QPAC
TOTAL
3 Year Warranty
CUSTOMER
SATISFACTION
Modular SCR Power
Controller for Custom
Tailoring to the Application
The QPAC SERIES from Watlow® is a modular Silicon
Controlled Rectifier (SCR) power controller with plug-in
features for flexibility. Bases are rated from 150 to 1000
amperes in one-phase, three-phase, two leg and three-phase,
three leg.
A variety of transformers from 120 to 575VAC along
with 50/60Hz operation enable the QPAC to operate in
applications anywhere. Plug-in control cards set the
QPAC’s SCR firing modes; solid state contactor, burst
firing (zero cross) or phase-angle models are available with
a wide variety of options. This power controller includes 200KA
short circuit current rating (SCCR) and high speed fuses to
minimize damage in the event of a short circuit.
Typical Applications
• Furnace and ovens
• Petrochemical
• Heat treating
• Duct heating
• Environmental chambers
• Kilns
Features and Benefits
200KA short circuit current rating (SCCR)
•
Minimizes damage in the event of a short circuit
Modular power controller
•
Unit base can be fitted with a variety of plug-in
transformers and control cards
Available in 150 to 1000 ampere ratings
•
Handles large or small loads
Available in solid state contactor, burst firing
(zero cross) or phase-angle fired mode
•
Meets most application requirements
Rugged design for 122°F (50°C) ambient operation
•
Full rating of the power controller can be used in
industrial applications
Semiconductor fuses and snubber protection included
•
Protects the SCR from voltage or current surges or spikes
Open heater or shorted SCR detector option
• Diagnostic capabilities
UL® 508 listed and C-UL® up to 1000 amperes
•
For applications requiring agency approvals
© 2013 Watlow Electric Manufacturing Company all rights reserved.
®
WIN-QPAC-0613
Specifications
Operation
Modular controller base with plug-in card and
transformer
• Plug-in control cards
Solid state contactor, dc input
Burst fire control, fixed or variable time base
Phase-angle fire control
Phase-angle control with soft start and current limiting
• Plug-in transformers (50/60Hz)
• 120, 208, 240, 380, 415, 480, 575VAC operation
Power bases
• 1-phase (Q01), 1 pair of SCRs
• 3-phase (Q32), 2 leg control, 2 pair SCRs
Resistive load only, burst firing only
• 3-phase (Q33), 3 pair hybrid SCRs/diodes
Recommended for phase-angle only with balanced load
Agency Approvals
• UL® 508 and C-UL® listed, 150 to 300A all configurations,
File #E73741
• UL® 508 and C-UL® listed, 400 to 1,000A on Q01 and Q32,
up to 480VAC
Control Card Inputs
(CD) Solid state contactor, dc input
• On, 4-32VDC; off, 0.5VDC
• Built-in noise reduction network
(BF) Burst firing control fixed time base
• Process input factory set @ 4-20mA DC
• Input impedance 250Ω (clip resistor for 5kΩ impedance
voltage input), or manual control input
• Time base 4 seconds (clip resistor for 1 sec)
(BV) Burst firing control, variable time base
• Process input factory set @ 4-20mA DC
• Input impedance 250Ω (clip resistor for 5kΩ impedance
voltage input), or manual control input. Requires an
accessory bias and gain card to calibrate for 0-5VDC input
(AF) Phase-angle control
• Process input factory set @ 4-20mA DC
• Input impedance 250Ω (clip resistor for 5kΩ impedance
voltage input), or manual control input
• Soft start approximately 6 seconds upon power-up,
1 second upon set point change
(AL) Phase-angle control with current limit
• Process input factory set @ 4-20mA DC
• Input impedance 250Ω (clip resistor for 5kΩ impedance
voltage input), or manual control input
• Soft start approximately 10 seconds upon power-up,
1 to 2 seconds upon set point change
• Current transformer included
Open Heater/Shorted SCR Detector
• Zero cross/burst fire models only
• Triac output
• 24 to 240VAC, 300mA @ 77°F (25°C), 125mA @
176°F (80°C)
• Energizes on alarm
• Holding current 200µA min.
• Latching current 5mA typical
Outputs
• 120 through 575VAC
• 1, 2 or 3 pole
• 150 to 1000A per pole
• SCCR, 200KA with original equipment specified
semiconductor fusing
Line Voltage / Power
• 50/60Hz ac line frequency, Q32 and Q33 models are
50/60Hz calibration dependent
• Voltage: ±10%, 120, 208, 240, 277, 380, 415, 480,
575VAC
Line Voltage Compensation
• 10% ∆ in line, 2% ∆ in load in the 30 to 70% power region
(AF, AL and BV)
Power Dissipation (Watts)
• 1.5 W/A per controlled leg
Isolation
• Command signal to load 1250VAC min.
Linearity
• 2%, 30 to 70% power region (All units except CD)
Off-State Leakage Current
• 20mA @ 480VAC
SCR Protection
• Semiconductor fuses provided dv/dt 200V/µsec min.
• MOV1 and RC snubber network standard
• (Q32) 3rd leg fuse kit may be used, but not required, with
3-phase, 2 leg models
Mounting
• Heat sink fins must be mounted in vertical orientation
Operating Environment
• 32 to 122°F (0 to 50°C)
• 0 to 90% RH, non-condensing
• 2,000 meters altitude
Storage Temperature
• -40 to 185°F (-40 to 85°C)
Options
• Manual Control Kit for process input cards
(1kΩ potentiometer) #08-5362
• 240VAC and 120VAC cooling fans
1
MOV comes only on Q33 (3-phase, 3 leg).
QPAC Weight Chart
Phase
Amps
150 15 (6.8) 36 (16.3) 50 (22.7)
200 15 (6.8) 36 (16.3) 50 (22.7)
300 15 (6.8) 36 (16.3) 50 (22.7)
400-600 44 (20.0) 85 (38.5) 100 (45.4)
800-1000 49 (22.2) 120 (54.4) 135 (61.2)
1Ø/Q01
lb (kg)
3Ø, 2-leg/Q32
lb (kg)
3Ø, 3-wire/Q33
lb (kg)