Model LF127W and LFF127W
High Capacity Water Pressure Reducing Valves
Size: 3" - 4"
Model LF127W and LFF127W High Capacity Water Pressure Reducing Valves are designed to reduce incoming water pres­sure to a sensible level to protect plumbing system components and reduce water consumption. The LF127W and LFF127W are remote control type regulators ideal for commercial and industrial applications where a regulator must reach full capacity with a minor drop in reduced pressure. These models are also suit­able for applications where close pressure regulation is required through extensive volume demand. These models are suitable for water supply pressures up to 175psi (12.1 bar) and may be adjusted from 25 – 100psi (172 – 690 kPa). All parts are quickly and easily serviceable.
The LF127W and LFF127W feature Lead Free* construction to comply with Lead Free* installation requirements.
Features
Contractor
Approval
Contractor’s P.O. No.  
Representative
––––––––––––––––––––––––––––––––––––––––––––
–––––––––––––––––––––––––––––––––––––––––––––
––––––––––––––––––––––––––––––––––––––––
(150, 178, or 200mm)
depending upon reduced
––––––––––––––––––––––––––––––––––
3" (80mm) LF127W
6", 8" or 10"
pressure range.
•  Lead Free* body construction
•  Replaceable stainless steel seat
•  Outstanding maintenance features
•  Close control of reduced pressure
•  High temperature-resisting diaphragm
•  Interchangeable diaphragm chamber
Specifications
A Water Pressure Reducing Valve shall be installed on the water service pipe near its entrance to the building where supply main pressure exceeds 60psi (413 kPa) to reduce it to 60psi (413 kPa) or lower. The water pressure reducing valve shall be constructed using Lead Free* materials. Lead Free* regulators shall comply with state codes and standards, where applicable, requiring reduced lead content. The valve shall be equipped with
3
a
8" tapping to receive equalizer piping and a 3⁄4" tapping to receive auxiliary regulator piping for low flow requirements. Valve shall be a Watts Model LF127W or LFF127W.
* The wetted surface of this product contacted by consumable
water contains less than 0.25% of lead by weight.
High temperature-resisting diaphragm.
Requirements of various pressure conditions can be quickly met by interchanging the various sizes of diaphragm cham­bers - 6", 8", 10" (150, 178, 200mm) as well as by interchanging spring.
Stainless steel stem.
Replaceable stainless steel seat.
Materials
Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with­out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.
Diaphragm chamber is easily changed by the removal of two cap screws.
Tapping provided in low pressure side of body for 4" valve to permit convenient, economical attachment of equalizer line.
Body: LF127W: Lead Free* cast copper silicon alloy
LFF127W: Iron
Seat: Replaceable stainless steel Stem: Stainless steel
Capacity
kPa psi
138 20
Pressure – Temperature
Temperature Range: 33˚F – 160˚F (0.5˚C – 71˚C) Maximum Working Pressure: 175psi (12.1 bar) Adjustable Reduced Pressure Range: 25 – 100psi
(17 – 690 kPa)
4" LFF127W
High Pressure
Piping not provided
Needle Valve
Reduced Pressure
3
4" LF223 regulator to handle low demands.
higher than LF127W or
Set 10psi (68 kPa)
LFF127W.
103 15
69 10
Pressure Drop
35 5
0 0
0 50 100 150 200 250 300 gpm
0 190 380 570 760 246 1140 lpm
Flow
NOTICE
The information contained herein is not intended to replace the full product installation and safety information available or the experience of a trained product installer. You are required to thoroughly read all installation instructions and product safety information before beginning the installation of this product.
Dimensions – Weights
SIZE DIMENSIONS WEIGHT
Connection A B C D
in. in. mm in. mm in. mm in. mm lbs. kgs.
3" threaded 8 203 161⁄8 410 22⁄5 70 23⁄8 60 40 18 3" flanged 8 203 16 4" flanged 12
1
8 308 161⁄8 410 23⁄10 59 41⁄2 114 84 38
1
8 410 37⁄10 93 33⁄4 95 42 19
B
C
D
A
A Watts Water Technologies Company
ES-LF127W 1315 © 2013 Watts
USA: Tel: (978) 688-1811 • Fax: (978) 794-1848 • www.watts.com
Canada: Tel: (905) 332-4090 • Fax: (905) 332-7068 • www.watts.ca 