Watlow Electric 97 User Manual

SERIES 97
An Over-temperature Limit Controller With User Defined Messages
Watlow’s SERIES 97 is a microprocessor-based controller with a single input, second auxiliary input and four outputs. Input one is used to measure temperature from a sensor.Input two can be utilized as a remote reset switch or a hardware lockout switch. With up to four outputs, the controller is versatile in handling applications that require a high/low limit, alarms, retransmit and communications. The control is so user friendly that it can be set up to display safety and limit messages created by the end user to meet the exact application need.
The SERIES 97 limit controller is added to thermal applications to limit over-temperature conditions.The SERIES 97 limit controller provides safety assurance against instances where a high temperature runaway condition could occur from a shorted input sensor or an output device that could fail in a closed position.
The SERIES 97 is recommended for any application where thermal runaway could result in large product scrap costs, affect operator safety, cause damage to equipment or create a fire hazard.
The SERIES 97 is manufactured by ISO 9001 registered Watlow Winona and reliably backed up by a three-year warranty.
1241 Bundy Boulevard Winona, Minnesota 55987-5580 USA Phone: +1 (507) 454-5300 Fax: +1 (507) 452-4507 Internet: www.watlow.com e-mail: info@watlow.com
WIN-97-1203
Registered Company
Winona, Minnesota USA
ISO 9001ISO 9001
Features and Benefits
Programmable messages
Controller can be set up to display user
programmed limit message
NEMA 4X (IP65)
Water and corrosion resistant; front panel
can be washed down
Microprocessor-based
Accurate set point settings and quick
output response
Second auxiliary input
Remote reset capability
Four outputs
Handles high/low limit, alarms, communication
and retransmit requirements
Software and hardware lockouts
High security
© 2003 Watlow Electric Manufacturing Company Printed in the USA on Recycled Paper, 15 Percent Postconsumer Waste
Specifications
Controller
• Microprocessor-based
• Universal input 1, auxiliary input 2, 4 outputs
• Input sample period; Single input 10Hz (100 msec), dual input 5Hz (200 msec) digital filter adjustable
• Display update; 2Hz (500 msec), time filter adjustable
• Input/Output/Communication isolation
• Displayed in °C, °F
Operator Interface
• Dual 4-digit LED displays: upper 10.2 mm (0.4 in.), lower 6.2 mm (0.244 in.)
• Advance, Up Arrow, Down Arrow, Reset tactile keys
Standard Conditions For Specifications
•Ambient temperature 77°F (25°C) ±3°C, rated line voltage, 50 to 60Hz, 0 to 90 percent RH non-condensing, 15 minute warm-up
Universal Input 1
Thermocouple
•Type J, K, T, N, C (W5), E, PTII, D (W3), B, R, S thermocouple types
• >20Minput impedance
• Maximum 20source resistance
• 30mA open detection bias
RTD
•2- or 3-wire platinum, 100
• JIS and DIN curves
•Whole or tenth degree indication
• 150µA nominal RTD excitation current
Input 2
Event Input
• Contact or voltage
• 20Kinput impedance
•Voltage input: event high state 3 to 36VÎ(dc), event low state 0 to 2VÎ(dc)
• Resistance/contact input: event high state > 23k, event low state 0 to 2k
Output Types Open Collector/Switched DC
• Open collector configuration: Maximum voltage 42VÎ(dc) Maximum current 200mA Maximum “on” resistance 1.1 Maximum offstate leakage current 100µA
• Switched dc configuration: Switched dc supply voltage 22 to 28VÎ(dc) dc supply current limited to 30mA
Solid State Relay
• Optically isolated
• Zero cross switched
• Without contact suppression
• Minimum load current 0.5mA rms
Solid State Relay (cont.)
•Maximum current 0.5A rms at 20 to 280VÅ(ac)
•Maximum offstate leakage current 10µA rms
•For resistive loads only, must use RC suppression for inductive loads
Electromechanical Relay
•Form C contact configuration
• Minimum load current 10mA @ 5VÎ(dc)
• Rated resistive and inductive loads: 2A @ 250VÅ(ac) or 30VÎ(dc) maximum
• Electrical life 100,000 cycles at rated current
•For resistive loads only, must use RC suppression for inductive loads
Retransmit
• Range selectable: 0-20mA, 4-20mA, 0-5VÎ(dc), 1-5VÎ(dc), 0-10VÎ(dc)
•0 to 10VÎ(dc) voltage output into a 1,000Ω minimum load resistance
•0 to 20mA current output into an 800maximum load resistance
• Resolution: Vdc ranges = 2.5mV nominal mA ranges = 5µA nominal
• Calibration accuracy: Vdc ranges = ±15mV mA ranges = ±30µA
•Temperature stability 100ppm/°C
Communications
• EIA/TIA-485, EIA/TIA-232
• Opto-isolated
• Modbus
TM
RTU protocol
• 1200, 2400, 4800, 9600, 19200 baud rates
• 32 maximum units can be connected (With additional 485 repeater hardware, up to 247 units may be connected)
Accuracy
• Input ranges Type J: 0 to 750°C or 32 to 1382°F Type K: -200 to 1250°C or -328 to 2282°F Type T: -200 to 350°C or -328 to 662°F Type N: 0 to 1250°C or 32 to 2282°F Type E: -200 to 900°C or -328 to 1470°F Type C(W5): 0 to 2315°C or 32 to 4200°F Type D(W3): 0 to 2315°C or 32 to 4200°F Type PTII: 0 to 1393°C or 32 to 2540°F Type R: 0 to 1450°C or 32 to 2642°F Type S: 0 to 1450°C or 32 to 2642°F Type B: 870 to 1700°C or 1598 to 3092°F DIN: -200 to 800°C or -328 to 1472°F JIS: -200 to 630°C or -328 to 1166°F
ModbusTMis a trademark of AEG Schneider Automation.