Watlow Silver OIT User Manual

Watlow Silver Series OIT
Installation Guide

Introduction

Thank you for purchasing a Silver Series graphic operator interface terminal (OIT) from Watlow. The Silver Series OITs are configured using the EZware-5000 software (available separately from Watlow) and include the following models:
4.3” TFT display TS00-0043-0000 HMI5043N
4.3” TFT display TS00-0043-E000 HMI5043T
7.0” TFT display TS00-0070-0000 HMI5070TH
10.2” TFT display TS00-0100-0000 HMI5100T
This booklet describes the steps necessary for installing the Silver Series OIT.
Watlow P/N
Maple Systems
P/N

Copyright Notice

This manual is a publication of Maple Systems, Inc. and is provided for use by its customers only. The contents of the manual are copyrighted by Maple Systems, Inc.; reproduction in whole or in part, for use other than in support of Maple Systems equipment is prohibited without specific written permission of Maple Systems.
The copyright of EasyBuilder-5000 and its related software belongs to Weintek Labs, Inc.

Applications Assistance

This manual is designed to provide the necessary in formation for trouble-free installation and operation of your new Operator
0600-0069-0000 Rev D
2 Watlow Silver Series OIT Installation Guide
Interface Terminal (OIT). However, if you need assistance, please call Watlow at (507) 494-5656 between 7 a.m. and 5 p.m. Central Standard Time (CST). Ask for an Applications Engineer. Or you may e-ma il your questions to wintechsupport@watlow.com.
For information on programming and configuring the OIT, please refer to the Silver Series Installation and Operations Manual available from Watlow.

Static Awareness

Do NOT remove the rear cover - doing so will void your warranty. When the rear cover is removed the circuitry inside is exposed to possible damage by electrostatic discharge during handling.

If Service is Required

Contact Watlow Customer Service at (507) 454-5300 for instructions on how to return a product and how to obtain a Return Materials Authorization (RMA) number.
Package the unit in its original packaging container or, if unavailable, any suitable rigid container. If a substitute container is used, surround the unit with shock absorbing material; damage in shipment is not covered by the warranty. Include a letter with the unit describing the difficulty and designating a contact person.
All returns will be tested to verify customer claims of noncompliance with the product warranty. Improper return packaging, which makes verification impossible, will void the warranty. Products passing the tests will be returned “AS IS” to the customer.
If noncompliance is verified and is not due to customer abuse or the other exceptions described with product warranty, Watlow will, at its option, repair or replace the Product returned to it, freight prepaid, which fail to comply with the foregoing warranty, provided Watlow is notified of such noncompliance within the two-year warranty period.
0600-0069-0000 Rev D
3 Watlow Silver Series OIT Installation Guide

Warranty

Maple Systems warrants each product to b e f r ee f r om electrical and mechanical defects in materials and workmanship for a period of two years from the date of shipment. This warranty does not apply to defects in the Products caused by abuse, misuse, accident, casualty, alteration, negligence, repair not authorized by Maple Systems, use on current or voltages other than specified by Maple Systems, or application or installation not in accordance with published instruction manuals. This warranty is in lieu of any other warranty either expressed or implied.
Maple Systems liability is limited to the repair or replacement of the Product only, and not costs of installation, removal, or damage to user’s property or other liabilities. If Maple Systems is unable to repair or replace a nonconforming Product, it may offer a refund of the amount paid to Maple Systems for such Product in full satisfaction of its warranty obligation. Maximum liability of Maple Systems is the cost of the Product.
Information furnished by Maple Syst ems, Inc., is believed to be accurate and reliable. However, no responsibi lity is assumed by Maple Systems for the use of this information, or for any infringements of patents or other rights of third parties which may result from its use. No license is granted by implication, or otherwise, under any patent or patent rights of Maple Systems, Inc. Maple Systems retains t he right to revise or change its products and documentation at any time without notice.

Installation of OITs

CE Compliance

The Silver Series Graphic OITs have been tested to conform to European CE requirements which meet or exceed the noise emissions and immunity requirements as set forth in the EN5 5022 (Emissions) and EN55024 (Immunity) standards. The products are designed to withstand electrical noise in harsh industrial environments. They also conform to requirements that limit electrical emissions. However, this does not guarantee that the products will be totally immune from possible malfunction in cases where severe electrical noise occurs. Therefore, we strongly recommend that you follow the guidelines outlined in this guide
0600-0069-0000 Rev D
4 Watlow Silver Series OIT Installation Guide
for proper wire routing and grounding to insure the proper operation of your graphic OIT.

NEMA Rating

The Silver Series is rated for NEMA 4/12 (indoor) or IP65 installations. This means that when the OIT is properly mounted to a NEMA 4 panel or other NEMA 4 rated enclosure, the front enclosure of the OIT wil l provide protection to the inside of the panel from splashing water, wind­blown dust, rain, or hose-directed water. The OIT must be installed according to the instructions in this manual to be properly sealed.

Environmental Considerations

The Silver Series is designed to operate in temperatures from 0 to 45 °C (32 to 113 °F). It is intended for indoor installations and may not be suitable for use in certain outdoor applications. Avoid installing the Silver Series OITs in environments with severe mechani cal vibration or shocks. Do not install the OIT in enclosures with rapid temperature variations or high humidity. Either will cause condensation of water inside the device and eventual damage to the OIT.

Safety Precautions

Please observe the following precautions when installing the OIT. Failure to comply with these restrictions could result in loss of life, serious personal injury, or equipment damage.
Warning: Do not operate the OIT in areas subject to explosion
due to flammable gases, vapors, or dusts.
Warning: Do not connect the OIT to an AC power source. You
will cause permanent damage to the OIT.
Warning: Do not attempt to use a DC power supply that does
not meet OIT power requirements. You may cause malfunction or permanent damage to the OIT.
Warning: Do not power the OIT with a DC power supply used
for inductive loads or for input circuitry to the programmable logic controller. Severe voltage spikes caused by these devices may damage the OIT.
0600-0069-0000 Rev D
5 Watlow Silver Series OIT Installation Guide

Control Panel Design Guidelines

Pay careful attention to the placement of system components and associated cable routing. These items can significantly enhance the performance and integrity of your control application.
Figure 1: Typical Panel Layout

Control Panel Grounding

The control panel must be connected to a good, high-integrity earth ground both for safety considerations and shielding purposes. Maple Systems cannot overemphasize the importance of good grounding. If you fail to use good grounding procedures during installation, sporadic malfunction of the OIT may occur:
- Connect the OITs chassis ground terminal to a r eliable earth
ground with a low-resistance path.
- Route all earth ground wires that lead from the OIT, the PLC, the
power supply, and the line filter to a central earth ground point such as a barrier strip. This will ensure that no ground current from one device influences the operation of the other devices.
- Connect the OIT chassis ground terminal to the control panel
door using a heavy-gauge short braided cable or ground wire to minimize resistance.
- Conn ect the power cable’s shield wire to the OIT’s chassis
ground terminal.