Series LFBP30
Diaphragm Operated Bypass Control Relief Valves
Size: 1⁄2" (15mm)
Series LFBP30 Lead Free* Diaphragm Operated Bypass Relief Valves regulate liquid pressure as supplied by a posi­tive pressure pump. These relief valves protect equipment by opening at desired setting and allowing excess volume to be bypassed back to source. They feature Lead Free cast copper silicon alloy body construction, sensitive rubber dia­phragms, and Buna-N discs.
The tee handle facilitates pressure change. The spring and adjustment handle are free from contact with liquid elements being controlled. The maximum temperature for this series is 180°F (82°C). The LFBP30 features Lead Free* construction to comply with Lead Free* installation requirements.
Contractor
Contractor’s P.O. No.
Representative
––––––––––––––––––––––––––––––––––––––––––––
–––––––––––––––––––––––––––––––––––––––––––––
––––––––––––––––––––––––––––––––––––––––
––––––––––––––––––––––––––––––––––
LFBP30
Features
•LeadFree*castcoppersiliconalloybody
•Sensitiverubberdiaphragm
•Teehandle
•Springandadjustmenthandleseparatedfromliquid
Dimensions
ModeL Size (dN) HeigHt LeNgtH WeigHt
in. mm in. mm in. mm lbs. kg.
LFBP301⁄2 15 53⁄4 146 21⁄4 57 11⁄8 .5
Pressure Ranges
Maximum Temperature 180°F (82° C) LFBP30 - Adjustable Opening Range 10-50psi (.1-3.4 bar) LFBP30 - Adjustable Opening Range 45-100psi (3.1-6.9 bar) LFBP30 - Adjustable Opening Range 75-175psi (5.2-12.1 bar)
NOTICE
The Watts products listed on this page are small type relief valves. Construction of these products does not meet the (ANSI Z21.22) nationally recognized applicable standard.
Materials
Body: Lead Free* cast copper silicon alloy Diaphragm: Buna-N Disc: Buna-N
Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.
NOTICE
Inquire with governing authorities for local installation requirements
*The wetted surface of this product contacted by consumable water contains less than 0.25% of lead by weight.