IMPORTANT: The information, specifications and illustrations in this manual are based on the latest information
available at the time of printing. The manufacturer reserves the right to make changes at any time without notice.
Model 9000/9100/9500
Job Specifications Sheet
Job Number ___________________________________________
Model Number _________________________________________
Water Test ____________________________________________
Capacity Of Unit ________________________ Max. _____________ Per Regeneration
Brine Tank Size _____________________________________
Salt Setting Per Regeneration ____________________________________
Control Valve Specifications
1. Type of Timer
A. 82 minute available regeneration time, 1/15 RPM
B. 164 minute available regeneration time, 1/30 RPM
A minimum of 25 lbs of water pressure is required for regeneration valve to operate effectively.
Electrical Facilities
An uninterrupted alternating current (A/C) supply is required. Make sure:
•Voltage supply is compatible with unit before installation.
•Current supply is always hot and cannot be turned off with another switch.
Existing Plumbing
Condition of existing plumbing should be free from lime and iron buildup. Replace piping that has heavy lime
and/or iron build-up. If piping is clogged with iron, install a separate iron filter unit ahead of the water softener.
Location of Softener and Drain
Locate the softener close to a clean working drain and connect according to local plumbing codes.
Bypass Valves
Always provide for the installation of a bypass valve if unit is not equipped with one.
CAUTION
•Do not exceed water pressure of 125 psi.
•Do not exceed 110°F water temperature.
•Do not subject unit to freezing conditions.
4
Model 9000/9100/9500
Equipment Configuration
9000/9100
tank two adapter
adapter clips
9500
tank two
1-1/2" copper
yokes
main control valve
Figure 1:9000/9100
tank one
water meter
outlet
inlet
bypass valve
outlet
inlet
meter dome
must face up
tank two adapter
control valve
tank two
Figure 2
:
9500
5
Model 9000/9100/9500
General and Commercial Installation Checklist
1. Place the softener tank where you want to install the unit.
NOTE:
2. During cold weather it is recommended that the installer warm the valve to room temperature before operating.
3. Perform all plumbing according to local plumbing codes.
— Use a 1/2" minimum pipe size for the drain.
— Use a 3/4" drain line for backwash flow rates that exceed 7 gpm or length that exceeds 20′ (6 m).
4. Both tanks must be the same height and diameter and filled with equal amounts of media.
5. The distributor tube must be flush with the top of each tank. Cut if necessary. Use only non-aerosol silicone
lubricant.
6. Lubricate the distributor o-ring seal and tank o
adapter on the second tank.
NOTE:
7. Solder joints near the drain must be done before connecting the Drain Line Flow Control fitting (DLFC). Leave
at least 6" (152 mm) between the DLFC and solder joints when soldering pipes that are connected on the
DLFC. Failure to do this could cause interior damage to DLFC.
8. Use only
9. Be sure the floor under the salt storage tank is clean and level.
10. Place approximately 1" (25 mm) of water above the grid plate. If a grid is not utilized, fill to the top of the air
check in the salt tank. Do not add salt to the brine tank at this time.
Be sure the tank is level and on a firm base.
-ring seal. Place the main control valve on one tank and the tank
If required, solder copper tubing for tank interconnection before assembling on the main control valve
and tank adapter. Maintain a minimum of 1" distance between tanks on final assembly.
Teflon
tape on the drain fitting.
11. On units with a bypass, place in Bypass position.
— Turn on the main water supply.
— Open a cold soft water tap nearby and let water run a few minutes or until the system is free of foreign
material (usually solder) resulting from the installation. Close the water tap when water runs clean.
12. Place the bypass In Service position and let water flow into the mineral tank. When water flow stops, slowly
open a cold water tap nearby and let water run until air is purged from the unit. Then close tap.
Electrical
13. Make all electrical connections according to codes. Plug the valve into an approved power source. Do not
insert meter cable into the meter yet.
14. Tank one has control valve and tank two has adapter. See
15. Look on the right side of the control valve, it has indicators showing which position the control valve is in during
Regeneration and which tank is In Service.
—
Figure 3, page 7
two on standby.
NOTE:
Make sure the meter cable is not inserted in the meter dome. Swing the timer out to expose the
program wheel (to swing timer out) grab onto the lower right corner of timer face and pull outward. See
Figure 5, page 8
shows the valve In Service position with tank one supplying conditioned water and tank
.
Figure 1, page 5
or
Figure 2, page 5
.
6
Model 9000/9100/9500
rapid rinse
brine rinse
backwash
tank one
Figure 3
brine fill
stand-by
tank two
: Control Valve Position Indicators
Figure 4
16. Cycle timer into backwash position. Turn manual knob so that the micro switch rides on the first set of pins.
— In this position the tanks switch (lower piston) and the control valve moves to the backwash position (upper
piston).
— Wait until the positioning of upper and lower pistons stops before advancing the timer further.
too fast
correct this, rotate the manual knob back to In Service and start again into backwash.
NOTE:
17. With all the air backwashed, slowly cycle the timer to the brine position; rapid rinse; and brine tank refill. Wait
for the control drive motor to position itself in each cycle and stop, before advancing on to the next position.
18. Once back in the In Service position, cycle the control valve again into the backwash position. The tanks
switch again, and air head backwashes out of the other tank. Cycle the control back to the In Service position.
Leave the timer in the open position. DO NOT insert meter cable yet.
the control will not
Once valve positions itself into the backwash cycle, the homing circuit locks in.
home
into the In Service position (it will not advance to any other position). To
: Timer
If advanced
7
Model 9000/9100/9500
pin
storage
NOTE:
Figure 5
Two motors are available:
1/15 RPM has 82 minute Regeneration Time.
1/30 RPM has 164 minute Regeneration Time. See
: Program Wheel
Figure 5
.
8
Model 9000/9100/9500
Regeneration Cycle Program Setting Procedure
Setting the Regeneration Cycle Program
The Regeneration cycle program on the water conditioner is preset at the factory. However, portions of the cycle or
program time may be lengthened or shortened for local conditions or system design.
1. Expose cycle program wheel by grasping timer in lower right hand corner and pulling. This releases snap
retainer and swings timer to the left
NOTE:
2. Remove the program wheel by grasping program wheel and squeezing protruding lugs towards center. Lift
program wheel off timer.
— Switch arms may require movement to facilitate removal.
3. Return timer to closed position by engaging snap retainer in back plate.
— Make certain all electrical wires locate above snap retainer post.
Changing Length of the Backwash Time
Meter cable
must
be removed from meter dome before opening timer.
The program wheel in
group of pins starting at zero determines the length of time the unit backwashes.
Example:
— The number of pins multiplied by two equals minutes of backwash.
If there are six pins in this section, the time of backwash is 12 minutes (2 minutes per pin). To
change the length of backwash time, add or remove pins as required.
Figure 5
is In Service position. Looking at the numbered side of the program wheel, the
Changing Length of Brine and Rinse Time
The group of holes between the last pin in the backwash section and the second group of pins determines the
length of time that a unit will brine and rinse (2 minutes per hole).
To change the length of brine and rinse time, add or remove pins in the rapid rinse group of pins to increase or
decrease the number of holes in the brine and rinse section.
— The number of holes multiplied by two equals minutes of brine and rinse.
Changing Length Of Rapid Rinse
The second group of pins on the program wheel determines the length of time the water conditioner rapid rinses (2
minutes per pin). To change the length of rapid rinse time, add or remove pins at the higher numbered end of this
section as required.
— The number of pins multiplied by two equals minutes of rapid rinse.
NOTE:
Program wheels with 0–82 minute cycle times, use one minute per pin or hole to set Regeneration
times. The layout of pins and holes on the program wheel follow the same procedure as on this page.
Changing Length of Brine Tank Refill Time
The second group of holes on the program wheel determines the length of time the water conditioner refills the
brine tank (2 minutes per hole).
To change the length of refill time, move the two pins at the end of the second group of holes as required.
The Regeneration cycle is complete when the two pin set at end of the brine tank refill section trips the outer
micro-switch. The program wheel, however, continues to rotate until the inner micro-switch drops into the notch on
the program wheel.
9
Model 9000/9100/9500
Time Brine Refill and Meter Setting Procedure
Programming
1. The control valve is set at the factory for backwash; brine and slow rinse; rapid rinse and brine tank fill times.
Change any of these times by repositioning the pins and holes or adding more pins.
NOTE:
2. The control valve has a separate brine tank fill cycle.
— Calculate the desired salt setting using the brine line flow control rate of refill (in gpm) multiplied by the
Example:
NOTE:
3. Setting the gallon wheel.
Knowing the amount of resin in each tank and the salt setting per Regeneration, calculate the gallons
available, using the following capacities as a guide:
Two speed timer motors are available
1/15 RPM has 82 minute Regeneration Time and each pin or hole equals one minute.
1/30 RPM has 164 minute Regeneration Time and each pin or hole equals two minutes.
timer setting. Then, using one gallon of fresh water dissolving approximately 3 lbs salt, calculate the refill
time.
A desired 30 lbs salt setting:
The unit has a 1.0 gpm refill rate so a 10 gallon fill is required.
10 gallons x 3 lbs/gals = 30 lbs salt
Set the timer refill section at 10 minutes.
10 minutes x 1.0 gpm = 10 gallon fill
There must always be two pins at the end of a refill time to stop the fill cycle.
With the Regeneration times set, place timer back to its original position, making sure the lower right
hand corner snaps back into the backplate and the meter cable slides through the backplate and does
not bind.
3
(capacity per ft
compensated hardness of H
x ft3 of resin per tank)
O
2
= gallons available
NOTE:
Example:
DO NOT SET THIS FIGURE - GO TO STEP 4
— Because the control valve regenerates with soft water from the other tank, subtract the water used for
Based on tank size:
More resin increases capacity, less resin decreases capacity.
More salt increases capacity, less salt decreases capacity.
tank diameter=16"
compensated hardness=35 grains per gal (tested sample)
3
resin (based on flow rate)
ft
lbs of salt=8
capacity per ft
(24,000 x 4 ft
Regeneration. Take each Regeneration cycle and calculate the water used.
3
3
of resin per tank)
35 grains
=4
=24,000
= 2740 gallons available before regeneration
10
Model 9000/9100/9500
Example:
4. Set meter wheel at approximately 2530 gallons. Lift the inner dial of the meter program wheel so that you can
rotate it freely. Position the white dot opposite the 2530 gallon setting.
NOTE:
Unit is set for a 16" diameter tank with 4 ft3 of resin and salted at 8 lbs. per ft3, 7 gpm backwash,
#3 injector, 1.0 gpm brine refill, and 60 psi and timer set for
rinse, 10 min. rapid rinse, 10 min. brine tank fill.
Backwash
Brine and Rinse
Rapid Rinse
Brine Tank Fill
With the 2740 gallons available calculated in Step 3, subtract the Regeneration water used from the
total water available.
2740 gallons available- 210 gallons used =2530 gallons
There is a slight delay between the time the meter zeros out and the cycle starts. Units using the:
1/15 RPM motor, 82 minute Regeneration Time has a 9
1/30 RPM motor, 180 minute Regeneration Time has an 18
This delay period is not critical on residential equipment. However, take this factor into consideration
for commercial applications by subtracting continuous flows for 9 minutes or 18 minutes from water
available.
10 minutes x 7.0 gpm =70.0 gallons
60 minutes x 1.0 gpm =60.0 gallons
10 minutes x 7.0 gpm =70.0 gallons
10 minutes x 1.0 gpm =10.0 gallons
Total Regeneration Water = 210.0 gallons
(in Regeneration, Step 4)
10 min. backwash, 60 min. brine and
minute delay
minute delay
.
5. Insert meter cable into meter.
6. Check bypass.
7. Plug in unit.
11
Model 9000/9100/9500
ET Timer Installation And Start-Up Procedures
1. In Normal Operation the Time Of Day and, if flow meter equipped, the Volume Remaining displays appear
alternately. Set the Time Of Day display. Press the Up or Down set button to display the correct time.
Example:
12:59 P.M.
Val ve
In Service
Figure 6
2.
Flow Meter Equipped Valves Only:
(including any reserve capacity) remaining prior to Regeneration. When there is no water usage the Meter
arrow should not appear or not change. Open a soft water tap. The Meter arrow begins flashing at a rate that
varies with flow rate. Close the tap after 3–5 gallons of water flow.
The Volume Remaining Display displays the volume of water in gallons
Example:
125 gallons of water remaining
Valve
In Service
No water flow
Volume below reserve capacity
Reserve arrow flashing
Figure 7
3. Manually initiate a Regeneration cycle and allow water to run to drain for 3 to 4 minutes. Press and release
the Extra Cycle button. With Immediate Regeneration timers the control goes into Regeneration immediately.
With Delayed Regeneration timers the In Service arrow flashes immediately and a Regeneration occurs at
the preset Regeneration Time. Press and hold the Extra Cycle button for 5 seconds. The control goes into
Regeneration immediately.
4. Manually step the valve through a Regeneration cycle, checking valve operation in each step. During
Regeneration the control displays the Regeneration step number to which the valve is advancing or has
reached and the time remaining in that step.
Example:
0 gallons of water remaining
Valve
In Service
Water flowing
Volume below reserve capacity
Reserve arrow flashing
12
Model 9000/9100/9500
Example:
Valve advancing to Regeneration Step #1
#1 flashing
Regeneration arrow on
— When the first cycle step is reached, a red LED turns on indicating the current Regeneration cycle step.
Example:
Regeneration Step #1 reached
10.0 minutes remain in Step #1
Regeneration arrow on
— Press the Extra Cycle button during a Regeneration step to immediately advance the valve to the next
Regeneration step position.
— Press the Up or Down set buttons during a Regeneration step to adjust the time remaining in the current
Regeneration step. Programmed Regeneration step times are not changed.
Backwash
Figure 8
Backwash
Figure 9
— Once all Regeneration cycle steps are complete, the valve returns to In Service and resumes normal
operation.
5. Manually step the valve to the Brine Draw position (see Step #15) and allow the valve to draw water from the
brine tank until it stops.
*NOTE:
6. Manually step the valve to the Brine Refill position and allow the valve to return to In Service automatically.
7. Make sure the brine refill time (salt dosage) is set as recommended by the manufacturer.
8. With the valve In Service, check that there is about 1″ of water above the grid in the brine tank, if one is used.
9. Fill the brine tank with salt.
NOTE:
The air check checks at approximately the midpoint of the screened intake area.
It is recommended a 9V Alkaline Battery be installed at all times for proper valve operation. The Low
Battery LED turns on when the battery needs to be replaced.
13
Model 9000/9100/9500
ET Timer Control Start-Up Procedure
Display ET
Service Indicator
Valve In Service, Arrow On
Manual Regeneration Tonight, Flashing Arrow
Time of Day Indicator
Reserve Indicator
Volume Remaining Above Reserve, Arrow Off
Volume Remaining At or Below Reserve, Arrow Flashing
Totalizer Indicator
Flow Indicator
No Water Flow, Arrow Off
Water Flow, Arrow Flashing
Sensor Indicator
Sensor Input Signal, Arrow Flashing
Valid Regeneration Signal, Arrow On
Flow Rate Indicator
Program Indicator
Volume Remaining Indicator
Lockout Indicator
Lockout Signal, Arrow On
Regeneration Indicator
Valve in Regeneration, Arrow On
Figure 10:ET
In Normal operation the Time Of Day display alternates with the Volume Remaining display. The meter arrow
flashes in direct relation to the water flow rate through the unit. As treated water is used, the Volume Remaining
display counts down from a maximum value to the calculated reserve capacity. The Reserve arrow flashes when
the reserve capacity is being used. At the preset Regeneration Time, a Regeneration cycle initiates.
Example:
125 gallons of water remaining
Valve
No water flow
Volume is below reserve capacity
Example:
0 gallons of water remaining
Valve
Water flowing
Meter arrow flashing
Volume is below reserve capacity
In Service
In Service
Timer Display
Figure 11
14
Model 9000/9100/9500
ET Timer Control Operation
Timeclock Regeneration Valves
When the number days since the last Regeneration reaches the preset number of days, a Regeneration cycles
initiates at the preset Regeneration Time.
Flow Meter Equipped Immediate Regeneration Valves
The Time Of Day display alternates with the Volume Remaining display. The Meter arrow flashes in direct relation
to the water flow rate through the unit. As treated water is used, the Volume Remaining display counts down from
a maximum value to zero and initiates a Regeneration cycle.
Example:
525 gallons of water remaining
Valve
Water flowing
Meter arrow flashing
In Service
Figure 12
Sensor Immediate Regeneration Valves
When the control receives a valid sensor input signal, a Regeneration cycle initiates. The Sensor Input arrow
flashes until the signal is determined to be valid.
Sensor Delayed Regeneration Valves
When the control receives a valid sensor input signal, a Regeneration cycle initiates at the preset Regeneration
Time. The Sensor Input arrow flashes until the signal is determined to be valid. The Reserve arrow flashes when
the reserve capacity is being used.
Example:
12:58 A.M. with invalid sensor signal
Valve
Sensor arrow flashing
Example:
12:59 A.M. with valid sensor signal
Valve
Sensor arrow on
Reserve arrow flashing
Delayed regeneration
In Service
In Service
Figure 13
Lockout Input Operation
The lockout arrow turns on whenever the control sends a lockout signal. Any requests for Regeneration are
delayed until this signal is removed. Regeneration then proceeds normally.
15
Model 9000/9100/9500
Figure 14
Start an Extra Cycle
Press the Extra Cycle button to start an Extra Regeneration tonight. Press and hold the Extra Cycle button for
5 seconds to start an Extra Cycle immediately.
Totalizer/Flow Rate
Press the Totalizer Flow Rate button to display the flow rate.
Press the button a second time to display the total accumulation of water flow through the valve since the last reset.
Press the button a third time to return the display to Time Of Day or Volume Remaining.
— Press and hold the button for 25 seconds to reset the Totalizer display. During the 25 seconds, the
Totalizer arrow flashes indicating that the display is resetting properly.
Low Battery Indicator
Figure 15
The red Low Battery LED turns on whenever the 9V Alkaline Battery (not included) requires replacement. The
battery is used for memory backup and is stored against the valve backplate. In the event of a power outage, the
battery maintains the current operating displays for approximately 24 hours at maximum battery capacity.
Immediate Regeneration Valves With Days Between Regeneration Override Set
When the valve reaches its set Days Since Regeneration Override value, a Regeneration cycle initiates
immediately. This event occurs regardless of the Volume Remaining display reaching zero gallons.
Delayed Regeneration Valves With Days Between Regeneration Override Set
When the valve reaches its set Days Since Regeneration Override value, a Regeneration cycle initiates at the
preset Regeneration Time. This event occurs regardless of the Volume Remaining display reaching the calculated
reserve capacity.
Control Operation During Regeneration
In Regeneration the control displays a special Regeneration display. The control shows the current
Regeneration step number to which the valve is advancing or has reached, and the time remaining in that step. The displayed step number flashes until the valve completes driving to the Regeneration step position. Once all
Regeneration steps are complete the valve returns to In Service and resumes normal operation.
16
Model 9000/9100/9500
Example:
Less than 10 minutes remaining in
Regeneration
Step #1
Figure 16
Press the Extra Cycle button during a Regeneration cycle to immediately advances the valve to the next cycle step
position and resume normal step timing.
Control Operation During Programming
The control enters Program Mode with the valve In Service. While in Program Mode the control continues to
operate normally, monitoring water usage and keeping all displays up to date. Control programming is stored in
memory permanently. There is no need for battery backup power.
Control Operation During A Power Failure
During a power failure all control displays and programming are stored for use upon power re-application. The
control retains these values for years, if necessary, without loss. The control is fully inoperative and any calls for
Regeneration are delayed. The control, upon power re-application, resumes normal operation from the point that it
was interrupted. An inaccurate or flashing Time of Day display indicates that a power outage has occurred.
Backwash
17
Model 9000/9100/9500
SE Timer Control Start-Up Procedures
Display SE
Figure 17:SE
In normal operation the Time Of Day display alternates with Volume Remaining and Tank in In Service displays
(
9000SE Timer
maximum value to zero or (----). Once this occurs a Regeneration cycle initiates immediately or delayed to the set
Regeneration Time. Water flow through the valve is indicated by the flashing Flow Dot Indicator.
only). As treated water is used, the Volume Remaining display counts down (in gallons) from a
Figure 18:SE
Timer Display During Normal Operation
Timer Display
Set Time of Day
When the valve is In Service, press either the Set Up or Set Down button once to adjust the Time Of Day by one
digit. Press and hold to adjust by several digits.
Start an Extra Regeneration Cycle
Press the Extra Regeneration button to start an Extra Regeneration tonight. Press and hold the Extra
Regeneration button for 5 seconds to start an Extra Regeneration immediately.
18
Model 9000/9100/9500
Set Control Programming
1. Press and hold both the Set Up and Set Down buttons for 5 seconds.
2. Set the Treated Water Capacity. Using the Set Up or Set Down buttons, set the amount of treated water to
flow through the unit before a Regeneration is required.
3. Press the Extra Regeneration button.
4. Set the Regeneration Time. Use the Set Up or Set Down buttons to set the desired time of day for
Regeneration to occur.
NOTE:
5. Press the Extra Regeneration button.
6. Set Regeneration Day Override. Use the Set Up or Set Down buttons to set the maximum number of days
before a Regeneration cycle must occur.
7. Press the Extra Regeneration button to exit the program.*
NOTE:
This does not display if Regeneration occurs immediately.
If setting up the system for the first time, perform the following Fast Cycle Regeneration:
1. Press the Extra Regeneration button for 5 seconds to force an Extra Regeneration immediately.
2. Once the valve reaches Regen Step #1, let water run to drain for approximately 5 minutes.
3. Press the Extra Regeneration button once to advance valve to Regen Step #2.
4. Press the Extra Regeneration button once to advance valve to Regen Step #3 (if active).
5. Press the Extra Regeneration button once to advance valve to Regen Step #4 (if active).
6. Press the Extra Regeneration button once to advance valve to Regen Step #5 (if active).
7. Press the Extra Regeneration button once more to advance the valve back to In Service.
19
Model 9000/9100/9500
Immediate Regeneration Valves With Days Between Regeneration Override Set
When the valve reaches its set Days Since Regeneration Override value, a Regeneration cycle initiates
immediately. This event occurs regardless of the Volume Remaining display reaching zero gallons.
Delayed Regeneration Valves With Days Between Regeneration Override Set
When the valve reaches its set Days Since Regeneration Override value a Regeneration cycle initiates at the
preset Regeneration Time. This event occurs regardless of the Volume Remaining display reaching zero gallons.
Control Operation During Regeneration
In Regeneration the control displays a special Regeneration display. While in Regeneration the control shows
the current Regeneration step number to which the valve is advancing or has reached, and the time remaining in
that step. The displayed step number flashes until the valve completes driving to this Regeneration step position.
Once all Regeneration steps are complete the valve returns to In Service and resumes normal operation.
Example:
Figure 19
Pressing the Extra Cycle button during a Regeneration cycle immediately advances the valve to the next cycle
step position and resumes normal step timing.
Control Operation During Programming
The control only enters the Program Mode with the valve In Service. While in the Program Mode the control
continues to operate normally monitoring water usage and keeping all displays up to date. Control programming is
stored in memory permanently. There is no need for battery backup power.
Control Operation During A Power Failure
During a power failure all control displays and programming are stored for use upon power re-application. The
control retains these values for years, if necessary, without loss. The control is fully inoperative and any calls for
Regeneration are delayed. The control, upon power re-application, resumes normal operation from the point that it
was interrupted. An inaccurate or flashing Time of Day display indicates that a power outage has occurred.
1113870-03timer housing assembly.
2117870label, capacity gallons
3115465label, Caution
4116930label, Instruction
5115227actuator plate
6110300screw, hex washer #8
7117513spring clip
8115407washer, plain #4
9115228spring
10116270-10gallon wheel assembly 3/4" standard range meter
16270-50gallon wheel assembly 3/4" extended range meter
16270-30gallon wheel assembly 1" standard range meter
16270-40gallon wheel assembly 1" extended range meter
16270-50gallon wheel assembly 1-1/2" standard range meter
114861-01NP valve body, machined (nickel plated)
2415137screw, hex washer #10-24 x 3/8"
3114906end plate
4114928end plug
5
6
7115471stand off
8160400piston assembly, top
160400-01piston assembly, top (hot water)
9160125seal and spacer kit, top
60125-HWseal and spacer kit, top (hot water)
60125-20seal and spacer kit, top (559PE)
10160421seal and spacer kit, bottom
60421-HWseal and spacer kit, bottom (hot water)
60421-20seal and spacer kit, (559PE)
11160401piston assembly, bottom
60401-01piston assembly, bottom (hot water)
12160385-XXXXinjector assembly
(see chart for dash numbers)
injectornumberDLFCnumberBLFCnumber
red #000Blank0Blank0
white #1011.210.251
blue #2021.520.502
yellow #3032.0 31.003
green #4042.44
3.0 5
3.56
4.0 7
5.08
7.0 9
12A160022-12brine line flow control assembly, 0.125 gpm
60022-25brine line flow control assembly, 0.250 gpm
60022-50brine line flow control assembly, 0.500 gpm
60022-100brine line flow control assembly, 1.00 gpm
12B160350brine valve assembly
Not Shown
1312763seal and space stuffer tool
1413061spacer puller tool
1513759DLFC retainer tool
27
Model 9000/9100/9500
9100 Control Valve Assembly
28
Figure 24
Model 9000/9100/9500
9100 Control Valve Assembly
ItemQuantityPart NumberDescription
1140688valve body assembly
2415137screw, hex washer #10-24 x 3/8”
3114906end plate
4114928end plug
5119054O-ring, 124
6118303O-ring, 336
7140538retainer, 32mm
8160400piston top assembly
9160125seal and spacer kit, top
60425-16plastic tube assembly,
7114865second tank adapter assembly,
8161419distributors adapter kit,
9000
9100
9100
9000
9000,
, up to 12" tanks
, up to 16" tanks
9100
9100
, 1.05"
nickel-plated
9500 second tank assembly
9116919-01second tank adapter assembly,
16919-01NPsecond tank adapter assembly,
16919-21second tank adapter assembly,
16919-21NPsecond tank adapter assembly,
10160715-16tube assembly 16" tanks
60715-16NPtube assembly 16" tanks, nickel-plated
60715-20tube assembly 20" tanks
60715-20NPtube assembly 20" tanks, nickel-plated
60715-24tube assembly 24" tanks
60715-24NPtube assembly 24" tanks, nickel-plated
9500
9500
, nickel-plated
9500
, BSP/Metric
9500
, BSP/Metric, nickel-plated
33
Model 9000/9100/9500
9000/9100/9500 Meter Assemblies
Figure 31
34
Figure 32
Figure 33
Model 9000/9100/9500
9000/9100/9500 Meter Assemblies
ItemQuantityPart NumberDescription
9000 meter assembly
11600863/4" meter assembly, standard range
ET
60086-503/4" meter assembly, electronic (
600873/4" meter assembly, extended range
1A114038meter cap assembly, standard range
1B14716meter cap assembly, electronic (ET)
1C15150meter cap assembly, extended range
1D115218meter cap assembly, brass standard range
15218NPmeter cap assembly, brass nickel-plated standard range
1E15237meter cap assembly, brass extended range
15237NPmeter cap assembly, brass nickel-plated extended range
2113509impeller
13509-01impeller, hot water
31197973/4" turbine meter assembly, less clips and screws
606263/4" turbine meter assembly with clips, screws, meter cable
60626-013/4" turbine meter assembly, with clips and screws
41603891" meter assembly, standard range
60389NP1" meter assembly, standard range
160389-201" meter assembly, standard range, BSP
603901" meter assembly, extended range
60390NP1" meter assembly, extended range, nickel-plated
60390-201" meter assembly, extended range, BSP
606121" meter assembly, standard range, hot water
606221" meter assembly, electronic
4A 1150781" adapter coupling
5
Not Shown
6*
7
8
160610-011-1/2" meter assembly, standard range
60610-01NP1-1/2" meter assembly, standard range, nickel-plated
60610-021-1/2" meter assembly, extended range
60610-02NP1-1/2" meter assembly, extended range, nickel-plated
60610-211-1/2" meter assembly, standard range, BSP
60610-21NP1-1/2" meter assembly, standard range, BSP, nickel-plated
60610-221-1/2" meter assembly, extended range, BSP
60610-22NP1-1/2" meter assembly, extended range, BSP, nickel-plated
60611-011-1/2" meter assembly, standard range, with 1" sleeve
60611-01NP1-1/2" meter assembly, standard range, with 1" sleeve, nickel-plated
60611-021-1/2" meter assembly, extended range, with 1" sleeve
60611-02NP1-1/2" meter assembly, extended range, with 1" sleeve, nickel-plated
17790
60460
60461
1-1/2" meter sleeve reduced to 1"
meter checker kit, standard range
meter checker kit, extended range
)
*
when reducing 1-1/2" meter to 1" program wheel and timer settings must be changed to 1" meter size
1. Softener fails to regenerate.A. Electrical service to unit has been
interrupted.
B. Timer is defective.
2. Hard water.A. Bypass valve is open.
B. No salt in brine tank.
C. Injector screen plugged.
D. Insufficient water flowing into brine
tank.
E. Hot water tank hardness.
F. Leak at distributor tube.
G. Internal valve leak.
3. Unit used too much salt.A. Improper salt setting.
B. Excessive water in brine tank.
4. Loss of water pressure.A. Iron buildup in line to water
conditioner.
B. Iron buildup in water conditioner.
C. Inlet of control plugged due to
foreign material broken loose from
pipe by recent work done on
plumbing system.
A. Assure permanent electrical
service (check fuse, plug, pull
chain or switch).
B. Replace timer.
A. Close bypass valve.
B. Add Salt to brine tank and maintain
salt level above water level.
C. Clean injector screen.
D. Check brine tank fill time and clean
brine line flow control if plugged.
E. Repeated flushing of the hot water
tank is required.
F. Make sure distributor tube is not
cracked. Check O-Ring and tube
pilot.
D. Replace seals and spacers and/or
piston.
A. Check salt usage and salt setting.
B. See Problem No. 7.
A. Clean line to water conditioner.
B. Clean control and add mineral
cleaner to mineral bed. Increase
frequency of regeneration and/or
backwash time.
C. Remove pistons and clean control.
5. Loss of mineral through drain line.A. Air in water system.
B. Drain line flow control too large.
6. Iron in conditioned water.A. Fouled mineral bed.A. Check backwash, brine draw and
7. Excessive water in brine tank.A. Plugged drain line flow control.
B. Plugged injector system.
C. Timer not cycling.
D. Foreign material in brine valve.
E. Foreign material in brine line flow
control.
F. Power loss during brine fill.
A. Assure that well system has
proper air eliminator control.
Check for dry well condition.
B. Check to ensure drain line flow
control is sized properly for your
mineral tank.
brine tank fill. Increase frequency
of regeneration.
A. Check flow control.
B. Clean injector and screen.
C. Replace timer.
D. Replace brine valve seat and clean
valve.
E. Clean brine line flow control.
F. Check power source.
44
Model 9000/9100/9500
PROBLEMCAUSECORRECTION
8. Softener fails to draw brine.A. Drain line flow control is plugged.
B. Injector is plugged.
C. Injector screen plugged.
D. Line pressure is too low.
E. Internal Control Leak
9. Control cycles continuously.A. Broken or shorted switch.A. Determine if switch or timer is
10.Drain flows continuously. A. Valve is not programming correctly.
B. Foreign material in control.
C. Internal control leak.
A. Clean drain line flow control.
B. Clean injector.
C. Clean screen.
D. Increase line pressure to
25 psi min.
E. Change seals, spacers and piston
assembly.
faulty and replace it, or replace
complete power head.
A. Check timer program and positioning
of control. Replace power head
assembly if not positioning properly.
B. Remove power head assembly and
inspect bore, remove foreign
material and check control in various
regeneration positions.
C. Replace seals and piston assembly.
General Service Hints
Problem: Softener delivers hard water
PROBLEMCAUSECORRECTION
Softener delivers hard water.Reserve capacity has been exceeded. Check salt dosage requirements and
reset program wheel to provide additional reserve.
Program wheel is not rotating with
meter output.
Meter is not measuring flow.Check output by observing rotation of
Pull cable out of meter cover and rotate
manually. Program wheel must move
without binding and cycle actuator must
start the cycle before the clutch
releases.
small gear on front of timer
(Note: Program wheel must not be
against regeneration stop for this check)
Each tooth is approximately 75 gallons
on 1-1/2″ installations. If not performing
properly, replace meter.
45
Model 9000/9100/9500
Mechanical Timer Valve Wiring
TM - TIMER MOTOR
VDM - VALVE DRIVE MOTOR
SW1 - TIMER HOMING SWITCH
SW2 - TIMER PROGRAM SWITCH
SW3 - VALVE HOMING SWITCH
SW4 - VALVE PROGRAM SWITCH
THCAM - TIMER HOMING CAM
TPCAM - TIMER PROGRAM CAM
Figure 46
46
Model 9000/9100/9500
ET Timer Valve Wiring
TB1 - HIGH VOLTAGE TERMINAL BLOCK
TB2 - LOW VOLTAGE TERMINAL BLOCK
CB1 - 3200ET CIRCUIT BOARD
F1 - TIMED AUXILIARY OUTPUT FUSE
VDM - VALVE DRIVE MOTOR
SW1 - HOMING SWITCH
SW2 - STEP SWITCH
SW3 - BRINE CAM SWITCH
HCAM - VALVE HOMING CAM
SCAM - VALVE STEP CAM
BVCAM - BRINE VALVE CAM
Twin Unit Meter/Timeclock/Sensor Regeneration
Figure 47
47
Model 9000/9100/9500
SE Timer Valve Wiring
CB1 - SE TIMER
T1 - 24V TRANSFORMER
TM - 3/4" TURBINE FLOW METER (OPTIONAL)
PWM - 1.0" PADDLE WHEEL FLOW METER (OPTIONAL)
VDM - VALVE DRIVE MOTOR
SW1 - VALVE HOMING SWITCH
SW2 - VALVE STEP SWITCH
HCAM - VALVE HOMING CAM
SCAM - VALVE STEP CAM
Figure 48
48
Model 9000/9100/9500
9000 Control Dimensions
Figure 49
49
Model 9000/9100/9500
9100 Control Dimensions
50
Figure 50
Model 9000/9100/9500
9500 Control Dimensions
Figure 51
51
Model 9000/9100/9500
Meter Flow Data
9000
Figure 52:9000
Meter Flow Data
52
Model 9000/9100/9500
9100
9500
Figure 53:9100
Figure 54:9500
Meter Flow Data
Meter Flow Data
53
Model 9000/9100/9500
Injector Flow Data
9000/9100
54
Figure 55:9000/9100—1600 Series Injectors
Model 9000/9100/9500
9500
Figure 56:9500—1600 Series Injectors
Figure 57
:
9500—1700 Series Injectors
55
P/N 40944Rev. A 01/03
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.