QUICK START
GUIDE
PM PLUS™ ControLLer
for configurations:
PM6 _ _ [E,F,C] [J,C,H] - _ AAA [P,V] _ _
For assistance contact Watlow: www.watlow.com
1-800-WATLOW2 (1-800-928-5692)
wintechsupport@watlow.com
Document #10-39213 Rev. A
Dec. 4, 2019
CONTROLLER INTERFACE
Up/Increment Key
Numeric Slider
Down/Decrement Key
Function Key
Back/Forward Select Arrows
Home
• Scroll up or down lists
using the + or - keys.
• Increase or decrease
numeric parameters
with the slider.
• Select items or move to lists
using the forward arrow.
• Return to the previous selection
with the back arrow.
• Return to the home screen from
any screen with the Home button.
1 - MOUNT TO PANEL
1. Make the panel cutout using the
measurements in figure 1.
2. Remove the green terminal
connectors and the mounting collar
assembly.
3. Insert the controller into the panel
cutout from the front.
4. Orient the collar base so the flat side
faces front and the screw openings
are on the sides (see figure 2), then slide the base over the
back of the controller.
5. Slide the mounting bracket over the controller with the
screws aligned to the collar base. Push the bracket gently
but firmly until the hooks snap into the slots in the case.
6. Tighten the two #6-19 x 1.5 in. screws with a Phillips
screwdriver until the device is flush to the panel (3 to 4 inlbs torque).
7. Reinstall the terminal connectors to their original locations.
(Or first connect field wiring as indicated in this guide and
then reinstall the connectors).
44.96 to 45.47 mm
(1.77 to 1.79 in.)
44.96 to 45.47 mm
(1.77 to 1.79 in.)
Figure 1
NOTE: Mounting requires access to
the back of the panel.
Figure 2
Figure 3
2 - CONNECT THE SENSOR INPUT
Connect your sensor as
indicated in the diagram for
your sensor input. Figure
4 is an example illustrating
the connection shown for a
Thermocouple.
Thermocouple
–
S1
+
R1
Process Voltage or Current
Voltage: 0 to 50 mV or 0 to 10V@ 20kΩ
Current: 0 to 20 mA @ 100Ω
T1
–
S1
+
R1
volts
+
–
T1
S1
R1
amperes
Figure 4: Thermocouple Wiring Example
Platinum 100Ω or 1000Ω RTD
20Ω max. round trip lead resistance
T1
S3
S1
S1
R1
2-wire
S2
S3
S1
T1
S1
R1
3-wire
3 - WIRE OUTPUT 1
Refer to the wiring diagram for your configuration
code and connect to the slots indicated.
PM6_ _ C _ - _ _ _ _ _ _ _: Switched DC or Open Collector
Internal Circuit
Common
–
24V(dc)
+
X1
W
Y1
1
+
Switched DC
Load
–
Open Collector
–
Power Supply
–
Load
+
+
PM6_ _ E _ - _ _ _ _ _ _ _: 5A Form C Relay
Internal Circuit
Normally
Open
5A @240 V(ac) or 30 V (dc)
Load
PM6_ _ F _ - _ _ _ _ _ _ _: Universal Process
L1
K1
J1
Normally
Closed
Common
AC
Load
Internal Circuit
–
0 to 10 V
4 to 20mA
+
+
F1
G1
H1
Voltage Load Current Loador
Load
Figure 5: Switched DC Output Wiring
0 to 20 mA: 800 Ω max. load
0 to 10V: 1kΩ min. load
Load
4 - WIRE OUTPUT 2
PM6_ _ _ J - _ _ _ _ _ _ _: 5A Form A Relay
Normally Open
L2
Load
K2
–
+
Normally Open
L2
Common
W
2
Y2
Load
Internal Circuit
PM6_ _ _ C - _ _ _ _ _ _ _: Switched DC
Common
24V(dc)
Internal Circuit
PM6_ _ _ H - _ _ _ _ _ _ _: No-Arc Relay
K2
Internal Circuit
Common
AC
Load
AC
5 - CONNECT POWER
6 - SET UP THE SENSOR INPUT
7 - SET UP OUTPUTS
Repeat for all outputs
Connect the power source for your
configuration code:
PM6 _ [1,2,3,4] _ _ - _ _ _ _ _ _ _
1 or 2:120-240 V (ac)
3 or 4: 24 V (ac or dc)
CAUTION
Do not connect high voltage to a controller that
requires low voltage.
8 - SET UP ALARM TYPES / SIDES
A
larm Types
process: alarm set points
are set directly
deviation: alarm set points
are relative to the control
loop’s set point.
Off: no alarm occurs
Alarm Sides
high: alarm when process
is above high alarm set
point.
low: alarm when process
is below low alarm set
point.
both: high and low alarms
are active.
Alarm sides allow you to
set a high alarm, a low
alarm, or both.
Alarm Type
1. From Home, tap the forward arrow to go to
Operations, then scroll to and select Setup.
2. Scroll to and select Alarm.
3. Scroll to and select Alarm 1, 2, 3, or 4.
4. Scroll to and select Alarm Type.
5. Scroll to and select the type: process,
deviation, or off
Alarm Sides
6. Use the back arrow to return to Alarm 1, 2, 3,
or 4.
7. Scroll to and select Alarm Sides.
8. Scroll to and select the desired sides option:
high, low, or both.
9. Use the back arrow to return to the Alarm list.
10. Scroll to the Alarm High Set Point or Alarm
Low Set Point, as necessary for your sides
selection.
Sensor Types
thermocouple
millivolts
volts
milliamp
100Ω RTD
1000Ω RTD
potentiometer
analog input off
Repeat for remaining alarms
1. From Home, tap the forward arrow to go to Operations.
2. Scroll to Setup using the +/- keys then press forward arrow
3. Scroll to and select Analog Input.
4. Scroll to and select Sensor Type.
5. Scroll to and select your sensor type.
6. If you select Thermocouple, a TC Linearization list
7. If you select 100Ω or 1000Ω RTD, press back arrow to
to select it.
opens. Use the +/- keys to find the correct type: J, K, N,
R, S, or T.
return to Sensor Type, scroll to and select RTD Leads,
then select 2 or 3, as needed for your sensor.
9 - CONTROL LOOP MODE, SET POINT, AUTOTUNE
NOTES: By default
the control loop Heat
algorithim is enabled
for PID control and the
Cool algorithim is OFF.
To enable, go to Control
Loop.
CAUTION: Autotune
turns on the loop’s heat
output until the process
value exceeds 90% of the
set point, then turns the
output off and repeats
this. When finished the
loop controls at the set
point. Before starting
Autotune, consider if it is
safe to do so.
The system must
be operational for
autotuning to select PID
settings.
Output Functions
heat control
cool control
event a
event b
alarm
output off
Control Mode
1. From Home, tap the forward arrow to go to
Operations.
2. Scroll to and select Setup.
3. Scroll to and select Control Loop.
4. Scroll to and select Control Mode.
5. Select Off, Auto, or Manual.
Auto: loop adjusts output so process matches set point.
Manual: user sets control loop output in percent power.
Off: no control loop output
Control Loop Set Point
1. Press the Home button to return to the
Home screen.
2. Use the numeric slider or the +/-keys to
choose the set point.
Autotune
1. From Setup, scroll to and select Control
Loop.
2. Scroll to and select AutoTune.
3. Select Yes.
1. From Home, tap the forward arrow to go to Operations.
2. Scroll to and select Setup.
3. Scroll to and select the Output list.
4. Scroll to Output 1 and press forward arrow to select it.
5. Scroll and select Output Function.
6. Scroll up or down the list to select the output function, then use
the back arrow to return to the Output list and select the settings
for that Output function:
• For alarm outputs, select Output Function Instance, then select
Alarm Instance 1 - 4.
• For heat or cool outputs, set the Time Base.
• For a Fixed Time Base, select Output Time Base and use
the numeric slider to set the time base cycle.
• If you have a Switched DC or Open Collector and prefer a
Variable Time Base, select Output Low Power Scale and set
it with the numeric slider. Use the back arrow to return to Output,
select Output High Power Scale, and set it with the numeric slider.
Please reference the electronic User Guide for Third Party
Software Licensing statements.