ES-LF40_LF140_LFN240_LF340
For Commercial Water Heater Applications
Job Name
Job Location
Engineer
Approval
LEAD FREE
–––––––––––––––––––––––––––––––––––––––––––
–––––––––––––––––––––––––––––––––––––––––
–––––––––––––––––––––––––––––––––––––––––––––
–––––––––––––––––––––––––––––––––––––––––––––
*
Series LF40, LF140,
LFN240, and LF340
Automatic Re-seating
T&P Relief Valves
The combined 2-in-1 Temperature & Pressure Relief Valve provides the
least expensive and proven means for protection against both excessive
temperature and pressure emergency conditions.
Fully automatic temperature and pressure relief protection for domestic
hot water supply tanks and heaters based on the latest ANSI Z21.22
Listing requirements for temperature discharge capacity. The LF40,
LF140, LFN240, and LF340 feature Lead Free* construction to comply
with Lead Free* installation requirements.
LF40XL with test lever and extension thermostat for installation in hot
water outlet within the allowable distance from the top of the tank based
on latest ANSI Z21.22. Sizes
LF40L with test lever and short thermostat for installation directly in
available tank tappings. Sizes
Series LF140, LFN240 and LF340 have the same basic body construction
and advanced design features as the Series LF40 except for discharge
capacity and size of inlet and outlet connections. For complete specifications (including specifications for the Series LF40) see other side. Sizes
1
1", 1
⁄4", 11⁄2" and 2" (25, 32, 40 and 50mm).
Features
•LeadFreecastbody
•Non-mechanicalseat-to-discalignment
•Tamper-resistantbonnetscrews
3
•Series
•Series1"LF140arefurnishedwithstainlesssteelthermostattube
•SeriesLFN240andLF340arehotfurnishedwithstainlesssteelther-
⁄4" LF40 and LF140 feature a unique thermostat with a special
thermo-bonded coating
mostat tube
3
⁄4" and 1" (20 – 25mm).
3
⁄4" and 1" (20 – 25mm).
Contractor
Approval
Contractor’s P.O. No.
Representative
––––––––––––––––––––––––––––––––––––––––––––
–––––––––––––––––––––––––––––––––––––––––––––
––––––––––––––––––––––––––––––––––
––––––––––––––––––––––––––––––––––––––––
Series LF40L
and LF40XL
Series LFN240X
Series LF140
Specifications
Temperature & Pressure Relief Valves
Each hot water storage heater shall be equipped with an automatic
temperature and pressure relief valve to protect the heater from excessive pressure and excessive temperature. The device shall be certified
as meeting the requirements of ASME low pressure heating boiler code
and ANSI Z21.22. The BTU discharge capacity of the device shall be in
excess of the BTU input rating of the heater. The device shall be constructed using Lead Free* materials. Lead Free* automatic re-seating
T&P relief valves shall comply with state codes and standards, where
applicable, requiring reduced lead content. The T&P valve shall be a
Watts Series LF40, LF140, LFN240 or LF340.
Following installation, the valve lever MUST be operated AT LEAST
ONCE A YEAR by the water heater owner to ensure that the waterways are clear. Certain naturally occurring mineral deposits may
adhere to the valve, blocking waterways, rendering it inoperative. When
the lever is operated, Hot water will discharge if the waterways are
clear. Precautions must be taken to avoid personal injury from contact
with hot water and to avoid property damage.
Series LF340
* The wetted surface of this product contacted by consumable
water contains less than 0.25% of lead by weight.
Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.
IMPORTANT: INQUIRE WITH GOVERNING AUTHORITIES
FOR LOCAL INSTALLATION REQUIREMENTS
Direct Side Tapping
FOR EXTERNAL FLUE HEATERS
Use extra length extension thermostat to extend into water storage tank.
FOR INTERNAL FLUE HEATERS
Use short or standard length thermostat. Vertical discharge line must be
installed with its direction downward.
Max. 6"
(152mm)
Standards
ASME Rated, ANSI Z21.22, Design certified and listed by CSA, National
Board of B&PVI to Section IV of the ASME B&PV code and meet current
FHA requirements and ANSI Z21.22 in addition to Military Spec. MIL-V136-12D, Type I.
Pressure – Temperature
Temperature relief 210°F (99°C)
Pressure range 75 – 150psi (5.2 – 10.3 bar)
Standard setting 75, 100, 125 and 150psi
(5.2, 6.9, 8.6 and 10.3 bar)
†
For Heaters with Direct Top Tapping
Use standard or extra length extension thermostat.
General Recommendations
For gas, electric or oil-fired storage water heaters between 180,000 to
205,000 BTU/Hr. rating: Use
under ANSI Z21.22 with ratings as certified and listed by CSA.
3
⁄4" (20mm) Series LF40, LF140 tested
For gas or oil-fired storage water heaters between 205,000 and 730,000
BTU/Hr. rating and for compliance with applicable water heater labeling requirements: Use 1" (25mm) LF40, LF140, LFN240 Series tested
under ANSI Z21.22 with ratings as certified and listed by CSA.
For installations of gas or oil-fired hot water supply boilers over 730,000
BTU/Hr. output heating domestic water and for steam coil storage water
heaters: Use Series LF340, LF342 tested under ANSI Z21.22 with rat-
ing as certified and listed by CSA.
Thermostat
Inlet X Length (in.) Dimensions (in.) CSA
Outlet (Below Inlet Height Weight Temp. Steam **ASME PRESSURE STEAM RATING BTU/HR
Model (in.) thread) (Less Thermostat) Width lbs. Rating BTU/HR @75psi set pres. @100psi set pres. @125psi set pres. @150psi set pres.
LF40L-3
LF40XL-5
LF40XL-8
LF140S-3
LF140X-5
LF140X-8
LF40L-2 1M x 1F 2 6
LF40XL-4 1M x 1F 4 6
LF40XL-7 1M x 1F 7 6
*LF140S-3 1F x 1F 3 5
*LF140X-6 1F x 1F 6 5
*LF140X-9 1F x 1F 9 5
*LFN240X-6 1F x 1F 6 6
*LFN240X-9 1F x 1F 9 6
*LFN241X-5 1
*LFN241X-8 1
*LF340-3 1
*LF340X-8 1
*LF342-3 2 M x 1
*LF342X-8 2 M x 1
3
⁄4 M x 3⁄4 F 3 55⁄8 25⁄8 13⁄4 180,000 777,600 997,600 1,217,600 1,437,600
3
⁄4 M x 3⁄4 F 5 55⁄8 25⁄8 13⁄4 205,000 777,600 997,600 1,217,600 1,437,600
3
⁄4 M x 3⁄4 F 8 55⁄8 25⁄8 13⁄4 205,000 777,600 997,600 1,217,600 1,437,600
3
⁄4 F x 3⁄4 F 3 55⁄8 25⁄8 13⁄4 180,000 777,600 997,600 1,217,600 1,437,600
3
⁄4 F x 3⁄4 F 5 55⁄8 25⁄8 13⁄4 205,000 777,600 997,600 1,217,600 1,437,600
3
⁄4 F x 3⁄4 F 8 55⁄8 25⁄8 13⁄4 205,000 777,600 997,600 1,217,600 1,437,600
1
⁄4 M x 1F 5 65⁄8 33⁄8 23⁄4 730,000 2,195,000 2,817,000 3,438,000 4,059,000
1
⁄4 M x 1F 8 65⁄8 33⁄8 23⁄4 730,000 2,195,000 2,817,000 3,438,000 4,059,000
1
⁄2 F x 11⁄2 F 3 93⁄4 41⁄2 7 1,150,000 3,450,000 4,426,000 5,403,000 6,379,000
1
⁄2 F x 11⁄2 F 8 93⁄4 41⁄2 8 1,150,000 3,450,000 4,426,000 5,403,000 6,379,000
1
⁄2 F 3 93⁄4 41⁄2 7 1,150,000 3,450,000 4,426,000 5,403,000 6,379,000
1
⁄2 F 8 93⁄4 41⁄2 8 1,150,000 3,450,000 4,426,000 5,403,000 6,379,000
1
⁄4 23⁄4 21⁄4 450,000 1,155,000 1,481,000 1,808,000 2,134,000
1
⁄4 23⁄4 21⁄4 500,000 1,155,000 1,481,000 1,808,000 2,134,000
1
⁄4 23⁄4 21⁄4 500,000 1,155,000 1,481,000 1,808,000 2,134,000
1
⁄2 3 21⁄4 570,000 1,670,000 2,140,000 2,610,000 3,085,000
1
⁄2 3 21⁄4 670,000 1,670,000 2,140,000 2,610,000 3,085,000
1
⁄2 3 21⁄4 670,000 1,670,000 2,140,000 2,610,000 3,085,000
5
⁄8 33⁄8 23⁄4 730,000 2,195,000 2,817,000 3,438,000 4,059,000
5
⁄8 33⁄8 23⁄4 730,000 2,195,000 2,817,000 3,438,000 4,059,000
*Furnished with stainless steel thermostat tube. M = Male F = Female
**ASME capacities are steam pressure ratings and do not reflect the CSA temperature relieving capacity of the valves for selection purposes.
†LFLL40XL and LFLLL40XL valves with extended inlet shanks should be used for water heaters that have extra thick insulation, Ask for ES-LFLL/LLL40XL.
Temperature and Pressure Relief Valves should be inspected AT LEAST ONCE EVERY TWO TO FOUR YEARS, and replaced, if necessary, by a
licensed plumbing contractor or qualified service technician, to ensure that the product has not been affected by corrosive water conditions and to ensure
that the valve and discharge line have not been altered or tampered with illegally. Certain naturally occurring conditions may corrode the valve or its
components over time, rendering the valve inoperative. Such conditions can only be detected if the valve and its components are physically removed and
inspected. Do not attempt to conduct an inspection on your own. Contact your plumbing contractor for a reinspection to ensure continuing safety.
A Watts Water Technologies Company