Watts 9D User Manual

For Non-Health Applications
ES-9DM3/M2
Job Name
––––––––––––––––––––––––––––––––––––––––––––
Contractor
––––––––––––––––––––––––––––––––––––––––––––
Job Location
––––––––––––––––––––––––––––––––––––––––––
––––––––––––––––––––––––––––––––––––––––––––––
Engineer
––––––––––––––––––––––––––––––––––––––––––––––
Contractor’s P.O. No.
–––––––––––––––––––––––––––––––––––
–––––––––––––––––––––––––––––––––––––––––––––
Representative
–––––––––––––––––––––––––––––––––––––––––
IMPORTANT: INQUIRE WITH GOVERNING AUTHORITIES
FOR LOCAL INSTALLATION REQUIREMENTS
Series 9D
Dual Check Valve with Intermediate Atmospheric Vent
Sizes: 1⁄2"M3 (15mm), 3⁄4"M2 (20mm)
Series 9D is specially made for smaller supply lines and ideally suited for laboratory equipment, processing tanks, sterilizers, dairy equipment and similar applications. It is particularly recom­mended for boiler feed lines to prevent backflow when supply pressure falls below system pressure.
Series 9D is suitable for use on hot or cold water and can be used under continuous pressure. It features a primary check valve utilizing a rubber disc seating against a mating rubber part to ensure tight closing. A secondary check valve utilizes a rub­ber disc-to-metal seating. In the event of fouling of the down­stream check valve, leakage would be vented to atmosphere through the vent port thereby safeguarding the potable water system. Construction is brass body with stainless steel working parts, integral strainer and durable rubber discs. Female union inlet and outlet connections. Sizes
1
2" (15mm) and 3⁄4" (20mm).
Drain is
1
2" (15mm) thread connection.
Features
• True line-sized construction allows the check modules to open further allowing dirt and debris to pass more freely reducing check fouling
• Stainless steel internal parts
• Maximum flow at low pressure drop
• Furnished with union connections to facilitate removal and replacement for maintenance
• Compact for economy combined with performance
• Design simplicity for easy maintenance
• Can be installed vertically or horizontally
Specifications
For Backflow Preventers with Atmospheric vents
A Dual Check Valve with Atmospheric Vent shall be installed at referenced cross-connections. Valve shall feature stainless steel and rubber internals protected by an integral strainer. Primary check shall be rubber to rubber seated, backed by the secondary check with rubber to metal seating. The device shall be ASSE approved under Std. 1012 and shall be a Watts Series 9D.
Available Models
Suffix:
S – for
1
2" (15mm) union end solder connections.
SC – for satin chrome finish
LU – less union
9D-M2
May also be installed vertically
Union outlet
Secondary check valve
Rugged mesh
stainless strainer screen
Primary
check valve
Vent and drain
connections
Brass body construction and stainless working parts throughout
Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with­out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.
Materials
Forged brass body construction
Stainless steel internal parts
Durable, tight seating rubber check valve assemblies
Pressure — Temperature
Temperature Range 33°F – 250°F (0.5°C – 121°C).
Maximum Working Pressure:175psi (12.1 bar)
Minimum Required Pressure: 25psi (172 kPa).
Standards
ASSE 1012
CSA B64
Approvals
39769
Certified by CSA
N.Y.C. BSA 104-75-SM
Tested and approved Conformance with Standard 1012 of the American Society of Sanitary Engineers and by all principal cities, states and areas having these requirements.
IMPORTANT: This valve should only be used and properly installed so that spillage of water could not cause damage. To avoid water damage due to valve operation, a drain pipe must be installed. It should terminate approximate 12" (305mm) above a floor drain or through an air gap piped to a floor drain, or other suitable place of disposal. Under no circumstances, should the vent opening or drain line be plugged.
Capacity
Installations
Performance Curve
kPa psi
207 30
172 25
138 20
103 15
69 10
34 5
00
0 2 4 5 8 10 12 14 16 18 20 gpm 0 8 15 23 30 38 46 53 61 68 76 lpm
Reduced Pressure Drop
Flow
MODEL SIZE DIMENSIONS WEIGHT
ABEE1
in. mm in. mm in. mm in. mm in. mm lbs. kg.
9DM3
1
2 15 415⁄16 125 29⁄16 65 115⁄16 49 29⁄16 65 11⁄2 .68
9DM3-S
1
2 15 43⁄8 111 29⁄16 65 115⁄16 49 29⁄16 65 11⁄2 .68
9DM2
3
4 20 41⁄2 114 29⁄16 65 115⁄16 49 29⁄16 65 13⁄4 .79
9DM2-S
3
4 20 413⁄16 122 29⁄16 65 21⁄16 52 23⁄4 70 13⁄4 .79
Boiler Installation
Watts 9DM3 Heating System Installation
Livestock Drinking Fountains
Supply
Boiler
Return
Vent
Drain
Floor Drain
Up Stream Control Valve
Water Supply Line
Air Gap
Drain
Drinking Cups
Water Hammer Shock ArrestorWatts
9DM3
Integral Strainer
Watts Model 1156F Feed Valve with Union
Watts 9DM3
A
B
E1
E
Dimensions — Weight
ES-9DM3/M2 0328 © 2009 Watts
USA: 815 Chestnut St., No. Andover, MA 01845-6098; www.watts.com
Canada: 5435 North Service Rd., Burlington, ONT. L7L 5H7; www.wattscanada.ca
A Watts Water Technologies Company