Watts F1110-18 User Manual

R
ON-OFF FLOAT VALVE with PRESSURE SUSTAINING FEATURE
01/05
F110-18 (Globe)
Classic Series
Operation
The On-Off Float Pilot directs upstream pressure into and out of the cover chamber of the 3-way Accelerator Pilot. When the cover of the Accelerator Pilot is pressurized, the main valve cover chamber is vented downstream, causing the valve to open. When the cover of the Accelerator Pilot is de-pressurized, the main valve cover chamber is connected to upstream pressure, causing the valve to close drip tight. Valve opening and closing speeds are separately adjustable. When water level reaches the adjustable high-level setpoint, the Float Pilot de-pressurizes the cover chamber of the 3-Way Accelerator, closing the valve drip tight. The valve remains closed as water level decreases. When water level reaches the adjustable low-level setpoint, the Float Pilot pressurizes the cover chamber of the 3-Way Accelerator, opening the valve. High and low levels are separately adjustable by positioning stop collars on the float rod(s) at desired opening and closing setpoints.
F1110-18 (Angle)
8550 Hansen Road Houston, Texas 77075 (Ph) 713.943.0688 (Fx) 713.944.9445 www.wattsacv.com
R
ON-OFF FLOAT VALVE with PRESSURE SUSTAINING FEATURE
01/05
F110-18 (Globe)
Classic Series
Installation Guidelines
Prior to installation, flush line to remove debris.
Install valve horizontally “in line” (cover facing UP), so flow arrow matches flow through the line. Avoid
installing valves 6” and larger vertically. Consult factory prior to ordering if installation is other than described.
Install inlet and outlet isolation valves. NOTE: When using butterfly valves, insure disc does not contact control valve. Damage or improper valve seating may occur.
Provide adequate clearance for valve servicing and maintenance.
Install pressure gauge to monitor valve inlet pressure. If On-Off Float Pilot is remotely mounted it should
be field connected with 3/8” minimum copper tubing in accordance with factory piping schematic.
Float Pilot, Rods, and Ball should be mounted in a field installed “stilling well” for protection against surface turbulence and interference.
Additional 12” Float Rods available. Consult Factory.
F1110-18 (Angle)
Other Watts ACV Float Control Valves
F110-10 / F1110-10 Modulating Float Control Valve F110-13 / F1110-13 Modulating Float Control Valve with Pressure Sustaining Feature F110-AS / F1110-AS Modulating Float Control Valve with Solenoid (On-Off) Feature F110-14 / F1110-14 On-Off Float Control Valve
8550 Hansen Road Houston, Texas 77075 (Ph) 713.943.0688 (Fx) 713.944.9445 www.wattsacv.com