Watts Aerco BMK 750, Aerco BMK 2500, Aerco BMK 3000, Aerco BMK 5000, Aerco BMK 6000 Operation And Service Manual

...
Operation and Serv ice Manual
Other documents for this product include :
OMM-0137_D • GF-211 • 7/16/2019
Benchmark® Platinum Boilers With Edge Controller
Natural Gas, Propane Gas and Dual Fuel Modulating & Condensing Boilers
Models 750 through 6000
OMM-0136, GF-210 210 Installation and Startup Man ual OMM-0138, GF-212 Reference Manual OMM-0139, GF-213 Edge Controller Manual TAG-0019, GF-2070 Boiler Application Guide
TAG-0022, GF-2050 Vent-Combustion Air Guide TAG-0047, GF-2030 Benchmark Gas Guide TAG-0048, GF-2060 Benchmark Power Guide
Applies to serial numbers:
G-19-0300 and above – B MK 750 – 3000 N-19-0100 and above – BMK 5000 & 6000
Benchmark Platinum-Edge: Operation-Service Manual
CONTENTS

Table of Contents

FOREWORD ...................................................................................................... 5
SECTION 1: SAFETY PRECAUTIONS ................................................................... 9
1.1 WARNINGS & CAUTIONS ..................................................................................................................... 9
1.2 EMERGENC Y SHUT D OWN ................................................................................................................. 10
1.3 PROLONGED SHUTDOWN ................................................................................................................. 10
1.4 IMPORTANT – FOR MASSACHUSETTS INSTALLATIONS ............................................................... 11
SECTION 2: EDGE CONTROLLER OPERATION .................................................. 13
2.1 INTRODUCTION ................................................................................................................................... 13
2.2 LOGIN AND PASSWORD ENTRY ....................................................................................................... 14
SECTION 3: START SEQUENCE ........................................................................ 15
3.1 INTRODUCTION ................................................................................................................................... 15
3.2 START SEQUENCE ............................................................................................................................. 15
3.3 START/STOP LEVELS ......................................................................................................................... 23
3.4 START/STOP LEVELS – AIR/FUEL & ENERGY INPUT ..................................................................... 24
3.4.1 BMK 750/1000 Air/Fuel Valve Position and Energy Input .............................................................................. 24
3.4.2 BMK 1500 Air/Fuel Valve Position and Energy Input ...................................................................................... 25
3.4.3 BMK 2000 Air/Fuel Valve Position and Energy Input ...................................................................................... 26
3.4.4 BMK 2500 Air/Fuel Valve Position and Energy Input ...................................................................................... 27
3.4.5 BMK 3000 Air/Fuel Valve Position and Energy Input ...................................................................................... 28
3.4.6 Benchmark 5000 Air/Fuel Valve Position and Energy Input ........................................................................... 29
3.4.7 Benchmark 6000 Air/Fuel Valve Position and Energy Input ........................................................................... 30
SECTION 4: INITIAL START-UP ........................................................................ 31
4.1 INITIAL START-UP REQUIREMENTS ................................................................................................. 31
4.2 TOOLS & INSTRUMENTS FOR COMBUSTION CALIBRATION ........................................................ 32
4.2.1 Required Tools & Instrumentation ................................................................................................................. 32
4.2.2 Installing Gas Supply Manometer ................................................................................................................... 32
4.2.3 Accessing the Analyzer Probe Port ................................................................................................................. 35
4.3 FUEL TYPES AND COMBUSTION CALIBRATION ............................................................................. 36
4.4 COMBUSTION CALIBRATION ............................................................................................................. 36
4.4.1 NATURAL GAS Manual Combustion Calibration ............................................................................................. 37
4.4.2 PROPANE GAS COMBUSTION CALIBRATION .................................................................................................. 42
4.5 REASSEMBLY ...................................................................................................................................... 47
4.6 DUAL FUEL SWITCHOVER ................................................................................................................. 48
4.7 OVER-TEMPERATURE LIMIT SWITCHES ......................................................................................... 49
4.7.1 Adjusting the Automatic Reset Limit Switch Temperature ............................................................................ 49
4.7.2 Resetting the Manual Reset Limit Switch ....................................................................................................... 50
4.7.3 Changing the Readout Between Fahrenheit and Celsius ................................................................................ 50
SECTION 5: SAFETY DEVICE TESTING .............................................................. 51
5.1 TESTING OF SAFETY DEVICES ......................................................................................................... 51
5.2 LOW GAS PRESSURE TEST .............................................................................................................. 52
5.2.1 LOW GAS PRESSURE TEST: BMK 750 – 2500 ................................................................................................... 52
5.2.2 LOW GAS PRESSURE TEST: BMK 3000 – 6000 Only ........................................................................................ 54
5.3 HIGH GAS PRESSURE TEST ............................................................................................................. 57
5.3.1 HIGH GAS PRESSURE TEST: BMK 750 – 2500 .................................................................................................. 57
OMM-0137_D • GF-211 7/16/2019 Technical Support (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 2 of 146
Benchmark Platinum-Edge: Operation-Service Manual
CONTENTS
5.3.2 HIGH GAS PRESSURE TEST: BMK 3000 – 6000 Only ........................................................................................ 59
5.4 LOW WATER LEVEL FAULT TEST ..................................................................................................... 62
5.5 WATER TEMPERATURE FAULT TEST .............................................................................................. 63
5.6 INTERLOCK TESTS ............................................................................................................................. 64
5.6.1 Remote Interlock Test..................................................................................................................................... 64
5.6.2 Delayed Interlock Test .................................................................................................................................... 64
5.7 FLAME FAULT TEST ............................................................................................................................ 65
5.8 AIR FLOW FAULT TESTS - BLOWER PROOF & BLOCKED INLET SWITCHES .............................. 66
5.8.1 Blower Proof Switch Test ................................................................................................................................ 66
5.8.2 Blocked Inlet Switch Test ................................................................................................................................ 68
5.9 SSOV PROOF OF CLOSURE SWITCH CHECK ................................................................................. 69
5.10 PURGE SWITCH OPEN DURING PURGE ........................................................................................ 70
5.11 IGNITION SWITCH OPEN DURING IGNITION ................................................................................. 72
5.12 SAFETY PRESSURE RELIEF VALVE TEST ..................................................................................... 72
SECTION 6: STANDALONE MODES OF OPERATION ......................................... 73
6.1 OUTDOOR RESET MODE ................................................................................................................... 73
6.1.1 Outdoor Air Temperature Sensor Installation ................................................................................................ 73
6.1.2 Outdoor Reset Mode Startup ......................................................................................................................... 74
6.2 CONSTANT SETPOINT MODE ........................................................................................................... 75
6.3 REMOTE SETPOINT MODE ................................................................................................................ 75
6.4 DIRECT DRIVE MODES....................................................................................................................... 76
6.5 AERCO CONTROL SYSTEM (ACS) .................................................................................................... 77
6.6 COMBINATION CONTROL SYSTEM (CCS) ....................................................................................... 78
6.6.1 Combination Control System Field Wiring ...................................................................................................... 79
6.6.2 Combination Control System Setup and Startup ............................................................................................ 79
SECTION 7: BOILER SEQUENCING TECHNOLOGY ............................................ 81
7.1 INTRODUCTION ................................................................................................................................... 81
7.1.1 Installation Notes............................................................................................................................................ 82
7.2 BST QUICK START CHART ................................................................................................................ 82
7.3 BST IMPLEMENTATION INSTRUCTION ............................................................................................ 83
7.3.1 Option 1 Constant Setpoint: Direct Wired Header Sensor ............................................................................. 83
7.3.2 Option 2 Constant Setpoint: Modbus Wired Header Sensor .......................................................................... 85
7.3.3 Option 3 Outdoor Reset: Direct Wired Header Sensor & Direct Wired Outdoor Sensor ............................... 87
7.3.4 Option 4 Outdoor Reset: Modbus Header Sensor & Modbus Outdoor Sensor .............................................. 89
7.3.5 Option 5 Remote Setpoint: Direct Wired Header Sensor & 4-20ma Setpoint Drive ...................................... 91
7.3.6 Option 6 Remote Setpoint: Direct Wired Header Sensor & Modbus Setpoint Drive ..................................... 93
7.3.7 Option 7 Remote Setpoint: Modbus Header Sensor & 4-20ma Setpoint Drive ............................................. 95
7.3.8 Option 8 Remote Setpoint: MODBUS Header Sensor & MODBUS Setpoint Drive ......................................... 97
SECTION 8: MAINTENANCE ............................................................................ 99
8.1 MAINTENANCE SCHEDULE ............................................................................................................... 99
8.2 IGNITER-INJECTOR – BMK 750 - 3000 ............................................................................................ 100
8.3 PILOT IGNITION ROD – BMK 5000 & 6000 ...................................................................................... 102
8.4 FLAME DETECTOR ........................................................................................................................... 102
8.5 O2 SENSOR ........................................................................................................................................ 103
8.5.1 Air Eductor Air Pump Maintenance – BMK 5000 & 6000 ........................................................................... 104
8.6 SAFETY DEVIC E T ESTING ............................................................................................................... 105
8.7 BURNER INSPECTION ...................................................................................................................... 105
8.8 CONDENSATE DRAIN TRAP ............................................................................................................ 108
OMM-0137_D • GF-211 7/16/2019 Technical Support • (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 3 of 146
Benchmark Platinum-Edge: Operation-Service Manual
CONTENTS
8.9 AIR FILTER CLEANING AND REPLACEMENT ................................................................................ 109
8.10 REFRACTORY REPLACEMENT – BMK 5000 & 6000 ONLY ......................................................................... 109
8.10.1 Rear Refractory Replacement .................................................................................................................... 110
8.10.2 Front Refractory Replacement .................................................................................................................. 112
8.11 SHUTTING BOILER DOWN FOR EXTENDED PERIOD ................................................................. 113
8.11.1 Benchmark 5000/6000 Long Term Blower Storage .................................................................................... 113
8.12 RETURNING THE BOILER TO SERVICE AFTER SHUTDOWN .................................................... 115
8.13 RECOMMENDED PERIODIC TESTING .......................................................................................... 116
8.14 RECOMMENDED SPARES ............................................................................................................. 118
SECTION 9: AERTRIM OPERATION ................................................................ 119
9.1 AERTRIM INTRODUCTION ............................................................................................................... 119
9.2 AERTRIM ACTI VATION ..................................................................................................................... 119
9.3 OPERATION DETAILS ....................................................................................................................... 120
9.4 AERTRIM O2 SENSOR AUTO CALIBRATION .................................................................................. 122
9.5 AERTRIM MENU VAL U ES AND DEFAULTS..................................................................................... 123
9.6 AERTRIM MAINTENANCE AND TROUBLESHOOTING ................................................................... 129
SECTION 10: TROUBLESHOOTING .................................................................. 131
10.1 INTRODUCTION ............................................................................................................................... 131
10.2 ADDITIONAL FAULTS WITHOUT SPECIFIC FAULT MESSAGES ................................................ 143
NOTES: .................................................................................................. 145
OMM-0137_D • GF-211 7/16/2019 Technical Support (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 4 of 146
Benchmark Platinum-Edge: Operation-Service Manual
INPUT RANGE (BTU/HR.)
OUTPUT RANGE (BTU/HR.)
FORWARD

FOREWORD

The AERCO Benchmark (BMK) 750 through 6000 natural gas and propane fueled boilers are modulating and condensing units. They represent a true industry advance that meets the needs of today's energy and environmental concerns. Designed for application in any closed loop hydronic system, the Benchmark's modulating capability relates energy input directly to fluctuating system loads. These BMK models provide extremely high efficiency operation and are ideally suited for modern low temperature, as well as, conventional heating systems.
The Benchmark models operate within the following input and output ranges:
IMPORTANT!
Unless otherwise specified:
All descriptions provided in this document apply to the Benchmark Platinum Series of boiler.
All measurements apply to both natural gas and propane models, unless otherwise
specified.
Benchmark Boiler Intake and Output Ranges
MODEL
MINIMUM MAXIMUM MINIMUM MAXIMUM
BMK 750 50,000 (14.6 kW) 750,000 (220 kW) 47,750 (14 kW) 716,250 (210 kW)
BMK 1000 50,000 (14.6 kW) 1,000,000 (293 kW) 48,300 (14.15 kW) 968,000 (284 kW)
BMK 1500 75,000 (22 kW) 1,500,000 (440 kW) 64,500 (18.9 kW) 1,395,000 (409 kW)
BMK 2000 100,000 (29.3 kW) 2,000,000 (586 kW) 86,000 (25.2 kW) 1,860,000 (545 kW)
BMK 2500 167,000 (48.9 kW) 2,500,000 (732 kW) 144,000 (42.2 kW) 2,395,000 (702 kW)
BMK 3000 200,000 (58.6 kW) 3,000,000 (879 kW) 174,000 (51.0 kW) 2,874,000 (842 kW)
BMK 5000 400,000 (117 kW) 5,000,000 (1465 kW) 348,000 (102 kW) 4,750,000 (1392 kW)
BMK 6000 400,000 (117 kW) 6,000,000 (1758 kW) 348,000 (102 kW) 5,700,000 (1670 kW)
The output of the boiler is a function of the unit’s firing rate (valve position) and return water temperature.
When installed and operated in accordance with this Instruction Manual, the BMK 750 – 2000 and 5000 & 6000 comply with the NOx emission standards outlined in: South Coast Air Quality Management District (SCAQMD), Rule 1146.2. In addition, the BMK 2500 – 6000 comply with the Bay Area Air Quality Management District regulation 9, Rule 7.
Whether used in singular or modular arrangements, the BMK boilers offer the maximum venting flexibility with minimum installation space requirements. These boilers are Category II and IV, positive pressure appliances. Single and/or multiple breeched units are capable of operation in the following vent configurations:
Room Combustion Air:
o Vertical Discharge o Horizontal Discharge
Ducted Combustion Air:
o Vertical Discharge o Horizontal Discharge
OMM-0137_D • GF-211 7/16/2019 Technical Support (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 5 of 146
Benchmark Platinum-Edge: Operation-Service Manual
Symbol rate, or simply the number of distinct symbol changes British Thermal Unit. A unit of energy approximately equal to the
Double Block and Bleed, a gas trains containing 2 Safety Shutoff
A control system developed by AERCO and currently used in all
FORWARD These boilers are capable of being vented utilizing Polypropylene and AL29-4C vent systems. In
addition, the BMK 750 & 1000 models are also approved for PVC and CPVC, vent systems (excluding the state of Massachusetts).
The Benchmark's advanced electronics are available in several selectable modes of operation offering the most efficient operating methods and energy management system integration.
AERCO Technical Terminology Meanings
TERMINOLOGY MEANING
A (Amp) Ampere ACS AERCO Control System, AERCO’s boiler management systems ADDR Address AGND Anal og Ground ALRM Alarm ANSI American National Standards Institute, ASME American Society of Mechanical Engineers AUX Auxiliary
BAS
Baud Rate
Building Automation System, often used interchangeably with EMS (see below)
(signaling events) transmitted per second. It is not equal to bits per
second, unless each symbol is 1 bit long. BMK (Benchmark) AERCO’s Benchmark series boilers BMS or BMS II AERCO Boiler Management Systems
BLDG (Bldg) Building BST AERCO on-board Boiler Sequencing Technology
BTU
heat required to raise 1 pound (0.45 kg) of water 1°F (0.55 °C) BTU/HR BTUs per Hour (1 BTU/hr = 0.29 W)
CCS Combination Control System CFH Cubic Feet per Hour (1 CFH = 0.028 m3/hr) CO Carbon Monoxide COMM (Comm) Communication Cal. Calibration CNTL Control CPU Central Processing Unit
DBB
Valves (SSOVs) and a solenoid operated vent valve. DIP Dual In-Line Package, a type of switch
ECU Electronic Control Unit (O2 sensor) Edge Controller
OMM-0137_D • GF-211 7/16/2019 Technical Support • (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 6 of 146
Benchmark Platinum boilers.
Benchmark Platinum-Edge: Operation-Service Manual
EMS
Energy Management System; often used interchangeably with BAS
LN
Low Nitrogen Oxide
MA (mA)
Milliampere (1 thousandth of an ampere)
MAX (Max)
Maximum
MBH
1000 BTUs per Hour
duplex data transmission protocol developed by AEG
NO (N.O.)
Normally Open
NOx
Nitrogen Oxide
NPT
National Pipe Thread
O2
Oxygen
FORWARD
AERCO Technical Terminology Meanings
TERMINOLOGY MEANING
FM Factor y Mutual. Used to define boiler gas trains. GF-xxxx Gas Fired (an AERCO document numbering system) GND Ground HDR Header Hex Hexadecimal Number (0 – 9, A – F) HP Horse Power HX Heat Exchanger Hz Hertz (Cycles Per Second) I.D. Inside Diameter IGN Ignition IGST Board Ignition/Stepper Board, contained in Edge Controller INTLK (INTL’K) Interlock I/O Input/Output I/O Box Input/Output (I/O) Box currently used on Benchmark boilers IP Internet Protocol ISO International Organization for Standardization Lbs. Pounds (1 lb = 0.45 kg) LED Light Emitting Diode
MIN (Min) Minimum Modbus®
A serial, half-
Modicon NC (N.C.) Normally Closed
O.D. Outside Diameter OMM, O&M Operation and Maintenance Manual onAER
AERCO’s on-line remote monitoring s y stem PCB Printed Circuit Board PMC Board Primary Micro-Contr oller (PMC) board, contained in the Edge P/N Part Number
OMM-0137_D • GF-211 7/16/2019 Technical Support • (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 7 of 146
Benchmark Platinum-Edge: Operation-Service Manual
POC
Proof of Closure
duplex (FDX) transmission of data based
SPDT
Single Pole Double Throw, a type of switch
SSOV
Safety Shut Off Valve
TEMP (Temp)
Temperature
prevent reflections that may cause invalid data in the
FORWARD
AERCO Technical Terminology Meanings
TERMINOLOGY MEANING
PPM Part s per Million PSI Pounds per Square Inch (1 PSI = 6.89 kPa) PTP Point-to-Point (usually over RS232 networks) P&T Pressure and Temperature ProtoNode Hardware interface between BAS and a boiler or water heater PVC Poly Vinyl Chloride, a common synthetic plastic PWM Pulse Width Modulation REF (Ref) Reference RES. Resistive RS232
(or EIA-232) RS485
(or EIA-485)
A standard for serial, full-
on the RS232 Standard
A standard for serial, half-duplex (HDX) transmission of data based
on the RS485 Standard RTN (Rtn) Return SETPT (Setpt) Setpoint Temperature SHLD (Shld) Shield
A resistor placed at each end of a daisy-chain or multi-drop network Terminating Resistor
in order to
communication Tip-N-Tell A device that indicates if a package was tipped during shipping UL A business that tests and validates products VAC Volts, Alternating Current VDC Volts, Direct Current VFD Variable Frequency Drive VPS Valve Proving System W Watt W.C. Water Column, a unit of pressure (1 W.C. = 249 Pa) µA Micro amp (1 millionth of an ampere)
OMM-0137_D • GF-211 7/16/2019 Technical Support • (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 8 of 146
Benchmark Platinum-Edge: Operation-Service Manual

SECTION 1: SAFETY PRECAUTIONS

SECTION 1: SAFETY PRECAUTIONS

1.1 WARNINGS & CAUTIONS

Installers and operating personnel MUST, at all times, observe all safety regulations. The following warnings and cautions are general and must be given the same attention as specific precautions included in these instructions. In addition to all the requirements included in this AERCO Instruction Manual, the installation of units MUST conform with local building codes, or, in the absence of local codes, ANSI Z223.1 (National Fuel Gas Code Publication No. NFPA-54) for gas-fired boilers and ANSI/NFPASB for LP gas-fired boilers. W here applicable, the equipment shall be installed in accordance with the current Installation Code for Gas Burning Appliances and Equipment, CSA B149.1, and applicable Provincial regulations for the class; which should be carefully followed in all cases. Authorities having jurisdiction should be consulted before installations are made.
See section 1.4 for important information regarding installation of units within the Commonwealth of Massachusetts.
IMPORTANT!
This manual is an integral part of the product and must be maintained in legible condition. It must be given to the user by the installer and kept in a safe place for future reference.
WARNING!
Do not use matches, candles, flames, or other sources of ignition to check for gas leaks.
Fluids under pressure may cause injury to personnel or damage to equipment when
released. Be sure to shut off all incoming and outgoing water shutoff valves. Carefully decrease all trapped pressures to zero before performing maintenance.
Before attempting to perform any maintenance on the unit, shut off all g as and electrical inputs to the unit.
The exhaust vent pipe of the unit operates under a positive pressure and therefore must be completely sealed to prevent leakage of combustion products into living spaces.
Electrical voltages up to 120 VAC (BMK 750 – 2000) and 208 or 460 VAC (BMK 2500/3000) or 208, 460 or 575 VAC (BMK 5000 & 6000) and 24 vo lts AC may be used
in this equipment. Therefore the cover on the unit’s power box (located behind the front panel door) must be installed at all times, except during maintenance and servicing.
A single-pole (120 VAC units) or three-pole (220 VAC and higher units) switch must be installed on the electrical supply line of the unit. The switch must be installed in an easily accessible position to quickly and safely disconnect electrical service. Do not affix switch to unit sheet metal enclosures.
CAUTION!
Many soaps used for gas pipe leak testing are corrosive to metals. The piping must be rinsed thoroughly with clean water after leak checks have been completed.
DO NOT use this boiler if any part has been under water. Call a qualified service technician to inspect and replace any part that has been under water.
OMM-0137_D • GF-211 7/16/2019 Technical Support • (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 9 of 146
Benchmark Platinum-Edge: Operation-Service Manual
VALVE
CLOSED
SECTION 1: SAFETY PRECAUTIONS

1.2 EMERGENCY SHUTDOWN

If overheating occurs or the gas supply fails to shut off, close the manual shutoff valve (Figure 1-
1) located external to the unit.
NOTE:
The Installer must identify and indicate the location of the emergency shutdown manual gas valve to operating personnel.
VALVE
OPEN
Figure 1-1: External Manual Gas Shutoff Valve
In addition, to ensure safety an emergency shutdown procedure that addresses the following points should be designed and implement at the site:
For automatically operated unattended boilers located in a boiler room, provide a manually operated remote shutdown switch or circuit breaker located just inside or outside each boiler room door. Design the system so activation of the emergency shutdown switch or circuit breaker will immediately shut off the fuel supply to the unit(s).
For automatically operated unattended boilers in a location other than a boiler room, provide a manually operated remote shutdown switch or circuit breaker marked for easy identification at a location readily accessible in the event of boiler mis-operation.
Design the system so activation of the emergency shutdown switch or circuit breaker will immediately shut off the fuel.
For boilers monitored and/or operated from a continuously occupied control room, provide an emergency shutdown switch in the control room that is hard-wired to immediately shut off the fuel upon activation.

1.3 PROLONGED SHUTDOWN

If there is an emergency, turn off the electrical power supply to the boiler and close the manual gas valve located upstream from the unit. The installer must identify the emergency shut-off device.
If the unit is being shut down for an extended period of time, such as a year or more, complete the instructions in Section 8.11: Shutting Boiler Down For Extended Period.
When returning a unit to service after a prolonged shutdown, it is recommended that the instructions in Section 4: Initial Startup Procedures and Section 5: Safety Device Testing be performed to verify that all system-operating parameters are correct.
.
OMM-0137_D • GF-211 7/16/2019 Technical Support • (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 10 of 146
Benchmark Platinum-Edge: Operation-Service Manual
Requirements For Massachusetts Installations
Boiler Installations within the Commonwealth of Massachusetts must conform to the
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling,
alled on each additional level of the dwelling,
be the responsibility of the property owner to secure the services of qualified licensed
the above requirements; provided, however, that during said thirty (30) day period, a
Each carbon monoxide detector as
accordance with the above provisions shall comply with NFPA 720 and be
VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS". (Continued)
SECTION 1: SAFETY PRECAUTIONS

1.4 IMPORTANT – FOR MASSACHUSETTS INSTALLATIONS

following requirements:
Boiler must be installed by a plumber or a gas fitter who is licensed within the
Commonwealth of Massachusetts.
Prior to unit operation, the complete gas train and all connections must be leak
tested using a non-corrosive soap.
The vent termination must be located a minimum of 4 feet above grade level. If
side-wall venting is used, the installation must conform to the following requirements extracted from 248 CMR 5.08 (2):
building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS: At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is inst building or structure served by the side wall horizontal vented gas fueled equipment. It shall
professionals for the installation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with
battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS: required in
ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE: A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS
OMM-0137_D • GF-211 7/16/2019 Technical Support (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 11 of 146
Benchmark Platinum-Edge: Operation-Service Manual
Requirements For Massachusetts Installations
observes carbon monoxide detectors and signage installed in accordance with the
venting system design or venting system components with the equipment, the instructions
When the manufacturer of a Product Approved side wall horizontally vented gas fueled
nd the
SECTION 1: SAFETY PRECAUTIONS
4. INSPECTION: The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector
provisions of 248 CMR 5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Section 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a
provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED.
equipment does not provide the parts for venting the flue gases, but identifies "special venting systems", the following requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The "special venting systems" shall be Product Approved by the Board, a instructions for that system shall include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
……………….[End of Extracted Information From 248 CMR 5.08 (2)]…………………
OMM-0137_D • GF-211 7/16/2019 Technical Support (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 12 of 146
Benchmark Platinum-Edge: Operation-Service Manual
temperature
temperature
1 2 3 6 7
10
11 4 5
9
8
SECTION 2: OPERATION

SECTION 2: EDGE CONTROLLER OPERATION

2.1 INTRODUCTION

This section provides a brief outline of how to gain access to Benchmark Boiler’s Edge Controller functionality. Full instructions for using the Edge Controller to setup, configure and operate a Benchmark Boiler are included in the Edge Controller Manual.
NOTE: The Edge Controller Manual is document number OMM-0139, GF-213.
The Edge Controller is shown below. This panel contains all of the controls, indicators and displays necessary to operate, adjust and troubleshoot the boiler.
The Edge Controller’s front panel consists of a touchscreen display along with a variety of indicators and buttons.
Multi-Function Bar, shows either:
1
Fire Rate
Valve Position
Parameter Indicator for both temperature read-outs:
2
LEFT: Inlet or Setpoint temperature
RIGHT: Outlet or System Header
Temperature scale indicator: Fahrenheit
3
or Celsius Configurable temperature read-outs (2):
LEFT: Inlet or Setpoint
4
RIGHT: Outlet or System Header
Operation Mode Indicators (2):
LEFT: Demand or Manual
5
RIGHT: Manager or Client (BST
6 Edge Controller Touchscreen 7 Soft Keys 8 onAER Indicator Light
Ready Light
9
10 Enable/Disable Switch
Low Water Level Buttons (2):
TEST: Initiates Low Water test
11
RESET: Resets unit after Low Water
temperature
only)
test
Figure 2-1 Edge Controller Front Panel
OMM-0137_D • GF-211 7/16/2019 Technical Support (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 13 of 146
Benchmark Platinum-Edge: Operation-Service Manual
SECTION 2: OPERATION

2.2 Login and Password Entry

The Edge Controller has multiple levels of password protection.
Level Password Description
1 No password The default. Many parameters are visible but “Read Only.” 2 159
A higher-level password is reserved AERCO Master Technicians (AMT). It is distributed on an individual basis.
To enter a password:
1. On the Edge Controller, go to Password screen appears.
2. Use the number keypad to enter the password (each number appears as a X), then pr es s Save. You will have access to the functionality associated with the level of the password entered.
Allows routine maintenance to be performed. Appropriate for AERCO Trained technicians (ATT).
Main Menu Advanced Setup Access. The Enter
Figure 2.2: Enter Password Screen
3. Once you have successfully logged into the system, the Main Menu appears. All Edge functionality is accessed through one of the six Main Menu items.
Figure 2-3: Edge Controller Main Menu
NOTE:
Full instruct ions for using the Edge Controller are in the Edge Controller Manual (GF-213).
OMM-0137_D • GF-211 7/16/2019 Technical Support • (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 14 of 146
Benchmark Platinum-Edge: Operation-Service Manual
SECTION 3 - START SEQUENCE

SECTION 3: START SEQUENCE

3.1 INTRODUCTION

The information in this section provides a guide to starting the Benchmark Boiler using the Edge Controller. It is imperative that the initial startup of this unit be performed by factory trained personnel. Operation prior to initial startup by factory trained personnel may void the equipment warranty. In addition, the following WARNINGS and CAUTIONS must be observed at all times.
WARNING!
All of the installation procedures in Section 2: Installation of the Benchmark Platinum- Edge: INSTALLATION Manual (GF-210) must be completed before the initial start-up of
the unit.
Electrical voltages up to 120 VAC (BMK 750 – 2000) and 208 or 460 VAC (BMK 2500/3000) or 208, 460 or 575 VAC (BMK 5000 & 6000) and 24 vo lts AC may be used
in this equipment. It must be serviced only by factory certified service technicians.
Do not attempt to dry fire the unit. Starting the unit without a full water level can seriously damage the unit and may result in injury to personnel or property damage. This situation will void any warranty.
Initial startup of the unit must be be performed by AERCO factory trained personnel. Operation prior to initial startup by factory trained personnel may void the equipment warranty. In addition, the following WARNINGS and CAUTIONS must be observed at all times.

3.2 START SEQUENCE

When the Edge Controller Enable/Disable switch is set to t he Enable position, it checks all pre­purge safety switches to ensure they are closed. These switches include:
High Water Temperature switch
High Gas Pressure switch
Low Gas Pressure switch
Low Water Level switch
Safety Shut-Off Valve (SSOV) Proof of Closure (POC) switch
NOTE:
The Blocked Inl et and downstream B lower Proof switches are not checked prior to starting the pre-purge.
If all of the above switches are closed, the READY light (above the Enable/Disable switch) will light when the switch is in the Enable position and the unit will be in the STANDBY mode.
NOTE:
If any of the Pre-Purge safety device switches are open, or the required conditions are not observed throughout the start sequence, appropriate fault messages will be displayed.
When there is a demand for heat, the following events occur:
OMM-0137_D • GF-211 7/16/2019 Technical Support • (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 15 of 146
Benchmark Platinum-Edge: Operation-Service Manual
SSOV
NATURAL GAS INLET
NATURAL GAS INLET
SECTION 3 - START SEQUENCE
Start Sequence
1. The Controller’s red DEMAND LED status indicator will light.
2. The unit checks all five pre-purge safety switches listed at the beginning of this section. The Edge Controller’s ignition sequence screen walks you through the ignition screens and demonstrates (or highlights) which switches are not met. SSOV locations are shown in Figure 3-1a thro ugh 3-1d.
TO AIR/FUEL VALVE
MANUAL SHUT-OFF VALVE
LOW GAS PRESSURE SWITCH
Figure 3-1a: BMK 750 & 1000 SSOV Location (P/N 22322 shown)
TO
AIR/FUEL
MANUAL SHUT-OFF VALVE
VALVE
SSOV
HIGH GAS PRESSURE SWITCH
LOW GAS PRESSURE SWITCH
Figure 3-1b: BMK 1500 & 2000 SSOV Location (P/N 22314 shown)
OMM-0137_D • GF-211 7/16/2019 Technical Support (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 16 of 146
Benchmark Platinum-Edge: Operation-Service Manual
VALVE
NATURAL GAS INLET
LOW GAS SWITCH
NATURAL GAS INLET
SECTION 3 - START SEQUENCE
Start Sequence
SSOV
TO AIR/FUEL
MANUAL SHUT-OFF VALVE
VALVE
LOW GAS PRESSURE SWITCH
Figure 3-1c: BMK 2500: SSOV Location (P/N 22318 shown)
TO AIR/FUEL
MANUAL
SHUT-OFF VALVE
HIGH GAS PRESSURE
SWITCH
Figure 3-1d: BMK 3000: SSOV L o cation (P/N 22310 shown)
SSOV
PRESSURE
OMM-0137_D • GF-211 7/16/2019 Technical Support • (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 17 of 146
Benchmark Platinum-Edge: Operation-Service Manual
STEPPER MOT OR
100
UPSTREAM
TO AIR/FUEL
GAS INLET
MANUAL SHUT-
DOWNSTREAM
HIGH GAS
UPSTREAM LOW GAS
SECTION 3 - START SEQUENCE
Start Sequence
SSOV
SSOV WITH
VALVE
OFF VALVE
POC
- BMK 6000: 10.5” W.C., 2.6 kPa
- BMK 5000: 11.0” W.C., 2.7 kPa
PRESSURE SWITCH
PRESSURE SWITCH
- BMK 6000: 8.5” W.C., 2.1 kPa
- BMK 5000: 8.0” W.C., 2.0 kPa
Figure 3-1e: BMK 5000-6000: SSOV Location
3. The Auxiliary Delay occurs for a configurable length of time and the Delayed Interlocks are closed.
4. Once all required safety device switches are closed, a purge cycle is initiated and the following events occur:
a. The Blower relay energizes and turns on the blower. b. The Air/Fuel Valve rotates to the full-open purge position and closes purge position
switch. The dial on the Air/Fuel Valve (Figure 3-2a and 3-2b) will read 100 to indicate that it is full-open (100%).
c. The Fire Rate bargraph on the Controller’s front face shows 100%.
AIR INLET
OMM-0137_D • GF-211 7/16/2019 Technical Support • (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 18 of 146
Figure 3-2a: BMK 750 & 1000 Air/Fuel Valve in Purge Position
TO
BLOWER
Benchmark Platinum-Edge: Operation-Service Manual
TO BLOWER
STEPPER MOTOR
AIR IN
SECTION 3 - START SEQUENCE
Start Sequence
PURGE
VALVE POSITION
DIAL AT 100%
Figure 3-2b: BMK 1500 – 6000 Air/Fuel Valve In Purge Position
5. Next, the Blower Proof and Blocked Inlet switches close (Figure 3-4a and 3-4b). On the Ignition Sequence screen the Purging indicator turns grey while purging is underway (Figure 3-3) and Purge Timer displays the purge cycle’s elapsed time in seconds.
Figure 3-3: Ignition Sequence Screen – Purging
BLOWER PROOF SWITCH
BLOCKED INLET SWITCH
Figure 3-4a: BMK 750 & 1000 Blower Proof Switch
OMM-0137_D • GF-211 7/16/2019 Technical Support (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 19 of 146
Benchmark Platinum-Edge: Operation-Service Manual
fire (Ignition) position and closes the ignition
cycle turns on the
the Ignition
AIR/FUEL VALVE OUTLET TO BLOWER
BLOWER
SWITCH
TRAIN
SECTION 3 - START SEQUENCE
Start Sequence
PROOF
AIR/FUEL VALVE INLET FROM GAS
BLOCKED
INLET
SWITCH
Figure 3-4b: BMK 1500 – 6000 Blower Proof Switch
6. Upon completion of the purge cycle, the Controller initiates an ignition cycle and the following events occur:
a) The Air/Fuel Valve rotates to the low-
switch. The Dial on the Air/Fuel Valve (Figure 3-5) will read between 25 and 35 to indicate that the valve is in the low fire position.
b) The Spark Cleaning cycle begins (default duration = 7 sec.) and the Ignition Sequence
screen’s Spark Cleaning indicator (Figure 3-3) turns grey. This ignition transformer to produce a spark (with no gas flowing) to remove moisture and carbon buildup from the spark element. For the duration of this cycle, the Controller displays the Cleaning Igniter status message.
c) Following the Spark Cleaning cycle, power is applied to the gas S afety Shut -off Val ve
(SSOV). When the SSOV indicates the Gas Valve is OPEN (POC) and Sequence screen’s Ignition indicator (Figure 3-3) turns grey.
d) If no spark is present 3 seconds into the ignition trial, the Controller aborts th e Igni tion
Cycle and shuts down the boiler. Refer to Section 10: Troubleshooting in this g uide for guidance if this occurs.
OMM-0137_D • GF-211 7/16/2019 Technical Support • (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 20 of 146
Benchmark Platinum-Edge: Operation-Service Manual
TO BLOWER
AIR IN
25% to 35%
STEPPER MOTOR
SECTION 3 - START SEQUENCE
Start Sequence
IGNITION
VALVE POSITIO N
DIAL AT
Figure 3-5: Air/Fuel Valve In Ignition Position
7. Up to 4 seconds are allowed for ignition to be detected. The ignition circuit is turned off one second after flame is detected.
8. After 2 seconds of continuous flame, the flame strength is indicated. After 5 seconds, the Unit Status screen appears.
9. With the unit firing properly, it will be controlled by the temperature control circuitry. The boiler’s fire rate or valve position (depending on which was chosen in Section 6.2.2: Front Panel Configuration of the Edge Controller Manual) will continuously display on the Controller’s bargraph.
10. Once the demand for heat has been satisfied, the Edge Controller will turn off the SSOV
gas valve. The blower relay will be deactivated and the Air/Fuel Valve wil l be closed. Standby is displayed.
OMM-0137_D • GF-211 7/16/2019 Technical Support • (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 21 of 146
Benchmark Platinum-Edge: Operation-Service Manual
Operating State
Pre-purge
PFEP
MFEP
Standby
T = 0
T = 30
T = 37
T = 44
Run
Component
PFEP
MFEP
C-More Controller
Scanner Power
Ignition Power
SSOV Power
Pilot Valve Closed
Pilot Valve Open
Ignition Transformer Off
Ignition Transformer On
UV Scanner Powered
UV Scanner "Ignored"
UV Scanner In Use
Relay 1 Coil
Relay 1 C-NC
Relay 1 C-NO
Relay 2 Coil Power from R1
Relay 2 Coil Power from SKP 15 POC
Relay 2 C-NC
Relay 2 C-NO
SKP15 Power from R1 Contacts
SKP15 Power from R2 contact and POC C-NO
SKP15 Proof of Closure C-NC
SKP15 Proof of Closure C-NO
SKP25
Power through R1
Power through R2 and AUX
Proof of Closure C-NC
Proof of Closure C-NO
SECTION 3 - START SEQUENCE
BMK 5000 & 6000 Function Timing Chart For Proved Pilot Control System
OMM-0137_D • GF-211 7/16/2019 Technical Support (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 22 of 146
Benchmark Platinum-Edge: Operation-Service Manual
TABLE 3-1a: Start/Stop Levels – NATURAL GAS
Level:
Level:
Position
TABLE 3-1b: Start/Stop Levels – PROPANE GAS
750
1000
1500
2000
2500
3000
5000
6000
Level:
Level:
SECTION 3 - START SEQUENCE

3.3 START/STOP LEVELS

The start and stop levels are the Air/Fuel Valve positions (% open) that start and stop the unit, based on load. These levels are Factory preset as follows:
Start
Stop
Ignition
Start
Stop
Ignition Position
BMK
750
22% 22% 20% 24% 24% 20% 24% 24%
18% 18% 16% 18% 16% 14% 18% 18%
35% 35% 29% 29% 29% 29% 35% 50%
BMK
22% 22% 20% 24% 26% 22% 24% 24%
18% 18% 16% 18% 18% 14% 18% 18%
35% 35% 29% 29% 29% 29% 35% 50%
BMK 1000
BMK
BMK 1500
BMK
BMK 2000
BMK
BMK 2500
BMK
BMK 3000
BMK
BMK 5000
BMK
BMK 6000
BMK
Normally, these settings do not require adjustment. Note that the energy input of the boiler is not linearly related to the Air/Fuel Valve position.
OMM-0137_D • GF-211 7/16/2019 Technical Support • (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 23 of 146
Benchmark Platinum-Edge: Operation-Service Manual
TABLE 3-2a: BMK 750/1000 Air/Fuel Valve Position – NATURAL GAS
CAPACITY)
BMK 750
BMK 1000
BMK 750
BMK 1000
0% 0 0
0
0
10% 0 0
0
0
18% (Stop Level)
50,000 (14.7 kW)
50,000 (14.7 kW)
6.7%
5%
20%
52,000 (15.2 kW)
54,000 (15.8 kW)
6.9%
5.4%
30%
108,000 (31.7 kW)
140,000 (41.0 kW)
14%
14%
40%
246,000 (72.1 kW)
297,000 (87.0 kW)
33%
30%
50%
369,000 (108.1 kW)
443,000 (126.9 kW)
49%
44%
60%
465,000 (136.3 kW)
564,000 (165.3 kW)
62%
56%
70%
554,000 (162.4 kW)
660,000 (193.4 kW)
74%
66%
80%
637,000 (186.7 kW)
789,000 (231.2 kW)
85%
79%
90%
733,000 (214.8 kW)
933,000 (273.4 kW)
98%
93%
100%
750,000 (219.8 kW)
1,000,000 (293.1 kW)
100%
100%
TABLE 3-2b: BMK 750/1000 Air/Fuel Valve Position – PROPANE GAS
BMK 750
BMK 1000
BMK 750
BMK 1000
0% 0 0
0
0
10% 0 0
0
0
18% (Stop Level)
50,000 (14.7 kW
50,000 (14.7 kW
6.7%
5.0%
20%
71,000 (20.8 kW)
71,000 (20.8 kW)
9.5%
7.1%
30%
128,000 (37.5 kW)
181,000 (53.0 kW)
17%
18%
40%
373,000 (109.3 kW)
400,000 (117.2 kW)
50%
40%
50%
508,000 (148.9 kW)
562,000 (164.7 kW)
68%
56%
60%
565,000 (165.6 kW)
703,000 (206.0 kW)
75%
70%
70%
621,000 (182.0 kW)
791,000 (231.8 kW)
83%
79%
80%
660,000 (193.4 kW)
865,000 (253.5 kW)
88%
87%
90%
723,000 (211.9 kW)
963,000 (282.2 kW)
96%
96%
100%
750,000 (219.8 kW)
1,000,000 (293.1 kW)
100%
100%
SECTION 3 - START SEQUENCE

3.4 START/STOP LEVELS – AIR/FUEL & ENERGY INPUT

The Tables below show the relationship between the energy input and Air/Fuel Valve position for the BMK models covered in this document.

3.4.1 BMK 750/1000 Air/Fuel Valve Position and Energy Input

AIR/FUEL VALVE
POSITION (%
OPEN)
Air/Fuel Valve
Position (%
Open)
ENERGY INPUT
(BTU/HR)
Energy Input
(BTU/Hr)
BOILER ENERGY
INPUT (% OF FULL
Boiler Energy Input (% of Full Capacity)
OMM-0137_D • GF-211 7/16/2019 Technical Support (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 24 of 146
Benchmark Platinum-Edge: Operation-Service Manual
TABLE 3-3a: BMK 1500 Air/Fuel Valve Position – NATURAL GAS
AIR/FUEL VALVE POSITION
(% OPEN)
ENERGY INPUT
(BTU/HR)
BOILER ENERGY INPUT
(% OF FULL CAPACITY)
16% (Stop Level)
75,000 (22.3 kW)
5.0%
20%
127,000 (37.2 kW)
8.5%
30%
366,000 (107.2 kW)
24.4%
40%
629,000 (184.3 kW)
41.9%
50%
822,000 (240.9 kW)
54.7%
60%
977,000 (286.2 kW)
65.0%
70%
1,119,000 (327.9 kW)
74.5%
80%
1,255,000 (367.7 kW)
83.5%
90%
1,396,000 (409.0 kW)
92.9%
100%
1,502,000 (440.1 kW)
100%
TABLE 3-3b: BMK 1500 Air/Fuel Valve Position – PROPANE GAS
AIR/FUEL VALVE POSITION
(% OPEN)
ENERGY INPUT
(BTU/HR)
BOILER ENERGY INPUT
(% OF FULL CAPACITY)
18% (Stop Level)
75,000
5.0%
20%
93,700
6.2%
30%
254,000
16.9%
40%
505,000
33.7%
50%
680,000
45.3%
60%
807,000
53.8%
70%
947,000
63.1%
80%
1,157,000
77.1%
90%
1,379,000
91.9%
100%
1,503,000
100%
SECTION 3 - START SEQUENCE

3.4.2 BMK 1500 Air/Fuel Valve Position and Energy Input

OMM-0137_D • GF-211 7/16/2019 Technical Support (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 25 of 146
Benchmark Platinum-Edge: Operation-Service Manual
TABLE 3-4a: BMK 2000 Air/Fuel Valve Position – NATURAL GAS
AIR/FUEL VALVE POSITION
(% OPEN)
ENERGY INPUT
(BTU/HR)
BOILER ENERGY INPUT (% OF FULL CAPACITY)
18% (Stop Level)
100,000 (29.3 kW)
5.7%
20%
143,000 (41.9 kW)
11%
30%
388,000 (113.7 kW)
23%
40%
759,000 (222.4 kW)
37%
50%
1,069,000 (313.2 kW)
51%
60%
1,283,000 (375.9 kW)
61%
70%
1,476,000 (432.5 kW)
74%
80%
1,675,000 (490.1 kW)
83%
90%
1,833,000 (537.1 kW)
93%
100%
2,000,000 (586.0 kW)
100%
TABLE 3-4b: BMK 2000 Air/Fuel Valve Position – PROPANE GAS
AIR/FUEL VALVE POSITION
(% OPEN)
ENERGY INPUT
(BTU/HR)
BOILER ENERGY INPUT
(% OF FULL CAPACITY)
18% (Stop Level)
100,000
5.0%
20%
126,600
6.3%
30%
363,000
18.2%
40%
677,000
33.9%
50%
898,000
44.9%
60%
1,070,000
53.5%
70%
1,242,000
62.1%
80%
1,523,000
76.2%
90%
1,845,000
92.3%
100%
2,000,000
100%
SECTION 3 - START SEQUENCE

3.4.3 BMK 2000 Air/Fuel Valve Position and Energy Input

OMM-0137_D • GF-211 7/16/2019 Technical Support (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 26 of 146
Benchmark Platinum-Edge: Operation-Service Manual
TABLE 3-5a: BMK 2500 Air/Fuel Valve Position – NATURAL GAS, Single Fuel
AIR/FUEL VALVE POSITION
(% OPEN)
ENERGY INPUT
(BTU/HR)
BOILER ENERGY INPUT
(% OF FULL CAPACITY)
16% (Stop Level)
167,000 (48.9 kW)
6.7%
30%
430,000 (126.0 kW)
17%
40%
770,000 (225.7 kW)
31%
50%
1,070,000 (313.6 kW)
43%
60%
1,440,000 (422.0 kW)
58%
70%
1,815,000 (531.9 kW)
73%
80%
2,030,000 (594.9 kW)
81%
90%
2,300,000 (674.1 kW)
92%
100%
2,500,000 (732.7 kW)
100%
TABLE 3-5b: BMK 2500 Air/Fuel Valve Position – PROPANE GAS
AIR/FUEL VALVE POSITION
(% OPEN)
ENERGY INPUT
(BTU/HR)
BOILER ENERGY INPUT
(% OF FULL CAPACITY)
18% (Stop Level)
155,000
6.2%
30%
400,000
16%
40%
808,000
32%
50%
1,055,000
42%
60%
1,330,000
53%
70%
1,671,000
67%
80%
1,998,000
80%
90%
2,280,000
91%
100%
2,500,000
100%
SECTION 3 - START SEQUENCE

3.4.4 BMK 2500 Air/Fuel Valve Position and Energy Input

OMM-0137_D • GF-211 7/16/2019 Technical Support (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 27 of 146
Benchmark Platinum-Edge: Operation-Service Manual
TABLE 3-6a: BMK 3000 Air/Fuel Valve Position – NATURAL GAS
AIR/FUEL VALVE POSITION
(% OPEN)
ENERGY INPUT
(BTU/HR.)
BOILER ENERGY INPUT (% OF FULL CAPACITY)
14% (Stop Level)
200,000 (58.6 kW)
6.7%
30%
520,000 (152 kW)
17%
40%
880,000 (258 kW)
29%
50%
1,270,000 (372 kW)
42%
60%
1,680,000 (492 kW)
56%
70%
2,100,000 (615 kW)
70%
80%
2,390,000 (700 kW)
80%
90%
2,650,000 (777 kW)
88%
100%
3,000,000 (879 kW)
100%
TABLE 3-6b: BMK 3000 Air/Fuel Valve Position – PROPANE GAS
AIR/FUEL VALVE POSITION
(% OPEN)
ENERGY INPUT
(BTU/HR)
BOILER ENERGY INPUT
(% OF FULL CAPACITY)
18% (Stop Level)
200,000
6.7%
30%
520,000
17%
40%
920,000
31%
50%
1,270,000
42%
60%
1,570,000
52%
70%
1,960,000
65%
80%
2,330,000
78%
90%
2,700,000
90%
100%
3,000,000
100%
SECTION 3 - START SEQUENCE

3.4.5 BMK 3000 Air/Fuel Valve Position and Energy Input

OMM-0137_D • GF-211 7/16/2019 Technical Support (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 28 of 146
Benchmark Platinum-Edge: Operation-Service Manual
BMK 5000 Air/Fuel Valve Position and Energy Input
Air Fuel Valve
Boiler Energy Input
BTU/Hr
% of Full Capacity
0%
0
0%
10%
0
0%
18% (Stop Level)
400,000 (117 kW)
8%
30%
997,217 (292 kW)
20%
40%
1,667,848 (489 kW)
33%
50%
1,992,380 (584 kW)
40%
60%
2,486,881 (729 kW)
50%
70%
2,981,381 (874 kW)
60%
80%
3,780,230 (1108 kW)
76%
90%
4,375,500 (1282 kW)
88%
100%
5,000,000 (1465 kW)
100%
BMK 5000 Gas Pressure De-Rating Chart
Gas Pressure @ SSOV
in inches W.C. (kPa)
Inlet
Outlet
56” (13.9 kPa)
6.8” (1.70 kPa)
5,000,000 (1465 kW)
5.7
0%
14” (3.49 kPa)
6.8” (1.70 kPa)
5,000,000 (1465 kW)
5.7
0%
10” (3.23 kPa)
6.8” (1.70 kPa)
5,000,000 (1465 kW)
5.7
0%
SECTION 3 - START SEQUENCE

3.4.6 Benchmark 5000 Air/Fuel Valve Position and Energy Input

Position
(% Full Open)
Energy Input in
BTU/hr
Oxygen
(%O
)
2
DeRating
(% Full Fire)
OMM-0137_D • GF-211 7/16/2019 Technical Support (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 29 of 146
Benchmark Platinum-Edge: Operation-Service Manual
BMK 6000 Air/Fuel Valve Position and Energy Input
Air Fuel Valve
Boiler Energy Input
BTU/Hr
% of Full Capacity
0%
0
0%
10%
0
0%
18% (Stop Level)
385,000 (113 kW)
6%
20%
400,000 (117 kW)
7%
30%
540,000 (158 kW)
9%
40%
770,000 (226 kW)
13%
50%
1,160,000 (340 kW)
19%
60%
1,650,000 (484 kW)
28%
70%
2,386,000 (699 kW)
40%
80%
3,515,000 (1030 kW)
59%
90%
4,650,000 (1362 kW)
78%
BMK 6000 Gas Pressure De-Rating Chart
in inches W.C. (kPa)
Inlet
Outlet
56” (13.9 kPa)
8” (1.99 kPa)
6,000,000 (1758 kW)
5.40
0%
14” (3.49 kPa)
8” (1.99 kPa)
6,000,000 (1758 kW)
5.40
0%
13” (3.23 kPa)
8” (1.99 kPa)
5,860,000 (1717 kW)
5.45
2%
SECTION 3 - START SEQUENCE

3.4.7 Benchmark 6000 Air/Fuel Valve Position and Energy Input

Position
(% Full Open)
Gas Pressure @ SSOV
Energy Input in
BTU/hr
Oxygen
(%O
)
2
DeRating
(% Full Fire)
OMM-0137_D • GF-211 7/16/2019 Technical Support (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 30 of 146
Loading...
+ 116 hidden pages