Watlow SDA Card Shorted Solid State Relay Detector User Manual

There is concern that if a solid state relay fails, it will most likely fail in a shorted condition. To alleviate this concern, Watlow Controls has designed a low-cost card (Watlow P/N 08-5386) that provides a shorted SSR alarm. It is designed to be used with DC input SSRs, rated 10 to 40 Amps on either a single phase or two-leg, three-phase system. In addition to the SDA card, we strongly recommend semiconductor fuses to protect the SSR, and a high limit cutout to protect the thermal system from any runaway conditions.
The SDA card mounts directly on the solid state relay and takes its power from the current flowing through the current transformer. If there is no input command signal from the temperature control to the SSR, and there is current flow to the load, the alarm becomes energized. The alarm circuit’s output is a triac rated for 300mA @ 120 or 240V~ (ac). This can be wired through a customer supplied latching relay and alarm to 120 or 240 volts.
Watlow Controls
1241 Bundy Blvd., P.O. Box 5580
Winona, MN 55987-5580
Phone: 507-454-5300, Fax: 507-452-4507
SDA Card
Shorted Solid State Relay Detector
Data Sheet
0600-0028-0004 Rev C (1278) Made in the U.S.A.
January, 1998 Printed on Recycled Paper
10% Postconsumer Waste
Figure 1 - SDA Card Dimensions (08-5386)
NOTE: Mount with two 6-32 screws 5/8” long. (Included with the SDA card.)
To Heater
TB1
2 1
(See below for wiring.)
Load
Line
Fuse
L1 L2
Load Number of Passes of Load Wire
Current Through Current Transformer
2 to 3 Amps 5 3 to 4 Amps 4 4 to 5 Amps 3
5 to 10 Amps 2
10 to 40 Amps 1
Figure 3 - SDA Card Wiring
Table 1 - Application of 16-0231 Current Transformer
Figure 2 - Three Dimensional View of Wiring
NOTE: The triac connection between connector TB1 pins 1 and 2 is closed when a shorted SSR condition is detected. This output is rated 24 to 240V~ (ac), 300mA @ 25°C, 125mA @ 80°C.
L2
AC Line
Voltage
L1
Semiconductor
Fuse
Output
Load
DC Input
Solid State Relay
DC
-
Input
+
Signal
- +
Input
TB1
2 1
Current
Transformer
30A to 20mA
- +
SDA Board
08-5386
120 V~ (ac)
T o Alarm
or Contactor
Customer Supplied Relay
(Philips ECG PIY 1055 or equivalent)