Watts LF909 User Manual

RP/IS-909/909RPDA
Installation, Maintenance, & Repair Series 909, LF909, 909RPDA, LF909RPDA
Reduced Pressure Zone Assemblies Reduced Pressure Detector Assemblies
Sizes: 21⁄2" – 10" (65 – 250mm)
!
WARNING
Read this Manual BEFORE using this equipment. Failure to read and follow all safety and use information
can result in death, serious personal injury, property damage, or damage to the equipment.
Keep this Manual for future reference.
Watts 909 OSY shown
Designed for inline servicing
Local building or plumbing codes may require modifications to the information provided. You are required to consult the local building and plumbing codes prior to installation. If this informa­tion is not consistent with local building or plumbing codes, the local codes should be followed.
Need for Periodic Inspection/Maintenance: This product must be tested periodically in compliance with local codes, but at least once per year or more as service conditions warrant. Corrosive water conditions, and/or unauthorized adjustments or repair could render the product ineffective for the service in­tended. Regular checking and cleaning of the product’s internal components helps assure maximum life and proper product function.
IMPORTANT: Inquire with governing authorities for local installa-
tion requirements.
NOTICE
For Australia and New Zealand, line strainers should be installed between the upstream shutoff valve and the inlet of the backflow pre­venter.
Its important that this device be tested periodically in compliance with local codes, but at least once per year or more as service con­ditions warrant. If installed on a fire sprinkler system, all mechanical checks, such as alarm checks and backflow preventers, should be flow tested and inspected internally in accordance with NFPA 13 and NFPA 25.
Testing
For field testing procedure, send for IS-TK-DL, IS-TK-9A, IS-TK-99E and IS-TK-99D.
For repair kits and service parts, reference PL-RP-BPD at www.watts.com
For technical assistance, contact your local Watts representative.
Basic Installation Instructions
NOTICE
The flange gasket bolts for the gate valves should be re tight ened during in stal la tion as the bolts may have loos ened due to stor age and ship ping.
High Capacity Relief Series: Location and Installation Considerations
1. Backflow preventers must be installed in high-visibility locations in order to allow for immediate notice of telltale discharge or other malfunction. This location should also facilitate testing and ser vic ing, and protect against freezing and vandalism.
2. Installing a backflow preventer in a pit or vault is not rec om­mend ed. However, if this becomes necessary, Watts highly rec­om mends that a licensed journeyman tradesperson, who is rec­ognized by the authority having jurisdiction, be consulted to ensure that all local codes and required safety provisions are met. An air gap below the relief port must be maintained so as to avoid flooding and submersion of the assembly, which may lead to a cross connection. *Please refer to Figure No. 1 for fur­ther information.
3. A strainer should be installed ahead of the backflow preventer to protect all internal components from unnecessary fouling.
!
CAUTION
Do not install a strainer ahead of the backflow preventer on seldom­used, emergency water lines (i.e. fire sprinkler lines). The strainer mesh could potentially become clogged with debris present in the water and cause water blockage during an emer gen cy.
4. Normal discharge and nuisance spitting are accommodated by the use of a Watts air gap fitting and a fabricated indirect waste line. Floor drains of the same size MUST be provided in case of excessive discharge. *Please refer to Figure No. 1 and Figure No. 2 for further in for ma tion.
5. When a 909/LF909 Series backflow preventer is installed for dead-end service applications. (i.e. boiler feed lines, cooling tower makeup or other equip ment with periodic flow require­ments), discharge from the relief vent may occur due to water supply pressure fluctuation during static no-flow con di tions. A check valve may be required ahead of the backflow preventer. *Please see “Troubleshooting”, Page 7, prior to installation.
Basic Installation Instructions Series 909/LF909
Sizes: 21⁄2" – 10" (65 – 250mm)
6. The relief valve module on 21⁄2" – 10" (65 – 250mm) 909/LF909 Series assemblies may be turned to discharge to the opposite side. To do so, unbolt the relief valve and turn the relief valve dis­charge port to the opposite side. Mount the high pressure hose on the op po site. This should be done by a licensed journeyman tradesperson, who is rec og nized by the authority having jurisdic­tion and only when space is critical for testing or repair.
7. ASSEMBLY: If the backflow preventer is disassembled during installation, it MUST be reassembled in its proper order. The gate valve with the test cock is to be mounted on the inlet side of the backflow preventer. The test cock must be on the inlet side of the wedge. Please see above. Failure to reassemble correctly will result in possible water damage due to excessive discharge from the relief port/vent and possible malfunction of the backflow pre­venter.
8. Installation procedures must comply with all state and local codes and must be completed by a licensed journeyman trades­person who is recognized by the authority having ju ris dic tion.
9. Prior to installation, thoroughly flush all pipe lines to remove any foreign matter.
10. START UP at Initial Installation and After Servicing: The down­stream shutoff should be closed. Slowly open upstream shutoff and allow the backflow preventer to fill slowly. Bleed air at each test cock. When backflow preventer is filled, slowly open the down stream shutoff and fill the water supply system. This is nec­essary to avoid dislodging O-rings or causing damage to internal com po nents.
11. TEST: The 909/LF909 Series backflow preventer may be tested by a certified tester at the time of installation in order to ascertain that the assembly is in full working order and may be relied upon to protect the safe drinking water as per applicable standard.
Watts No. 909/LF909
1
2
2" – 10" (65 – 250mm)
Inlet Shutoff Valve
First Check
Second Check
Relief Valve
Second Shutoff Valve
Figure 1
Series 909/LF909 Relief Valve Dis charge Rates
175
150
125
21⁄2” – 3” 909
100
75
50
ZONE PRESSURE (PSIG)
25
0
0 100 200 300 400 500 600 700 800 900
FLOW RATE (GPM)
4” – 10” 909
Figure 2
VALVE SIZE TYPICAL FLOW RATES AS SIZED BY
FLOOR DRAIN MANUFACTURERS
in. mm in. mm
1
2 65 55 gpm 2 50
2
DRAIN SIZE
3” 80 112 gpm 3 65 4” 100 170 gpm 4 100
6”, 8”, 10” 150,200,250 350 gpm 5 125
2
Installation
A. Series 909/LF909 should be installed in a horizontal and upright
position. This positions the relief valve below the first check valve, enabling the zone to drain through the relief valve outlet. The shutoff valve with the test cock is to be mounted on the inlet side of the backflow preventer. The test cock is on the inlet side of the shutoff valve.
B. The 909/LF909 should always be installed in an accessible loca-
tion to facilitate testing and servicing. Check the state and local codes to insure that the backflow preventer is installed in compli­ance, such as the proper height above the ground.
C. Water discharge from the relief valve should be vented in accor-
dance with code requirements. The relief valve should never be solidly piped into a drainage ditch, sewer or sump. The dis­charge should be funneled through a Watts air gap fitting piped to a floor drain.
D. Watts recommends a strainer be installed ahead of Watts 909
Series assemblies to protect the discs from unnecessary fouling.
E. Backflow preventers should never be placed in pits unless abso-
lutely necessary and then only when and as approved by local codes. Consult your local or state plumbing or health inspector. Watts recommends installation indoors or above ground in an insulated enclosure.
Start Up
F. The downstream shutoff should be closed. Open upstream
slowly, fill the valve and bleed the air through Test cock 2, 3 and
4. When valve is filled, open the downstream shutoff slowly and fill the water supply system. This is necessary to avoid water hammer or shock damage.
G. The installation of a Watts air gap with the drain line terminating
above a floor drain will handle any normal discharge or nuisance spitting through the relief valve. However, floor drain size may need to be designed to prevent water damage caused by a cat­astrophic failure condition. Do not reduce the size of the drain line from the air gap fitting.
H. Two or more smaller size valves can be piped in parallel (when
approved) to serve a larger supply pipe main. This type of instal­lation is employed where increased capacity is needed beyond that provided by a single valve and permits testing or servicing of an individual valve without shutting down the complete line.
The number of assemblies used in parallel should be determined by the engineer’s judgement based on the operating conditions of a specific installation.
Indoors
Watts 909S/LF909S FDA
1
2
2” - 10” (65 - 250mm)
Main
Meter Strainer
Air Gap
12” (300mm)
Above Ground
Min. 12” (300mm)
Now available, WattsBox Insulated Enclosures, for more information, send for ES-WB.
Parallel
Watts 909/LF909
21⁄2" – 10" (65 – 250mm)
Air Gap
support
Strainer
TABLE ONE - CAPACITY REQUIRED FOR SYSTEM
50 GPM 100 GPM 150 GPM 200 GPM 250 GPM 350 GPM
Two 3⁄4" Two 1" Two 11⁄4" Two 11⁄2" Two 11⁄2" Two 2" Devices Devices Devices Devices Devices Devices
450 GPM 640 GPM 1000 GPM 2000 GPM 3000 GPM 5000 GPM
Two 21⁄2" Two 3" Two 4" Two 6" Two 8" Two 10"
Devices Devices Devices Devices Devices Devices
Table shows total capacity provided with dual valve installations of various sizes.
3
Test Procedure for Reduced Pressure Zone Backflow Preventers
The following Test Procedure is one of several that is rec og nized through out the Unit ed States for ver i fi ca tion of the func tion ing of backflow pre ven ters.
The following procedure is not a specific rec om men da tion. The Watts se ries of test kits are ca pa ble of per form ing any of the rec og­nized backflow test procedures.
A. Open TC #4 and flush test cocks Nos. 1, 2, and 3 on BF
assembly, then close TC #4.
B. Turn tester on (before connecting hoses). Tester must read all
zeros. Close VA and VB.
Test No. 1 - Relief Valve
1. Install high side hose between TC #2 and tester connection A.
2. Install low side hose between TC #3 and tester connection B.
3. Open VB then TC #3. Now open VA then TC #2 slowly. Close VA then VB.
4. Close #2 shutoff valve.
5. Observe the apparent first check valve differential pressure (A ­B).
6. Install bypass hose between VA and VB. Open VB and bleed air by loosening hose connection at VA. Tighten hose connection and close VB.
Push - Print Head (wait) then Push - Start Test
7. Open VA, then slowly open VB (no more than 1⁄4 turn). When relief valve drips, push the “hold” button for 2 seconds. Record reading (must be 2 psid or more).
Push - Stop Test
8. Close VA and VB.
Test No. 2 - Test No. 2 Check Valve
9. Install bypass hose between VA and TC #4. Open VA, then bleed air by loosening hose connection at TC #4. Tighten hose connection. Close VA.
Push - Start Test
10. Open VB to reestablish pressure with in the “zone”. Close VB.
11. Open VA then TC #4. If relief valve does not drip, record second check valve as “closed tight”.
Test No. 3 - Test No. 1 Check Valve
12. Open VB to reestablish first check valve differential pressure. Close VB. Record pressure dif fer en tial.
Stop Test (Push Stop Test twice)
13. Close test cocks and remove tester, return assembly to normal operating condition.
Watts TK-DP
RPZ
Test 1
RPZ
Test 2
RPZ
Test 3
VA
B VB
A
A
VA
B VB
A
VA
B VB
For complete testing information, send for IS-TK-9A or IS-TK-DP/DL.
4
For repair kits and parts, refer to Backflow Prevention Products Repair Kits & Service Parts price list PL-RP-BPD on www.watts.com
Servicing First and Second Checks
Sizes: 21⁄2" – 10" (65-250mm)
1. Remove the hatch cover bolts. NOTE: The 909 is designed so that when the bolts are backed off re leased from the cover and retained by the check module.
!
CAUTION
Be sure to verify this before removing all the bolts.
2. Lift the check valve module straight out taking care not to hit and damage the seating.
3. The seat ring may be removed and replaced by pulling out the two wire retainers on sizes 4" – 10" (100 – 250) while on sizes
1
2" – 3" (65 – 80mm), one quarter turn twist removes seat. The
2 wire retainers are 10” long. One is drawn out clockwise and the other is drawn out counterclockwise.
4. With the retainer wires removed, the seat ring can be lifted straight up and removed.
!
CAUTION
5. The check valve spring is in compression. The spring load is captured by the two spring retainers and the stem. The spring re tainers are not to be removed for servicing. If there is a need to re place the spring, spring retainer or stem, an assembled module must be obtained from the factory. These modules are not interchangeable, be sure to replace the first check with a first check mod ule and the second check with a second check module.
6. To replace the disc on sizes 2 remove the re tain ing nut or for sizes 6” – 10” (150 – 250mm) remove the allen head socket screws. Reverse this procedure to install the new disc.
1
2", all the spring load is
1
2" – 4" (65 – 100mm) simply
No special tools
required to service
Series 909
909OSY/ LF909OSY
21⁄2" – 3" (65 – 80mm)
First and second checks are not interchangeable
First Check
Relief Valve
*Disc & Spring As sem bly
Seat
Seat O-ring
Cover O-ring
Second
Check
For further details contact your tech ni cal sales representative, see back page.
4" – 10" (100 – 250mm)
*Disc & Spring As sem bly
Disc
Seat
Lower Stem
O-ring (6” only) Retainer wire Seat O-ring Cover O-ring
!
WARNING
*Spring as sem bly is factory assembled. DO NOT DIS AS SEM BLE
5
Servicing the Relief Valve
Sizes: 21⁄2" – 10" (65-250mm)
1. Remove the relief valve cover bolts. Note the 909/LF909 is designed so that when the bolts are backed off
1
2" all the relief
valve spring load is retained by the bottom plug spring module.
!
CAUTION
Be sure to verify this before removing all the bolts.
2. Remove the cover and diaphragm. The relief valve piston assembly can be lifted straight up and out.
3. Replace the wiper seal and piston O-ring and apply grease to the O-ring.
4. To replace the relief valve disc, hold the upper guide fin and unscrew the diaphragm pressure plate. It may be necessary to lightly tap the cast webs and the pressure plate to loosen. Replace with a new disc holder assembly and O-ring. Note: the disc rubber is molded into the disc holder and is supplied as a disc holder assembly.
5. Removal of the bottom plug and spring assembly. During nor­mal field service there is no need to remove the bottom plug spring assembly other than inspection. It can be removed by simply unscrewing with a large pipe wrench.
!
CAUTION
The spring as retained on the bottom plug is highly loaded. NO attempt should be made in the field to remove the spring. For replacement, a complete bottom plug assembly must be obtained from the factory.
For further details contact your technical sales representative, see back page.
Relief Module
CLEARANCE REQUIRED FOR SERVICING
in. mm A B
1
2 – 3 65-80 10" 11"
2
4 100 15" 14"
B
6 150 15" 16" 8 200 23" 21"
10 250 25" 21"
Adapter O-ring
Diaphragm
Relief Valve Disc
Relief Valve Piston Assembly
Piston O-Ring
Sizes
1
2
2" – 3"
(65 – 80mm)
O-ring
Seat
Adapter O-ring
Diaphragm
Relief Valve Piston Assembly
Piston seal
Seat
O-ring
Sizes 4", 6" (100, 150mm) 8"M1, 10"M1
Plug &
Spring Piston
Assembly
Adapter o-ring
Diaphragm
Relief Valve Assembly
Seat
O-ring
Sizes 8", 10" (200, 250mm)
Plug & Spring Assembly
6
Troubleshooting Guide - Backflow Preventers
Problem Cause Solution A. Valve spits periodically
from the vent
B. Valve drips continually
from the vent
C. Valve exhibits high
pressure drop.
D. No water flows down-
stream of valve.
E. Valve does not test
properly
F. Valve quickly and
repeatedly fouls follow­ing servicing.
G. Winterization of back-
flow preventers.
A.1 Fluctuating supply pressure. A.1 Install a soft seated check valve immediately upstream
A.2 Fluctuating downstream pressure A.2 Install a soft seated check valve downstream of the
B.1 Fouled first check B.1 Flush valve. If flushing does not resolve problem, dis-
B.2 Damage or fouled relief valve seat. B.2 Clean or replace the relief valve seat. B.3 Relief valve piston O-ring not free to
move due to pipe scale, dirt or build up of mineral deposits.
B.4 Excessive back pressure, freezing, or
water hammer has distorted the sec­ond check.
B.5 Electrolysis or relief valve seat or first
check seats.
B.6 Valve improperly reassembled. B.6 If valve is dis as sem bled during installation, caution
C.1 Fouled strainer. C.1 Clean strainer element or replace.
C.2 Valve too small for flows encountered. C.2 Install proper size device based upon
D. Valve installed backwards. D. Install valve in accordance with flow direction arrow.
E.1 Follow manufacturer’s test procedure E.1, E.2 Clean or replace gate valve with full port ball
E.2 Leaky downstream gate valve. F. Debris in pipe line is too fine to be
trapped by strainer.
of the de vice.
device close as possible to the shutoff valve.
assemble valve and clean or re place the first check.
B.3 Clean, grease or replace the piston O-ring.
B.4 Elim i nate source of excessive backpressure or water
hammer in the system downstream of the device. Use Watts No. 15 to eliminate water hammer. Replace defective second check assembly. In case of freezing; thaw, dis as sem ble and inspect internal components.
Replace as necessary.
B.5 Replace relief valve seat or inlet cover.
Electrically ground the piping system and/or electri­cally isolate the device with plastic pipe immediately upstream and down stream of the device.
must be exercised to install check springs in their proper location.
flow requirements.
valves or resilient wedge shutoff valves.
F. Install finer mesh strainer element in the strainer.
G. Electric heat-tape wrap closely together around valve
body. Build a small shelter around the valve with a large light bulb installed and left on at all times. If supply line is not used during the winter, removal of the com plete body is the best. This would create an air gap to eliminate any possible backflow.
7
WARNING: This product contains chemicals known to the State of California to cause cancer and birth defects or other reproductive harm.
For more information: www.watts.com/prop65
Limited Warranty: Watts Regulator Co. (the “Company”) warrants each product to be free from defects in material and workmanship under normal usage for a period of one year from the date of
original shipment. In the event of such defects within the warranty period, the Company will, at its option, replace or recondition the product without charge.
THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY WARRANTY GIVEN BY THE COMPANY WITH RESPECT TO THE PRODUCT. THE COMPANY MAKES NO OTHER WARRANTIES, EXPRESS OR IMPLIED. THE COMPANY HEREBY SPECIFICALLY DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
The remedy described in the first paragraph of this warranty shall constitute the sole and exclusive remedy for breach of warranty, and the Company shall not be responsible for any incidental, special or consequential damages, including without limitation, lost profits or the cost of repairing or replacing other property which is damaged if this product does not work properly, other costs resulting from labor charges, delays, vandalism, negligence, fouling caused by foreign material, damage from adverse water conditions, chemical, or any other circumstances over which the Company has no control. This warranty shall be invalidated by any abuse, misuse, misapplication, improper installation or improper maintenance or alteration of the product. Some States do not allow limitations on how long an implied warranty lasts, and some States do not allow the exclusion or limitation of incidental or consequential damages. Therefore the above limitations may not apply to you. This Limited Warranty gives you specific legal rights, and you may have other rights that vary from State to State. You should consult applicable state laws to determine your rights. SO FAR AS IS CONSISTENT WITH APPLICABLE STATE LAW, ANY IMPLIED WARRANTIES THAT MAY NOT BE DISCLAIMED, INCLUDING THE IMPLIED WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED IN DURATION TO ONE YEAR FROM THE DATE OF ORIGINAL SHIPMENT.
A Watts Water Technologies Company
USA: Tel: (978) 688-1811 • Fax: (978) 794-1848 • www.watts.com
Canada: Tel: (905) 332-4090 • Fax: (905) 332-7068 • www.watts.ca
RP-IS-909-909RPDA 1319 EDP# 1915172 © 2013 Watts
Loading...