ONE-WAY FLOW ALTITUDE VALVE
with DELAYED OPENING FEATURE
01/05
F127-11 (Globe)
Classic Series
Operation
The Watts ACV One Way Flow Altitude Valve with Delayed Opening Feature is designed to open, allowing
flow into a reservoir or elevated storage tank (tank fill), and close drip tight when high water level is achieved.
The valve also has an adjustable delayed opening feature, allowing a calculated “draw-down” of water level,
before opening for tank fill operation. The Altitude Pilot remotely senses static tank head pressure (water
level) through a field installed sensing line, and directs pressure into and out of the cover chamber of the 3way Accelerator Pilot. When the cover of the Accelerator Pilot is pressurized, the main valve cover chamber
is vented downstream (dry drain) or to atmosphere (wet drain), causing the valve to open fully. When the
cover of the Accelerator Pilot is de-pressurized, the main valve cover chamber is connected to upstream
pressure, causing the valve to close drip tight.
As water level decreases, static tank head pressure falls below the adjustable setpoint of the Altitude Pilot,
causing it to pressurize the cover of the Accelerator Pilot, opening the valve. As water level increases, static
tank head exceeds the adjustable setpoint of the Altitude Pilot, causing it to depressurize the cover of the
Accelerator Pilot, closing the valve drip tight. Valve opening and closing speeds are separately adjustable.
The Position Indicator with Air Bleed Petcock allows for visual indication of valve position, and easy venting
of air entrapped in the main valve cover chamber.
F1127-11 (Angle)
The adjustable Delayed Opening Feature “holds” high level static tank head pressure in the Altitude Pilot,
causing the main valve to remain closed as water level decreases. When static tank head pressure falls
below the setpoint of the Delayed Opening Pilot, the Altitude Pilot commands the main valve to open for tank
fill operation. Reservoir filling can be “delayed” until water level falls 3-15 feet (adjustable) below desired
shut-off point to increase water circulation through the tank.
Specify Tank height PRIOR to ordering.
8550 Hansen Road • Houston, Texas 77075 • (Ph) 713.943.0688 • (Fx) 713.944.9445 • www.wattsacv.com
ONE-WAY FLOW ALTITUDE VALVE
with DELAYED OPENING FEATURE
01/05
F127-11 (Globe)
Classic Series
Installation Guidelines
• Prior to installation, flush line to remove debris.
• Install valve horizontally “in line” (cover facing UP), so flow arrow matches flow through the line. Avoid
installing valves 6” and larger vertically. Consult factory prior to ordering if installation is other than
described.
• Install inlet and outlet isolation valves. NOTE: When using butterfly valves, insure disc does not contact
control valve. Damage or improper valve seating may occur.
• Provide adequate clearance for valve servicing and maintenance.
• Install pressure gauges to monitor valve inlet, outlet, and static head pressure.
• Provide adequate drain for cover chamber discharge if “wet drain” option is selected. Consult “Valve
Cover Capacity” chart on appropriate main valve Engineering Bulletin.
• Install static tank head sense line. For optimum control, sense line should be: 1) Installed with an
upward angle (towards reservoir) to avoid air accumulation, 2) Connected no further than forty-five pipe
diameters from the reservoir, and 3) A minimum of 1/2” diameter.
F1127-11 (Angle)
Other Watts ACV Altitude Control Valves
F127-1 / F1127-1 One Way Flow Altitude Valve
F127-2 / F1127-2 Two Way Flow Altitude Valve
F127-8 / F1127-8 One Way Flow Altitude Valve with Pressure Sustaining Feature
F127-31 / F1127-31 Two Way Flow Altitude Valve with Solenoid Override Feature
F127-32 / F1127-32 One Way Flow Altitude Valve with Solenoid Override Feature
8550 Hansen Road • Houston, Texas 77075 • (Ph) 713.943.0688 • (Fx) 713.944.9445 • www.wattsacv.com