faster closure. Adjust Opening Speed Control
(if equipped) clockwise for slower opening, and counterclockwise for faster opening.
6
Page 7
LFM115 (Globe)
Mustang series
Specications
The Lead Free* Pressure Reducing Control Valve shall be a pilot operated diaphragm valve designed to
automatically reduce a uctuating higher upstream pressure to a constant lower downstream pressure regardless of varying ow rates.
The main valve shall be a hydraulically operated, single diaphragm actuated, globe or angle pattern valve.
Y-pattern valves shall not be permitted. The valve shall contain a disc and diaphragm assembly that forms
a sealed chamber below the valve cover, separating operating pressure from line pressure. The diaphragm
shall be constructed of nylon reinforced Buna-N, and shall not seal directly against the valve seat and shall
be fully supported by the valve body and cover. Rolling diaphragm construction will not be allowed and there
shall be no pistons operating the main valve or any pilot controls.
The main valve body and cover shall be Ductile Iron ASTM A536, and all internal cast components shall be
Ductile Iron or CF8M (316) Stainless Steel. All Ductile Iron components, including the body and cover, shall
be lined and coated with an NSF 61 Certied Epoxy Coating applied by the electrostatic heat fusion process.
All main valve trim and throttling components (cover bearing, valve seat and disc guide) shall be Stainless
Steel. The valve body and cover must be machined with a 360-degree locating lip to assure proper alignment.
LFM1115 (Angle)
The disc and diaphragm assembly shall contain a Buna-N synthetic rubber disc with a rectangular cross-
section that is securely retained on 3-1/2 sides by a disc retainer and disc guide. Diaphragm assemblies
utilizing bolts or cap screws for component retention will not be permitted.
The exposed portion of the seat disc shall contact the valve seat and seal drip-tight. The disc and diaphragm
assembly must be guided by two separate bearings, one installed in the valve cover and one concentrically
located within the valve seat, to avoid deection and assure positive disc-to-seat contact. Center guided
valves will not be permitted. All necessary repairs shall be made from the top of the valve while the body
remains in line.
Pilot control systems for valves 3" and smaller shall contain a Flow Clean Strainer, Fixed Orice Closing
Speed, Adjustable Opening Speed Control and Pressure Reducing Pilot. Pilot control systems for valves 4"
and larger shall contain an external Y-Strainer, Fixed Orice Closing Speed, Pressure Reducing Pilot and
Isolation Ball Valves on all body connections. All pilot control systems shall utilize copper tubing and brass
ttings regardless of valve size. The adjustment range of the pressure reducing pilot shall be 30-300 psi.
The valve shall be Watts ACV Model LFM115 (Globe) or LFM1115 (Angle) pattern Pressure Reducing Con-
trol Valve.
Other Watts ACV Pressure Reducing Control Valves
LFM115-3 / LFM1115-3 Pressure Reducing Valve with Hydraulic Check Feature
LFM115-7 / LFM1115-7 Pressure Reducing Valve with Downstream Surge Control Feature
LFM115-74 / LFM1115-74 Pressure Reducing Valve with Low Flow By-Pass
*The wetted surface of this product contacted by consumable
water contains less than 0.25% of lead by weight.