Watts A2C-WB User Manual

Watts IntelliFlow
®
Automatic Washing Machine Shutoff Valve Model A2C-M1, A2C-WB-M1
Important! Read instructions completely before proceeding.
Note: This unit is not compatible with 240VAC powered wash-
ing machines or combination washer/dryers that are 240VAC powered. A Watts A2-IntelliTimer (purchased separately) may be used with the IntelliFlow ers that are 240VAC powered. (See page 5)
®
with washing machines or washer/dry-
IS-A2C-M1/A2C-WB-M1
*This valve requires a 120VAC, 60 Hz, 20 amp ground fault protected circuit.
*Ground Fault Interrupter – A GFI circuit is not required for proper operation of the IntelliFlow®, but is strongly recom­mended as a safety device.
Surge Protection – Although a surge protector is not required for proper operation of the IntelliFlow®, it is strongly recommended, especially in areas where power surges or lightning strikes frequently occur.
Operating Instructions
The Watts IntelliFlow®Automatic Washing Machine Shutoff Valve is equipped with a state-of-the-art electric current sensing device. When the washing machine is turned on, the device senses current flow to the washing machine. This causes it to actuate its solenoid water valves, allowing water to flow to the washing machine. When the washing machine shuts off upon completion of the full wash cycle, the device senses the lack of current and closes the water valves. The IntelliFlow
®
remains closed until
the next time you turn the washer on.
The leak sensor provides additional protection from water damage while the washing machine is in operation. Water detected at the sensor results in immediate shut off of water flow to the washing machine hose.
By installing an IntelliFlow
®
, you are protecting your home from potential major water dam-
age from a burst or leaking washing machine inlet hose.
Operating Specifications
Electrical Rating: 120VAC, 60 Hz
Circuit Breaker Requirements: 20A GFI*
Max. Appliance Current Rating: 15A
Current Draw: 20mA (with appliance off)
Electrical Cord: 6 ft. type SJT 14 AWG
*Ground Fault Interrupter – A GFI circuit is not required for proper operation of the
IntelliFlow
®
, but is strongly recommended as a safety device. In accordance with National Electric Code, NFPA 70, Section 210.11 Branch Circuits Required, at least one 20-ampere branch circuit shall be provided to supply the laundry receptacle outlets(s) required by Section 210.52(F). This circuit shall have no other outlets.
*Surge Protection – Although a surge protector is not required for proper operation of the IntelliFlow
®
, it is strongly recommended, especially in areas where power surges or lightning strikes frequently occur.
Max. Temperature: 180°F (82°C)
Max. Pressure: 150psi (10.3 bar)
Valve Body: Reinforced Polysulfone
Rubber Goods: Buna-N, EPDM
A2C-M1 IntelliFlow
Patent Number 6,003,536
®
Leak Sensor
Model A2C-M1
from washing machine
1
2" solder connectors for exposed piping
Standardly furnished with 1⁄2" solder copper adapters. Either connection may be used for the hot or cold water supply.
Model A2C-WB
from washing machine
Model A2C-M1
Electrical
power source
ground fault
protected
Water supply
One for cold
One for hot
Electrical
power source
ground fault
protected
Water supply
One for cold
One for hot
Model A2C-WB-M1
Includes wall mount box. Wall mount box has water inlet connection holes spaced 23⁄8" center to center. Furnished with tion may be used for the hot or cold water supply.
1
2" solder connectors. Either connec-
Installing the A2C-M1 IntelliFlow
®
WARNING:
Power MUST be off during installation or
servicing of the valve!
IMPORTANT: Do not plug valve into supply circuit
until completion of assembly.
For Vertical Installation Only!
1. Shut off electrical power supply.
2. Shut off both hot and cold water supply lines.
3. If retrofitting to an existing installation, disconnect the wash­ing machine hoses from the existing shutoff valve(s).
4. Loosen the two (2) adapter nuts and remove both adapters from IntelliFlow
5. Place adapter nuts over piping prior to soldering adapters.
6. Solder adapters onto piping. Note: Piping must be 23⁄8" on center (Figure 3).
7. Place O-rings on adapter grooves (Figure 3A).
8.
Align and slip the valve body over adapters. Tighten adapter nuts.
Caution: Do not over-tighten nuts. Caution: To avoid cross threading, check thread alignment.
9. Connect the washing machine hoses to the IntelliFlow and cold water outlets.
10. Plug the washing machine into the IntelliFlow Note: Appliance current rating must not exceed 15 amps.
11. Plug the IntelliFlow receptacle (Figure 4). Note: The IntelliFlow®requires a 120VAC, 60Hz, 15 amp ground-fault protected receptacle.*
IMPORTANT: The IntelliFlow®will detect any current flow to the washing machine when the washing machine is off. The IntelliFlow
®
threshold required to activate the shutoff valves. To calibrate the IntelliFlow
®
valve body.
®
’s electrical outlet.
®
’s power cord into a house electrical
must be calibrated to adjust the current flow
®
see Calibration: (Startup) on page 4.
®
’s hot
Install Upright
O-Ring
21⁄2"
Figure 3
Adapter Nut
Adapter
Water Supply Piping
Figure 3A
12.
Turn on both hot and cold water supply lines, and check for leaks.
13. If there are no leaks, turn on the electrical power. Installation of the A2C-M1 IntelliFlow
®
is now complete.
*Ground Fault Interrupter – A GFI circuit is not required for proper operation of the IntelliFlow
®
, but is strongly
recommended as a safety device.
CAUTION:
Use of the Watts Automatic Washing Machine Valve
outlet for appliances other than a washing machine
is not recommended and voids the warranty.
Watts A2C-M1
Washer
Power supply
Water supply
Figure 4
IMPORTANT:
Do not plug valve into electrical supply circuit until
you have completed installing the unit and
reconnecting the water supply lines.
2
ground fault
protected
U
L
R
LISTED 3P47
Installing the IntelliFlow®Wall Box Unit (A2C-WB-M1)
WARNING:
Power MUST be off during installation or
servicing of the valve!
IMPORTANT: Do not plug valve into supply circuit
until completion of assembly.
For Vertical Installation Only!
1. Shut off electrical power supply.
2. Shut off both hot and cold water supply lines.
3. Remove trim plate (Figs. No.5 & 6) and set aside until you’ve completed wall finishing (painting, wall papering, paneling, etc.).
4. Install the four mounting tabs provided in slots on the sides of the wall box enclosure (Fig. No. 7).
5. Position the A2C-WB-M1 between the wall studs as shown in Fig. No. 7. Check that it is level and fasten the mounting tabs to the studs.
6. Remove drain plug knock out. Install drain piping and water supply piping to the appropriate IntelliFlow Either IntelliFlow
®
connection may be used for the hot or
cold water supply. Caution: Excessive heat from soldering can damage plastic components. Use a heat sink to prevent damage.
7. Place O-rings on adapter grooves (Figure No. 3A).
8.
Align and slip the valve body over adapters. Tighten adapter nuts.
Caution: Do not over tighten nuts. Caution: To avoid cross threading, check thread alignment.
9. Prior to installing wall materials, turn on water supply (both hot and cold) and test for leaks. Test drain piping for leaks.
10. Turn off water supply until you’ve completed installing wall materials. Note: Installation must comply with local codes and ordi­nances. Inspection and approval of installation by local authorities may be required prior to installation of wall mate­rial. Check with local plumbing authorities for requirements.
11. Once you’ve finished the wall, install trim plate, connect washing machine water supply hoses to the IntelliFlow valve and to the washing machine.
12. Plug washing machine into the IntelliFlow Note: Appliance current rating must not exceed 15 amps.
13. Insert the IntelliFlow
®
’s power cord into a house
electrical outlet. Note: The IntelliFlow®requires a 120VAC, 60Hz, 15 amp ground-fault protected receptacle.*
IMPORTANT: The IntelliFlow®will detect any current flow to the washing machine when the washing machine is off. The IntelliFlow threshold required to activate the shutoff valves. To calibrate the IntelliFlow
®
must be calibrated to adjust the current flow
®
see Calibration: (Startup) on page 4.
14. Turn on both hot and cold water supply lines, and check for leaks.
15. If there are no leaks, turn on the electrical power. Installation of the IntelliFlow
®
A2C-WB-M1 Wall Box Unit is now complete.
®
connection.
®
®
’s electrical outlet.
Trim Plate
Wall Box
Figure 5
(side view)
Trim Plate
Water supply connections
Drain connection
Figure 6
(front view)
Finished Wall
Mounting Tabs (4)
16" on center – Typical
Trim Plate
Mounting Slots (4)
Drain
Figure 7
(top view)
*Ground Fault Interrupter – A GFI circuit is not required for proper operation of the IntelliFlow recommended as a safety device.
®
, but is strongly
Wall
Studding
Drain
Knockout
3
Loading...
+ 5 hidden pages