Watts CIVIC4 Installation And Operation Manual

CIVIC4
Gas detection control
Installation manual
UK
Installation and Operation Manual
IT
Manuale di Installazione e Uso
WattsWater.eu
Index
- General
- Technical features
- Installation
- Commissioning
- Operation
- Gas Alarm
- Environmental compatibility and disposal
- Troubleshooting
- Terminal Board
- Connection diagrams
- Dimensions
Indice
- Generale
- Caratteristiche tecniche
- Installazione
- Messa in servizio
- Funzionamento
- Allarme gas
- Compatibilità ambientale e smaltimento
- Analisi dei guasti
- Morsettiera
- Schemi di collegamento
- Ingombri
EN
CIVIC1-MOI-IT-W-ML-09-18-Rev.1
EN
CIVIC4 control unit (data with UR20S detectors in brackets)
General
The CIVIC4 control unit can be used to connect one detector (model UR13 or UR20S) to create gas detection systems in envi­ronments such as boiler rooms, workshops, warehouses, laboratories etc.; the incorporated alarm relay can be used to control a solenoid valve or an accessory device (siren, flashing light, extractor, etc.). The installation of a gas or carbon monoxide detection system does not constitute a release from compliance with all regulations for the installation and use of gas devices and with the relative safety standards and legal provisions in force for this kind of system. Installation, periodic inspections and maintenance of devices and systems must be carried out by qualified service technicians.
Technical features
Power supply: 12Vac/dc ± 10% Consumption with 1 detector: About 160mA (320mA) Consumption with 4 detectors: About 280mA (920mA) Connections: Two terminals of 2.5 mm Protection: Power input fuse 1A 5x20mm Inputs: 4 for UR13 detector or UR20S detectors (different types of gas) Detector terminations: Three terminals of 2.5 mm2: C (-12...24V); S (+4…20mA); A (+12...24V) Max cable run length: 50 m for each detector Diameter of the 3 wires: 1.5 mm Alarm output: 1 relay with one contact SPDT 8A 250Vac Failure output: 1 relay with one contact SPDT 8A 250Vac Output connections: 3 terminals of 2.5 mm2 for C-NC-NO relay
1 green LED: power on
Visual alarms:
Audible alarms: 1 buzzer noise level > 60db at 1m “Reset/Test” button: 1 for alarm Reset and detector Test Enclosure: RAL7035 grey, self-extinguishing plastic house Dimensions and weight: 158x90x58 mm (9 modules to standard DIN 43880), 250 g Mounting: Back panel Omega DIN rail (EN 50022) Protection rating: IP20; IP40 when correctly installed in electric panel Room temperature: 0÷50 °C Humidity ≤90% RH (non condensing) EC Conformity Product standards: Standards EN 60079-29-1; CEI 216-5/1 LV Directives/Standards LV 2014/35/EU, Standard EN 60730-1 EMC Directives/Standards EMC 2014/30/EU, Standard EN 50270
1 yellow LED: general abnormality 4 yellow LEDs: failure for each detector line 4 red LEDs: gas alarm for each detector line"
2
UR13 (UR20S) detectors
Power supply from the CIVIC4 control unit Consumption 40mA (200mA)
Connections
Models
UR20S Models Various gases, see dedicated data sheet
Calibration:
Enclosure: Self-extinguishing plastic house Dimensions and weight: 66x90x45 mm (depending on model), 65 g Mounting: Wall-mounted using plastic screws and anchors Protection: IP44 (IP44, IP55 or IP65 depending on model) Room temperature: 0÷50°C (-20÷50°C) Humidity: ≤90% RH (non condensing) LV Directives/Standards Not applicable EMC Directives/Standards EMC 2014/30/EU, Standard EN 50270
three terminals of 2.5 mm2 per detector: C (-12...24V); S (+4…20mA); A (+12...24V) Methane Gas Cod. 0940561 LPG Cod. 0940562 Carbon monoxide Cod. 0940563
UR13: 10% LEL of Methane UR13: 12% LEL of Isobutane UR13: 200ppm of CO (UR20S: 20% LEL combustibles, 100ppm CO)
2
CIVIC1-MOI-IT-W-ML-09-18-Rev.1
EN
Installation
Mounting
Ensure correct environmental conditions (See Technical features).
CIVIC4 control unit
To guarantee the correct protection rating for the device it must be installed in an electric panel manufactured according to the laws in force for workplaces and that can also house the power supply system. Mount the control unit on a rail (to DIN EN 50022), using accessories for standard electric panels. It can be installed on a mounting plate or in DIN rail modules.
UR13 (UR20S) detectors
To be used for wall-mounting (vertical), attached by plastic screws and anchors. To install, insert a screwdriver in the recess at the bottom of the enclosure to open it; avoid damage to the sensor and do not touch the calibration devices.
The detectors must be correctly positioned for the system to­in zones with constant natural air circulation
- in zones free of dust and dirt that could clog up the sensor and make it ineffective
- never near running water, exhaust vents, windows, openings etc.
- at a suitable distance from the gas-fuelled equipment to avoid the system taking inappropriate action due to possible functional loss.
The positioning also depends on the type of gas that is to be detected, in particular:
- UR13: Methane gas - high, about 20-30 cm from ceiling
- UR13: LPG - low, about 20-30 cm from floor
- UR13: CO - about 1.5 m from floor For new plants, the detector must be installed at the last
possible moment so that typical worksite activities (particularly welding, painting, sealing etc.), do not damage the actual detector (particularly the sensing part).
UR20S detectors
See installation instructions on dedicated data sheet.
Electrical connections
Normal electric cables can be used. Still, if detectors are to be installed in environments with high exposure to EMI, it is advisable to use shielded cables. The detection system must always be operating, so power switches or other devices that could inadvertently make the detector inoperative must not be used. Do not touch the sensing element and the electronic circuits for any reason whatsoever. Tampering of any kind may cause the system to operate incorrectly.
Ensure compliance with all current electric standards.
UR13 or UR20S detector
Prepare wiring connections according to the electrical dia­grams contained in these instructions, using wires with a min­imum diameter of 1.5 mm2 for a maximum length of 50 m. for each detector.
Commisioning
The CIVIC4 control unit and the UR13 or UR20S detectors are safety control devices, therefore they must not be tampered with; do not touch the sensor or the electronics for any reason whatsoever. Carry out the following controls:
- the power supply for the control unit must comply with the values provided (12 Vac/dc ± 10%)
- make sure the power consumed by any devices connected to the relay terminals is below or the same as the maximum capacity of the contacts (See Technical features)
- if there are no detectors on the respective control unit terminals, resistances 18 KOhm ¼W 5% are supplied as standard (terminals C and S). In any case, these terminals must be disconnected from the inputs where there are detectors
- the detectors must be compatible with the type of gas to monitor and correctly connected to the control unit.
Depending on the type of detector to connect, jumper pairs E5-E6, E7-E8, E9-E10, E11-E12 must be positioned for each detector as follows (example for detector 1):
Warning To enable the UR20S sensors to operate, it is also necessary to set jumpers E3 and E4 as instructed in the chapter:
Description of device.
- the operating mode (positive or negative logic) selected must be consistent with the system choices. As regards this, check the position of Jumper E1 (See Operation).
- the operating mode selected for the relay must be consistent with the system choices. As regards this, check the position of Jumper E2 (See Operation).
- test the gas alarm and the detector failure condition events (See Operation).
Operation
The Jumper E1 can be used to select the operating mode (positive or negative logic). The control unit signals its operat­ing status through LEDs. Depending on the operating mode selected through Jumper E1, in a normal situation (no alarm), the LEDs and the relays are as follows:
positive operating logic: LEDs on; relays energised negative operating logic: LEDs off; relays de-energised
If the negative operating logic is selected, the alarm relay can be permanently or impulse controlled, depending on the position of Jumper E2:
CIVIC4 control unit
The control unit must be powered at 12 Vac/dc; use transformers with double insulation, sized for uninterrupt­ed use for the power utilised (See Technical features). For connecting the relay output use wires with a minimum diameter of 1.5 mm2. Prepare wiring connections according to the electrical diagrams contained in these instructions.
CIVIC1-MOI-IT-W-ML-09-18-Rev.1
Loading...
+ 8 hidden pages