Watts 9500 User Manual

Model 9000/9100/9500
Service Manual
IMPORTANT: Fill in pertinent information on
page 3
for future reference.
Model 9000/9100/9500
Table of Contents
General and Commercial Installation Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
General and Commercial Installation Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
ET
Timer Installation And Start-Up Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
ET
Timer Control Start-Up Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
ET
Timer Control Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
SE
Timer Control Start-Up Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
ET
and SE Timer Assemblies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
9000/9100/9500 9000/9100/9500 9000/9100/9500 9000
Control Valve Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
9100
Control Valve Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
9500
Control Valve Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
9500
Brine Valve Systems (
9000/9100/9500 9000/9100/9500 9000/9100 2310
Safety Brine Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
9500,2350 2300
Safety Brine Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Water Conditioner Flow Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
ET
Timer Valve Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
SE
Timer Valve Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
9000
Control Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
9100
Control Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
9500
Control Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Meter Flow Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Injector Flow Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Electro Mechanical Timer Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Power Head . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Power Head . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
1600
and
1700
Series) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Second Tank Assemblies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Meter Assemblies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Bypass Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Safety Brine Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
IMPORTANT: The information, specifications and illustrations in this manual are based on the latest information available at the time of printing. The manufacturer reserves the right to make changes at any time without notice.
Model 9000/9100/9500
Job Specifications Sheet
Job Number ___________________________________________
Model Number _________________________________________
Water Test ____________________________________________
Capacity Of Unit ________________________ Max. _____________ Per Regeneration
Brine Tank Size _____________________________________
Salt Setting Per Regeneration ____________________________________
Control Valve Specifications
1. Type of Timer
A. 82 minute available regeneration time, 1/15 RPM
B. 164 minute available regeneration time, 1/30 RPM
2. Type of Meter
Mechanical Valves
(gallon settings)
Meter Standard Range Extended Range
3/4" 125–2,125 625–10,625 1" 310–5,270 1,150–26,350 1-1/2" 625–10,625 3,125–53,125
Electrical Timers
(minutes per cycle)
Meter ET SE
(0–999.9 minutes per cycle) (0–99 minutes per cycle) 3/4" 9,999,999 9,999 1" 9,999,999 9,999 1-1/2" 9,999,999
3. Timer Gallon Setting ______________________________ gal.
4. Regeneration Program Setting
A. Backwash___________________________________ min.
B. Brine and Slow Rinse _________________________ min.
C. Rapid Rinse _________________________________ min.
D. Brine Tank Refill _____________________________ min.
5. Drain Line Flow Control __________________________ gpm
6. Brine Refill Rate _______________________________ gpm
7. Injector Size _______________________________________
3
Model 9000/9100/9500
General and Commercial Installation Checklist
Water Pressure
A minimum of 25 lbs of water pressure is required for regeneration valve to operate effectively.
Electrical Facilities
An uninterrupted alternating current (A/C) supply is required. Make sure:
Voltage supply is compatible with unit before installation.
Current supply is always hot and cannot be turned off with another switch.
Existing Plumbing
Condition of existing plumbing should be free from lime and iron buildup. Replace piping that has heavy lime and/or iron build-up. If piping is clogged with iron, install a separate iron filter unit ahead of the water softener.
Location of Softener and Drain
Locate the softener close to a clean working drain and connect according to local plumbing codes.
Bypass Valves
Always provide for the installation of a bypass valve if unit is not equipped with one.
CAUTION
Do not exceed water pressure of 125 psi.
Do not exceed 110°F water temperature.
Do not subject unit to freezing conditions.
4
Model 9000/9100/9500
Equipment Configuration
9000/9100
tank two adapter
adapter clips
9500
tank two
1-1/2" copper
yokes
main control valve
Figure 1:9000/9100
tank one
water meter
outlet
inlet
bypass valve
outlet
inlet
meter dome
must face up
tank two adapter
control valve
tank two
Figure 2
:
9500
5
Model 9000/9100/9500
General and Commercial Installation Checklist
1. Place the softener tank where you want to install the unit.
NOTE:
2. During cold weather it is recommended that the installer warm the valve to room temperature before operating.
3. Perform all plumbing according to local plumbing codes.
— Use a 1/2" minimum pipe size for the drain.
— Use a 3/4" drain line for backwash flow rates that exceed 7 gpm or length that exceeds 20 (6 m).
4. Both tanks must be the same height and diameter and filled with equal amounts of media.
5. The distributor tube must be flush with the top of each tank. Cut if necessary. Use only non-aerosol silicone lubricant.
6. Lubricate the distributor o-ring seal and tank o adapter on the second tank.
NOTE:
7. Solder joints near the drain must be done before connecting the Drain Line Flow Control fitting (DLFC). Leave at least 6" (152 mm) between the DLFC and solder joints when soldering pipes that are connected on the DLFC. Failure to do this could cause interior damage to DLFC.
8. Use only
9. Be sure the floor under the salt storage tank is clean and level.
10. Place approximately 1" (25 mm) of water above the grid plate. If a grid is not utilized, fill to the top of the air check in the salt tank. Do not add salt to the brine tank at this time.
Be sure the tank is level and on a firm base.
-ring seal. Place the main control valve on one tank and the tank
If required, solder copper tubing for tank interconnection before assembling on the main control valve and tank adapter. Maintain a minimum of 1" distance between tanks on final assembly.
Teflon
tape on the drain fitting.
11. On units with a bypass, place in Bypass position.
— Turn on the main water supply.
— Open a cold soft water tap nearby and let water run a few minutes or until the system is free of foreign
material (usually solder) resulting from the installation. Close the water tap when water runs clean.
12. Place the bypass In Service position and let water flow into the mineral tank. When water flow stops, slowly open a cold water tap nearby and let water run until air is purged from the unit. Then close tap.
Electrical
13. Make all electrical connections according to codes. Plug the valve into an approved power source. Do not insert meter cable into the meter yet.
14. Tank one has control valve and tank two has adapter. See
15. Look on the right side of the control valve, it has indicators showing which position the control valve is in during Regeneration and which tank is In Service.
Figure 3, page 7
two on standby.
NOTE:
Make sure the meter cable is not inserted in the meter dome. Swing the timer out to expose the program wheel (to swing timer out) grab onto the lower right corner of timer face and pull outward. See
Figure 5, page 8
shows the valve In Service position with tank one supplying conditioned water and tank
.
Figure 1, page 5
or
Figure 2, page 5
.
6
Model 9000/9100/9500
rapid rinse
brine rinse
backwash
tank one
Figure 3
brine fill
stand-by
tank two
: Control Valve Position Indicators
Figure 4
16. Cycle timer into backwash position. Turn manual knob so that the micro switch rides on the first set of pins.
— In this position the tanks switch (lower piston) and the control valve moves to the backwash position (upper
piston).
— Wait until the positioning of upper and lower pistons stops before advancing the timer further.
too fast
correct this, rotate the manual knob back to In Service and start again into backwash.
NOTE:
17. With all the air backwashed, slowly cycle the timer to the brine position; rapid rinse; and brine tank refill. Wait for the control drive motor to position itself in each cycle and stop, before advancing on to the next position.
18. Once back in the In Service position, cycle the control valve again into the backwash position. The tanks switch again, and air head backwashes out of the other tank. Cycle the control back to the In Service position. Leave the timer in the open position. DO NOT insert meter cable yet.
the control will not
Once valve positions itself into the backwash cycle, the homing circuit locks in.
home
into the In Service position (it will not advance to any other position). To
: Timer
If advanced
7
Model 9000/9100/9500
pin
storage
NOTE:
Figure 5
Two motors are available: 1/15 RPM has 82 minute Regeneration Time. 1/30 RPM has 164 minute Regeneration Time. See
: Program Wheel
Figure 5
.
8
Model 9000/9100/9500
Regeneration Cycle Program Setting Procedure
Setting the Regeneration Cycle Program
The Regeneration cycle program on the water conditioner is preset at the factory. However, portions of the cycle or program time may be lengthened or shortened for local conditions or system design.
1. Expose cycle program wheel by grasping timer in lower right hand corner and pulling. This releases snap retainer and swings timer to the left
NOTE:
2. Remove the program wheel by grasping program wheel and squeezing protruding lugs towards center. Lift program wheel off timer.
— Switch arms may require movement to facilitate removal.
3. Return timer to closed position by engaging snap retainer in back plate.
— Make certain all electrical wires locate above snap retainer post.
Changing Length of the Backwash Time
Meter cable
must
be removed from meter dome before opening timer.
The program wheel in group of pins starting at zero determines the length of time the unit backwashes.
Example:
— The number of pins multiplied by two equals minutes of backwash.
If there are six pins in this section, the time of backwash is 12 minutes (2 minutes per pin). To change the length of backwash time, add or remove pins as required.
Figure 5
is In Service position. Looking at the numbered side of the program wheel, the
Changing Length of Brine and Rinse Time
The group of holes between the last pin in the backwash section and the second group of pins determines the length of time that a unit will brine and rinse (2 minutes per hole).
To change the length of brine and rinse time, add or remove pins in the rapid rinse group of pins to increase or decrease the number of holes in the brine and rinse section.
— The number of holes multiplied by two equals minutes of brine and rinse.
Changing Length Of Rapid Rinse
The second group of pins on the program wheel determines the length of time the water conditioner rapid rinses (2 minutes per pin). To change the length of rapid rinse time, add or remove pins at the higher numbered end of this section as required.
— The number of pins multiplied by two equals minutes of rapid rinse.
NOTE:
Program wheels with 0–82 minute cycle times, use one minute per pin or hole to set Regeneration times. The layout of pins and holes on the program wheel follow the same procedure as on this page.
Changing Length of Brine Tank Refill Time
The second group of holes on the program wheel determines the length of time the water conditioner refills the brine tank (2 minutes per hole).
To change the length of refill time, move the two pins at the end of the second group of holes as required.
The Regeneration cycle is complete when the two pin set at end of the brine tank refill section trips the outer micro-switch. The program wheel, however, continues to rotate until the inner micro-switch drops into the notch on the program wheel.
9
Model 9000/9100/9500
Time Brine Refill and Meter Setting Procedure
Programming
1. The control valve is set at the factory for backwash; brine and slow rinse; rapid rinse and brine tank fill times. Change any of these times by repositioning the pins and holes or adding more pins.
NOTE:
2. The control valve has a separate brine tank fill cycle.
— Calculate the desired salt setting using the brine line flow control rate of refill (in gpm) multiplied by the
Example:
NOTE:
3. Setting the gallon wheel.
Knowing the amount of resin in each tank and the salt setting per Regeneration, calculate the gallons available, using the following capacities as a guide:
Two speed timer motors are available 1/15 RPM has 82 minute Regeneration Time and each pin or hole equals one minute. 1/30 RPM has 164 minute Regeneration Time and each pin or hole equals two minutes.
timer setting. Then, using one gallon of fresh water dissolving approximately 3 lbs salt, calculate the refill time.
A desired 30 lbs salt setting: The unit has a 1.0 gpm refill rate so a 10 gallon fill is required.
10 gallons x 3 lbs/gals = 30 lbs salt
Set the timer refill section at 10 minutes.
10 minutes x 1.0 gpm = 10 gallon fill
There must always be two pins at the end of a refill time to stop the fill cycle. With the Regeneration times set, place timer back to its original position, making sure the lower right hand corner snaps back into the backplate and the meter cable slides through the backplate and does not bind.
3
(capacity per ft
compensated hardness of H
x ft3 of resin per tank)
O
2
= gallons available
NOTE:
Example:
DO NOT SET THIS FIGURE - GO TO STEP 4
— Because the control valve regenerates with soft water from the other tank, subtract the water used for
Based on tank size: More resin increases capacity, less resin decreases capacity. More salt increases capacity, less salt decreases capacity.
tank diameter = 16" compensated hardness = 35 grains per gal (tested sample)
3
resin (based on flow rate)
ft lbs of salt = 8
capacity per ft
(24,000 x 4 ft
Regeneration. Take each Regeneration cycle and calculate the water used.
3
3
of resin per tank)
35 grains
=4
= 24,000
= 2740 gallons available before regeneration
10
Model 9000/9100/9500
Example:
4. Set meter wheel at approximately 2530 gallons. Lift the inner dial of the meter program wheel so that you can rotate it freely. Position the white dot opposite the 2530 gallon setting.
NOTE:
Unit is set for a 16" diameter tank with 4 ft3 of resin and salted at 8 lbs. per ft3, 7 gpm backwash, #3 injector, 1.0 gpm brine refill, and 60 psi and timer set for
rinse, 10 min. rapid rinse, 10 min. brine tank fill.
Backwash
Brine and Rinse
Rapid Rinse
Brine Tank Fill
With the 2740 gallons available calculated in Step 3, subtract the Regeneration water used from the total water available.
2740 gallons available - 210 gallons used = 2530 gallons
There is a slight delay between the time the meter zeros out and the cycle starts. Units using the: 1/15 RPM motor, 82 minute Regeneration Time has a 9 1/30 RPM motor, 180 minute Regeneration Time has an 18
This delay period is not critical on residential equipment. However, take this factor into consideration for commercial applications by subtracting continuous flows for 9 minutes or 18 minutes from water available.
10 minutes x 7.0 gpm = 70.0 gallons 60 minutes x 1.0 gpm = 60.0 gallons 10 minutes x 7.0 gpm = 70.0 gallons 10 minutes x 1.0 gpm = 10.0 gallons
Total Regeneration Water = 210.0 gallons
(in Regeneration, Step 4)
10 min. backwash, 60 min. brine and
minute delay
minute delay
.
5. Insert meter cable into meter.
6. Check bypass.
7. Plug in unit.
11
Model 9000/9100/9500
ET Timer Installation And Start-Up Procedures
1. In Normal Operation the Time Of Day and, if flow meter equipped, the Volume Remaining displays appear alternately. Set the Time Of Day display. Press the Up or Down set button to display the correct time.
Example:
12:59 P.M.
Val ve
In Service
Figure 6
2.
Flow Meter Equipped Valves Only:
(including any reserve capacity) remaining prior to Regeneration. When there is no water usage the Meter arrow should not appear or not change. Open a soft water tap. The Meter arrow begins flashing at a rate that varies with flow rate. Close the tap after 3–5 gallons of water flow.
The Volume Remaining Display displays the volume of water in gallons
Example:
125 gallons of water remaining
Valve
In Service
No water flow Volume below reserve capacity Reserve arrow flashing
Figure 7
3. Manually initiate a Regeneration cycle and allow water to run to drain for 3 to 4 minutes. Press and release the Extra Cycle button. With Immediate Regeneration timers the control goes into Regeneration immediately. With Delayed Regeneration timers the In Service arrow flashes immediately and a Regeneration occurs at the preset Regeneration Time. Press and hold the Extra Cycle button for 5 seconds. The control goes into Regeneration immediately.
4. Manually step the valve through a Regeneration cycle, checking valve operation in each step. During Regeneration the control displays the Regeneration step number to which the valve is advancing or has reached and the time remaining in that step.
Example:
0 gallons of water remaining
Valve
In Service
Water flowing Volume below reserve capacity Reserve arrow flashing
12
Model 9000/9100/9500
Example:
Valve advancing to Regeneration Step #1
#1 flashing Regeneration arrow on
— When the first cycle step is reached, a red LED turns on indicating the current Regeneration cycle step.
Example:
Regeneration Step #1 reached
10.0 minutes remain in Step #1 Regeneration arrow on
— Press the Extra Cycle button during a Regeneration step to immediately advance the valve to the next
Regeneration step position.
— Press the Up or Down set buttons during a Regeneration step to adjust the time remaining in the current
Regeneration step. Programmed Regeneration step times are not changed.
Backwash
Figure 8
Backwash
Figure 9
— Once all Regeneration cycle steps are complete, the valve returns to In Service and resumes normal
operation.
5. Manually step the valve to the Brine Draw position (see Step #15) and allow the valve to draw water from the brine tank until it stops.
*NOTE:
6. Manually step the valve to the Brine Refill position and allow the valve to return to In Service automatically.
7. Make sure the brine refill time (salt dosage) is set as recommended by the manufacturer.
8. With the valve In Service, check that there is about 1 of water above the grid in the brine tank, if one is used.
9. Fill the brine tank with salt.
NOTE:
The air check checks at approximately the midpoint of the screened intake area.
It is recommended a 9V Alkaline Battery be installed at all times for proper valve operation. The Low Battery LED turns on when the battery needs to be replaced.
13
Model 9000/9100/9500
ET Timer Control Start-Up Procedure
Display ET
Service Indicator
Valve In Service, Arrow On Manual Regeneration Tonight, Flashing Arrow
Time of Day Indicator
Reserve Indicator
Volume Remaining Above Reserve, Arrow Off Volume Remaining At or Below Reserve, Arrow Flashing
Totalizer Indicator
Flow Indicator
No Water Flow, Arrow Off Water Flow, Arrow Flashing
Sensor Indicator
Sensor Input Signal, Arrow Flashing Valid Regeneration Signal, Arrow On
Flow Rate Indicator
Program Indicator
Volume Remaining Indicator
Lockout Indicator
Lockout Signal, Arrow On
Regeneration Indicator
Valve in Regeneration, Arrow On
Figure 10:ET
In Normal operation the Time Of Day display alternates with the Volume Remaining display. The meter arrow flashes in direct relation to the water flow rate through the unit. As treated water is used, the Volume Remaining display counts down from a maximum value to the calculated reserve capacity. The Reserve arrow flashes when the reserve capacity is being used. At the preset Regeneration Time, a Regeneration cycle initiates.
Example:
125 gallons of water remaining
Valve No water flow Volume is below reserve capacity
Example:
0 gallons of water remaining
Valve Water flowing Meter arrow flashing Volume is below reserve capacity
In Service
In Service
Timer Display
Figure 11
14
Model 9000/9100/9500
ET Timer Control Operation
Timeclock Regeneration Valves
When the number days since the last Regeneration reaches the preset number of days, a Regeneration cycles initiates at the preset Regeneration Time.
Flow Meter Equipped Immediate Regeneration Valves
The Time Of Day display alternates with the Volume Remaining display. The Meter arrow flashes in direct relation to the water flow rate through the unit. As treated water is used, the Volume Remaining display counts down from a maximum value to zero and initiates a Regeneration cycle.
Example:
525 gallons of water remaining
Valve Water flowing
Meter arrow flashing
In Service
Figure 12
Sensor Immediate Regeneration Valves
When the control receives a valid sensor input signal, a Regeneration cycle initiates. The Sensor Input arrow flashes until the signal is determined to be valid.
Sensor Delayed Regeneration Valves
When the control receives a valid sensor input signal, a Regeneration cycle initiates at the preset Regeneration Time. The Sensor Input arrow flashes until the signal is determined to be valid. The Reserve arrow flashes when
the reserve capacity is being used.
Example:
12:58 A.M. with invalid sensor signal
Valve Sensor arrow flashing
Example:
12:59 A.M. with valid sensor signal
Valve Sensor arrow on Reserve arrow flashing Delayed regeneration
In Service
In Service
Figure 13
Lockout Input Operation
The lockout arrow turns on whenever the control sends a lockout signal. Any requests for Regeneration are delayed until this signal is removed. Regeneration then proceeds normally.
15
Model 9000/9100/9500
Figure 14
Start an Extra Cycle
Press the Extra Cycle button to start an Extra Regeneration tonight. Press and hold the Extra Cycle button for 5 seconds to start an Extra Cycle immediately.
Totalizer/Flow Rate
Press the Totalizer Flow Rate button to display the flow rate.
Press the button a second time to display the total accumulation of water flow through the valve since the last reset.
Press the button a third time to return the display to Time Of Day or Volume Remaining.
— Press and hold the button for 25 seconds to reset the Totalizer display. During the 25 seconds, the
Totalizer arrow flashes indicating that the display is resetting properly.
Low Battery Indicator
Figure 15
The red Low Battery LED turns on whenever the 9V Alkaline Battery (not included) requires replacement. The battery is used for memory backup and is stored against the valve backplate. In the event of a power outage, the battery maintains the current operating displays for approximately 24 hours at maximum battery capacity.
Immediate Regeneration Valves With Days Between Regeneration Override Set
When the valve reaches its set Days Since Regeneration Override value, a Regeneration cycle initiates immediately. This event occurs regardless of the Volume Remaining display reaching zero gallons.
Delayed Regeneration Valves With Days Between Regeneration Override Set
When the valve reaches its set Days Since Regeneration Override value, a Regeneration cycle initiates at the preset Regeneration Time. This event occurs regardless of the Volume Remaining display reaching the calculated reserve capacity.
Control Operation During Regeneration
In Regeneration the control displays a special Regeneration display. The control shows the current Regeneration step number to which the valve is advancing or has reached, and the time remaining in that step. The displayed step number flashes until the valve completes driving to the Regeneration step position. Once all Regeneration steps are complete the valve returns to In Service and resumes normal operation.
16
Model 9000/9100/9500
Example:
Less than 10 minutes remaining in Regeneration Step #1
Figure 16
Press the Extra Cycle button during a Regeneration cycle to immediately advances the valve to the next cycle step position and resume normal step timing.
Control Operation During Programming
The control enters Program Mode with the valve In Service. While in Program Mode the control continues to operate normally, monitoring water usage and keeping all displays up to date. Control programming is stored in memory permanently. There is no need for battery backup power.
Control Operation During A Power Failure
During a power failure all control displays and programming are stored for use upon power re-application. The control retains these values for years, if necessary, without loss. The control is fully inoperative and any calls for Regeneration are delayed. The control, upon power re-application, resumes normal operation from the point that it was interrupted. An inaccurate or flashing Time of Day display indicates that a power outage has occurred.
Backwash
17
Loading...
+ 39 hidden pages