Watlow Electric 96 User Manual

SERIES 96
Registered Company
Winona, Minnesota USA
ISO 9001ISO 9001
Plug and Play Firmware and Hardware
Features and Benefits
Burst fire
Increase heater life/better temperature controllability
One input, one auxiliary input, four outputs
Powerful flexibility at a competitive price
No dipswitches
Easily configurable from the front panel
Multiple set points
Flexible automatic control
Pluggable output modules
Field expandable
Fast 10Hz sampling
Improved control responsiveness
Programmable menus (Patent pending)
Can be self-tailored for exact user needs
Open loop break protection
Indication of thermal loop problem
NEMA 4X (IP65)
Water and corrosion resistant front panel can be
washed down
16 programmable ramp and soak steps
Profiles of dynamic production processes can be
programmed into the controller
Automatic tuning
Easy one step tuning of PID control parameters
Watlow’s SERIES 96 is a powerful 1⁄16 DIN dual display controller that offers many advanced functions. This new controller can be tailored to perform hardware and software needs with hardware modules that are pluggable and exchangeable and software menus that may be user programmed to fit exact application requirements.
With one universal input, a second auxiliary input and four outputs the SERIES 96 can be programmed to perform: temperature measurement, input event switching, remote set point input, heating, boost heating, cooling, alarms, digital communications, ramp and soak and retransmit. These features make this controller ideally suited for applications in markets such as plastics packaging, semiconductor, food processing and lab equipment.
Set point ramping operations include two files with eight steps in each. The files can be linked to create a 16-step profile.
With fast 10Hz sampling, variable time base burst firing outputs, NEMA 4X front panel and 0.1 percent calibration accuracy this control can easily handle some of the toughest application needs.
The SERIES 96 is manufactured by ISO 9001 registered Watlow Controls and reliably backed by a three-year warranty.
Your Authorized Watlow Distributor Is:
WIN-96-0307
1241 Bundy Boulevard, P.O. Box 5580 Winona, Minnesota 55987-5580 USA Phone: +1 (507) 454-5300 FAX: +1 (507) 452-4507 Internet: www.watlow.com E-mail: info@watlow.com
© 2007 Watlow Electric Manufacturing Company Printed in the USA on Recycled Paper, 15% Postconsumer Waste
Specifications
Controller
• Microprocessor-based, user selectable control modes
• Heat and cool auto-tune for control outputs
• Universal input 1, auxiliary input 2, 4 outputs
• Control outputs user selectable as on-off, P, PI, PID
• Input sample period; Single input 10Hz (100 ms), dual input 5Hz (200 ms) adjustable digital filter
• Display update; 2Hz (500 ms), adjustable digital filter
• Output update; burst, 0.1 to 999.9 seconds
• Input/Output/Communication isolation
• Displayed in °C, °F, or process units
Operator Interface
• Dual 4-digit LED displays: upper 10.2 mm (0.4 in.), lower 6.2 mm (0.244 in.)
• Advance, Up Arrow, Down Arrow, Infinity tactile keys
Standard Conditions For Specifications
• Ambient temperature 25°C/77°F ±3°C, rated line voltage, 50 to 60Hz, 0 to 90 percent RH non-condensing, 15 minute warm-up
Universal Input 1
Thermocouple
• Type J, K, T, N, C (W5), E, Pt 2, D (W3), B, R, S thermocouple types
• >20M
• Maximum 20
• 30µA open detection bias
RTD
• 2- or 3-wire platinum, 100
• JIS and DIN curves
• Whole or tenth degree indication
• 150µA nominal RTD excitation current
Process
• Range selectable: 0-10VÎ(dc), 0-5VÎ(dc),
• Voltage input impedance 20k
• Current input impedance 100
• Minimum current source resistance 1M
• Input resolution 50,000 bits (approx.) at full scale
• mV input impedance 20M
Input 2
Event Input
• Contact or voltage
• 20K
• Voltage input: event high state 3 to 36V
• Resistance/contact input: event high state > 23k
Remote Set Point Input: mA or VDC Range Selectable
• Voltage input impedance 20k
• Current input impedance 100
input impedance
source resistance
Î(dc), 0-20mA, 4-20mA,
1-5V
input impedance
event low state 0 to 2V
event low state 0 to 2k
Î(dc),
Î(dc)
Ω,
Output Types Open Collector/Switched DC
• Open collector configuration: Maximum voltage 42V Maximum current 200mA Maximum “on” resistance 1.1 Maximum offstate leakage current 100µA
• Switched dc configuration: Switched dc supply voltage 22 to 28V dc supply current limited to 30mA
Solid State Relay
• Optically isolated
• Zero cross switched
• Without contact suppression
• Minimum load current 0.5mA rms
• Maximum current 0.5A rms at 20 to 280V
• Maximum offstate leakage current 10µA rms
• For resistive loads only, must use RC suppression for inductive loads
Electromechanical Relay
• Form C contact configuration
• Minimum load current 10mA @ 5V
• Rated resistive and inductive loads: 2A @ 250V
Î(dc) maximum
or 30V
• Electrical life 100,000 cycles at rated current
• For resistive loads only, must use RC suppression for inductive loads
Process
• Range selectable: 0-20mA, 4-20mA, 0-5VÎ(dc),
Î(dc), 0-10VÎ(dc)
1-5V
• Reverse or direct acting
• 0 to 10V resistance
• 0 to 20mA current output into 800 resistance
• Resolution: dc ranges = 2.5mV nominal mA ranges = 5µA nominal
• Calibration accuracy: dc ranges = ±15mV mA ranges = ±30µA
• Temperature stability 100ppm/°C
Retransmit
• Range selectable: 0-20mA, 4-20mA, 0-5VÎ(dc), 1-5V
• 0 to 10V load resistance
• 0 to 20mA current output into an 800 resistance
• Resolution: dc ranges = 2.5mV nominal mA ranges = 5µA nominal
• Calibration accuracy: dc ranges = ±15mV mA ranges = ±30µA
• Temperature stability 100ppm/°C
Î(dc) voltage output into 1000minimum load
Î(dc), 0-10VÎ(dc)
Î(dc) voltage output into a 1,000minimum
Î(dc)
Î(dc)
Å(ac)
Î(dc)
Å(ac)
maximum load
maximum load
Communications
• EIA/TIA-485 or EIA/TIA-232
• Opto-isolated
TM
• Modbus
RTU protocol
• 1200, 2400, 4800, 9600, 19200 baud rates
• 32 maximum units can be connected (With additional 485 repeater hardware, up to 247 units may be connected)
Accuracy
• Input ranges Type J: 0 to 750°C or 32 to 1382°F Type K: -200 to 1250°C or -328 to 2282°F Type T: -200 to 350°C or -328 to 662°F Type N: 0 to 1250°C or 32 to 2282°F Type E: -200 to 900°C or -328 to 1470°F Type C(W5): 0 to 2315°C or 32 to 4200°F Type D(W3): 0 to 2315°C or 32 to 4200°F Type Pt 2: 0 to 1393°C or 32 to 2540°F Type R: 0 to 1450°C or 32 to 2642°F Type S: 0 to 1450°C or 32 to 2642°F Type B: 870 to 1700°C or 1598 to 3092°F DIN: -200 to 800°C or -328 to 1472°F JIS: -200 to 630°C or -328 to 1166°F Process: -1999 to 9999 units
Thermocouple Inputs
• Calibration accuracy ±0.1 percent of span ±1°C at standard conditions
Exceptions: Type T; 0.12 percent of span for -200°C to -50°C,
Types R and S; 0.15 percent of span for 0°C to 100°C Types B; 0.24 percent of span for 870°C to 1700°C
• Accuracy span: 540°C/1000°F minimum
• Temperature stability: ±0.1 degree per degree change in ambient
RTD Inputs
• Calibration accuracy ±0.1 percent of span ±1°C at standard conditions
• Accuracy span: 540°C/1000°F minimum
• Temperature stability: ±0.05 degree per degree change in ambient
Process Inputs
• Voltage input ranges Accuracy ±10mV ±1 LSD at standard conditions Temperature stability ±100ppm/°C maximum
• Milliamp input ranges Accuracy ±20µA ±1 LSD at standard conditions Temperature stability ±100ppm/°C maximum
Agency Approvals
•UL®916 file number E185611, C-UL®, CE, NEMA 4X
Terminals
• Touch safe
• 22 to 12 AWG
Power
• 100-240Vı(ac/dc) +10 percent, -15 percent; 50/60Hz, ±5 percent
• 24-28V
ı(ac/dc) +10 percent, -15 percent; 50/60Hz,
±5 percent
• 7.0VA maximum power consumption
• Data retention upon power failure via nonvolatile memory
Operating Environment
• 0 to 65°C, 32 to 149°F
• 0 to 90% RH, non-condensing
• Storage temperature: -40 to 85°C, -40 to 185°F
Dimensions
• Width 52 mm (2.05 in.)
• Height 52 mm (2.05 in.)
• Length 107 mm (4.2 in.)
• Depth behind panel surface 98.4 mm (3.875 in.)
• Approximate controller weight 0.2 kg (0.4 lbs)
Allowable Operating Ranges
Type J: 1.0 0 to 815°C or 32 to 1500°F
0.1 0.0 to 815.0°C or 32.0 to 999.9°F
Type K: 1.0 -270 to 1370°C or -454 to 2500°F
0.1 -199.9 to 999.9°C or -199.9 to 999.9°F
Type T: 1.0 -270 to 400°C or -454 to 750°F
0.1 -199.9 to 400.0°C or -199.9 to 750.0°F
Type N: 1.0 0 to 1300°C or 32 to 2372°F
0.1 0.0 to 999.9°C or 32.0 to 999.9°F
Type E: 1.0 -270 to 800°C or -454 to 1470°F
0.1 -199.9 to 800.0°C or -199.9 to 999.9°F
Type C: 1.0 0 to 2315°C or 32 to 4200°F
0.1 0.0 to 999.9°C or 32.0 to 999.9°F
Type D: 1.0 0 to 2315°C or 32 to 4200°F
0.1 0.0 to 999.9°C or 32.0 to 999.9°F
Type Pt 2: 1.0 0 to 1395°C or 32 to 2543°F
0.1 0.0 to 999.9°C or 32.0 to 999.9°F Type R: 1.0 0 to 1760°C or 32 to 3200°F Type S: 1.0 0 to 1760°C or 32 to 3200°F Type B: 1.0 0 to 1816°C or 32 to 3300°F
DIN 1.0 -200 to 800°C or -328 to 1472°F
0.1 -199.9 to 800.0°C or -199.9 to 999.9°F JIS 1.0 -200 to 630°C or -328 to 1166°F
0.1 -199.9 to 630.0°C or -199.9 to 999.9°F
Process -1999 to 9999 units

Functionality Matrix

Universal Remote 232/485
Input Set Point Control Alarm Retransmit Comm
Input 1
Input 2
Output 1
Output 2
Output 3
Output 4
Event &
ModbusTMis a trademark of AEG Schneider Automation. UL®and C-UL®are registered trademarks of the Underwriter’s
Laboratories, Inc.
Note: These specifications are subject to change without prior notice.

Ordering Information

SERIES 96 9 6 - -
Microprocessor-based
1
16 DIN with universal input 1. Options include: software, power supply, input 2, four outputs and display color
Power Supply
A = 100-240Vı(ac/dc) B = 24-28Vı(ac/dc)
Input 2
0 = None 1 = Event input & 0-5VÎ(dc)/ 4-20mA
(Remote set point input)
Output 1
C = Switched dc/open collector D = Electromechanical relay, Form C,
2A, without RC suppression
F = Universal Process, range selectable:
0-20mA, 4-20mA, 0-5VÎ(dc), 1-5VÎ(dc), 0-10VÎ(dc)
K = 0.5A solid state relay without
RC suppression
Output 2
A = None C = Switched dc output/open collector D = Electromechanical relay, Form C,
2A, without RC suppression
F = Universal Process, range selectable:
0-20mA, 4-20mA, 0-5VÎ(dc), 1-5VÎ(dc), 0-10VÎ(dc)
K = 0.5A solid state relay without
RC suppression
Output 3
A = None D = Electromechanical relay, Form C,
2A, without RC suppression
Output 4
A = None D = Electromechanical relay, Form C,
2A, without RC suppression
M = Universal Retransmit, range selectable:0-20mA,
4-20mA, 0-5VÎ(dc), 1-5VÎ(dc), 0-10VÎ(dc) R = EIA/TIA 232 Communications U = EIA/TIA 485 Communications
Software/Preset Parameters
00 = Standard software (order with Standard Display/Overlay) AA = Ramping software (order with Ramping Display/Overlay) XX = Custom software XX = Preset parameters
Standard Display/Overlay
Upper/Lower RR = Red/Red display RG = Red/Green display GR = Green/Red display GG = Green/Green display
Ramping Display/Overlay
Upper/Lower BA = Red/Red display BB = Red/Green display BC = Green/Red display BD = Green/Green display
2 3 4%
96
1
To be automatically connected to the nearest North American Technical and Sales Office call:
1-800-WATLOW2
International Technical and Sales Offices: Australia, +61-3-9335-6449 • China, +86-21-3950-9510 • France, +33 (0) 3073-2425 •
Germany, +49 (0) 7253-9400-0 • Italy, +39 (0) 2 458-8841 • Japan, +81-3-3518-6630 • Korea,+82-2-575-9804 • Malaysia, +60-3-7980-7741 • Mexico, +52 (442) 217-6235 • Shanghai, +86-21-3950-9504 • Singapore, +65-6773-9469 • Spain, +34 91 675 1292 • Sweden, +46 35-27-11-66 • Taiwan,+886-7-288-5168 • United Kingdom, +44 (0) 115-964-0777
52.070 mm (2.050 in.)
(9.322 mm)
0.367 in.
(107.747 mm)
4.242 in. (98.425 mm)
3.875 in.
Customer's Front Panel
Panel Cutout
44.958 mm x 44.958 mm (1.77 in. x 1.77 in.)
52.070 mm (2.050 in.)
(59.182 mm)
2.330 in.
Loading...