Watlow VPAC-BT User Manual

General Description
The BT card (Watlow P/N 08-5406) is time proportioning with a variable (very fast) time base. At 50% power, one full cycle is ON, and one full cycle is OFF. At 25% power, it is ON one cycle and OFF for three. At 90%, it is ON nine cycles and OFF for one. As the command signal gets farther from 50% power, the time base gets longer. The maximum time base resolution is 1 in 360 ac cycles. The BT card is factory set for 4-20mA into 250. It can be changed to a voltage input by removing the 300, R22 resistor, located on the lower right corner of the card. Without R22, it is a 5K input impedance. See the illustration on the reverse side. Bias and gain pots allow the card to be adjusted for any voltage from 0-3VÎ (dc) to 15VÎ (dc) or current between 0 to 25mA.
BT card power supply requirements are 24VÅ (ac) cen­ter tap transformer secondary. Transformer primary must be connected to the same line phase as the heater load. For example, is the heater is powered by L1 and L2, then the power transformer must also be connected to L1 and L2. See the illustration on the reverse side.
Dimensions
Specifications (1276)
Input
Process input factory set @ 4-20mA Î (dc)
Input impedance 250(clip resistor for 5KΩ voltage input), or manual control input
Output
Burst firing control, variable time base
TTL compatible (5V logic) at about 5mA @ 5V. Will drive one industry standard 3-32VÎ (dc) input ran­dom fire SSR. For single phase only.
Line Voltage Power
50/60 Hz V~ (ac) line frequency
Voltage ±10%, 120, 208, 240, 277, 380, 415, 480V~ (ac). Power transformer is supplied with the BT card. When ordering, specify power supply voltage and line frequency.
Line Voltage Compensation
10%in line, 2%in load in the 30% to 70% power region.
Input to Output Linearity
2%, 30% to 70% power region
Operating Environment
32 to 122°F (0 to 50°C)
Storage Temperature
-40 to 185°F (-40 to 85°C)
Options
Manual control kit for voltage input cards (1K potentiometer) #08-5362. Includes dial, knob, 1K pot and wiring.
Ordering Information
Watlow P/N 08-5406
2.5"
(64 mm)
2.5"
(64 mm)
3.0"
(76 mm)
Input
+
_
Bias
Gain
To VÎ (dc) Input SSR
08-5406
R22
Watlow Controls
1241 Bundy Blvd., P.O. Box 5580
Winona, MN 55987-5580
Phone: 507-454-5300, Fax: 507-452-4507
VPAC-BT
Remote Mount Transformer
Data Sheet
0600-0028-0002 Rev C (1277) Made in the U.S.A.
January, 1998 Printed on Recycled Paper
10% Postconsumer Waste
Input
Pot (+) (-)
Transformer Plug
R22
Zero Cross
SSR
- +
BT
8
7
6
5
4
3
2
1
4
3
2
1
Heater
Safety Contactor
if required
Semiconductor
Fuse
Branch Circuit
Fuses
Transformer
Fuses
Primary
Transformer
Connections
(bottom view)
red
black
white
black
240
Volt
120
Volt
Secondary
Transformer
Connections
(top view)
Note:
Input is 250 ohms.
For 5K input, cut R22.
Common
Positive
Pot (+) (-)
Manual Control
L1
L2
12V~(ac)
Common
(center tap)
12V~(ac)
orange
white
violet
Note:
The controls transformer must
be on the same phase as the
load. See wiring diagram. All
hot lines to the transformer
should be fused at 1 amp with
the proper line voltage.
For manual control, a 1K
potentiometer may be connected
to the AT card input terminals.
Watlow offers a Manual Control
Kit, P/N 08-5362. Using this
potentiometer requires removing
the 5K, R2 resistor for higher
impedance.
Bias and gain adjustment is
required when changing from 4-
20mA input to a manual control
input or a voltage input.
Wiring Diagram for VPAC-BT
Remote Mount Transformer