Watlow V4T User Manual

1998
November 2000
On-line version of 1967
Users Manual
1241 Bundy Boulevard, P.O. Box 5580, Winona, Minnesota USA 55987-5580
Phone: +1 (507) 454-5300, Fax: +1 (507) 452-4507, http://www.watlow.com

Series V4

General Purpose
2 Watlow Series V4

Overview

The V4 1/4 DIN panel mount controller is a general purpose industrial PID temperature controller.The V4 provides a reliable cost-effective solution for most temperature control applications.Thermocouple, RTD, and Current and Voltage sensors are supported. Dual outputs can be configured to support heating and cooling.The secondary output can also be configured as an alarm.
V4 features include: a NEMA 4X front panel seal, a 3-year warranty, meets European CE requirements and has a 4 inch deep case with removable connectors for wiring convenience.
Figure 2a — Series V4 inputs and outputs.
Figure 2b - Controller dimensions.
Dual Control Output -
Single Input ­Type J, K, T, N or S Thermocouple, RTD or Process
V4
1 2 %
PID or ON/OFF, User Selectable
Output 1 ­Heat or Cool
Output 2 ­Heat, Cool, Alarm or None
Mounting Brackets
External
Gasket
Front Bezel
Mounting Collar Customer's Front Panel
4.25"
(107.9mm)
M3 Mounting Screw
Terminal
Block
Mounting Slots
Terminal
Block
3.83"
(97.18mm)
4.21"
(106.83mm)
3.58"
(91.03mm)
Watlow Series V4 3

Installation and Removal

Figure 3 - Series V4 multiple panel cutout dimensions.
NOTE: Measurements between panel cutouts are the minimum recommended.

Installing the Series V4 Controller

Installing and mounting requires access to the back panel.
1. Make the panel cutout using the panel cutout dimensions as shown in Figure 4.
2. Make sure the rounded side of the external case gasket is facing the panel surface.
3. Check to see that the gasket is not twisted, and is seated within the case bezel flush with the panel.
4. Slightly compress the top and bottom side of the V4 Case while pulling the controller into the panel cutout (Figure 5a). Slide the mounting collar over the back of the controller.The tabs on the collar must line up with the mounting ridges on the case for secure installation. The tab holes are facing the back of the controller.
5. Adjust the mounting bracket screws enough to allow for the mounting collar and panel thickness. Snap the upper and lower mounting brackets on the case of the controller (Figure 5 b). Make sure all the grips are well engaged on the mounting slots of the controller. (The four screw heads are fac­ing the back of the controller.)
6. Make sure the case is seated properly.Tighten the installation screws firmly against the mounting collar to secure the unit (Figure 5c). To ensure NEMA 4X seal, there should be no space between the bezel and panel. Over tightening the screws will distort the case and make it diffi­cult to remove or replace the controller.
V4
1 2 %
Panel Cutout
Panel
Thickness
0.375"
9.5 mm)
3.62"
(92mm)
3.62"
(92mm)
0.85"
(20mm)
minimum
0.85"
(20mm)
minimum
3.93"
(99.82mm)
Watlow Series V4 4
Installation and Removal (continued)
Figure 4a - Slightly compress the case while Figure 4b - Snap the top and bottom mounting pulling the controller into the panel cutout. bracket into the slots.
Figure 4c - Tighten screw to secure the controller. Figure 4d - Remove the controller using a flat
screwdriver.
NOTE: Be careful not to over-tighten the screws. This may cause the mounting cover to fail. Over-tighten­ing occurs when the front bezel is touching the customers front panel.

Removing the Series V4 Controller

1. Loosen the upper and lower mounting bracket screws.
2. Use a flat screw driver to unsnap the four grips on the opposite side of upper and lower mounting brackets. Push the brackets back and forth gently until they can be pulled off easily.
3. Remove controller from the panel.
Watlow Series V4 5

Wiring the Series V4

Power Wiring

High Voltage 100 to 240VÅ (ac), nominal (85 to 264 actual) V4TH - _ _ _ _ - _ _ _ _ Low Voltage 14 to 24V(ac/dc) V4TL - _ _ _ _ - _ _ _ _
Figure 5 - Power wiring.

Sensor Installation Guidelines

We suggest you mount the sensor at a location in your process or system where it reads an average temperature. Put the sensor as near as possible to the material or space you want to control. Air flow past this sensor should be mod­erate. The sensor should be thermally insulated from the sensor mounting.
ç
WARNING:
To avoid damage to property and equip­ment and/or injury or loss of life, use National Electric Code (NEC) standard wiring practices to install and operate this unit. Failure to do so could result in injury and/or death, or such damage.
NOTE:
Taking the unit out of the case is not a nor­mal operating condi­tion and should only be done by a quali­fied maintenance installation techni­cian. Power to the case should be dis­connected before removing or installing the con­troller into its case.
WARNING:
The case terminals may still carry live voltage when the unit is removed.
WARNING: Irreversible damage will occur if high voltage is applied to the low voltage unit.
L1 L2
18
OFF
1 2
4
5
6
17
16
15
14
13
8
7
fuse
8
7
6 Watlow Series V4

Input Wiring

Figure 6a – Thermocouple

Extension wire for thermocouples must be of the same alloy as the thermo­couple itself to limit errors.
Figure 6b – RTD (2- or 3-Wire) 100Platinum
There could be a +2°F input error for every 1of lead length resistance when using a 2-wire RTD. That resistance,when added to the RTD element resistance, will result in erroneous input to the instrument. To overcome this problem, use a 3-wire RTD sensor,which compensates for lead length resistance. When extension wire is used for a 3-wire RTD,all wires must have the same electrical resistance (i.e. same gauge, same length, multiple­stranded or solid, same metal.
Figure 6c – Process,4-20mA Figure 6d – Process,0-5VÎ (dc)
Input impedance: 5 Input impedance: 10k
NOTE:
Successful installa­tion requires five steps:
Choose the con­trollers hardware configuration and model number;
Choose a sensor;
Install the con-
troller;
Wire the controller and
Configure the con­troller.
ç
WARNING:
To avoid damage to property and equip­ment and/or injury or loss of life, use National Electric Code (NEC) standard wiring practices to install and operate this unit. Failure to do so could result in injury and/or death, or such damage.
NOTE: When an external device with a non-isolated circuit common is connect­ed to the 4-20mA or dc output, you must use an isolated or ungrounded thermo­couple.
ç
CAUTION: Process input does not have sensor break protec­tion. Outputs can remain full on.
DIP Switch Orientation 1: OFF 2: ON
+
T/C
-
DIP Switch Orientation 1: OFF 2: OFF
S1
4
S2
5
S3
6
5
6
RTD
OFF
1 2
3-wire
RTD
OFF
1 2
TC
OFF
1 2
DIP Switch Orientation
4
5
6
DIP Switch Orientation 1: OFF
RTD
OFF
1 2
2: OFF
S1
S2
S3
4
5
6
OFF
1 2
DIP Switch Orientation
4
5
6
OFF
1 2
DIP Switch Orientation
4
5
6
2-wire RTD
Jumper Terminals 5 & 6
(customer supplied)
DIP Switch Orientation 1: ON 2: ON
I
dc
- 4
+ 6
PROC
OFF
1 2
DIP Switch Orientation
PROC
OFF
1 2 1: ON 2: ON
OFF
1 2
DIP Switch Orientation
4
5
6
V
dc
+
5
6
-
OFF
1 2
DIP Switch Orientation
4
5
6
Watlow Series V4

Output 1 Wiring

Figure 7a – Mechanical Relay

Without Contact Suppression
V4T _ - D _ _ _ - _ _ _ _
Form C, rated at 8A @ 125V~ (ac) or 5A @ 240V~ (ac) Minimum load current: 100mA @ 5VÎ (dc)

Figure 7b – Solid State Relay

Without Contact Suppression
V4T _ - K _ _ _ - _ _ _ _
0.5 amps (AC loads only)
ç
WARNING:
To avoid damage to property and equip­ment and/or injury or loss of life, use National Electric Code (NEC) standard wiring practices to install and operate this unit. Failure to do so could result in injury and/or death, or such damage.
NOTE:
Switching inductive loads (relay coils, solenoids, etc.) with the mechanical relay, switched dc or solid­state relay output options requires use of an R.C. suppres­sor.
Watlow carries the R.C. suppressor Quencharc brand name, which is a trademark of ITW Pakron. Watlow Part No. 0804-0147-0000.
18
18
17
16
17
15
14
16
13
15
OFF
1 2
4
5
6
14
8
13
7
COM
NC NO
Customer Supplied
Quencharc
Customer Supplied
Quencharc
18
17
18
16
15
17
14
13
16
OFF
1 2
4
5
6
15
14
8
7
13
SS1
SS1
Fuse
L1
External
Load
L2
L2
External
Load
L1
Fuse
8 Watlow Series V4
Output 1 Wiring

Figure 8a – Switched DC, Open Collector

V4T _ - C _ _ _ - _ _ _ _

Figure 8b – 4-20mA Process

V4T _ - F _ _ _ - _ _ _ _
Maximum load impedance: 800
NOTE:
When an external device with a non­isolated circuit com­mon is connected to the 4-20mA or dc out­put, you must use an isolated or unground­ed thermocouple.
OFF
1 2
4
5
6
V+
unregulated
V—
Internal Circuitry
18
17
18
16
15
17
14
13
16
+
External
-
Load
15
14
8
13
7
18
16
OFF
1 2
4
5
6
18
18
17
16
17
15
14
16
13
+
External
-
Load
15
14
8
13
7
Watlow Series V4 9

Output 2 Wiring

Figure 9a – Mechanical Relay Without Contact Suppression
V4T _ - _ D _ _ - _ _ _ _
Form C, rated at 8A @ 125V~ (ac) or 5A @ 240V~ (ac). Minimum load cur­rent: 100mA @ 5VÎ (dc)
Figure 9b – Solid State Relay Without Contact Suppression
V4T _ - _ K _ _ - _ _ _ _
0.5 amps (AC loads only)

Figure 93 – Switched DC, Open Collector

V4T _ - _ C _ _ - _ _ _ _
18
18
17
17
16
15
16
14
13
15
8
7
14
13
Customer
OFF
1 2
4
5
6
COM
NC NO
Supplied
Quencharc
Fuse
L1
External
Load
L2
18
18
17
16
15
17
14
13
16
OFF
1 2
4
5
6
15
14
8
13
7
Customer Supplied
Quencharc
SS2
SS2
18
18
17
16
17
15
14
16
13
15
OFF
1 2
1 2
4
5
6
14
8
13
7
+
-
L2
External
Load
L1
Fuse
External
Load
V+
unregulated
V
15
13
Internal Circuitry
Watlow Series V4 10

Wiring Example

Figure 10 - System wiring example.
ç
WARNING:
To avoid damage to property and equip­ment and/or injury or loss of life, use National Electric Code (NEC) standard wiring practices to install and operate this unit. Failure to do so could result in injury and/or death, or such damage.
L1
120V~(ac)
L2
Earth Ground
fuse
fuse
coil
high limit
mechanical
contactor
fuses
V4TH-CAAA-AARR
TC
OFF
1 2
4
5 (+)
5
6
6 (-)
120V~ (ac)
L1
1
Temperature
Controller
DIP Switch Orientation
18
18
17
16
15
16
14
13
8
8
7
7
7 (-) 6 (+)
T1 T2
Heater
DIN-a-mite
DA1C-1624-C000
process sensor limit sensor
L1 L2
Series V4
V4TH - CAAA - AARR
Temperature Controller
(+)
TC+
(-)
TC-
DC+1
94AA-1DK1-00RG
Limit
5 (+)
6 (-)
TC
OFF
1 2
4
5
6
Controller
DIP Switch Orientation
L2L1
18
18
17
16
16
15
14
13
8
8
7
7
L2
2
DC-1
1 CR-1
1
L1
1
TC+
TC-
COM1
1
(-)(+)
L1 L2
T1
T2
Heater
Series 94
94AA-1DK1-00RG
Limit Controller
DIN-a-mite
DA1C-1624-C000
L2
NO1
NC1
1CR
2
2
2
Watlow Series V4 11

Keys and Displays

Upper Display: Indicates the process value, actual temperature, operating parameter values or an open sensor. When powering up, the Process display will be blank for five seconds.
To set to blank, set [`dsP] to [`SEt] in the Setup Menu.
Lower Display: Indicates set point, output value, parameters for data in the upper display, or error and
alarm codes.
To set to blank, set [`dsP] to [`Pro] in the Setup Menu.
Advance Key: Press to advance through the Operations, Setup, and Calibration Menus. In the Auto mode, new data is self-entering in five seconds.
Infinity/Home Key:
Press once to clear any latched alarms. Also disables deviation alarm output if silencing is enabled.
Press again within five seconds to change from Auto to Manual or vice versa. While in Manual mode, percent power is in the lower display sensor error.
Output 1 Indicator Light: Lit when Output 1 is energized.
Output 2 Indicator Light: Lit when Output 2 is active. This output can be configured as a control or alarm output.
V4
1 2 %
% Percent Power Indicator Light:
Lit: the controller is in Manual operation. Press the ˆInfinity key twice to enter Automatic operation.
Blinking: press the ˆInfinity key to toggle between Auto and Manual. Returns to its previous state and stops blinking if the ˆInfinity key is not pressed within five seconds.
Up-arrow and Down-arrow Keys: Increases or decreases the value of the displayed parameter.
Press lightly to increase or decrease the value by one.
Press and hold down to increase or decrease the displayed value at a rapid rate. New data will self-enter in five seconds, or can be entered by pressing the Advance Key.
Press both simultaneously for three seconds to enter the Setup Menu. The [`LOC] parameter appears.
Continue pressing both keys to enter the Calibration Menu.
Watlow Series V4 12
Setting up the Series V4 is a simple process. First set the DIP switches to match your input type. Refer to the orientation on the back of the controller to select the [``In] Input value. Next, configure the Series V4's features to your application in the Setup Menu, then enter values in the Operating Menu. Both tasks use the Advance key to move through the menus and the Up-arrow/Down-arrow keys to select data.
Before entering information in the Setup Menu, set the [`dFL] parameter. If [``SI] is selected, °C, proportional band in % of span, derivative and integral are the defaults.If [``US] is selected,°F,proportional band in degrees,reset and rate are the defaults. Changing the [`dFL] prompt will set parameters to their factory default. Document all current parameter settings first. See the cal­ibration section in the Appendix to change this parameter.

Entering the Setup Menu

The Operation Menu will appear as the default menu of the Series V4.The Setup Menu displays the parameters that configure the Series V4's features to your application.
Enter the Setup Menu by pressing the ¿Up-arrow and ¯Down-arrow keys si­multaneously for 3 seconds.The lower display shows the [`LOC] Lock parame­ter, and the upper display shows its current level. All keys are inactive until you release both keys.You can reach the Lock parameter from anywhere.
Use the Advance key to move through the menus and the ¿Up-arrow and ¯Down-arrow keys to select data. You will not see all parameters in this menu, depending on the controller's configuration and model number. After stepping through the menu it returns to the set point parameter under the Operation Menu. If no keys are pressed for approximately 60 seconds, the controller returns to the default display, Process over Set Point.
93
93
WARNING:
Remove power from the controller before remov­ing the chassis from the case or changing the DIP switches. Removing the controller from the chas­sis is not a normal oper­ating condition and should only be done by a qualified technician.

How to Set Up the Series V4

Figure 12a ­Entering the Setup Menu.
Figure 12b ­The Setup Menu.
NOTE:
While in the Setup Menu, all outputs are off.
[`LOC] Lock [``In] Input [`dEC] Decimal* [`C_F] Celsius - Fahrenheit* [``rL] Range Low [``rH] Range High [`Ot1] Output 1 [`HSC] Hysteresis Control [`Ot2] Output 2 [`HSA] Hysteresis Alarm* [`LAT] Latching* [`SIL] Silencing* [`rtd] RTD* [`rP`] Ramping [`rT`] Rate* [`P`L] Power Limiting* [`dSP] Display
* Parameter may not always appear.
Setup Menu
Watlow Series V4 13
At the top of the Setup Menu the Series V4 displays the user level of operation in the upper display and the [`LOC] parameter in the lower display .
Press the Advance key and the value of the next parameter appears in the upper display, and the parameter appears in the lower display.
Lock: Selects the level of operator lock-out as defined below. Range: 0 to 4 Default: 0
[```0]: All operating parameters may be viewed or changed. Manual operation
is permitted. When in manual operation, percent power is adjustable. Bumpless transfer to manual mode will occur on sensor break.
[```1] The set point, process value and alarm settings are the only visible parameters, set point is adjustable in this level. Manual operation and auto­tune are permitted. When in manual operation, percent power is adjustable. Bumpless transfer to manual mode will occur on sensor break.
[```2] The set point, process value and alarm settings are the only visible parameters, set point is adjustable in this level. Manual operation is permit- ted. When in manual operation, percent power is adjustable. Bumpless transfer to manual mode will occur on sensor break.
[```3] The set point and process value are the only visible parameters, set point is adjustable in this level. Manual operation is not permitted. Bumpless transfer is defeated and outputs are disabled on sensor break.
[```4] The set point and process value are the only visible parameters, set point is not adjustable in this level of lock-out. Manual operation is not per­mitted. Bumpless transfer is defeated and outputs are disabled on sensor break.
Input: Selects the sensor input type. The internal DIP switch must also match the {`In} parameter. See DIP switch orientation, and see input type tempera­ture ranges in the following chart.
Range: [```J], [```H] (K), [```t], [```n], [```S], [`rtd], [`r†d], [`0-5], [`420] Default: J
Decimal: Selects the location of the decimal point for all process-related data. This parameter only appears if the [``In] parameter is set to 0-5 or 420. Make sure the internal DIP switch matches the [``In] parameter.
Range: 0, 0.0, 0.00 Default: 0 Celsius — Fahrenheit: Selects the units of temperature measurement for the
control. This parameter only appears if the [``In] parameter is set to a thermo­couple or RTD input. The default is dependent on the [`dFL] parameter located in the Calibration Menu. Refer to the Appendix. Range: [```C] or [```F] If [`dFL] is set to [``SI]: Default: [```C] If [`dFL] is set to [``US]: Default: [```F]
Range Low: Selects the low limit of the set point. Also used to scale the low end of the process input. 0.0VÎ (dc) and 4mA represent [``rL] Range Low for a process input. The process input is linearly scaled between [``rL] and [``rH]. See the model number and specification in the Appendix for range values,or refer to the following table.
Range: Sensor range low to [``rh] Range High Default: Low limit of sensor type for a thermocouple or RTD. -500 for a process
input.

Setup Parameters

{``In}
{`dEC}
{`C-F}
ç
CAUTION:
A process input does not have sensor break protection or bumpless transfer.
NOTE:
Shaded parameters may not appear, depending on the controller’s configuration and model number.
ç
CAUTION:
Changing [``In] sets all parameters to factory defaults. Document all set­tings before changing this parameter.
NOTE:
Set the [`LOC] parameter
value as the final step in
programming the Series V4
controller to prevent locking
yourself out of the Operation
and Setup Menu during ini-
tial programming.
[`LOC}
{``rL}
Watlow Series V4 14
{`HSC}
{`Ot1}
{`Ot2}
{`HSA}
{``rh}
{`LAt}
{`SIL}
{`rtd}
{``rt}
{`rP`}
Range High: Selects the high limit of the operating range. Also used to scale the high end of the process input. 5.0VÎ (dc) and 20mA represent Range High [``rh] for a process input. The process input is linearly scaled between [``rL] and [``rH]. See the model number and specification information in the Appendix for your range values, or refer to the following table.
Range: Sensor range high to [``rL] Default: High limit of sensor type for a thermocouple or RTD. 9999 for process input.
Output 1: Selects the action for the primary output in response to the difference
between set point and process variable. Select [``ht] (heat) for reverse acting or select [``CL] (cool) for direct acting.
Range: [``ht], [``CL] Default: [``ht] Hysteresis-Control: Selects the switching hysteresis for Output 1 and 2 when you
select 0 (on-off) under the [`Pb1] parameter and [`Ot2] is set to [`Con].
Range: 1 to 55, 0.1 to 5.5, 0.01 to 0.55°C/1 to 99, 0.1 to 9.9, 0.01 to 0.99°F Default: 2, 0.2, 0.02°C/3, 0.3, 0.03°F
Output 2: Selects the output action for the secondary output. Range:
[`Con] Control mode opposite Output 1 (heat or cool) [`PrA] Process alarm with alarm message displayed [``Pr] Process alarm with no alarm message displayed [`dEA] Deviation alarm with alarm message displayed [``dE] Deviation alarm with no alarm message displayed [``no] None
Default: [`Con] Hysteresis - Alarm: Selects the switching hysteresis for Output 2 when [`Ot2] is
an alarm. Appears only if [`Ot2] is not set to [`Con] or [``no]. See the Operation Menu for [`Pb1].
Range: 1 to 5555, 0.1 to 555.5, 0.01 to 55.5°C/1 to 9999, 0.1 to 999.9, 0.01 to 99.99°F Default: 2, 0.2, 0.02°C/3, 0.3, 0.03°F
Latching: Selects whether the alarm is latching or non-latching. Latching alarms
must be cleared by pressing the ˆInfinity key before the alarm output will reset. Selecting non-latching will automatically reset the alarm output when the condition clears.Appears only if [`Ot2] is not set to [`Con] or [``no].
Range: [`LAt] or [`nLA] Default: [`nLA] Silencing: Selects alarm silencing (inhibit) for the alarm. Appears only when
[`Ot2] is set to [`dEA] or [``dE]. For more information see Chapter 5.
Range: [``On] or [`OFF] Default: [`OFF] RTD: Selects the RTD calibration curve for RTD inputs.Will not appear unless
[``In] is set to [`rtd] or [`r†d]. [`JIS] is 0.003916Ω/°C, [`Din] is
0.003850Ω/Ω°C.
Range: [`din] or [`JIS] Default: [`din] Ramping: Choose [`Str], and the set point ramps at the selected rate in °/hr. from
the process (actual) temperature to the set point, when power is applied to the con­troller (start up). It will not ramp with a set point change. [`On] is the same as [`Str], but ramps with a set point change. It ramps from the previous set point to a new one at the selected ramp rate. Select [`OFF] for no ramping action. When ramping, the lower display alternately flashes [``rP]. The set point displayed is the desired end set point. The ramping set point is not shown. Entering the Setup Menu or manual operation disables the outputs and ramp. Once you exit either one, the Series V4 controls to the last entered set point.
Range: [`Str], [``On], [`OFF] Default: [`OFF] Rate: Selects the ramping rate in degrees per hour.Will not appear if [``rP] is set
to [`OFF]. Range: 0 to 9999 Default: 100°/hr.
Watlow Series V4 15
Power Limiting: The power limiting function in % power for heat only. Power Limiting will function if [`pb1] is set to [```0].
Range: Dependent on output type. 0 to100 Default: 100 Display: Selects which displays are active or viewable. Five seconds after selected,
the appropriate display goes blank. Press Advance, ¿Up-arrow or ¯Down-arrow to override this feature and cause the current value to be displayed for 5 seconds.
Range: [`nor] Normal displays Default: [`nor]
[`SEt] Set Point - lower display only [`Pro] Process - upper display only

Setup Menu

Parameter Value Range Factory Default Appears If:
[`LOC]
**
[```0], [```1], [```2], [```3], [```4] 0
[``In] [```J], [```H], [```t], [```n], [```J] DIP switch selectable.
[```S], [`rtd], [`r†d], [`0-5], [`420]
[`dEC] 0, 0.0, 0.00 0 [``In] is set to [`0-5]
or [`420]
[`C_F] [```C] or [```F] Dependent on [`dFL] [``In] is set to [```J],
[```H], [```t], [```n],
[```S], [`rtd], or [`r†d] [``rL] [``rL] to [``rh] Input dependent. [``rh] [``rh] to [``rL] Input dependent. [`Ot1] [``ht] or [``CL] [``ht] [`HSC] 1 - 99, 0.1 - 9.9, 0.01 - 0.99°F 3, 0.3, 0.03°F
1 to 55, 0.1 to 5.5, 0.01 to 0.55°C 2, 0.2, 0.02°C
[`Ot2] [`Con] = Control [`Con]
[`PrA] = Process Alarm [``Pr] = Process with no alarm message [`dEA] = Deviation alarm [``dE] = Deviation with no alarm message [``no] = None
[`HSA] 1 - 9999, 0.1 - 999.9, 0.01 - 99.99°F 3, 0.3, 0.03°F [`Ot2] is not set to [`Con]
1 - 5555, 0.1 - 555.5, 0.01 - 55.55°C 2, 0.2, 0.02°C or [``no]
[`LAt] [`LAt] or [`nLA] [`nLA] [`Ot2] is not set to [`Con]
or [``no] [`SIL] [``On] or [`OFF] [`OFF] [`Ot2] is set to [`dEA] or
[``dE] [`rtd] [`JIS] or [`din] [`din] [``In] is set to [`rtd] or
[`r†d] [`rP`] [`Str] is set to Ramping on power up [`OFF]
[``on] is set to Ramping to set point always
[`OFF] is set to None [`rt`] 0 to 9999 100°/hr [``rP] is not set to [`OFF] [`P`L] 0 to 100 100 [`dsP] [`nor] = normal [`nor]
[`SEt] = Set Point (lower only)
[`Pro] = Process (upper only)
**LOC Functions
[```0]
: All operating parameters may be viewed or changed. Manual operation is permitted. Bumpless transfer to manual
mode will occur on sensor break.
[```1]
: The set point, actual, and alarm settings are only visible parameters, set point is adjustable in this level. Manual
operation and auto-tune are permitted. Bumpless transfer to manual mode will occur on sensor break.
[```2]
: The set point, actual, and alarm settings are the only visible parameters, set point is adjustable in this level. Manual
operation is permitted. Bumpless transfer to manual mode will occur on sensor break.
[```3]
: The set point and actual are the only visible parameters, set point is adjustable in this level. Manual operation is not
permitted. Bumpless transfer is defeated and outputs are disabled on sensor break.
[```4]
: The set point and actual are the only visible parameters, set point is not adjustable in this level. Manual operation is
not permitted. Bumpless transfer is defeated and outputs are disabled on sensor break.
Input Type Sensor Range Low Sensor Range High
[```J] 0°C/32°F 750°C/1382°F [```H] -200°C/-328°F 1250°C/2282°F [```t] -200°C/-328°F 350°C/662°F [```n] 0°C/32°F 1250°C/2282°F [```S] 0°C/32°F 1450°C/2642°F [`rtd] (1°) -200°C/-328°F 700°C/1292°F [`r†d] (0.1°) -128.8°C/-199.9°F 537.7°C/999.9°F [`420] 4mA/-999 units 20mA/9999 units
[`0-5] 0VÎ (dc)/-999 units 5VÎ (dc)/9999 units
Table 15a ­Input Ranges.
{`dSP}
Table 15b ­Setup Menu Prompts and Descriptions.
[`P`L]
Watlow Series V4 16

Operation Parameters

Set Point: Sets the operating set point for Output 1. Represents the process value the system tries to achieve for Output 1. "SP" does not appear on the lower display. The control set point value is displayed and can be incremented or decremented without pressing the Advance key.The lower display may be blank if [`dSP] is set to [`Pro]. In a ramping mode, the lower display alternately flashes the desired end set point and [``rP].
Proportional Band 1 and 2: A proportional band, expressed in degrees or % of span, within which a proportioning function is active for Output 1 or 2. When [`Pb1] is set to 0, the unit functions as an on-off control on Output 1 and 2. [`Pb2] will not appear if [`Pb1] is set to 0 or [`Ot2] is not set to [`Con]. The switching differential is determined by the [`HSC] parameter. Range if [`dFL] is set to [``US]: [`Pb1]: 0 to 555°C/0 to 999°F/0 to 999 Units; 0.0 to 5.5°C/0.0 to 9.9°F/0.0 to 9.9 units, [`Pb2]: The same as [`Pb1] except lower limit is 1 or 0.1. Defaults: [`Pb1] is set to 2.5°C/25°F [`Pb2] is set to 25
Range if [`dFL] is set to [``SI]: 0 to 999.9% of span Defaults: [`Pb1] is set to 3.0% [`Pb2] is set to 3.0%
Reset /Integral 1 and 2: An integral control action for Output 1 or 2 that auto-
matically eliminates offset, or "droop," between set point and actual process temper­ature. [`rE1]/[`It1]: Will not appear if [`Pb1] is set to 0. [`rE2]/[`It2]: Appears if [`Pb1] is not set to 0 and [`Ot2] is set to [`Con]. Either reset [``rE] or integral [``It] will appear depending on how the [`dFL] parameter is set in the Calibration Menu. See the Appendix.
Range if [`dFL] is set to [``US]: 0 to 9.99 repeats/minute Default: 0.00 Range if [`dFL] is set to [``SI]: 00.1 to 9.99 minutes per repeat Default: 0.00
Rate/Derivative 1 and 2: The rate (derivative) function for Output 1 or Output 2.
Eliminates overshoot on startup, or after the set point changes. [`rA1]/[`dE1]: Will not appear if [`Pb1] is set to 0. [`rA2]/[`dE2]: Appears if [`Pb1] is not set to 0 and [`Ot2] is set to [`Con]. Either rate [``rA] or derivative [``dE] appears de­pending on how [`dFL] is set in the Calibration Menu.
Range if [`dFL] is set to [``US] or [``SI]: 0 to 9.99 minutes Default: 0.0 Cycle Time 1 and 2: Time for a controller to complete one time-proportioned cycle
for Output 1 or Output 2; expressed in seconds. [`Ct1]: Will not appear if [`Pb1] is set to 0, or Output 1 is 4-20mA. [`Ct2]: Will not appear if [`Pb1] is set to 0 or [`Ot2] is not set to [`Con].
NOTE:
Shaded parameters may not appear, depending on the controller’s configu­ration and model number.
[``SP}
NOTE:
The upper display will always return to the process value after 1 minute with­out key strokes.
{`rE1} {`It1}
{`rE2} {`It2}
{`Ct1}
{`Ct2}
{`rA1} {`dE1}
{`rA2} {`dE2}
{`Pb1} {`Pb2}
[``93] Control Set Point [`Pb1] Proportional Band 1 [`rE1] Reset 1* [`It1] Integral 1* [`rA1] Rate 1* [`dE1] Derivative 1* [`Ct1] Cycle Time 1* [`ALO] Alarm Low* [`AHI] Alarm High* [`Pb2] Proportional Band 2* [`rE2] Reset 2* [`It2] Integral 2* [`rA2] Rate 2* [`dE2] Derivative 2* [`Ct2] Cycle Time 2* [`CAL] Calibration Offset [`AUt] Autotune

Operation Menu

* Parameter may not always appear.
Operation Menu
Figure 16 ­The Operation Menu.
Watlow Series V4 17
If a mechanical relay or contactor is switching power to the load, a longer cycle time may be desirable to minimize wear on the mechanical compo­nents. Typical life of a mechanical relay is 100,000 cycles. Range: 0.1 to 999.9 seconds Default: 5.0 seconds
Alarm Low: Represents the low process alarm or low deviation alarm. This param-
eter will not appear if [`Ot2] is set to no or [`Con].
Range if [`Ot2] is set to [`dEA] or [``dE]: -999 to 0 Default: -999 Range if [`Ot2] is set to [`PrA] or [``Pr]: [``rL] to [`AHI] Default: [``rL]
Alarm High: Represents the high process alarm or high deviation alarm. This
parameter will not appear if [`Ot2] is set to [``no] or [`Con].
Range if [`Ot2] is set to [`dEA] or [``dE]: 0 to 999 Default: 999 Range if [`Ot2] is set to [`PrA] or [``Pr]: [`ALO] to [``rH] Default: [``rH]
Calibration Offset: Adds or subtracts degrees from the input signal. Range: -100°C to 100°C/-180°F to 180°F/-180 units to 180 units; or
-10.0°C to 10.0°C/-18.0°F to 18.0°F Default: 0 Autotune: Initiates an autotune.
Range: 0 is set to off, 1 is set to slow, 2 is set to medium, 3 is set to fast Default: 0
Table 17 ­Operation Menu Prompts and Descriptions.
{`ALO}

Operation Menu Parameters

Document your Series V4 Operation Parameters.
{`AHI}
{`AUt}
{`CAL}
Parameter Value Range Factory Default
[`Pb1] If [`dFL] is set to [``US]:
0 - 999°F/0 - 555°C/0 - 999 Units 25°F 0 - 99.9°F/0 - 55.5°C/0 - 99.9 Units 2.5°F 0 is set to ON/OFF control. [`HSC] is set to switch diff. If [`dFL] is set to [``SI]: 0.0 to 999.9% of span 3%
[`rE1] 0.00 to 9.99 repeats/minute 0.00 repeats/minute
0.00 = No Reset. Won't appear if [`Pb1] is set to 0 or [`dFL] is set to [``SI].
[`It1] 0.0 - 99.9 minutes/rpt. 0.00 = No Integral. 00.0 minutes/repeat
Won't appear if [`Pb1] is set to 0 or [`dFL] is set to [``US].
[`rA1] 0.00 to 9.99 minutes 0.00 minutes
0.00 = No Rate. Will not appear if [`Pb1] is set to 0 or [`dFL] is set to [``SI].
[`dE1] 0.00 - 9.99 minutes. 0.00 = No Derivative. 0.00 minutes
Won't appear if [`Pb1] is set to 0 or [`dFL] is set to [``US].
[`Ct1] 0.1 to 999.9 5.0 seconds
Won't appear if [`Pb1] = 0, or [`420].
[`Pb2] Same as [`Pb1]. [`Pb2] lower limit = 1, 0.1, 0.01 [`rE2] Same range as [`rE1]. [`It2] Same range as [`It1]. [`rA2] Same range as [`rA1]. [`dE2] Same range as [`dE1]. [`Ct2] Same range as [`Ct1]. [`ALO]
Deviation [``dE] -999 to 0 -999 Process [``Pr] [``rL] to [`AHI] [``rL]
Will not appear if [`Ot2] is set to [``no] or [`Con].
[`AHI]
Deviation [``dE] 0 to 999 999 Process [``Pr] [`ALO] to [``rH] [``rH]
Will not appear if [`Ot2] is set to [``no] or [`Con].
[`CAL] ±180°F/±100°C/±180 Units 0 [`AUt] 0-3 0
18 Watlow Series V4

Troubleshooting Alarms and Errors

Indication Probable Cause(s) Corrective Action
Error Code Messages ([----] in the upper display indicates a Series V4 error; error code number is visible in bottom display)
• Sensor input generated a value lower than allowable signal range, or A/D circuitry malfunctioned. Enter a valid input. Make sure
[``In]
parameter (Setup Menu) matches your sensor and DIP switches are set accordingly.
• Microprocessor is faulty; consult factory.
• Unless power interruption occurred while controller was storing data, nonvolatile memory is bad; consult factory.
• A/D circuit is underrange. Check sensor; if function­ing properly, consult factory. Make sure
[``In]
parameter (Setup Menu) matches your sensor and DIP switches are set accordingly.
• A/D circuit is overrange. Check sensor; if functioning properly, consult factory. Make sure
[``In]
parame­ter (Setup Menu) matches your sensor and DIP switches are set accordingly.
• Sensor underrange error (applies only to RTD units)
• Configuration error.
• Non-volatile checksum error.
• A/D underflow error.
• A/D overflow error.
[----] [`Er2]
[----] [`Er4]
[----] [`Er5]
[----] [`Er6]
[----] [`Er7]
• Check the alarm logic for compatibility with system peripherals and annunciators.
• Check the power limit setting
• Check the operation mode.
• Check the alarm output function.
• Check the °C or °F setting.
• Check the calibration offset value; set it to a lower level.
• Alarm may be latched.
• Alarm set points may be incorrect..
• Alarm hysteresis may be incorrect.
• Input may be in error condition.
• Alarm won’t occur.
• Configure output as an alarm.
• Check alarm set points.
• To clear the alarm, correct the alarm condition; check to see if the alarm is latched.
• Check the alarm sides setting.
• Check the alarm type setting.
• Alarm output may be off.
• Alarm set points may be incorrect.
• Alarm may be silenced.
• Alarm sides may be incorrect.
• Controller may be in diagnostics mode.
• Alarm won’t occur.
Alarms
• Check switches, fuses, breakers, interlocks, limits, connectors, etc. for energized condition and proper connection.
• Measure power upstream for required level. Check part number for input power required.
• Check wire size.
• Check for bad connections.
• Power to unit may be off.
• Fuse may be blown.
• Breaker may be tripped.
• Safety interlock door switch, etc. may be activated.
• Separate system limit control may be latched.
• Wiring may be open.
• Input Power may be incorrect.
• No power.
Power
Watlow Series V4 19

Calibration

Before attempting to calibrate, make sure you read through the procedures carefully and have the proper equipment called for in each procedure. Make sure the DIP switches are in the proper position for the input type.

Entering the Calibration Menu

In the Calibration Menu, various input signals must be supplied for the con­troller to go through its auto calibration. The Calibration Menu can only be entered from the [`LOC] Lock parameter in the Setup Menu. Press the ¿Up- arrow/¯Down-arrow keys simultaneously for 3 seconds (± 1 second). The [`CAL] parameter appears in the lower display with "no" in the upper display.
Any inadvertent change in the displayed data, when pressing the ¿Up- arrow/¯Down-arrow keys, is ignored. Calibration values won't be retained unless you are in the manual mode. Press the ¿Up-arrow or ¯Down-arrow key to change the upper display to [`YES] Press Advance to enter the calibration sequence.
Upon entering the calibration menu, the upper display window indicates [`CAL]. It continues to indicate [`CAL] (with the exception of calibration of the 4-20mA output) while the operator walks through the entire calibration parameter list. While calibrating the 4-20mA output, the upper display contains a numeric value to be slewed up or down until the output value is correct. The controller uses the lower display to prompt the user as to what the input should be.
With the [`dFL] parameter,select either [``US] parameters which include dis­playing °F, rate, reset, and proportional band in degrees or units. Or select [``SI] (System International) and the displayed parameters are °C, integral, derivative, and proportional band in % of span.
Once the information has been properly established and maintained for at least 5 to 10 seconds, the Advance key may then be used to display the next prompt. After the final input is established, press the Advance key twice to return the controller to the configuration menu at the top of the parameter list.
Figure 19 ­Entering the Calibration Menu.
NOTE:
While in the Calibration Menu, the controller out­put(s) go off and the alarm output (if present) is on.
NOTE: Calibration values will not be retained unless you are in the MANUAL mode. Do not enter the MANUAL mode until you are at the correct input parameters.
V4
1 2 %
V4
1 2 %
The [`rSt] parameter restores the factory calibration values to the Series V4. If you calibrate your control incorrectly, you have the option to default to the origi­nal values. Once you leave the [`CAL] menu, the values are entered.
1. Press the ¿Up-arrow/¯Down-arrow keys simultaneously for three seconds. The LOC parameter appears in the lower display. Continue holding the ¿Up-arrow/¯Down-arrow keys until the lower display reads [`CAL].
2. Press the ¿Up-arrow key until [`YES] appears in the upper display.
3. Advance through the calibration menu until [`rSt] appears in the lower display.
4. Press the ¿Up-arrow key until [`YES] appears in the upper display.
5. Press the Advance key and the V4 advances to test the displays.
6. To conclude, wait 60 seconds or press the Advance key to reach the next prompt or to exit from the CAL menu.
This procedure is used only to restore calibration, it is not meant to clear values.

Restoring Factory Calibration

20 Watlow Series V4

Calibration Menu

[`)00] Input 0.00mV for low input. [`5)0]
Input 50.00mV for high input.
[``tC]
Connect a Type "J" ambient compensator with inputs shorted.
[`440] Set the low resistance to 44.01Ω. [`225] Set the high resitance to 255.42. [`)00]
Set the voltage source to 0.000 volts.
[`%00] Set the voltage source to 5.000 volts. [`$00] Set the cursource to 4.00mA [`2)0] Set the current source to 20.00mA [`4A0] Enter 4-20mA output calibration value for 4mA [`2A0] Enter 4-20mA output calibration value for 20mA [`rSt] Restores factory calibration values. [`dSP] Test display. [`dFL] Select US (rate, reset, proportional band in degrees or units, °F) or
SI (integral, derivative, proportional band in % of span, °C)
Calibration Menu
[``NO]
[`CAL]
[`YES]
[`CAL]
Figure 20 ­Calibration Parameters.
NOTE: Before calibration on an installed controller, make sure all data and parameters are docu­mented.
Equipment Required
Type "J" Reference Compensator with reference junction at 32°F/0°C, or Type "J" Thermocouple Calibrator set at 32°F/0°C.
Precision millivolt source, 0-50mV min. range, 0.01mV resolution
Setup And Calibration
1. Connect the ac line voltage L1 and L2 to the proper terminals.
2. Connect the millivolt source to Terminal 6 Negative and Terminal 5 Positive on the Series V4 terminal block. Use regular 20 - 24 gauge wire. Make sure the DIP switch is set for thermocouple input.
3. Apply power to the controller and allow it to warm up for 15 minutes. After warm-up put the controller in the Calibration Menu. Select [`YES].
4. Press the ˆInfinity key twice to enter the manual mode. The controller is calibrating when % indicator light is on. Make sure the controller is in manual mode only when you are in the correct parameters.
5. At the 0.00 prompt, enter 0.00mV from the millivolt source to the control. Allow at least 10 seconds to stabilize. Press the
Advance key.
6. At the 50.0 prompt, enter 50.00mV from the millivolt source to the Series V4.Allow at least 10 seconds to stabilize. Press the Advance key.
7. At the [``tC] prompt, disconnect the millivolt source, and connect the reference com­pensator or thermocouple calibrator to Terminal 6 Negative, and Terminal 5 Positive on the Series V4 terminal block. If using a compensator, turn on and short the input wires. If using "J" calibrator, set to simulate 32°F/0°C.Allow 10 seconds for the control to stabilize. The controller will leave the [`CAL] mode if one minute passes between key activations. Press the ˆInfinity key twice to exit the manual mode. To conclude the thermocouple calibration, advance the
Advance key to the next prompt or exit the
[`CAL] menu.

Thermocouple Field Calibration Procedure

Watlow Series V4 21
Equipment Required
Precision dc voltage source 0-5 volt minimum range with 0.001 volt resolution.
Setup and Calibration
1. Connect the ac line voltage L1 and L2 to the proper terminals on the V4.
2. Connect the voltage/current source to Terminal 5 (+) and 6 (-) on the Series V4 termi­nal block. Use regular 20 - 24 gauge wire. Make sure the DIP switch is set for process input.
3. Apply power to the controller and allow it to warm up for 15 minutes. After warm-up put the controller in the [`CAL] menu. See Figure A.3. Select [`YES]. Press the
Advance key until 0.00 is displayed.
4. Press ˆInfinity twice to enter the manual mode. The controller is calibrating when the % indicator light is on. Make sure the controller is in the manual mode only when you are in the correct parameters.
5. At the 0.00 parameter, set the voltage source to 0.000 volts. Allow at least 10 seconds to stabilize. Press the
Advance key.
6. At the 5.00 parameter, set the voltage source to 5.000VÎ (dc). Allow at least 10 sec­onds to stabilize. The controller leaves the [`CAL] mode if 1 minute passes between key activations. Press ˆInfinity twice to exit the manual mode. To conclude the 0-5 volt calibration, press the
Advance key to the next prompt or exit the [`CAL] menu.
NOTE:
Before calibration on an installed controller, make sure all data and parameters are docu­mented.

0-5 Volt Input Field Calibration Procedure

NOTE: When the % indicator light is on, the controller is automatically calibrat­ing. Your sequence is VERY important. Always move to the next param­eter before changing the calibration equipment.
Equipment Required
1Kprecision decade resistance box with 0.01resolution.
Setup And Calibration
1. Connect the ac line voltage L1 and L2 to the proper terminals.
2. Connect the decade resistance box to Terminal 4, 5 and 6 on the terminal block. Use regular 20 - 24 gauge wire of the same length and type. Make sure the DIP switch is set for RTD input.
3. Apply power to the controller and allow it to warm up for 15 minutes. After warm-up put the controller in the [`CAL] menu. Select [`YES]. Press the Advance key until the 440 prompt is displayed.
4. Press the ˆInfinity key twice to enter the manual mode. The controller is calibrating when the % indicator light is on. Make sure the controller is in manual mode only when you are in the correct parameters.
5. At the 440 prompt, set the decade resistance box to 44.01. Allow at least 10 seconds to stabilize. Press the Advance key.
6. At the 255 prompt, set the decade resistance box to 255.42. Allow at least 10 seconds to stabilize. Press the ˆInfinity key twice to exit the manual mode. The controller will leave the [`CAL] mode if one minute passes between key activations.To conclude the RTD calibration, press the Advance key to the next prompt or exit the [`CAL] menu.

RTD Field Calibration Procedure

22 Watlow Series V4
NOTE: When the % indicator light is on, the controller is automatically calibrat­ing. Your sequence is VERY important. Always move to the next param­eter before changing the calibration equipment.

4-20mA Input Field Calibration Procedure

Equipment Required:
Precision current source 0-20mA minimum range with 0.01mA resolution.
Setup and Calibration
1. Connect the ac line voltage L1 and L2 to the proper terminals on the V4.
2. Connect the current source to Terminal 4 (-) and 6 (+) on the Series V4 terminal block. Use regular 20 - 24 gauge wire. Make sure the DIP switch is set for process input, see.
3. Apply power to the controller and allow it to warm up for 15 minutes. After warm-up put the controller in the [`CAL] menu. Select YES. Press the
Advance key until 4 is
displayed.
4. Press ˆInfinity twice to enter the manual mode. The controller is calibrating when the % indicator light is on. Make sure the controller is in the manual mode only when you are in the correct parameters.
5. At the 4.00 parameter, set the current source to 4.00mA. Allow at least 10 seconds to stabilize. Press the
Advance key.
6. At the 20.0 parameter, set the current source to 20.00mA. Allow at least 10 seconds to stabilize. The controller leaves the [`CAL] mode if 1 minute passes between key activa­tions. Press ˆInfinity twice to exit the manual mode. To conclude, press the Advance key to the next prompt or exit the [`CAL] menu.

4-20mA Output Field Calibration Procedure

Equipment Required:
300, 1/2 watt 10% resistor.
4 - 1/2 digit Digital Multimeter.
Setup And Calibration
1. Connect the ac line voltage L1 and L2 to the proper terminals of the V4. Set the multi­meter to measure current.
2. Connect the multimeter in series with the 300resistor to Terminal 18 Positive and 16 Negative on the Series V4 terminal block. Use regular 20 - 24 gauge wire.
3. Apply power to the controller and allow it to warm up for 15 minutes. After warm-up put the controller in the [`CAL] menu. Select YES. Press the Advance key until the 4A0 prompt is displayed.
4. Press the ˆInfinity key twice to enter the manual mode. The controller is calibrating when the % indicator light is on.
5. At the [`4A0] prompt, the multimeter should read approximately 4mA. Allow at least 10 seconds to stabilize.
6. Use the ¿Up-arrow/¯Down-arrow keys (reverse acting) to adjust the reading on the multimeter for 3.85mA ± 0.10mA. Press the Advance key.
7. At the [`2A0] prompt, the multimeter should read approximately 20mA. Allow at least 10 seconds to stabilize. The controller will leave the [`CAL] mode if one minute passes between key activations except for 4-20mA units.
8. Use the ¿UP/¯DOWN keys (reverse acting) to adjust the reading on the multimeter for 20.15mA ±0.10mA.
9. To conclude the 4-20mA output calibration, advance the Advance key to the next prompt or exit the [`CAL] menu.
NOTE:
Before calibration on an installed controller, make sure all data and parameters are docu­mented.
Watlow Series V4 23

Specifications (1968)

Control Mode
• Microprocessor-based, user selectable control modes
• Single process input, dual output
• 2.5Hz input sampling rate
• 1Hz display update rate
• Ramp to set point: 0 to 9999 degrees or units per hour
• Heat and cool auto-tune operator interface
Operator Interface
• Sealed membrane front panel
• Dual, four-digit red or green displays
Advance, ¿Up-arrow, ¯Down-arrow, and ˆInfinity keys
• User selectable screen display
Accuracy
• Calibration accuracy and sensor conformity: ±0.1% of span, ±1°C @ 77°F ± 5°F (25°C ± 3°C) ambient and rated line voltage
• Accuracy span: 1000°F (540°C) minimum
• Temperature stability: ±0.2°F/°F (±0.2°C/°C) rise in ambient maximum
Sensors/Inputs
• Thermocouple, grounded or ungrounded sensors
• RTD 2- or 3-wire, platinum, 100@ 0°C calibration to DIN curve (0.00385Ω/Ω/°C) or JIS curve (0.003916Ω/Ω/°C); user selectable
• Process, 4-20mA @ 5, or 0-5VÎ (dc) @ 10k input impedance
• Sensor break protection de-energizes control output to protect system or selectable bumpless transfer to manual operation
• °F or °C or process units display, user selectable
Input Range
Specified temperature ranges represent the
controller’s operational span.
Thermocouple
Type J 32 to 1382°F or 0 to 750°C Type K -328 to 2282°F or -200 to 1250°C Type N 32 to 2282°F or 0 to 1250°C Type S 32 to 2642°F or 0 to 1450°C Type T -328 to 662°F or -200 to 350°C
RTD Resolution (DIN or JIS)
-328 to 1292°F or -200 to 700°C
0.1° -199.9 to 999.9°F or -128.8 to 537.7°C
Process
4-20mA @ 5 or -999 to 9999 units 0-5V (dc) @ 10k or -999 to 9999 units
Output 1 (Heating or Cooling)
• Electromechanical relay1. Form C, rated at 8A @ 125V~ (ac) or 5A @ 240V~ (ac) or 5A @ 30VÎ (dc), max. at resistive load, without contact suppression. Max. switching current is 10A, max. switching power is 2500VA, and max. switching voltage is 277V~ (ac) or 110VÎ (dc).
• Switched dc signal provides a non-isolated minimum turn on voltage of 3VÎ (dc) into a minimum 500
load; maximum on voltage not greater than 12VÎ (dc) into an infinite load.
• 4-20mA reverse or direct acting, non-isolated 0 to 800load.
• Solid-state relay3, Form A, 0.5A @ 24V~ (ac) min., 264V~ (ac) max., opto-isolated burst fire switched, without contact suppression. Off-state output impedance is 31MΩ.
Output 2 (Heat, Cool or Alarm)
• Electromechanical relay1. Form C, rated at 8A @ 125V~ (ac) or 5A @ 240V~ (ac) or 5A @ 30VÎ (dc), max. at resistive load, without contact suppression. Max. switching current is 10A, max. switching power is 2500VA, and max. switching voltage is 277V~ (ac) or 110VÎ (dc).
• Switched dc signal provides a non-isolated minimum turn on voltage of 3VÎ (dc) into a minimum 500 load; maximum on voltage not greater than 12VÎ (dc) into an infinite load.
• Solid-state relay3, Form A, 0.5A @ 24V~ (ac) min., 264V~ (ac) max., opto-isolated burst fire switched, without contact suppression. Off-state output impedance is 31MΩ.
• Alarm output can be latching or non-latching, and process or deviation with separate high and low values. Alarm silencing (inhibit) on power up (for deviation alarms only).
Output Configurations
Output 1
User selectable as: on/off: P, PI, PD, PID, heat or cool action
• Adjustable switching differential: 1 to 99°F (1 to 55°C)
• Proportional band: 0 (off) or 1 to 999°F (0 to 555°C) or 0.0 to 999.9 units
Integral: 0 (off) or 0.1 to 99.9 minutes per repeat Reset: 0 (off) or 0.01 to 9.99 repeats per minute Rate/derivative: 0 (off) or 0.01 to 9.99 minutes Cycle time: 0.1 to 999.9 seconds
Output 2
User selectable as: Control with action opposite that of Output 1 (heating or cooling)
• Process or deviation alarm with flashing alarm message
• Process or deviation alarm without alarm message
• Alarm with separate high and low set points
• Hysteresis: 1 to 9999° or units switching differential
Line Voltage/Power
• 100-240V~ (ac), -15%, +10%; (85-264V~ [ac]) 50/60Hz, ±5%
• 14-24Vı (ac/dc), +10%, -15%; (12-26Vı [ac/dc]) 50/60Hz, ±5%
• Fused internally (factory replaceable only) Slo-Blo® type (time-lag): 1A, 250V for high voltage versions 2A, 250V for low voltage versions
• Maximum power consumption: 12VA (100 to 240V~ [ac]), 7VA (12 to 24Vı [ac/dc])
• Data retention upon power failure via non-volatile memory
Watlow Series V4 24
Operating Environment
• 32 to 149°F (0 to 65°C)
• 0 to 90% RH, non-condensing
Storage Temperature
• -40° to 185°F (-40° to 85°C)
Terminals
• Touch-safe, plugable terminal blocks
• 22 to 12 AWG
Controller Weight
• 0.68 lb (310g)
Shipping Weight
• 0.75 lb (0.34 kg)
Dimensions
• 1⁄4 DIN size and NEMA 4X2front panel make the Series V4 easy to apply and maintain in a wide variety of applications. Unique mounting brackets, gasket and collar make installation a snap.
Overall Height: 4.3 inches (109 mm)
Width: 4.3 inches (109 mm) Depth: 4.0 inches (101 mm)
Depth Behind Panel Surface:
3.875 inches (98.4 mm)
Agency Approvals
• UL, C-UL, CE, NEMA 4X
• CE 89/336/EEC (EN 50082-2, EN 50081-2 )
• CE 73/23/EEC (EN61010-1, EN 60730-1 and EN 60730-2-9 )
1
Electromechanical relays warranted for 100,000 closures only. Solid-state switching devices recommended for applications requiring fast cycle times or extended service life.
2
To effect NEMA 4X rating requires a minimum mounting panel thickness of 0.06inch (1.5 mm) and surface finish not rougher than 0.000032 inch (0.000812 mm).
3
Switching inductive loads (relay coils, etc.) requires using an RC suppressor.
Note: These specifications are subject to change
without prior notice.

Ordering Information

(1466)
V 4 T _ - _ _ A A- A A _ _
Series V4
Temperature controller, single analog input, single control output, dual 4-digit displays
Power Supply
H = 100-240V~(ac) L = 14-24Vı(ac/dc)
Output 1
C = Switched dc output, non-isolated D = Electromechanical relay, Form C, max. switching current
8A (refer to specifications), without contact suppression
1,3
F = Process, 4-20mAÎ(dc), non-isolated K = Solid state relay, Form A, 0.5A,
without contact suppression
3
Output 2
A = None C = Switched dc output, non-isolated D = Electromechanical relay, Form C, max. switching current
8A (refer to specifications), without contact suppression
1,3
K = Solid state relay, Form A, 0.5A,
without contact suppression
3
Display Options
Upper/Lower RR = Red/Red display RG = Red/Green display GR = Green/Red display GG = Green/Green display XX = Custom Overlays
Watlow Series V4 25

Declaration of Conformity

Series V4
WATLOW SINGAPORE PTE LTD Asia Controls
55, Ayer Rajah Crescent, #03-23 Ayer Rajah Industrial Estate Singapore 139949
Declares that the following product: English Designation: Series V4 Model Number(s): V4T(H or L)-(C D F or K) (A C D or K) AA-AA (Any two letters or
numbers)
Classification: Control, Installation Category II, Pollution Degree II Rated Voltage: 100 to 240V~ (ac) or 24Vı (ac/dc) Rated Frequency: 50/60 Hz. Rated Power Consumption: 12VA maximum Meets the essential requirements of the following European Union Directive(s) using the rele­vant section(s) of the normalized standards and related documents shown:
89/336/EEC Electromagnetic Compatibility Directive
EN 50082-2: 1995 EMC Generic immunity standard, Part 2, Industrial environment
EN 61000-4-2: 1995 Electrostatic discharge EN 61000-4-4: 1995 Electrical fast transients ENV 50140: 1994 Radiated immunity ENV 50141: 1994 Conducted immunity ENV 50204: 1995 Cellular phone
EN 50081-2: 1994 EMC Generic emission standard, Part 2: Industrial environment
EN 55011: 1991 Limits and methods of measurement of radio disturbance characteristics
of industrial, scientific and medical radio-frequency equipment (Class A) EN 61000-3-2: 1995 Limits for harmonic current emissions EN 61000-3-2: 1995 Limitations of voltage fluctuations and flicker
72/23/EEC Low-Voltage Directive
EN 61010-1: 1993 Safety requirements for electrical equipment for measurement,
control, and laboratory use, Part 1: Generic requirements
W
ATSON NG SAI HIONG SINGAPORE
Name of Authorized Representative Place of issue
General Manager December, 1998 Title of Authorized Representative Date of Issue
Signature of Authorized Representative
(1469)
Watlow Series V4 26
NOTE:
Details of a Note appear here in the narrow margin on the outside of each page.
CAUTION:
Details of a Caution appear here in the narrow margin on the outside of each page.
WARNING:
Details of a Warning appear here in the narrow margin on the outside
of each page.
Quality and Mission Statement:
Watlow Controls will be the world’s best supplier of industrial temperature control products, services, and systems by exceeding our customers’, employees’, and shareholders’ expectations.

Safety Information

We use note, caution and warning symbols throughout this book to draw your attention to important operational and safety information.
A NOTEmarks a short message in the margin to alert you to an important detail.
A CAUTIONsafety alert appears with information that is important for pro­tecting your equipment and performance. Be especially careful to read and fol­low all cautions that apply to your application.
A WARNINGsafety alert appears with information that is important for pro­tecting you, others and equipment from damage. Pay very close attention to all warnings that apply to your application.
The safety alert symbol,
ç
, (an exclamation point in a triangle) precedes a gener-
al CAUTION or WARNING statement.
The electrical hazard symbol,
Ó
, (a lightning bolt in a triangle) precedes an
electric shock hazard CAUTION or WARNING safety statement.

Technical Assistance

If you encounter a problem with your Watlow controller, see the Trouble­shooting Table and review all of your configuration information to verify that your selections are consistent with your application: inputs; outputs; alarms; lim­its; etc. If the problem persists after checking the above, you can get technical support by dialing 507/494-5656, 7 a.m. to 7 p.m. Central Standard Time. An applications engineer will discuss your application with you.
Please have the following information available when calling:
Complete model number All configuration information
Users Manual Diagnostic menu readings

Your Feedback

Your comments or suggestions on this manual are welcome. Please send them to: Technical Writer, Watlow Controls,1241 Bundy Boulevard, P.O. Box 5580, Winona, MN 55987-5580. The Series V4 Users Manual is copyrighted by Watlow Winona, Inc., © July 2000, with all rights reserved.

How to Reach Us

Phone: (507) 454-5300.
Fax:(507) 452-4507.
For technical support,ask for an Applications Engineer.
To place an order, ask for Customer Service.
To discuss a custom option, ask for a Series V4 Product Manager.

Warranty

The Watlow Series V4 is warranted to be free of defects in material and work­manship for 36 months after delivery to the first purchaser for use, providing that the units have not been misapplied. Since Watlow has no control over their use, and sometimes misuse, we cannot guarantee against failure. Watlow's obli­gations hereunder, at Watlow's option, are limited to replacement, repair or refund of purchase price, and parts which upon examination prove to be defec­tive within the warranty period specified. This warranty does not apply to dam­age resulting from transportation, alteration, misuse, or abuse.

Returns

Call or fax Customer Service for a Return Material Authorization (RMA)
number before returning a controller.
Put the RMA number on the shipping label, and also on a written description
of the problem.
A restocking charge of 20% of the net price is charged for all standard units
returned to stock.
Loading...