Watlow Electric Microprocessor-Based SCR User Manual

P OW E R S E R I E S C O N T R O L L E R S
M i c ro p ro c e s s o r- B a s e d SCR Power Contro l l e r Designed fo r Application Flex i b i l i t y
Watlow has manufactured solid state power controllers for over thirty years. Watlow’s POWER SERIES represents the latest in SCR power controller technology.This microproces­sor-based product offers features and application flexibility unmatched by any other SCR power controller on the market today.
Capabilities of Watlow’s POWER SERIES controllers include single-phase and three-phase models from 65 to 250 amps. Field configurable phase angle or zero cross firing improves application flexibility on site where you need it.The 50/60Hz independent operation allows utilization almost everywhere in the world without special calibration considerations. Serial communication utilizing Modbus™protocol provides remote control setup and monitoring of load status from a nearby computer station or control room.
On-board semiconductor fusing improves reliability by protecting the SCRs from heater short circuits. Plus, on-board heater bakeout and control diagnostics can help eliminate initial start up problems. All these benefits are in a touch-safe package that can be quickly and easily mounted in your control cabinet.
Watlow’s POWER SERIES controllers are UL®and C-UL recognized, so users can be assured that the controllers meet world safety and operational standards.
®
Features and Benefits
Microprocessor-based technology
Extremely versatile and field configurable
Snap-fit on a pre-mounted plate
Simplifies installation
Models 65 through 250 amp ratings
Handles a wide range of loads
Adjustable soft start
Provides application flexibility
Heater and control diagnostics capability
Monitors actual heater and controller performance
Electrically touch-safe package
Enhances safety for installer and users
Serial communications with Modbus™RTU protocol
Provides computer control and/or monitoring
Multizone capability
Increases application flexibility and reduces panel space
UL®and C-UL®are registered trademarks of the Underwriter’s Laboratories, Inc. Modbus™ is a trademark of Schneider Automation Inc.
1241 Bundy Boulevard Winona, Minnesota 55987-5580 USA Phone: 507-454-5300 Fax: 507-452-4507 Internet: www.watlow.com e-mail: info@watlow.com
© 2003 Watlow Electric Manufacturing Company Printed in the USA on Recycled Paper, 15% Postconsumer Waste
WIN-PS-0403
Specifications
Power Bases
• Single phase, (2 SCRs)
• 3 phase, 2 leg control, (4 SCRs) Resistive load only, zero cross firing only
• 3 phase, 3 leg control, (6 SCRs)
• 3 phase, 3 leg control, (6 SCRs) for 4-wire wye loads
• Multizone, two and three single-phase zones
Output Control Options
• Zero cross contactor, VÎ(dc) input
• Zero cross control, fixed time base
• Time base one or four seconds with digital programmer
• Zero cross control, variable time base
• Phase angle control and phase angle control with current limit (not for 3-phase, 2-leg models)
• Soft start factory default four seconds upon power-up, and
adjustable from 0.0 to 120 seconds
• Soft start upon input signal change, output rate of change
adjustable to limit max rate of change from 0.1 to 100 percent per 0.1 second. Factory default 10 percent
• Current transformer included when required
• Line voltage compensated (variable time base and phase angle controllers only)
• Standby or non-operational mode
Output Voltage and Current Rating
• 24 to 120VÅ(ac) (+10 percent, -15 percent)
• 200 to 480VÅ(ac) (+10 percent, -15 percent)
• 200 to 600VÅ (ac) (+10 percent, -15 percent)
• 65 through 250 amps per pole, model dependent; see Output Amperage Chart and Rating Curves
• Minimum load 1 amp rms ac
• Maximum leakage current 5mA
Alarms
• Single alarm relay
• Latching or non-latching
• Separate high and low values
• Alarm silencing (inhibit) on power up for alarm
• Alarm indication LEDs, shorted SCR, open heater, fuse
• Electromechanical relay, form C contact, software configurable
• Minimum load current 10mA @ 5VÎ(dc)
• Rated resistive loads: 3 amps @ 250VÅ(ac) or 30VÎ(dc)
max., inductive load rating 1.5 amps with a power factor 0.4 without contact suppression
Heater Bakeout
• For single-phase (phase to neutral) and 3-phase 6 SCR models only (not for 3-phase, 2-leg models)
• Soft start with over current trip, runs until programmed bakeout time expires, then goes burst or phase angle firing. Factory default of 24 hours
• Adjustable 0 - 9999 minutes with over current trip
• Internal current transformer included
Command Signal Input Analog
• Field selectable linear voltage and current of low and high points within 0-20mA and 0-10VÎ(dc)
• Manual control input through front panel
• Factory default 4-20mA input
• Voltage input impedance 11kW nominal
• Current input impedance 100W nominal
Digital
• On-board digital programmer/display and optional serial communications
Retransmit
• Field selectable and scalable within 0-20mA, 800W maximum or 0-10VÎ(dc), load, 1KW minimum load. The default is 4-20mA
• Resolution: mA ranges = ±5µA VÎ(dc) = ranges 2.5mV nominal
• Calibration accuracy: mA ranges = ±20µA VÎ(dc) ranges = 10mV nominal
• Temperature stability: 100ppm°C
Digital Programmer/Display and Communications Capabilities
• Programming functions
• Adjust input and output control type, alarms and soft start,
heater bakeout and current limit prompts
• Monitoring functions
• Display input and output values along with actual
output current
• Data retention of digital programmer/display upon power failure via nonvolatile memory
Serial Communications
• RS-232 for single drop control
• EIA-485 for single or multidrop control
• 32 units maximum can be connected.With additional
485 repeater hardware, up to 247 units may be connected
• Isolated
• Modbus™RTU protocol
• 1200, 2400, 4800, 9600, 19200 baud rates
Controller Power Supply
• Universal line voltage input range 100 to 240VÅ(ac) (+10 percent, -15 percent) at 55VA max
• 50/60Hz ± 5 percent line frequency independent
• Controller line voltage for electronic power supply can be run on separate line voltage
Natural Convection and Fan Cooled Models
• Cabinet venting may be required
• See Amperage chart on the back page for all models.
Power Dissipation (Watts)
• Approximately 1.25 watts/amp per controlled leg
Isolation
• Command signal to load and line/load to ground 2200VÅ(ac) minimum
• On-board semiconductor fuses provide SCR protection
Mounting
• Mounts on a removable subplate
• Heat sink fins must be mounted in vertical orientation
High Current Terminals
• Touch safe
• 10 mm (3⁄8in.) Allen head compression terminals will accept #6 AWG to 350 MCM wire. Allen wrench adapter (included) for 10 mm (3⁄8in.) socket, 6 point only
• Torque to 180 in.-lbs (20.3 Nm)
• Wire strip to 30 mm (11⁄8 in.)
Controller Terminals
• Touch safe
• 2.5 mm (1⁄8 in.) blade screwdriver, accepts 12-22 AWG or 2 No. 22-18 AWG wires
• Torque to 8 in.-lbs (0.9 Nm)
• Wire strip to 6 mm (0.24 in.)
Operating Environment
• 50°C (122°F) base rating
• 0 to 60°C (32 to 140°F) fan cooled
• 0 to 65°C (32 to 149°F) natural convection cooled
• 0 to 90 percent RH, non-condensing
• Meets EN50178, Pollution degree three
Storage Temperature
• -40 to 85°C (-40 to 185°F)
Shipping Weight
• 10.3 kg (23 lbs)
Agency Approvals
• UL®508 listed, File #E73741, Vol. three, Sec.two
• C-UL®listed to C22.2 NO. 14
• VDE EN 50178 License 115054
• CE 89/336/EEC (EN61326), Class A with filter, CE 73/23/EEC (EN50178)
Modbus™ is a trademark of Schneider Automation, Inc.

Package Style C Dimensions

Mounting Plate Dimensions

POWER SERIES Front View
POWER SERIES Top View
354 mm
(14.0 in.)
200 mm (7.9 in.)
Mounting Holes (4)
7 mm
(0.27 in.)
Key Slots
102 mm
(4.00 in.)
151 mm
(5.93 in.)
Release Tab
178 mm
(7.00 in.)
25 mm
(0.97 in.)
39 mm (1.53 in.)
191 mm
(7.5 in.)

POWER SERIES Features

Ordering Information

POWER SERIES P C _ _ - _ _ _ _ - _ _ _ _
Microprocessor-based, solid state power controller
Package Style
C = 65 to 250 amps
Phase
1 = 1 phase 2 = 3-phase/2-leg control, (4 SCRs) 3 = 3-phase/3-leg control, (6 SCRs) 4 = 3-phase/4-wire, wye
connected load 8 = 2 single-phase zones 9 = 3 single-phase zones
Heater Diagnostics
0 = None 1 = Heater diagnostics (required for any
heater current monitoring or current
limiting).
Output Amperage Rating
(See amperage chart to the right)
Output Voltage Rating
A = 24 to 120V B = 200 to 480V C = 200 to 600V
Communications
0 = None 1 = EIA/TIA-232/485 communications,
opto-isolated (field selectable)
Feedback/Retransmit
0 = None 1 = Load current feedback (0-10V or 0-20mA scalable
retransmit output) (Must have heater
diagnostics selected)
Custom
00 = None AA = No Watlow logo with agency approval marks XX = Custom, consult factory for options
Your Authorized Watlow Distributor Is:
Single Phase Configuration
This configuration can be purchased with any or all the features available on the POWER SERIES, based on customer preference. It is intended for resistive heaters, but can also be used on transformer connected loads in the phase angle firing mode.
Three-Phase,Two Leg Configuration
This configuration is intended for zero cross firing only into a stable resistive heater.Typically, a three-phase delta or ungrounded wye connected heater is used and only two of the three V~ line phases are switched.The third phase is a direct connection through a bussbar on board the POWER SERIES. Heater current monitoring and kVA options are available via the heater diagnostics option.
Three-Phase,Three Leg Configuration
All POWER SERIES options are ava i l a ble with this c o n fig u ra t i o n . It wo rks well with phase angle firing into a t h r e e - p h a s e, three-wire wye or delta connected heater.In this c o n fig u ration, the more common applications are tra n s fo rm e r connected loads with heaters requiring a soft start and/or current limiting.
The three-phase, four-wire configuration is intended for zero cross firing into a three-phase grounded wye/star heater (This is a separate hardware option, model number dependent.)
Single-Phase, Multizone Configuration
This configuration is available in two and three single-phase zones and all the features of a single-phase unit are available.(Note that there is only one alarm relay and all zones in the controller must use the same control method.)
Heater Diagnostics
Heater diagnostics may include some or all of the features that require heater current monitoring, depending on the model selected. Heater current monitoring is only available with heater diagnostics installed on the controller. The features dependent on heater current monitoring are heater bakeout, current limiting, heater kVA monitoring, retransmit and heater monitoring alarms such as open heater, heater out of tolerance, load balance and shorted SCR detection/error.Heater diagnostics must also be installed if you need phase angle control with current limit.
Amperage Chart—50˚C (122˚F)
Non-Fan Cooled
2 Zone and 3 Zone and
Single Phase 3 Phase, 2 Leg 3 Phase, 3 Leg
Code Amperage Code Amperage Code Amperage
N20 100A N20 80A N20 65A N25 140A N25 105A N25 85A N30 165A N30 120A N30 105A
Fan Cooled
Single Phase 3 Phase, 2 Leg 3 Phase, 3 Leg
Code Amperage Code Amperage Code Amperage
F20 125A F20 120A F20 90A F25 200A F25 160A F25 140A F30 250A F30 185A F30 155A
North American Sales Offices: Atlanta, (770)972-4948 • Austin, (512)249-1900 • Birmingham, (205)678-2358 • Charlotte, (704)573-8446 •
Chicago, (847)458-1500 • Cincinnati, (513)398-5500 • Cleveland, (330)467-1423 • Dallas, (972)620-6030 • Denver, (303)798-7778 • Detroit, (248)651-0500 • Eastern Canada, (450)433-1309 • Houston, (281)440-3074 • Indianapolis, (317)575-8932 • Kansas City, (913)897-3973 • Los Angeles, (714)935-2999 • Louisiana, (318)864-2864 • Maryland/Virginia, (215)345-8130 • Minneapolis/Manitoba, (952)892-9222 • Nashville, (615)264-6148 • New England, (603)882-1330 • NewYork/New Jersey/Philadelphia, (215)345-8130 • New York,Upstate, (716)438-0454 • Ontario, (905)979-3507 • Orlando, (407)351-0737 • Phoenix, (602)298-6960 • Pittsburgh, (412)322-5004 • Portland, (503)245-9037 • Raleigh/Greensboro, (336)766-9659 • St.Louis, (314)878-4600 • Sacramento, (707)425-1155 • San Diego, (714)935-2999 • San Francisco, (408)434-1894 • Seattle, (425)222-4090 • Tampa/St. Petersburg, (407)647-9052 • Tulsa, (918)496-2826 • Western Canada, (604)444-4881 • Wisconsin, North (920)993-2161 • Wisconsin, South (262)723-5990
Asian Sales Offices: Australia, +61 (3) 9335-6449 • China, +86 (21) 6277-2138 • Japan, +81 (03) 5403-4688 • Korea, +82 (02) 575-9804 •
Malaysia, +60 (4) 641-5977 • Singapore, +65 777-9488 • Taiwan, +886 (0) 7-288-5168 European Sales Offices: France, +33 (01) 3073-2425 • Germany, +49 (0) 7253-9400-0 • Italy, +39 (02) 458-8841 • Sweden, +46 31 7014959 • United Kingdom, +44 (0) 115-964-0777
Latin American Sales Office: Mexico, +52 (442) 217-6235
Loading...