Watlow VPAC-AT User Manual

VPAC-AT
Remote Mount Transformer
Data Sheet
General Description
The AT card (Watlow P/N 08-5422) provides a delayed SCR turn ON, providing an infinitely variable voltage and current from full OFF to full ON. The AT card can be used on resistive, inductive, or Tungsten lamp loads. It includes a 2-4 second soft start on power up, and a one second soft start on input signal step change. The AT also includes a missing half cycle detector to put it into emergency shutdown (ESD), and retrigger the soft start. A low signal on the ESD terminals puts the unit into ESD. The input is factory set for 4-20mA into 250. It can be converted to a voltage input by removing R2 and readjusting the bias and gain potentiometers for any volt­age from 0-3VÎ (dc) to 0-15VÎ (dc). Without R2, it is a 5K input impedance. See the illustration on the reverse side.
AT card power supply requirements are 24VÅ (ac) cen­ter tap transformer secondary. Transformer primary must be connected to the same line phase as the heater load. For example, is the heater is powered by L1 and L2, then the power transformer must also be connected to L1 and L2. See the illustration on the reverse side.
Dimensions
Specifications
Input
Process input factory set @ 4-20mA Î (dc)
Input impedance 250(clip resistor for 5KΩ voltage input), or manual control input
Soft start approximately 2-4 seconds upon power­up, 1 second upon set point change
Output
Phase angle control
TTL compatible (5V logic) at about 5mA @ 5V. Will drive one industry standard 3-32VÎ (dc) input ran­dom fire SSR. For single phase only.
Line Voltage Power
50/60 Hz V~ (ac) line frequency
Voltage ±10%, 120, 208, 240, 277, 380, 415, 480V~ (ac). Power transformer is supplied with the AT card. When ordering, specify power supply voltage and line frequency.
Line Voltage Compensation
10%in line, 2%in load in the 30% to 70% power region.
Input to Output Linearity
2%, 30% to 70% power region
Operating Environment
32 to 122°F (0 to 50°C)
Storage Temperature
-40 to 185°F (-40 to 85°C)
Options
Manual control kit for voltage input cards (1K potentiometer) #08-5362. Includes dial, knob, 1K pot and wiring.
Ordering Information
Watlow P/N 08-5422
(1274)
Watlow Controls
1241 Bundy Blvd., P.O. Box 5580
Phone: 507-454-5300, Fax: 507-452-4507
0600-0028-0001 Rev D Made in the U.S.A.
August, 1999 Printed on Recycled Paper
(1275)
Winona, MN 55987-5580
10% Postconsumer Waste
Remote Mount Transformer
Wiring Diagram for VPAC-AT
Note:
The controls transformer must
be on the same phase as the
load. See wiring diagram. All
hot lines to the transformer
should be fused at 1 amp with
the proper line voltage.
For manual control, a 1K
potentiometer may be connected
to the AT card input terminals.
Watlow offers a Manual Control
Kit, P/N 08-5362. Using this
potentiometer requires removing
the 5K, R2 resistor for higher
impedance.
Bias and gain adjustment is
required when changing from 4-
20mA input to a manual control
input or a voltage input.