Watts 9500 User Manual

Model 9000/9100/9500
Service Manual
IMPORTANT: Fill in pertinent information on
page 3
for future reference.
Model 9000/9100/9500
Table of Contents
General and Commercial Installation Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
General and Commercial Installation Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
ET
Timer Installation And Start-Up Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
ET
Timer Control Start-Up Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
ET
Timer Control Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
SE
Timer Control Start-Up Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
ET
and SE Timer Assemblies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
9000/9100/9500 9000/9100/9500 9000/9100/9500 9000
Control Valve Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
9100
Control Valve Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
9500
Control Valve Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
9500
Brine Valve Systems (
9000/9100/9500 9000/9100/9500 9000/9100 2310
Safety Brine Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
9500,2350 2300
Safety Brine Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Water Conditioner Flow Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
ET
Timer Valve Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
SE
Timer Valve Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
9000
Control Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
9100
Control Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
9500
Control Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Meter Flow Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Injector Flow Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Electro Mechanical Timer Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Power Head . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Power Head . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
1600
and
1700
Series) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Second Tank Assemblies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Meter Assemblies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Bypass Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Safety Brine Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
IMPORTANT: The information, specifications and illustrations in this manual are based on the latest information available at the time of printing. The manufacturer reserves the right to make changes at any time without notice.
Model 9000/9100/9500
Job Specifications Sheet
Job Number ___________________________________________
Model Number _________________________________________
Water Test ____________________________________________
Capacity Of Unit ________________________ Max. _____________ Per Regeneration
Brine Tank Size _____________________________________
Salt Setting Per Regeneration ____________________________________
Control Valve Specifications
1. Type of Timer
A. 82 minute available regeneration time, 1/15 RPM
B. 164 minute available regeneration time, 1/30 RPM
2. Type of Meter
Mechanical Valves
(gallon settings)
Meter Standard Range Extended Range
3/4" 125–2,125 625–10,625 1" 310–5,270 1,150–26,350 1-1/2" 625–10,625 3,125–53,125
Electrical Timers
(minutes per cycle)
Meter ET SE
(0–999.9 minutes per cycle) (0–99 minutes per cycle) 3/4" 9,999,999 9,999 1" 9,999,999 9,999 1-1/2" 9,999,999
3. Timer Gallon Setting ______________________________ gal.
4. Regeneration Program Setting
A. Backwash___________________________________ min.
B. Brine and Slow Rinse _________________________ min.
C. Rapid Rinse _________________________________ min.
D. Brine Tank Refill _____________________________ min.
5. Drain Line Flow Control __________________________ gpm
6. Brine Refill Rate _______________________________ gpm
7. Injector Size _______________________________________
3
Model 9000/9100/9500
General and Commercial Installation Checklist
Water Pressure
A minimum of 25 lbs of water pressure is required for regeneration valve to operate effectively.
Electrical Facilities
An uninterrupted alternating current (A/C) supply is required. Make sure:
Voltage supply is compatible with unit before installation.
Current supply is always hot and cannot be turned off with another switch.
Existing Plumbing
Condition of existing plumbing should be free from lime and iron buildup. Replace piping that has heavy lime and/or iron build-up. If piping is clogged with iron, install a separate iron filter unit ahead of the water softener.
Location of Softener and Drain
Locate the softener close to a clean working drain and connect according to local plumbing codes.
Bypass Valves
Always provide for the installation of a bypass valve if unit is not equipped with one.
CAUTION
Do not exceed water pressure of 125 psi.
Do not exceed 110°F water temperature.
Do not subject unit to freezing conditions.
4
Model 9000/9100/9500
Equipment Configuration
9000/9100
tank two adapter
adapter clips
9500
tank two
1-1/2" copper
yokes
main control valve
Figure 1:9000/9100
tank one
water meter
outlet
inlet
bypass valve
outlet
inlet
meter dome
must face up
tank two adapter
control valve
tank two
Figure 2
:
9500
5
Model 9000/9100/9500
General and Commercial Installation Checklist
1. Place the softener tank where you want to install the unit.
NOTE:
2. During cold weather it is recommended that the installer warm the valve to room temperature before operating.
3. Perform all plumbing according to local plumbing codes.
— Use a 1/2" minimum pipe size for the drain.
— Use a 3/4" drain line for backwash flow rates that exceed 7 gpm or length that exceeds 20 (6 m).
4. Both tanks must be the same height and diameter and filled with equal amounts of media.
5. The distributor tube must be flush with the top of each tank. Cut if necessary. Use only non-aerosol silicone lubricant.
6. Lubricate the distributor o-ring seal and tank o adapter on the second tank.
NOTE:
7. Solder joints near the drain must be done before connecting the Drain Line Flow Control fitting (DLFC). Leave at least 6" (152 mm) between the DLFC and solder joints when soldering pipes that are connected on the DLFC. Failure to do this could cause interior damage to DLFC.
8. Use only
9. Be sure the floor under the salt storage tank is clean and level.
10. Place approximately 1" (25 mm) of water above the grid plate. If a grid is not utilized, fill to the top of the air check in the salt tank. Do not add salt to the brine tank at this time.
Be sure the tank is level and on a firm base.
-ring seal. Place the main control valve on one tank and the tank
If required, solder copper tubing for tank interconnection before assembling on the main control valve and tank adapter. Maintain a minimum of 1" distance between tanks on final assembly.
Teflon
tape on the drain fitting.
11. On units with a bypass, place in Bypass position.
— Turn on the main water supply.
— Open a cold soft water tap nearby and let water run a few minutes or until the system is free of foreign
material (usually solder) resulting from the installation. Close the water tap when water runs clean.
12. Place the bypass In Service position and let water flow into the mineral tank. When water flow stops, slowly open a cold water tap nearby and let water run until air is purged from the unit. Then close tap.
Electrical
13. Make all electrical connections according to codes. Plug the valve into an approved power source. Do not insert meter cable into the meter yet.
14. Tank one has control valve and tank two has adapter. See
15. Look on the right side of the control valve, it has indicators showing which position the control valve is in during Regeneration and which tank is In Service.
Figure 3, page 7
two on standby.
NOTE:
Make sure the meter cable is not inserted in the meter dome. Swing the timer out to expose the program wheel (to swing timer out) grab onto the lower right corner of timer face and pull outward. See
Figure 5, page 8
shows the valve In Service position with tank one supplying conditioned water and tank
.
Figure 1, page 5
or
Figure 2, page 5
.
6
Model 9000/9100/9500
rapid rinse
brine rinse
backwash
tank one
Figure 3
brine fill
stand-by
tank two
: Control Valve Position Indicators
Figure 4
16. Cycle timer into backwash position. Turn manual knob so that the micro switch rides on the first set of pins.
— In this position the tanks switch (lower piston) and the control valve moves to the backwash position (upper
piston).
— Wait until the positioning of upper and lower pistons stops before advancing the timer further.
too fast
correct this, rotate the manual knob back to In Service and start again into backwash.
NOTE:
17. With all the air backwashed, slowly cycle the timer to the brine position; rapid rinse; and brine tank refill. Wait for the control drive motor to position itself in each cycle and stop, before advancing on to the next position.
18. Once back in the In Service position, cycle the control valve again into the backwash position. The tanks switch again, and air head backwashes out of the other tank. Cycle the control back to the In Service position. Leave the timer in the open position. DO NOT insert meter cable yet.
the control will not
Once valve positions itself into the backwash cycle, the homing circuit locks in.
home
into the In Service position (it will not advance to any other position). To
: Timer
If advanced
7
Model 9000/9100/9500
pin
storage
NOTE:
Figure 5
Two motors are available: 1/15 RPM has 82 minute Regeneration Time. 1/30 RPM has 164 minute Regeneration Time. See
: Program Wheel
Figure 5
.
8
Model 9000/9100/9500
Regeneration Cycle Program Setting Procedure
Setting the Regeneration Cycle Program
The Regeneration cycle program on the water conditioner is preset at the factory. However, portions of the cycle or program time may be lengthened or shortened for local conditions or system design.
1. Expose cycle program wheel by grasping timer in lower right hand corner and pulling. This releases snap retainer and swings timer to the left
NOTE:
2. Remove the program wheel by grasping program wheel and squeezing protruding lugs towards center. Lift program wheel off timer.
— Switch arms may require movement to facilitate removal.
3. Return timer to closed position by engaging snap retainer in back plate.
— Make certain all electrical wires locate above snap retainer post.
Changing Length of the Backwash Time
Meter cable
must
be removed from meter dome before opening timer.
The program wheel in group of pins starting at zero determines the length of time the unit backwashes.
Example:
— The number of pins multiplied by two equals minutes of backwash.
If there are six pins in this section, the time of backwash is 12 minutes (2 minutes per pin). To change the length of backwash time, add or remove pins as required.
Figure 5
is In Service position. Looking at the numbered side of the program wheel, the
Changing Length of Brine and Rinse Time
The group of holes between the last pin in the backwash section and the second group of pins determines the length of time that a unit will brine and rinse (2 minutes per hole).
To change the length of brine and rinse time, add or remove pins in the rapid rinse group of pins to increase or decrease the number of holes in the brine and rinse section.
— The number of holes multiplied by two equals minutes of brine and rinse.
Changing Length Of Rapid Rinse
The second group of pins on the program wheel determines the length of time the water conditioner rapid rinses (2 minutes per pin). To change the length of rapid rinse time, add or remove pins at the higher numbered end of this section as required.
— The number of pins multiplied by two equals minutes of rapid rinse.
NOTE:
Program wheels with 0–82 minute cycle times, use one minute per pin or hole to set Regeneration times. The layout of pins and holes on the program wheel follow the same procedure as on this page.
Changing Length of Brine Tank Refill Time
The second group of holes on the program wheel determines the length of time the water conditioner refills the brine tank (2 minutes per hole).
To change the length of refill time, move the two pins at the end of the second group of holes as required.
The Regeneration cycle is complete when the two pin set at end of the brine tank refill section trips the outer micro-switch. The program wheel, however, continues to rotate until the inner micro-switch drops into the notch on the program wheel.
9
Model 9000/9100/9500
Time Brine Refill and Meter Setting Procedure
Programming
1. The control valve is set at the factory for backwash; brine and slow rinse; rapid rinse and brine tank fill times. Change any of these times by repositioning the pins and holes or adding more pins.
NOTE:
2. The control valve has a separate brine tank fill cycle.
— Calculate the desired salt setting using the brine line flow control rate of refill (in gpm) multiplied by the
Example:
NOTE:
3. Setting the gallon wheel.
Knowing the amount of resin in each tank and the salt setting per Regeneration, calculate the gallons available, using the following capacities as a guide:
Two speed timer motors are available 1/15 RPM has 82 minute Regeneration Time and each pin or hole equals one minute. 1/30 RPM has 164 minute Regeneration Time and each pin or hole equals two minutes.
timer setting. Then, using one gallon of fresh water dissolving approximately 3 lbs salt, calculate the refill time.
A desired 30 lbs salt setting: The unit has a 1.0 gpm refill rate so a 10 gallon fill is required.
10 gallons x 3 lbs/gals = 30 lbs salt
Set the timer refill section at 10 minutes.
10 minutes x 1.0 gpm = 10 gallon fill
There must always be two pins at the end of a refill time to stop the fill cycle. With the Regeneration times set, place timer back to its original position, making sure the lower right hand corner snaps back into the backplate and the meter cable slides through the backplate and does not bind.
3
(capacity per ft
compensated hardness of H
x ft3 of resin per tank)
O
2
= gallons available
NOTE:
Example:
DO NOT SET THIS FIGURE - GO TO STEP 4
— Because the control valve regenerates with soft water from the other tank, subtract the water used for
Based on tank size: More resin increases capacity, less resin decreases capacity. More salt increases capacity, less salt decreases capacity.
tank diameter = 16" compensated hardness = 35 grains per gal (tested sample)
3
resin (based on flow rate)
ft lbs of salt = 8
capacity per ft
(24,000 x 4 ft
Regeneration. Take each Regeneration cycle and calculate the water used.
3
3
of resin per tank)
35 grains
=4
= 24,000
= 2740 gallons available before regeneration
10
Model 9000/9100/9500
Example:
4. Set meter wheel at approximately 2530 gallons. Lift the inner dial of the meter program wheel so that you can rotate it freely. Position the white dot opposite the 2530 gallon setting.
NOTE:
Unit is set for a 16" diameter tank with 4 ft3 of resin and salted at 8 lbs. per ft3, 7 gpm backwash, #3 injector, 1.0 gpm brine refill, and 60 psi and timer set for
rinse, 10 min. rapid rinse, 10 min. brine tank fill.
Backwash
Brine and Rinse
Rapid Rinse
Brine Tank Fill
With the 2740 gallons available calculated in Step 3, subtract the Regeneration water used from the total water available.
2740 gallons available - 210 gallons used = 2530 gallons
There is a slight delay between the time the meter zeros out and the cycle starts. Units using the: 1/15 RPM motor, 82 minute Regeneration Time has a 9 1/30 RPM motor, 180 minute Regeneration Time has an 18
This delay period is not critical on residential equipment. However, take this factor into consideration for commercial applications by subtracting continuous flows for 9 minutes or 18 minutes from water available.
10 minutes x 7.0 gpm = 70.0 gallons 60 minutes x 1.0 gpm = 60.0 gallons 10 minutes x 7.0 gpm = 70.0 gallons 10 minutes x 1.0 gpm = 10.0 gallons
Total Regeneration Water = 210.0 gallons
(in Regeneration, Step 4)
10 min. backwash, 60 min. brine and
minute delay
minute delay
.
5. Insert meter cable into meter.
6. Check bypass.
7. Plug in unit.
11
Model 9000/9100/9500
ET Timer Installation And Start-Up Procedures
1. In Normal Operation the Time Of Day and, if flow meter equipped, the Volume Remaining displays appear alternately. Set the Time Of Day display. Press the Up or Down set button to display the correct time.
Example:
12:59 P.M.
Val ve
In Service
Figure 6
2.
Flow Meter Equipped Valves Only:
(including any reserve capacity) remaining prior to Regeneration. When there is no water usage the Meter arrow should not appear or not change. Open a soft water tap. The Meter arrow begins flashing at a rate that varies with flow rate. Close the tap after 3–5 gallons of water flow.
The Volume Remaining Display displays the volume of water in gallons
Example:
125 gallons of water remaining
Valve
In Service
No water flow Volume below reserve capacity Reserve arrow flashing
Figure 7
3. Manually initiate a Regeneration cycle and allow water to run to drain for 3 to 4 minutes. Press and release the Extra Cycle button. With Immediate Regeneration timers the control goes into Regeneration immediately. With Delayed Regeneration timers the In Service arrow flashes immediately and a Regeneration occurs at the preset Regeneration Time. Press and hold the Extra Cycle button for 5 seconds. The control goes into Regeneration immediately.
4. Manually step the valve through a Regeneration cycle, checking valve operation in each step. During Regeneration the control displays the Regeneration step number to which the valve is advancing or has reached and the time remaining in that step.
Example:
0 gallons of water remaining
Valve
In Service
Water flowing Volume below reserve capacity Reserve arrow flashing
12
Model 9000/9100/9500
Example:
Valve advancing to Regeneration Step #1
#1 flashing Regeneration arrow on
— When the first cycle step is reached, a red LED turns on indicating the current Regeneration cycle step.
Example:
Regeneration Step #1 reached
10.0 minutes remain in Step #1 Regeneration arrow on
— Press the Extra Cycle button during a Regeneration step to immediately advance the valve to the next
Regeneration step position.
— Press the Up or Down set buttons during a Regeneration step to adjust the time remaining in the current
Regeneration step. Programmed Regeneration step times are not changed.
Backwash
Figure 8
Backwash
Figure 9
— Once all Regeneration cycle steps are complete, the valve returns to In Service and resumes normal
operation.
5. Manually step the valve to the Brine Draw position (see Step #15) and allow the valve to draw water from the brine tank until it stops.
*NOTE:
6. Manually step the valve to the Brine Refill position and allow the valve to return to In Service automatically.
7. Make sure the brine refill time (salt dosage) is set as recommended by the manufacturer.
8. With the valve In Service, check that there is about 1 of water above the grid in the brine tank, if one is used.
9. Fill the brine tank with salt.
NOTE:
The air check checks at approximately the midpoint of the screened intake area.
It is recommended a 9V Alkaline Battery be installed at all times for proper valve operation. The Low Battery LED turns on when the battery needs to be replaced.
13
Model 9000/9100/9500
ET Timer Control Start-Up Procedure
Display ET
Service Indicator
Valve In Service, Arrow On Manual Regeneration Tonight, Flashing Arrow
Time of Day Indicator
Reserve Indicator
Volume Remaining Above Reserve, Arrow Off Volume Remaining At or Below Reserve, Arrow Flashing
Totalizer Indicator
Flow Indicator
No Water Flow, Arrow Off Water Flow, Arrow Flashing
Sensor Indicator
Sensor Input Signal, Arrow Flashing Valid Regeneration Signal, Arrow On
Flow Rate Indicator
Program Indicator
Volume Remaining Indicator
Lockout Indicator
Lockout Signal, Arrow On
Regeneration Indicator
Valve in Regeneration, Arrow On
Figure 10:ET
In Normal operation the Time Of Day display alternates with the Volume Remaining display. The meter arrow flashes in direct relation to the water flow rate through the unit. As treated water is used, the Volume Remaining display counts down from a maximum value to the calculated reserve capacity. The Reserve arrow flashes when the reserve capacity is being used. At the preset Regeneration Time, a Regeneration cycle initiates.
Example:
125 gallons of water remaining
Valve No water flow Volume is below reserve capacity
Example:
0 gallons of water remaining
Valve Water flowing Meter arrow flashing Volume is below reserve capacity
In Service
In Service
Timer Display
Figure 11
14
Model 9000/9100/9500
ET Timer Control Operation
Timeclock Regeneration Valves
When the number days since the last Regeneration reaches the preset number of days, a Regeneration cycles initiates at the preset Regeneration Time.
Flow Meter Equipped Immediate Regeneration Valves
The Time Of Day display alternates with the Volume Remaining display. The Meter arrow flashes in direct relation to the water flow rate through the unit. As treated water is used, the Volume Remaining display counts down from a maximum value to zero and initiates a Regeneration cycle.
Example:
525 gallons of water remaining
Valve Water flowing
Meter arrow flashing
In Service
Figure 12
Sensor Immediate Regeneration Valves
When the control receives a valid sensor input signal, a Regeneration cycle initiates. The Sensor Input arrow flashes until the signal is determined to be valid.
Sensor Delayed Regeneration Valves
When the control receives a valid sensor input signal, a Regeneration cycle initiates at the preset Regeneration Time. The Sensor Input arrow flashes until the signal is determined to be valid. The Reserve arrow flashes when
the reserve capacity is being used.
Example:
12:58 A.M. with invalid sensor signal
Valve Sensor arrow flashing
Example:
12:59 A.M. with valid sensor signal
Valve Sensor arrow on Reserve arrow flashing Delayed regeneration
In Service
In Service
Figure 13
Lockout Input Operation
The lockout arrow turns on whenever the control sends a lockout signal. Any requests for Regeneration are delayed until this signal is removed. Regeneration then proceeds normally.
15
Model 9000/9100/9500
Figure 14
Start an Extra Cycle
Press the Extra Cycle button to start an Extra Regeneration tonight. Press and hold the Extra Cycle button for 5 seconds to start an Extra Cycle immediately.
Totalizer/Flow Rate
Press the Totalizer Flow Rate button to display the flow rate.
Press the button a second time to display the total accumulation of water flow through the valve since the last reset.
Press the button a third time to return the display to Time Of Day or Volume Remaining.
— Press and hold the button for 25 seconds to reset the Totalizer display. During the 25 seconds, the
Totalizer arrow flashes indicating that the display is resetting properly.
Low Battery Indicator
Figure 15
The red Low Battery LED turns on whenever the 9V Alkaline Battery (not included) requires replacement. The battery is used for memory backup and is stored against the valve backplate. In the event of a power outage, the battery maintains the current operating displays for approximately 24 hours at maximum battery capacity.
Immediate Regeneration Valves With Days Between Regeneration Override Set
When the valve reaches its set Days Since Regeneration Override value, a Regeneration cycle initiates immediately. This event occurs regardless of the Volume Remaining display reaching zero gallons.
Delayed Regeneration Valves With Days Between Regeneration Override Set
When the valve reaches its set Days Since Regeneration Override value, a Regeneration cycle initiates at the preset Regeneration Time. This event occurs regardless of the Volume Remaining display reaching the calculated reserve capacity.
Control Operation During Regeneration
In Regeneration the control displays a special Regeneration display. The control shows the current Regeneration step number to which the valve is advancing or has reached, and the time remaining in that step. The displayed step number flashes until the valve completes driving to the Regeneration step position. Once all Regeneration steps are complete the valve returns to In Service and resumes normal operation.
16
Model 9000/9100/9500
Example:
Less than 10 minutes remaining in Regeneration Step #1
Figure 16
Press the Extra Cycle button during a Regeneration cycle to immediately advances the valve to the next cycle step position and resume normal step timing.
Control Operation During Programming
The control enters Program Mode with the valve In Service. While in Program Mode the control continues to operate normally, monitoring water usage and keeping all displays up to date. Control programming is stored in memory permanently. There is no need for battery backup power.
Control Operation During A Power Failure
During a power failure all control displays and programming are stored for use upon power re-application. The control retains these values for years, if necessary, without loss. The control is fully inoperative and any calls for Regeneration are delayed. The control, upon power re-application, resumes normal operation from the point that it was interrupted. An inaccurate or flashing Time of Day display indicates that a power outage has occurred.
Backwash
17
Model 9000/9100/9500
SE Timer Control Start-Up Procedures
Display SE
Figure 17:SE
In normal operation the Time Of Day display alternates with Volume Remaining and Tank in In Service displays (
9000SE Timer
maximum value to zero or (----). Once this occurs a Regeneration cycle initiates immediately or delayed to the set Regeneration Time. Water flow through the valve is indicated by the flashing Flow Dot Indicator.
only). As treated water is used, the Volume Remaining display counts down (in gallons) from a
Figure 18:SE
Timer Display During Normal Operation
Timer Display
Set Time of Day
When the valve is In Service, press either the Set Up or Set Down button once to adjust the Time Of Day by one digit. Press and hold to adjust by several digits.
Start an Extra Regeneration Cycle
Press the Extra Regeneration button to start an Extra Regeneration tonight. Press and hold the Extra Regeneration button for 5 seconds to start an Extra Regeneration immediately.
18
Model 9000/9100/9500
Set Control Programming
1. Press and hold both the Set Up and Set Down buttons for 5 seconds.
2. Set the Treated Water Capacity. Using the Set Up or Set Down buttons, set the amount of treated water to flow through the unit before a Regeneration is required.
3. Press the Extra Regeneration button.
4. Set the Regeneration Time. Use the Set Up or Set Down buttons to set the desired time of day for
Regeneration to occur.
NOTE:
5. Press the Extra Regeneration button.
6. Set Regeneration Day Override. Use the Set Up or Set Down buttons to set the maximum number of days before a Regeneration cycle must occur.
7. Press the Extra Regeneration button to exit the program.*
NOTE:
This does not display if Regeneration occurs immediately.
If setting up the system for the first time, perform the following Fast Cycle Regeneration:
1. Press the Extra Regeneration button for 5 seconds to force an Extra Regeneration immediately.
2. Once the valve reaches Regen Step #1, let water run to drain for approximately 5 minutes.
3. Press the Extra Regeneration button once to advance valve to Regen Step #2.
4. Press the Extra Regeneration button once to advance valve to Regen Step #3 (if active).
5. Press the Extra Regeneration button once to advance valve to Regen Step #4 (if active).
6. Press the Extra Regeneration button once to advance valve to Regen Step #5 (if active).
7. Press the Extra Regeneration button once more to advance the valve back to In Service.
19
Model 9000/9100/9500
Immediate Regeneration Valves With Days Between Regeneration Override Set
When the valve reaches its set Days Since Regeneration Override value, a Regeneration cycle initiates immediately. This event occurs regardless of the Volume Remaining display reaching zero gallons.
Delayed Regeneration Valves With Days Between Regeneration Override Set
When the valve reaches its set Days Since Regeneration Override value a Regeneration cycle initiates at the preset Regeneration Time. This event occurs regardless of the Volume Remaining display reaching zero gallons.
Control Operation During Regeneration
In Regeneration the control displays a special Regeneration display. While in Regeneration the control shows the current Regeneration step number to which the valve is advancing or has reached, and the time remaining in that step. The displayed step number flashes until the valve completes driving to this Regeneration step position. Once all Regeneration steps are complete the valve returns to In Service and resumes normal operation.
Example:
Figure 19
Pressing the Extra Cycle button during a Regeneration cycle immediately advances the valve to the next cycle step position and resumes normal step timing.
Control Operation During Programming
The control only enters the Program Mode with the valve In Service. While in the Program Mode the control continues to operate normally monitoring water usage and keeping all displays up to date. Control programming is stored in memory permanently. There is no need for battery backup power.
Control Operation During A Power Failure
During a power failure all control displays and programming are stored for use upon power re-application. The control retains these values for years, if necessary, without loss. The control is fully inoperative and any calls for Regeneration are delayed. The control, upon power re-application, resumes normal operation from the point that it was interrupted. An inaccurate or flashing Time of Day display indicates that a power outage has occurred.
20
Model 9000/9100/9500
ET and SE Timer Assemblies
Figure 20
Item Quantity Part Number Description
1 1 configured item 2 1 configured item 3 1 40427-03 wire harness
ET
timer assembly
SE
timer assembly
21
Model 9000/9100/9500
9000/9100/9500 Electro Mechanical Timer Assembly
22
Figure 21
Model 9000/9100/9500
9000/9100/9500 Electro Mechanical Timer Assembly
Item Quantity Part Number Description
1 1 13870-03 timer housing assembly. 2 1 17870 label, capacity gallons 3 1 15465 label, Caution 4 1 16930 label, Instruction 5 1 15227 actuator plate 6 1 10300 screw, hex washer #8 7 1 17513 spring clip 8 1 15407 washer, plain #4 9 1 15228 spring 10 1 16270-10 gallon wheel assembly 3/4" standard range meter
16270-50 gallon wheel assembly 3/4" extended range meter 16270-30 gallon wheel assembly 1" standard range meter 16270-40 gallon wheel assembly 1" extended range meter 16270-50 gallon wheel assembly 1-1/2" standard range meter
16270-60 gallon wheel assembly 1-1/2" extended range meter 11 1 13806 program wheel retainer 12 1 13748 screw, flathead #6-20 13 2 11999 button decal 14 1 15223 cycle actuator gear 15 1 13886-01 knob 16 4 13296 screw, hex washer #6-20 17 1 17724 drive pinion 18 1 17723 drive pinion clutch 19 1 14276 spring, meter clutch 20 1 14253 retainer 21 3 14087 insulator 22 1 15314 switch 23 1 15320 switch 24 2 11413 screw, pan head #4-40 25 1 13018 idler shaft 26 1 18563 spring, idler shaft 27 1 13017 idler gear 28 1 13164 drive gear 29 1 13887 motor mounting plate 30 1 18743 motor, 120V 60 Hz.-1/30 RPM
18824 motor, 220V 50 Hz.-1/30 RPM
19170 motor, 120V 60 Hz.-1/15 RPM
18825 motor, 220V 50 Hz.-1/15 RPM 31 2 13278 screw, #6-32 32 1 14265 spring clip 33 1 15055 main drive gear 34 1 19210-02 program wheel, 90 minute
19210-05 program wheel, 180 minute 35 23 15493 roll pin 36 1 15203 harness 37 2 12681 wire nut 38 1 60320-02 auxiliary timer switch kit (not shown)
23
Model 9000/9100/9500
9000/9100/9500 Power Head
24
Figure 22
Model 9000/9100/9500
9000/9100/9500 Power Head
Item Quantity Part Number Description
1 2 18728 nut, clip #8-32 2 1 11838 power cord, 6' U.S. 120V
11839 power cord, 12' U.S.120V 40084-12 power cord, 12' U.S. 120V ( 11545-01 power cord, 5' European 220V 14678 power cord, 6' U.S. 220V 19303-01 power cord, Australian 8' 220V 40085-12 power cord, 12' U.S. 220V ( 19674 transformer, U.S., 110V to 24V 25651 transformer, European, 220V to 24V
3 1 15202 wire harness, mechanical
14822 wire harness auxiliary drive switch
40041-06 wire harness, low voltage ( 4 1 15134 drive gear assembly, lower 5 1 15135 drive gear assembly 6 1 14896 geneva wheel 7 2 40422 wire connector 8 2 19367 cover screw 9 1 15175 position decal 10 2 14917 retaining ring 11 1 15199 ground plate 12 1 14430 screw, hex washer #6 13 2 19160 screw, motor mounting 14 1 18737 drive motor, 24V, 50/60 Hz (red wires)
1 18738 drive motor, 120V, 60 Hz (black wires) 1 18739 drive motor, 220V, 50 Hz (yellow wires)
15 1 15131 backplate, mechanical and
17784-05 backplate,
17784-06 backplate, 16 2 15172 screw, flat head #4-40 17 2 10340 washer, lock #4 18 10218 micro switch (homing) 19 1 10339 nut, micro switch 20 1 15331 screw, valve mounting 21 2 15133 drive gear assembly, upper 22 1 13547 strain relief 23 1 15810 retaining ring, drive gear 24 1 15132 triple cam (
17331 triple cam (
17765 triple cam ( 25 1 15638 cable guide (
1 17337 cable guide ( 26 2 15372 washer, thrust 27 1 15216 meter cable, 15.25", 1" meter, mechanical
15425 meter cable, 13.25", 3/4" meter, mechanical 17744 meter cable, 20.75", 1-1/2" meter, mechanical 19121-01 meter cable, 1" meter, 19121-05 meter cable, 3/4" and 1" meter,
19791-01 meter cable, 1" meter, 28 2 15692 spacer 29 1 16433 micro switch (program) 30 1 10302 insulator 31 2 15173 screw
Not Shown
32 1 60232-110 cover, black
1 60232-112 cover, black - left window
33 1 60320-09 optional auxiliary drive switch (
1 60320-10 optional auxiliary drive switch (
ET ET
9000/9100 9500
)
9500
auxiliary switch)
9000/9100 9500
)
)
)
SE
SE
ET
)
ET
)
ET
)
SE
ET
9000/9100 9500
)
)
25
Model 9000/9100/9500
9000 Control Valve Assembly
26
Figure 23
Model 9000/9100/9500
9000 C ontrol Va l ve Assembl y
Item Quantity Part Number Description
1 1 14861-01 valve body, machined
1 14861-01NP valve body, machined (nickel plated) 2 4 15137 screw, hex washer #10-24 x 3/8" 3 1 14906 end plate 4 1 14928 end plug 5 6 7 1 15471 stand off 8 1 60400 piston assembly, top
1 60400-01 piston assembly, top (hot water) 9 1 60125 seal and spacer kit, top
60125-HW seal and spacer kit, top (hot water) 60125-20 seal and spacer kit, top (559PE)
10 1 60421 seal and spacer kit, bottom
60421-HW seal and spacer kit, bottom (hot water) 60421-20 seal and spacer kit, (559PE)
11 1 60401 piston assembly, bottom
60401-01 piston assembly, bottom (hot water)
12 1 60385-XXXX injector assembly
(see chart for dash numbers)
injector number DLFC number BLFC number
red #0 00 Blank 0 Blank 0
white #1 01 1.2 1 0.25 1
blue #2 02 1.5 2 0.50 2
yellow #3 03 2.0 3 1.00 3
green #4 04 2.4 4
3.0 5
3.5 6
4.0 7
5.0 8
7.0 9
12A 1 60022-12 brine line flow control assembly, 0.125 gpm
60022-25 brine line flow control assembly, 0.250 gpm 60022-50 brine line flow control assembly, 0.500 gpm 60022-100 brine line flow control assembly, 1.00 gpm
12B 1 60350 brine valve assembly
Not Shown
13 12763 seal and space stuffer tool 14 13061 spacer puller tool 15 13759 DLFC retainer tool
27
Model 9000/9100/9500
9100 Control Valve Assembly
28
Figure 24
Model 9000/9100/9500
9100 Control Valve Assembly
Item Quantity Part Number Description
1 1 40688 valve body assembly 2 4 15137 screw, hex washer #10-24 x 3/8” 3 1 14906 end plate 4 1 14928 end plug 5 1 19054 O-ring, 124 6 1 18303 O-ring, 336 7 1 40538 retainer, 32mm 8 1 60400 piston top assembly 9 1 60125 seal and spacer kit, top
1 60125-20 seal and spacer kit, top (559PE)
10 1 60421 seal and spacer kit, bottom
1 60421-20 seal and spacer kit, bottom (559PE) 11 1 60401 piston assembly, bottom 12 1 60385-XXXX injector assembly
(see following chart for dash numbers)
injector number DLFC number BLFC number
red #0 00 Blank 0 Blank 0
white #1 01 1.2 1 0.25 1
blue #2 02 1.5 2 0.50 2
yellow #3 03 2.0 3 1.00 3
green #4 04 2.4 4
12A 1 60022-12 brine line flow control assembly, 0.125 gpm
60022-25 brine line flow control assembly, 0.250 gpm 60022-50 brine line flow control assembly, 0.500 gpm
60022-100 brine line flow control assembly, 1.00 gpm 12B 1 60350 brine valve assembly 13 1 61419 distributor adapter kit, 1.05"
3.0 5
3.5 6
4.0 7
5.0 8
7.0 9
Not Shown
14 12763 seal and space stuffer tool 15 13061 spacer puller tool 16 13759 DLFC retainer tool
29
Model 9000/9100/9500
9500 Control Valve Assembly
Figure 25
Item Quantity Part Number Description
1 1 16919-01 valve body
16919-01NP valve body 16919-21 valve body
16919-21NP valve body 2 1 60080-XX injector assembly (see chart for dash numbers) 3 1 60039-XX injector assembly (see chart for dash numbers)
4 1 60134 seal and spacer kit, top
60134-01 seal and spacer kit, top, hot water
60134 seal and spacer kit, top, silicone 5 1 60108 piston assembly, top
60108-01 piston assembly, top, hot water 6 1 60109 piston assembly, bottom
60109-01 piston assembly, bottom, hot water 7 1 60133 seal and spacer kit, bottom
60133-01 seal and spacer kit, bottom, hot water
60133-10 seal and spacer kit, bottom, silicone 8 1 16455 O-ring, 347 9 1 13577 O-ring, 226 10 1 16955 end plug 11 1 16394 O-ring, 029 12 1 14906 end plate 13 4 15137 screw, hex washer machine, 1-24 x 3/8
17657 screw, hex M5-40, Metric
Not Shown
14 16516 tool, seal and spacer stuffer 15 17623 tool, spacer puller
9500
NPT, mechanical base
9500
NPT, mechanical base, nickel-plated
9500
BSP/Metric, mechanical base
9500
BSP/Metric, mechanical base, nickel-plated
injector
blue #2
yellow #3
green #4
white #5
number
02 03 04 05
30
Model 9000/9100/9500
9500 Brine Valve Systems (1600 and 1700 Series)
Figure 26
Figure 27
Item Quantity Part Number Description
1 1 16922 bracket, brine valve 2 2 15137 screw, brine valve bracket 3 1 60037-610 brine valve assembly, 0.25 gpm
60020-620 brine valve assembly, 0.50 gpm 60020-630 brine valve assembly, 1.00 gpm 60020-690 brine valve assembly, blank 60037HW brine valve assembly, hot water
3A 1 60020-25 brine line flow control assembly, 0.25 gpm
60020-50 brine line flow control assembly, 0.50 gpm
60020-100 brine line flow control assembly, 1.00 gpm 4 1 tube, brine valve 5 1 adapter kit 6 1 16922 bracket, brine valve 7 2 15137 screw, brine valve bracket 8 2 15414 nut, tube 9 1 16959 tube, brine valve 10 1 60039-00 brine valve assembly, blank
60039-10 brine valve assembly, 1.0 gpm
60039-12 brine valve assembly, 1.2 gpm
60039-15 brine valve assembly, 1.5 gpm
60039-20 brine valve assembly, 2.0 gpm
60039-24 brine valve assembly, 2.4 gpm
60039-30 brine valve assembly, 3.0 gpm
60039-35 brine valve assembly, 3.5 gpm
60039-40 brine valve assembly, 4.0 gpm
1600 Series Brine System
1700 Series Brine System
31
Model 9000/9100/9500
9000/9100/9500 Second Tank Assemblies
Figure 28
32
Figure 29
Figure 30
Model 9000/9100/9500
9000/9100/9500 Second Tank Assemblies
Item Quantity Part Number Description
9000 second tank assembly
1 4 14202-01 screw, hex head #8-32 2 4 13255 clip, hold-down 3 4 15078-01 coupling assembly, 4 1 14864-01 second tank adapter assembly,
14864-01NP second tank adapter assembly,
5 1 15823-06 yoke assembly 6" tanks, 6" tubes
15823-06NP yoke assembly 6" tanks, 6" tubes, nickel-plated 15823-12 yoke assembly 12" tanks, 8-1/2" tubes 15823-12NP yoke assembly 12" tanks, 8-1/2" tubes, nickel-plated 15823-14 yoke assembly 14" tanks, 10-1/2" tubes 15823-14NP yoke assembly 14" tanks, 10-1/2" tubes, nickel-plated 15823-16 yoke assembly 16" tanks, 12-1/2" tubes 15823-16NP yoke assembly 16" tanks, 12-1/2" tubes, nickel-plated
9100 second tank assembly
6 1 60425-12 plastic tube assembly,
60425-16 plastic tube assembly, 7 1 14865 second tank adapter assembly, 8 1 61419 distributors adapter kit,
9000
9100 9100
9000 9000,
, up to 12" tanks , up to 16" tanks
9100
9100
, 1.05"
nickel-plated
9500 second tank assembly
9 1 16919-01 second tank adapter assembly,
16919-01NP second tank adapter assembly,
16919-21 second tank adapter assembly,
16919-21NP second tank adapter assembly, 10 1 60715-16 tube assembly 16" tanks
60715-16NP tube assembly 16" tanks, nickel-plated
60715-20 tube assembly 20" tanks
60715-20NP tube assembly 20" tanks, nickel-plated
60715-24 tube assembly 24" tanks
60715-24NP tube assembly 24" tanks, nickel-plated
9500 9500
, nickel-plated
9500
, BSP/Metric
9500
, BSP/Metric, nickel-plated
33
Model 9000/9100/9500
9000/9100/9500 Meter Assemblies
Figure 31
34
Figure 32
Figure 33
Model 9000/9100/9500
9000/9100/9500 Meter Assemblies
Item Quantity Part Number Description
9000 meter assembly
1 1 60086 3/4" meter assembly, standard range
ET
60086-50 3/4" meter assembly, electronic (
60087 3/4" meter assembly, extended range 1A 1 14038 meter cap assembly, standard range 1B 14716 meter cap assembly, electronic (ET) 1C 15150 meter cap assembly, extended range 1D 1 15218 meter cap assembly, brass standard range
15218NP meter cap assembly, brass nickel-plated standard range 1E 15237 meter cap assembly, brass extended range
15237NP meter cap assembly, brass nickel-plated extended range 2 1 13509 impeller
13509-01 impeller, hot water 3 1 19797 3/4" turbine meter assembly, less clips and screws
60626 3/4" turbine meter assembly with clips, screws, meter cable
60626-01 3/4" turbine meter assembly, with clips and screws 4 1 60389 1" meter assembly, standard range
60389NP 1" meter assembly, standard range
1 60389-20 1" meter assembly, standard range, BSP
60390 1" meter assembly, extended range
60390NP 1" meter assembly, extended range, nickel-plated
60390-20 1" meter assembly, extended range, BSP
60612 1" meter assembly, standard range, hot water
60622 1" meter assembly, electronic 4A 1 15078 1" adapter coupling
5
Not Shown
6* 7 8
1 60610-01 1-1/2" meter assembly, standard range
60610-01NP 1-1/2" meter assembly, standard range, nickel-plated
60610-02 1-1/2" meter assembly, extended range
60610-02NP 1-1/2" meter assembly, extended range, nickel-plated
60610-21 1-1/2" meter assembly, standard range, BSP
60610-21NP 1-1/2" meter assembly, standard range, BSP, nickel-plated
60610-22 1-1/2" meter assembly, extended range, BSP
60610-22NP 1-1/2" meter assembly, extended range, BSP, nickel-plated
60611-01 1-1/2" meter assembly, standard range, with 1" sleeve
60611-01NP 1-1/2" meter assembly, standard range, with 1" sleeve, nickel-plated
60611-02 1-1/2" meter assembly, extended range, with 1" sleeve
60611-02NP 1-1/2" meter assembly, extended range, with 1" sleeve, nickel-plated
17790
60460
60461
1-1/2" meter sleeve reduced to 1" meter checker kit, standard range meter checker kit, extended range
)
*
when reducing 1-1/2" meter to 1" program wheel and timer settings must be changed to 1" meter size
35
Model 9000/9100/9500
9000/9100 Bypass Valve
Figure 34
Item Quantity Part Number Description
1 1 60040SS 3/4" bypass valve NPT
60040-10 3/4" bypass valve BSP 60041SS 1" bypass valve NPT 60041-10 1" bypass valve BSP
2 1 60049 plastic bypass valve
Not Shown
3 40157 plastic bypass T-handle wrench
36
Model 9000/9100/9500
2310 Safety Brine Valve
Figure 35
Item Quantity Part Number Description
1 1 60014 2 1 60068
60026-30 float assembly red/white (float fill)
3 1 60002 #500 air check
2310
safety brine valve
2310
float assembly
37
Model 9000/9100/9500
9500, 2350 Safety Brine Valve
Figure 36
Item Quantity Part Number Description
1 1 60038 1A 1 61024 2 1 60026-30 float assembly red/white
60076-30SAN float assembly green/green (hot water)
3 1 60009-00 #900 air check
1 60009-01 #900 air check hot water
Not Shown
4 18603 5 18604 #900 fittings for
2350
safety brine valve
2350
actuator assembly
2350
fittings for
1700
brine system
1700
brine system
38
Model 9000/9100/9500
2300 Safety Brine Valve
Figure 37
Item Quantity Part Number Description
1 1 60027-FFA
60027-FFS
2 1 60028-30 float assembly blue/white
60026-30SAN float assembly green/green, hot water
3 1 60002 #500 air check
60003 #500 air check, hot water
2300
safety brine valve, fitting facing arm
2300
safety brine valve, fitting facing stud
39
Model 9000/9100/9500
Water Conditioner Flow Diagrams
In Service Position
Tanks Switching
Figure 38
: In Service Position
40
Figure 39
: Tanks Switching, Meter Initiated Regeneration
Model 9000/9100/9500
Backwash
Brine Draw
Figure 40
: Backwash Position
Figure 41
: Brine Draw
41
Model 9000/9100/9500
Slow Rinse
Rapid Rinse
Figure 42
: Slow Rinse
42
Figure 43
: Rapid Rinse
Model 9000/9100/9500
Brine Tank Fill Position
In Service, Tanks Switched
Figure 44
: Brine Tank Fill Position
Figure 45
: In Service, Tanks Switched
43
Model 9000/9100/9500
Troubleshooting
PROBLEM CAUSE CORRECTION
1. Softener fails to regenerate. A. Electrical service to unit has been interrupted.
B. Timer is defective.
2. Hard water. A. Bypass valve is open.
B. No salt in brine tank.
C. Injector screen plugged.
D. Insufficient water flowing into brine
tank.
E. Hot water tank hardness.
F. Leak at distributor tube.
G. Internal valve leak.
3. Unit used too much salt. A. Improper salt setting.
B. Excessive water in brine tank.
4. Loss of water pressure. A. Iron buildup in line to water conditioner.
B. Iron buildup in water conditioner.
C. Inlet of control plugged due to
foreign material broken loose from pipe by recent work done on plumbing system.
A. Assure permanent electrical
service (check fuse, plug, pull chain or switch).
B. Replace timer.
A. Close bypass valve. B. Add Salt to brine tank and maintain
salt level above water level. C. Clean injector screen. D. Check brine tank fill time and clean
brine line flow control if plugged. E. Repeated flushing of the hot water
tank is required. F. Make sure distributor tube is not
cracked. Check O-Ring and tube
pilot. D. Replace seals and spacers and/or
piston.
A. Check salt usage and salt setting. B. See Problem No. 7.
A. Clean line to water conditioner.
B. Clean control and add mineral
cleaner to mineral bed. Increase
frequency of regeneration and/or
backwash time. C. Remove pistons and clean control.
5. Loss of mineral through drain line. A. Air in water system.
B. Drain line flow control too large.
6. Iron in conditioned water. A. Fouled mineral bed. A. Check backwash, brine draw and
7. Excessive water in brine tank. A. Plugged drain line flow control. B. Plugged injector system. C. Timer not cycling. D. Foreign material in brine valve.
E. Foreign material in brine line flow
control.
F. Power loss during brine fill.
A. Assure that well system has
proper air eliminator control. Check for dry well condition.
B. Check to ensure drain line flow
control is sized properly for your mineral tank.
brine tank fill. Increase frequency of regeneration.
A. Check flow control. B. Clean injector and screen. C. Replace timer. D. Replace brine valve seat and clean
valve.
E. Clean brine line flow control.
F. Check power source.
44
Model 9000/9100/9500
PROBLEM CAUSE CORRECTION
8. Softener fails to draw brine. A. Drain line flow control is plugged. B. Injector is plugged. C. Injector screen plugged. D. Line pressure is too low.
E. Internal Control Leak
9. Control cycles continuously. A. Broken or shorted switch. A. Determine if switch or timer is
10.Drain flows continuously. A. Valve is not programming correctly.
B. Foreign material in control.
C. Internal control leak.
A. Clean drain line flow control. B. Clean injector. C. Clean screen. D. Increase line pressure to
25 psi min.
E. Change seals, spacers and piston
assembly.
faulty and replace it, or replace complete power head.
A. Check timer program and positioning
of control. Replace power head assembly if not positioning properly.
B. Remove power head assembly and
inspect bore, remove foreign material and check control in various regeneration positions.
C. Replace seals and piston assembly.
General Service Hints Problem: Softener delivers hard water
PROBLEM CAUSE CORRECTION
Softener delivers hard water. Reserve capacity has been exceeded. Check salt dosage requirements and
reset program wheel to provide addi­tional reserve.
Program wheel is not rotating with meter output.
Meter is not measuring flow. Check output by observing rotation of
Pull cable out of meter cover and rotate manually. Program wheel must move without binding and cycle actuator must start the cycle before the clutch releases.
small gear on front of timer
(Note: Program wheel must not be against regeneration stop for this check)
Each tooth is approximately 75 gallons on 1-1/2installations. If not performing properly, replace meter.
45
Model 9000/9100/9500
Mechanical Timer Valve Wiring
TM - TIMER MOTOR
VDM - VALVE DRIVE MOTOR
SW1 - TIMER HOMING SWITCH
SW2 - TIMER PROGRAM SWITCH
SW3 - VALVE HOMING SWITCH
SW4 - VALVE PROGRAM SWITCH
THCAM - TIMER HOMING CAM
TPCAM - TIMER PROGRAM CAM
Figure 46
46
Model 9000/9100/9500
ET Timer Valve Wiring
TB1 - HIGH VOLTAGE TERMINAL BLOCK
TB2 - LOW VOLTAGE TERMINAL BLOCK
CB1 - 3200ET CIRCUIT BOARD
F1 - TIMED AUXILIARY OUTPUT FUSE
VDM - VALVE DRIVE MOTOR
SW1 - HOMING SWITCH
SW2 - STEP SWITCH
SW3 - BRINE CAM SWITCH
HCAM - VALVE HOMING CAM
SCAM - VALVE STEP CAM
BVCAM - BRINE VALVE CAM
Twin Unit Meter/Timeclock/Sensor Regeneration
Figure 47
47
Model 9000/9100/9500
SE Timer Valve Wiring
CB1 - SE TIMER
T1 - 24V TRANSFORMER
TM - 3/4" TURBINE FLOW METER (OPTIONAL)
PWM - 1.0" PADDLE WHEEL FLOW METER (OPTIONAL)
VDM - VALVE DRIVE MOTOR
SW1 - VALVE HOMING SWITCH
SW2 - VALVE STEP SWITCH
HCAM - VALVE HOMING CAM
SCAM - VALVE STEP CAM
Figure 48
48
Model 9000/9100/9500
9000 Control Dimensions
Figure 49
49
Model 9000/9100/9500
9100 Control Dimensions
50
Figure 50
Model 9000/9100/9500
9500 Control Dimensions
Figure 51
51
Model 9000/9100/9500
Meter Flow Data
9000
Figure 52:9000
Meter Flow Data
52
Model 9000/9100/9500
9100
9500
Figure 53:9100
Figure 54:9500
Meter Flow Data
Meter Flow Data
53
Model 9000/9100/9500
Injector Flow Data
9000/9100
54
Figure 55:9000/9100—1600 Series Injectors
Model 9000/9100/9500
9500
Figure 56:9500—1600 Series Injectors
Figure 57
:
95001700 Series Injectors
55
P/N 40944 Rev. A 01/03
Loading...