MicroDIN User’s Manual & Quick Start Guide
CE Compliance
Purpose
To meet Mark CE requirements, this addendum provides supplemental information to the
MicroDIN User’s Manual (W0UD-XUMN Rev A), and the
MicroDIN Quick Start Guide (W0UD-XQRN Rev A).
Power Supply Rating
MicroDIN CE Mark compliance requires an IEC 742 rated power supply. This applies to
the following power supply references:
User’s Manual: p. 3.2, 3.7 (fig. 3.7e), 3.10 (fig. 3.10), 3.11 (fig. 3.11) and A.14
Quick Start Guide: p. 13 (fig. 3.4e), 16, 17 and 22
Figure 3.7e—
Power Wiring
NOTE: An IEC
742 rated power
supply is
required for CE
compliance.
External DC Output Fusing
Also, a customer supplied 1A fuse is required for external dc output connection to meet CE
compliance. This applies to the following external dc output references:
User’s Manual: p. 3.7 (fig. 3.7b)
Quick Start Guide: p. 13 (fig. 13b)
Figures 3.7b
and 13b—
Control Output,
Open Collector
with External
Power Supply
External DC Output Derating
For MicroDIN CE Mark compliance, external load switching (maximum) for an open
collector is derated from 60V @ 1A to 42V @ 1A. This applies to the following output rating
W0UD-XADN Rev AWatlow MicroDIN CE Addendum 1
April 1997
references:
User’s Manual: p. 3.7 (fig. 3.7b) and A.14
Quick Start Guide: p. 13 (fig. 13b) and 22
(1044)
CE Addendum
Declaration of Conformity
WATLOW CONTROLS
1241 Bundy Boulevard
Series MicroDIN
97
Winona, Minnesota 55987 USA
Declares that the following product:
Designation:Series MicroDIN
Model Number(s):UD 1 A -1CES - (Any four numbers or letters)
Classification:Control, Installation Category II, Polution Degree II
Rated Voltage:24 to 28V‡ (ac/dc)
Rated Frequency:50/60 Hz
Rated Power Consumption: 5VA maximum
Meets the essential requirements of the following European Union Directive(s)
using the relevant section(s) of the normalized standards and related documents
shown:
EN 50082-2:1995 EMC Generic immunity standard, Part 2: Industrial
EN 61000-4-2: 1995 Electrostatic discharge
EN 61000-4-4: 1995 Electical fast transients
ENV 50140:1994 Radiated immunity
ENV 50141:1994 Conducted immunity
ENV 50204:1995 Cellular phone
EN 50081-2:1994 EMC Generic emission standard, Part 2: Industrial
EN 55011:1991 Limits and methods of measurement of radio disturbance
environment
environment
characteristics of industrial, scientific and medical radiofrequency equipment (Class A)
73/23/EEC Low-Voltage Directive
EN 61010-1:1993 Safety requirements for electrical equipment for
Déclare que le produit suivant :
Désignation :Série MicroDIN
Numéro(s) de modèle(s) :UD 1 A - 1CES - (quatre chiffres ou lettres
Classification :Commande, installation catégorie II, degré de
Tension nominale :24 à 28 V ‡ (c.a./c.c.)
Fréquence nominale :50/60 Hz
Consommation
d’alimentation nominale :5 VA maximum
Conforme aux exigences de la (ou des) directive(s) suivante(s) de l’Union
Européenne figurant aux sections correspondantes des normes et documents
associés ci-dessous :
measurement, control, and laboratory use, Part 1:
General requirements
quelconques)
pollution II
89/336/EEC Directive de compatibilité électromagnétique
EN 50082-2 :1995 Norme générique d’insensibilité électromagnétique,
EN 61000-4-2 : 1995 Décharge électrostatique
EN 61000-4-4 : 1995 Courants électriques transitoires rapides
ENV 50140 :1994 Insensibilité à l’énergie rayonnée
ENV 50141 :1994 Insensibilité à l’énergie par conduction
ENV 50204 :1995 Téléphone cellulaire
EN 50081-2 :1994 Norme générique sur les émissions
EN 55011 :1991 Limites et méthodes de mesure des caractéristiques
Partie 2 : Environnement industriel
électromagnétiques, Partie 2 : Environnement
industriel
d’interférences du matériel radiofréquence industriel,
scientifique et médical (Classe A)
73/23/EEC Directive liée aux basses tensions
EN 61010-1 :1993 Exigences de sécurité pour le matériel électrique
de mesure, de commande et de laboratoire, Partie 1 :
Exigences générales
English
Français
Erklärt, daß das folgende Produkt:
Beschreibung:Serie MicroDIN
Modellnummer(n):UD 1 A - 1 CES - (4 beliebige Zahlen oder
Buchstaben)
Klassifikation:Regelsystem, Installationskategorie II,
Emissionsgrad II
Nennspannung:24 bis 28 V‡ (ac/dc)
Nennfrequenz:50/60 Hz
Nominaler Stromverbrauch: Max. 5 VA
Erfüllt die wichtigsten Normen der folgenden Anweisung(en) der Europäischen
Union unter Verwendung des wichtigsten Abschnitts bzw. der wichtigsten
Abschnitte der normalisierten Spezifikationen und der untenstehenden
einschlägigen Dokumente:
Deutsch
89/336/EEC EWG Elektromagnetische Verträglichkeit
EN 50082-2:1995 EMC-Rahmennorm für Störsicherheit, Teil 2:
EN 61000-4-2: 1995 Elektrostatische Entladung
EN 61000-4-4: 1995 Elektrische schnelle Stöße
ENV 50140:1994 Strahlungsimmunität
ENV 50141:1994 Leitungsimmunität
ENV 50204:1995 Mobiltelefon
EN 50081-2:1994 EMC-Rahmennorm für Emissionen, Teil 2: Industrielle
EN 55011:1991 Beschränkungen und Methoden der Messung von
Industrielle Umwelt
Umwelt
Funkstörungsmerkmalen industrieller, wissenschaftlicher
und medizinischer Hochfrequenzgeräte (Klasse A)
72/23/EEC EWG Niederspannungsrichtlinie
EN 61010-1:1993 Sicherheitsrichtlinien für Elektrogeräte zur Messung,
Declara que el producto siguiente:
Designación:Serie MicroDIN
Números de modelo:UD 1 A - 1CES - (Cualquier combinación de cuatro
Clasificación:Control, categoría de instalación II, grado de
Tensión nominal:24 a 28V ‡ (Vca/Vcc)
Frecuencia nominal:50/60 Hz
Consumo nominal
de energía:5 VA máximo
Cumple con los requisitos esenciales de las siguientes directivas de la Unión
Europea, usando las secciones pertinentes de las reglas normalizadas y los
documentos relacionados que se muestran:
zur Steuerung und im Labor, Teil 1: Allgemeine
Richtlinien
Español
números y letras)
contaminación ambiental II
89/336/EEC Directiva de compatibilidad electromagnética
EN 50082-2: 1995 Norma de inmunidad genérica del EMC, parte 2: Ambiente
EN 50081-2:1994 Norma de emisión genérica del EMC, parte 2: Ambiente
EN 55011:1991 Límites y métodos de medición de características de
industrial
industrial
perturbaciones de radio correspondientes a equipos de
radiofrecuencia industriales, científicos y médicos (Clase A)
73/23/EEC Directiva de baja tensión
EN 61010-1:1993 Requerimientos de seguridad para equipos eléctricos
Erwin D. LowellWinona, Minnesota, USA
Name of Authorized RepresentativePlace of Issue
General ManagerFebruary 1, 1997
Title of Authorized RepresentativeDate of Issue
________________________________________
Signature of Authorized Representative
de medición, control y uso en laboratorios, Parte 1:
Requerimientos generales
W0UD-XCEM-0000 Rev A01
(1043)
Meet the MicroDIN Team
We stand behind our product and are committed to your total satisfaction.
Pictured below are some of the people at Watlow who have worked hard to
bring you one of the finest industrial temperature controllers available today.
Included in the photo are members of the development team, production team,
and representatives from our core manufacturing and customer service areas.
TOTAL
CUSTOMER
SA TISFACTION
3 Y ear W arranty
ii Watlow MicroDIN
Front Row: Rob Hermann, board assembly; Gene Lauer, product manager; Keith Ness, engineering team leader;
Steve Lubahn, group leader; Doug Wolfe, technician; Mark Hoven, engineer. 2nd Row, Sitting behind Front Row:
Sally Kotschevar, purchasing; Lisa Voelker, technician; Carolyn Konkel, wave inspection; Mollee Smith, PACE line;
John Pham, product development engineer; Randy Haack, application engineer. Standing: Barb Lowenhagen; Dave
Zill, board assembly; Erin Benson, technician; Kathy Holzworth, production test; John Gabbert, technical documentation; Tonya Adank, surface mount; Stan Breitlow, engineering; Shirley Brown, final assembly; Jason Beyer, application engineer; Rose Johnson, final assembly; Jamil Al-Titi, R & D; Brian Dulek, wave; Jim Brickner, Winona management; Steve Griffiths, manufacturing engineer; Mary White, customer service planner; Dan Johnson, agency coordinator; Les Stellpflug, R & D.
About Watlow Controls
Watlow Controls is a division of Watlow Electric Mfg. Co., St. Louis, Missouri,
a manufacturer of industrial electric heating products, since 1922. Watlow
begins with a full set of specifications and completes an industrial product that
is manufactured totally in-house, in the U.S.A. Watlow products include electric heaters, sensors, controls and switching devices. The Winona operation has
been designing solid state electronic control devices since 1962, and has earned
the reputation as an excellent supplier to original equipment manufacturers.
These OEMs depend upon Watlow Controls to provide compatibly engineered
controls which they can incorporate into their products with confidence.
Watlow Controls resides in a 100,000 square foot marketing, engineering and
manufacturing facility in Winona, Minnesota.
NOTE:
Details of a “Note”
appear here in the
narrow margin on
the outside of each
page.
ç
CAUTION:
Details of a
“Caution” appear
here in the narrow
margin on the outside of each page.
Safety Information
We use note, caution and warning symbols throughout this book to draw your
attention to important operational and safety information.
A bold text “NOTE” marks a short message in the margin to alert you to an
important detail.
A bold text “CAUTION” safety alert appears with information that is important for protecting your equipment and performance. Be especially careful to
read and follow all cautions that apply to your application.
A bold text “WARNING” safety alert appears with information that is important for protecting you, others and equipment from damage. Pay very close
attention to all warnings that apply to your application.
Ó
WARNING:
Details of a
“Warning” appear
here in the narrow
margin on the outside of each page.
The safety alert symbol, ç, (an exclamation point in a triangle) precedes a
general CAUTION or WARNING statement.
The electrical hazard symbol, Ó, (a lightning bolt in a triangle) precedes an
electric shock hazard CAUTION or WARNING safety statement.
Technical Assistance
If you encounter a problem with your Watlow controller, see the Troubleshooting Table on page 6.5 first, review all of your configuration information to
verify that your selections are consistent with your application: inputs; outputs; alarms; limits; etc. If the problem persists after checking the above, you
can get technical assistance from your local Watlow representative, or by dialing (507) 454-5300.
An applications engineer will discuss your application with you.
Please have the following information available when calling:
• Complete model number• All configuration information
The Watlow MicroDIN controller is a DIN rail-mounted, temperature controller.
It uses one input and two outputs, network connections and dozens of
parameters to satisfy a broad variety of control needs.
The single input can use either a thermocouple or RTD sensor. The single
control output provides an open collector or switched dc output signal for a
power switching device with a DC input. The single alarm output is an
electromechanical relay. The network connections allow as many as 32
controllers to be configured and monitored from a single personal computer.
You can configure, operate and monitor the MicroDIN almost entirely from a
PLC or personal computer via a serial connection using RJ-11 jacks. Indicator
lights on the face of the controller monitor error states, power, communications
activity and output activity.
Communications Input and Output
to and from Personal Computer
Figure 1.2 - MicroDIN
inputs and outputs in a
thermal system
1-32 devices/
EIA-485 Network
Per Unit:
• Sensor Input from the process
• Control Output to the process
• Alarm Output about the process
MicroDIN
MicroDIN
MicroDIN
Temperature Controller
Temperature Controller
Power
Comms
Control
Output
Alarm
Input
Error
Address
1 2 3 4
MicroDIN
Temperature Controller
Temperature Controller
Power
Comms
Control
Output
Alarm
Input
Error
Address
MicroDIN
MicroDIN
Temperature Controller
Temperature Controller
Power
Comms
Control
Output
Alarm
Input
Error
Address
MicroDIN
MicroDIN
Temperature Controller
Temperature Controller
Power
Comms
Control
Output
Alarm
Input
Error
Address
1.2 Watlow MicroDIN1.2 Watlow MicroDIN
Setup Steps
Address
Power
Comms
Alarm
Temperature Controller
MicroDIN
Temperature Controller
MicroDIN
Control
Output
Input
Error
Indicator Lights
Figure 1.3 - MicroDIN
indicator lights
1. Set up communications.
2. Set the controller’s address and baud speed with the DIP switches on the top
panel (see Chapter 2, Communications Setup). The controller uses eight data
bits with no parity.
3. Mount the controller (see Chapter 3, Wiring).
4. Wire the controller (see Chapter 3, Wiring).
5. Communicate with MicroDIN via an EIA-485 network with Modbus
RTU
protocol.
Power
Green light stays
lit when the power is on
and the controller is ok.
• If it isn’t on or pulsates,
check your power source.
Control Output
Green light is lit or flashes
when the control output is
energized.
• If it does not light up, the
output is not turning on.
Alarm
Red Light is lit during an
input alarm condition.
If it is lit:
• Correct alarm condition
Communications
Green Light
controller sends or receives
valid data over its network port.
• If it does not light up, check
the controller address and the
communications setup.
Input Error
Red Light is lit if there is a
sensor problem. If it is lit:
• Verify the sensor wiring,
polarity and function.
• Rewire or replace as
necessary.
Address Field
Record the unit’s address in
erasable marker here.
The MicroDIN uses the EIA-485 (formerly, ÒRS-485Ó) hardware interface to
communicate with three wires in a half-duplex configuration, up to 32 remote
devices with a master unit on a network up to 4,000 feet long using 14-26 gauge
wire.
Modbus Protocol
The MicroDIN uses ModbusªRTU protocol to read and write to registers that
can be viewed or changed from a personal computer. Each MicroDIN
ÔparameterÕ has a corresponding Modbusªregister and access privileges. The
MicroDIN parameter register numbers and the order of priority appear later in
this chapter. Chapter 5 details all the MicroDIN parameters, and the Appendix
provides information on how to write custom Modbusªapplications
Set Address/Baud Rate
You must configure the communications speed and network address of the
MicroDIN controller with the eight-bit DIP switch on the top of the unit. Set the
controller address with the first six switches and the network speed (9,600 or
19,200 baud) with the eighth switch. Turn to the DIP switch page later in this
chapter.
Serial Data Format
The MicroDIN uses the an 8-N-1 data format; 8 data bits, no parity, 1 stop bit,
and 1 start bit. See the data format table later in this chapter.
Wiring Tasks
In addition to wiring the controllerÕs input, outputs and power connections, you
must also wire the EIA-232-to-EIA-485 converter; connect your computer to the
MicroDIN, and connect the MicroDIN communications daisy chain. See
ÒCommunications WiringÓ in Chapter 3 for full detail.
Communications Software
Watlow offers a Windows application for MicroDIN, called, ÒWatLink,Ó which
will both set up and run multiple MicroDINs over an EIA-485 network using the
Modbusªprotocol. Turn to a screen sample at the end of this chapter.
You may also write your own application (see Appendix for more detail), or
purchase any of several available Modbusª-capable control software packages.
2.2 Watlow MicroDIN
EIA-485 Network
The MicroDIN EIA-485 (RS-485) Network Characteristics
An EIA-485 interface uses three wires in a half-duplex configuration.
The EIA-485 standard specifies a T+/R+ line; a T-/R- line; and a common line.
EIA-485 interprets a -5 volt signal <None> as a 1, a +5-volt signal as a 0. Up to
32 remote devices can be connected to a master on a multi-drop network up to
4,000 feet long.
For industrial networks, EIA-485 offers low impedance, a multiple-device
capability, strong noise immunity and the long distance capability.
PC Connection via 232/485 Converter
Watlow recommends connecting the MicroDIN to your personal computers with
an EIA-232 (RS-232) to EIA-485 (RS-485) converter.
The 232-to-485 converters are proven reliable, low cost, and readily available.
We recommend these suppliers:
•B & B Electronics Manufacturing Company
707 Dayton Road, PO Box 1040, Ottawa, IL 61350
Tel: (815) 433-5100; Fax: (815) 434-7094; Web: http://www.bb-elec.com
Request part number: 485OIC with a power supply and the correct 25-pin
gender connector for your computer.
•CMC (Connecticut microComputer, Inc.)
P.O. Box 186, Brookfield, CT 06804
Tel: (800) 426-2872, (203) 740-9890; Fax: (203) 775-4595
Request part number: ADA485L with the correct 25-pin gender connector
for your computer.
Setup
Communications
See Chapter 3
for wiring details.
Watlow MicroDIN 2.3
Special Case 485 Network Considerations
If your EIA-485 network does not work, it may require termination resistors.
Communication
Setup
çCAUTION:
Apply termination and
pull-up/pull-down
resistors only if
necessary to establish
data communications.
Adding this resistance to
a network where it is not
required could result in
loss of communications
and damage to process
product.
Termination Resistor at the Last MicroDIN
In some cases long distance networks may require termination resistors. If the
continuity checks good and you still cannot get valid responses, add termination.
You can make a terminator by placing a 120½ resistor across the C and D
terminals of a standard RJ-11 phone plug. Plug the terminator into the open
socket in the furthest MicroDIN from the computer.
See Chapter 3, ÒInstallation and Wiring,Ó for a wiring diagram.
Termination and Pull-Up/Pull-Down Resistors at the Converter
If you use a terminator, you should also add pull-up and pull-down resistors to
the EIA-485 converter box.
Place a 120-ohm resistor across the transmit/receive terminals (C and D) of the
converter box.
Add 1K½ pull-up and pull-down resistors as shown in Chapter 3 to maintain the
correct voltage during the idle state.
See Chapter 3 for wiring diagram.
2.4 Watlow MicroDIN
MicroDIN, A Modbus™Remote Terminal Unit (RTU)
RTU
The MicroDIN uses Modbus™RTU (remote terminal unit) protocol to read and
write to registers that can be viewed or changed from a personal computer.
Sending ASCII text commands to the MicroDIN will not work.
Access Via Registers
MicroDIN Supports...
çCAUTION:
Avoid writing
continuously to
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.
See Disable Nonvolatile Memory
(System Group),
Ch. 5.
Each MicroDIN parameter has a corresponding Modbus™register and access
privileges. The value of each parameter is stored in a Modbus™register. The
access privilege — read only, write only or read/write — determines whether you
can change and/or view a parameter’s value. Chapter 5 explains some of the
interactions between parameters. The tables at the end of this chapter show the
parameters and their setup order.
Multiple Register Reads
MicroDIN supports Modbus™Commands 03 and 04 read of a 1- to 32-register
block. Responses from -1999 to 9999 are valid data for up to 32 register writes.
Modbus™32000 Errors
A Modbus™read command response of -32000 indicates that a register is not
implemented; -32001, register not active; or -32002, not read accessible.
Single Register Writes
MicroDIN supports a Modbus™write command (06) to a single register.
Multiple Register Writes
MicroDIN supports a Modbus™write command (16) for multiple writes as long
as the data length is 1.
Writing to address 0 broadcasts to all devices on the network.
MicroDIN supports a Modbus™write command 08, “loop back” to echo a
message.
Setup
Communications
Compatible Software
You will need compatible software to interact with a MicroDIN controller. One
such program is included with the MicroDIN Startup Kit. If you are accustomed
to using a Modbus™, see the Appendix for information to help write your own
Modbus™software application.
Watlow MicroDIN 2.5
Modbus Register Numbers
Address
Absolute Relative Parameters
400010Model Number (Diagnostics)
Communication
400021Serial Number (Characteristics)
Setup
400032Serial Number 2 (Characteristics)
400043Software ID number (Characteristics)
400054Software Revision (Characteristics)
400065Date of Manufacture (Characteristics)
400076Ship Date (Characteristics )
4001716Control Output Hardware (Control Output)
4001817Alarm Output Hardware (Alarm)
4002524Disable Non-volatile Memory (System)
40101100Input Actual (Input)
40102101Input Error (Input)
40104103Output Power (Control Output)
40107106Alarm Condition (Alarm Output)
40201200Operation Mode (Operation)
40205204PID Output Power (PID)
40206205Proportional Term (PID)
40207206Integral Term (PID)
40208207Derivative Term (PID)
40210209System Error (Error)
40211210Open Loop Error (Error)
40301300Set Point (Operation)
40302301User Operation Mode (Operation)
40305304Auto-tune Set Point (PID)
40306305Initiate Auto-tune (PID)
40311310Manual Output Power (Operation)
40312311Clear Error (Error)
40322321Alarm Low (Alarm Output)
40323322Alarm High (Alarm Output)
40332331Clear Alarm (Alarm Output)
40333332Silence Alarm (Alarm Output)
40501500Proportional Band (PID)
40502501Integral (PID)
40503502Reset (PID)
40504503Derivative (PID)
40505504Rate (PID)
40507506Cycle Time (PID)
40508507Control Output Hysteresis (PID)
40601600Sensor Type (Input)
Address
Absolute Relative Parameters
40602601Input Type (Input)
40603602Range Low (Input)
40604603Range High (Input)
40605604Filter Time Constant (Input)
40606605Calibration Offset (Input)
40607606Decimal Point (System)
40608607Error Clearing Mode (Error)
40701700Control Output Function (Control Output)
40714713Power Limit Set Point (Control Output)
40715714High Side Power (Control Output)
40716715Low Side Power (Control Output)
40718717Alarm Output Function (Alarm Output)
40720719Alarm Type (Alarm Output)
40721720Alarm Hysteresis (Alarm Output)
40722721Alarm Latching Mode (Alarm Output)
40723722Alarm Silencing Mode (Alarm Output)
40724723Alarm Active Sides (Alarm Output)
40725724Alarm Logic (Alarm Output)
40901900Units Type (System)
40902901C or F (System)
40903902Input Error Action (Input)
40904903Fixed Manual Output (Control Output)
40905904Activate Open Loop Detect (Error)
415011500Ambient (CJC) Temperature (System)
415021501Ambient (CJC) A-to-D Counts (Diagnostics)
415031502RTD Lead Compens. A-to-D Counts (Diag)
415041503RTD Lead Resistance (Diagnostics)
415051504Input A-to-D Counts (Diagnostics)
415131512Enter Diagnostics Mode (Diagnostics)
415141513Test Displays (Diagnostics)
415151514Test Outputs (Diagnostics)
416011600Enter Calibration Mode (Calibration)
416021601Restore to Factory Calibration (Calibration)
416031602Reset Factory Defaults (Calibration)
416041603Calibration Commands (Calibration)
2.6 Watlow MicroDIN
Set Address/Baud Rate
Configure the communications speed and network address of the MicroDIN
controller with the eight-bit DIP switch on the top panel. Set the controller
address with the first six switches. Set an address between 1 and 63. The
network will not work correctly if any two controllers have the same address.
DIP switch 1 sets the left-most binary digit. Switch 6 sets the right-most digit.
Record the MicroDIN’s address in erasable marker on the white space
on the front of the unit.
The seventh switch has no effect.
Set the network speed (9,600 or 19,200 baud) with the eighth switch.
Setup
Communications
Figure 2.7 MicroDIN top view with
DIP switches and baud
settings
This table provides 1) the correct order of entry, 2) the effect of a parameter change, and 3) a place to document settings.
Changing this
Affects this
Communication
Setup
➝
Units Type
C or F
Input Error Action
Control Output Function
Set Fixed Manual OutputO
Open Loop Detect
Sensor Type
Input TypeO
Range LowCD DC
Range HighCD DC
Decimal PointD D
Calibration OffsetCD DC
Filter Time ConstantD D
Error Clearing Mode
Power Limit Set PointCD DC
High Side PowerO
Low Side PowerO
Alarm Output Function
Alarm TypeD D
Alarm HysteresisCD DC
Alarm Latching Mode
Alarm Silencing Mode
Alarm Active Sides
Alarm Logic
Alarm HighCD DOC
Alarm LowCD DOC
PropbandCD DC
IntegralO
ResetO
Derivative
Rate
Cycle Time
Output HysteresisCD DC
Operation Mode
Set Point
Manual Output PowerOO OO
Set PointCD D O OC
Table 2.8 - Parameters Setup order.
Watlow MicroDIN 2.8
➝
ç
CAUTION:
Parameters
should be set
up in this order.
➝
C or F
Units Type
Control Output Function
Input Type
Sensor Type
Low Side Power
High Side Power
Range High
Range Low
Decimal
Operation Mode
Alarm Type
Note: This table also appears
inside the back cover, p. A.19
Key:
D = Changing will change the default
C = Changing will convert the
temperature scale
O = Other effect (see Ch. 5
(See Parameter Index, p. A.18
)
, for detail)
Document your settings below
Serial Data Format
Configure your computer’s COM1 or COM2 (communications) port data format
to match the MicroDIN’s settings in the table below.
Table 2.9a Serial Data Format
MicroDIN Installation Wiring Tasks
Communications Software
WatLink
Figure 2.9b WatLink for MicroDIN
sample software screen
Data BitsParityStop BitStart Bit
8None 11
MicroDIN requires these wiring tasks for a successful installation
1. Wire MicroDIN sensor input.
2. Wire MicroDIN Output 1, the control output.
3. Wire MicroDIN Output 2, the alarm output.
4. Wire MicroDIN power.
5. Connect the MicroDIN communications daisy chain.
6. Wire the 232-to-485 converter; connect to the computer.
7. If necessary, wire the termination and pull-up/pull-down resistors.
Watlow offers a Modbus
package in WatLink,
software that will set up
and run multiple
MicroDINs over an EIA485 network. WatLink,
a Windows 3.31 or
Windows 95 application,
is available from any
Watlow sales representative or authorized
distributor. WatLink can
handle up to 32 different
MicroDIN units.
™
Setup
Communications
Other Software
To communicate with
MicroDIN, you must use a Modbus™RTU (remote terminal unit) compatible
software package. Sending ASCII commands via a standard serial
communication application will not work. Refer to the Appendix if you’re writing
your own Modbus™RTU application.
Watlow MicroDIN 2.9
Notes
Communication
Setup
2.10 Watlow MicroDIN
3
Installation and Wiring ■
Chapter Three:
Installation and Wiring
Introduction
Set DIPs First ......................................3.2
Mount on DIN Rail Tabs...................... 3.2
Wire Unit I/O .......................................3.2
Wiring Example .................................... 3.10
Wiring Example .................................... 3.11
Install and Wire
Watlow MicroDIN 3.1
Introduction
Set DIP Switch First
For a successful MicroDIN installation you need to cover the tasks cited in the
subheads below. If you do all these things and the MicroDIN doesn’t work, go to
the troubleshooting chart in Chapter 6.
If you haven’t done it already, set the controller’s address and baud speed with
the DIP switches on the top of the unit (see Chapter 2, Communications Setup).
The controller uses eight data bits with no parity, and 1 stop bit.
Install and Wire
Mount on DIN Rail or Tabs
Mount the controller(s) either on an EN 50022 35mm x 7.5mm DIN rail or with
the built-in mounting tabs.
Wire Unit I/O
Wire the MicroDIN’s input, output, communications and power connections
using the diagrams in this chapter.
straight through)
0836-0445-0000 Included, 10-pin removable connector with screw terminals
Not Included:
0219-0217-0000 7-foot communications cable (RJ-11, 4-conductor, straight
through)
0830-0473-0000 Communications converter (EIA-232 to EIA-485)
0830-0474-0000 Power supply (120VÅ (ac) input, 24VÎ (dc) output)
3.2 Watlow MicroDIN
Mounting the MicroDIN
To mount a MicroDIN on a DIN rail, hook the upper lip of the rail mounting
bracket onto the rail and press the controller down until the bottom lip of the
mount snaps onto the rail. To remove, as you push the back of the controller
down lift the front up until the bottom lip unsnaps from the rail.
To mount a MicroDIN on a panel, use the dimensions below to drill screw holes
for the mounting bracket.
Figure 3.3 Mounting a MicroDIN
controller.
Side View
3.750 in
(146 mm)
DIN
rail
bracket for
panel mounting
(#6 screw
or m3.5 required)
4.225 in
(107 mm)
4.650 in
(118 mm)
.318 in
(8 mm)
MicroDIN
MicroDIN
Temperature Controller
Temperature Controller
Power
Comms
Control
Output
Alarm
Input
Error
Address
Top/bottom
mount
hole offset
Front View
Install and Wire
Min. Clearance
between rail
centerlines
5.750 in
(146 mm)
2.875 in
(73 mm)
ç
CAUTION:
Maintain the correct
spacing between rows of
controllers to allow
sufficient air circulation
and installation
clearance. Failure to do
so could result in
damage to equipment.
5.062 in
(129 mm)
Attachment Angle
DIN
rail
10°
Min. Clearance 2 in
(51 mm)
1.637 in
(42 mm)
MicroDIN
MicroDIN
MicroDIN
Temperature Controller
Temperature Controller
Power
Comms
Control
Output
Alarm
Input
Error
Address
MicroDIN
Temperature Controller
Temperature Controller
Power
Comms
Control
Output
Alarm
Input
Error
Address
1.650 in
(42 mm)
Use DIN EN 50022 35mm x 7.5mm Rail
Watlow MicroDIN 3.3
Mounting the MicroDIN on a DIN rail
To Mount MicroDIN
1. Push unit in and down to catch rail hook
on top of rail.
2. Rotate bottom of unit in toward rail.
3. Rail clasp will audibly “snap” into place.
If the MicroDIN does not snap into place,
check to see if the rail is bent.
Install and Wire
①
Figure 3.4a -
Mounting a MicroDIN
controller on a DIN rail.
To Dismount MicroDIN
1. Press down on back of controller until the
bottom hook clears the rail.
2. Then rotate bottom up and away from
rail.
Figure 3.4 b-
Dismounting a MicroDIN
controller from a DIN rail.
➂ "Snap"
➁
➁
①
3.4 Watlow MicroDIN
MicroDIN RJ-11 and 10-pin Connectors
12345678910
12345678910
ABCD
The MicroDIN 10-pin screw terminal connector, on the bottom of the case, links
Ó
WARNING:
To avoid potential
electric shock, use
National Electric Code
(NEC) safety practices
when wiring and
connecting this unit to a
power source and to
electrical sensors or
peripheral devices.
Failure to do so could
result in injury or death.
it to its power supply, control input, control output and alarm output. Use 26- to
14-gauge wire to connect to the plug terminals.
The alarm output is an electromechanical relay.
See the Appendix for information on sensor ranges and specifications. See
Chapter 5
: Parameters for information about software configuration.
communications
sockets 1 and 2
(RJ-11)
Bottom View
Install and Wire
Figure 3.5 - Bottom view
of MicroDIN case with
connector assignments.
ç
WARNING:
Install high or low
temperature limit control
protection in systems
where an over
temperature fault
condition could present a
fire hazard or other
hazard. Failure to install
temperature limit control
protection where a
potential hazard exists
could result in damage to
equipment and property
and injury to personnel.
Front of Unit
10-pin removable connector
Input
1. S1 or thermocouple+
2. S3 or thermocouple-
3. S2
Control Output
4. dc+
5. dc-
6. common (COM)
Alarm Output (electromechanical relay)
7. alarm normally open (NO)
8. alarm common (COM)
Power
9. L2, 24V‡ (ac/dc)-
10. L1, 24V‡ (ac/dc)+
Watlow MicroDIN 3.5
Input Wiring
Figure 3.6a — MicroDIN Isolation Diagram
Power Supply
SafetyIsolationUL/CE
Install and Wire
Logic
and
Input
Alarm
Outputs
Control
Output
Comms
500V
Noise
Isolation
Figure 3.6b — Control Input, Thermocouple
12345678910
+-
Figure 3.6c — Control Input, 2-wire RTD
12345678910
3.6 Watlow MicroDIN
S1 S3
Figure 3.6d — Control Input, 3-wire RTD
12345678910
S1
S2
S3
Output and Power Wiring
NOTE:
The current limit feature
is disabled in this version
of the controller.
Ó
WARNING:
To avoid potential
electric shock, use
National Electric Code
(NEC) safety practices
when wiring and
connecting this unit to a
power source and to
electrical sensors or
peripheral devices.
Failure to do so could
result in injury or death.
Figure 3.7a —
Control Output, Switched DC
with Internal Power Supply
dc+
COM
dc-
12345678910
External
External
Switching
-
Load
Device
+
Figure 3.7b —
Control Output, Open Collector
with External Power Supply
External
External
Switching
Device
Figure 3.7c — Internal Output Circuitry
+24VÎ(dc)
2KΩ
20Ω
Internal Circuitry
4
dc+5dc-6COM
dc+
COM
dc-
12345678910
Power
-
Supply
60V max.
+
1A max.
Load
-
+
Install and Wire
NOTE:
Relay suppression
required only for
inductive loads.
Figure 3.7d — Alarm Output
N.O.
COM
12345678910
Fuse
Relay
Suppression
External
Load
Figure 3.7e — Power Wiring
10123456789
L1
24V‡ (ac/dc)
-+
L2
Watlow MicroDIN 3.7
Communications Wiring
Address
Power
Comms
Alarm
Temperature Controller
MicroDIN
Temperature Controller
MicroDIN
Control
Output
Input
Error
Address
Power
Comms
Alarm
Temperature Controller
MicroDIN
Temperature Controller
MicroDIN
Control
Output
Input
Error
Address
Power
Comms
Alarm
Temperature Controller
MicroDIN
Temperature Controller
MicroDIN
Control
Output
Input
Error
Address
Power
Comms
Alarm
Temperature Controller
MicroDIN
Temperature Controller
MicroDIN
Control
Output
Input
Error
1 2 3 4
Green
RJ-11 to MicroDIN
TD (A)
TD (B)
RD (A)
RD (B)
SIG GND
TD (A)
TD (A)
Yellow
120V~
EIA-232
EIA-485
EIA-485
Power Supply
AD-1210
+
–
CBAD
9ÎVdc (see NOTE)
120VÅ (Vac)
Comms Plug
Red
Yellow
YellowGreen
0219-0217-0000
7 ft. comms cable
EIA232
ADA485L
EIA-485
CBAD
A
B
A
B
G
9VDC
G
DI/ODI/O
Figure 3.8a - MicroDIN
communications daisy
chain via RJ-11
connectors.
NOTE:
If your network doesn’t
function, see Chapter 2
for special
WARNING:
To avoid potential electric
shock, use National
Electric Code (NEC) safety
practices when wiring and
connecting this unit to a
power source and to
electrical sensors or
peripheral devices.
Failure to do so could
result in injury or death.
Figure 3.8c - CMC
Converter to MicroDIN
Wiring
(CMC Connecticut MicroComputer, Inc.
Ph. 800-426-2872)
3.8 Watlow MicroDIN
NOTE:
The CMC converter requires an external power supply when used with a laptop.
Special EIA-485 Network Considerations
+5V
B
A
GND
T+/R+
T-/R-
Com
1KΩ
120Ω
1KΩ
Converter box
termination
with pull-up
and pull-down
resistors.
ABCD
If your MicroDIN network needs termination and pull-up and pull-down
resistors, wire them per the diagrams below. See Chapter 2, “Communications
Setup.”
Figure 3.9 a- Termination
for MicroDIN; RJ-11
phone plug with 120Ω
resistor across C and D
120Ω
Plug terminator into open socket in MicroDIN controller furthest from
computer, the last unit on the network.
RJ-11 Terminals
C (green) and D (yellow)
Install and Wire
Figure 3.9b Termination for
EIA-232/EIA-485
Converter with pull-up
and pull-down resistors.
Watlow MicroDIN 3.9
Wiring Examples
Ó
WARNING:
To avoid potential
electric shock, use
National Electric Code
(NEC) safety practices
Install and Wire
when wiring and
connecting this unit to a
power source and to
electrical sensors or
peripheral devices.
Failure to do so could
result in injury or death.
Figure 3.10 System wiring example,
schematic.
L1
120VÅ (ac)
L2
Earth Ground
Temperature
UD1A-CES-0000
EIA485 to RS232
EIA485
Loop
Watlow
MicroDIN
Controller
21 345678910
Converter
1A
0830-0474-0000
Power Supply
PC
OR
20A
17-8020
ModBus
Converter
Branch
Circuit Fuse
High Limit
Mechanical
Contactor
Semiconductor
Fuse
DA1C-1624-C000
T1
Thermocouples
Coil
DIN-a-mite
Heater
T2
R
1A
L2L1
92A3-1DJ1-DC
High
temp.
5A
light
21 3456789
Limit Control
1110 121314151617
Optional
Normally
Open
Momentary
Switch
ç
WARNING:
Install high or low
temperature limit control
protection in systems
where an over
temperature fault
condition could present a
fire hazard or other
hazard. Failure to install
temperature limit control
protection where a
potential hazard exists
could result in damage to
equipment and property
and injury to personnel.
3.10 Watlow MicroDIN
Ó
WARNING:
To avoid potential
electric shock, use
National Electric Code
(NEC) safety practices
when wiring and
connecting this unit to a
power source and to
electrical sensors or
peripheral devices.
Failure to do so could
result in injury or death.
L1
1
1
3
Loop
EIA485
PC
EIA485
120V~(ac)
0830-0474-0000
Power Supply
++
–
4
5
1
2
3
8
3
4
5
6
7
9
–
6
7
8
9
10
22
MicroDIN
UD1A-1CES-0000
L2
1CR-1
2
1
101011
Semiconductor
Fuse
3
4
11
L1
DIN-a-mite
+
9
DA1C-1624-C000
–
8
2
L2
T2T1
2
Figure 3.11 System wiring example,
ladder diagram.
ç
WARNING:
Install high or low
temperature limit control
protection in systems
where an over
temperature fault
condition could present a
fire hazard or other
hazard. Failure to install
temperature limit control
protection where a
potential hazard exists
could result in damage to
equipment and property
and injury to personnel.
Open Loop Detect ............................ 4.14
Bumpless Transfer ........................... 4.15
Features
Watlow MicroDIN 4.1
The System
Features
Auto-tune
Auto-tuning allows the controller to explore the responsiveness of the system in
order to determine an effective set of parameters for PID control. To do this it
crosses an auto-tune set point five times, then controls at the normal set point
using the new parameters.
Use Auto-tune Set Point (PID Group) to select the temporary set point, as a
percentage of the normal set point, that the controller will tune to. Initiate or
cancel the auto-tune process with Auto-tune (PID Group). The default value is
90%.
Process Set Point
Auto-tune initiated by user
Auto-tune Set Point
(default 90% of process set point)
Auto-tune complete
Figure 4.2 — Auto-tuning
Temperature
Time
4.2 Watlow MicroDIN
Power Limit
A high side power limit and low side power limit set the maximum output power
within two ranges
A low side power limit limits the output to a percentage of the maximum output
power while the process temperature or value is below the power limit set point.
The high side power limit limits the output to a percentage of the maximum output
power while the process temperature or value is above the power limit set point.
The low side power limit can be viewed or changed with Low Side Power Limit
(Control Output Group).
The high side power limit can be viewed or changed with High Side Power Limit
(Control Output Group).
The power limit set point can be viewed or changed with Power Limit Set Point
(Control Output Group).
The actual output power can be viewed with Output Power (Control Output
Power Group).
Set Point
Figure 4.3 — Power Limits
Process
Power Limit Set Point
(between Range Low
Temperature
and Range High)
Process temperature
with no power limit
Range Low
Process Temperature with power limit
Output Power is limited to
Low Side Power Limit
Time
Range High
Output Power switches
to High Side Power Limit
Features
Watlow MicroDIN 4.3
Input
Calibration Offset
Calibration offset allows a device to compensate for an inaccurate sensor, lead
resistance or other factors that affect the input value. Apositive offset increases
the input value, and a negative offset decreases the input value.
The input offset value can be viewed or changed with Calibration Offset (Input
Group).
Temperature Reading
from Sensor
Negative Calibration Offset will
compensate for the difference
between the Sensor Reading and
the Actual Temperature.
Features
Figure 4.4 — Calibration Offset
Temperature
Actual Process Temperature
Time
4.4 Watlow MicroDIN
Filter Time Constant
A time filter smooths an input signal by sampling the input at designated time
intervals. Either the viewed value or both the viewed and control values can be
filtered.
View or change the time filter with Filter Time Constant (Input Group). A
positive value affects only the viewed values. Anegative value affects both the
viewed and control values. The filter is a single pole low pass.
Temperature
Unfiltered Input Signal
Filtered Input Signal
Temperature
Figure 4.5 — Filtered and Unfiltered Input Signals
Time
Features
Time
Watlow MicroDIN 4.5
Sensor Selection
You need to configure a controller to match the input device, which is normally a
thermocouple or RTD. When you select an input device the controller
automatically sets the input linearization to match the sensor. It also sets high
and low limits, which in turn limit the range high and range low values.
Use Sensor Type and Input Type (Input Group) to select the appropriate sensor.
Temperature
High Limit of selected Sensor Range
Range High Range (between High Limit of Sensor and Range Low)
Range High
Set Point Range (must be between Range High and Range Low)
Range Low
Features
Figure 4.6 — Sensor Ranges
Range Low Range (between Low Limit of Sensor and Range High)
Low Limit of selected Sensor Range
Time
Range Low and Range High
The controller constrains the set point to a value between range high and range
low. Range high cannot be set higher than the sensor high limit or lower than
range low. Range low cannot be set lower than the sensor low limit or higher
than range high.
Use Set Point (Operation Group), Range High and Range Low (Input Group) to
select or view values for the corresponding parameters.
4.6 Watlow MicroDIN
Control Methods
On/Off Control
On/off control switches the output either full on or full off, depending on the
input, set point and hysteresis values. The hysteresis value creates a buffer zone
that increases the time interval that the output is off or on. With hysteresis set
to 0 the process value would stay closer to the set point, but the output would
switch on and off more frequently, causing “chattering.”
Set hysteresis with Output Hysteresis (PID Group).
Heating Action switches off when the Process Temperature
rises above the Set Point
Temperature
Process Temperature
Heating Action switches
on at Startup
Cooling Action switches
on at Startup
Cooling Action Switches on when the
Process Temperature rises above the
Set Point
Heating Action switches on when the Process Temperature
drops below the Set Point minus the Hysteresis
Time
Set Point plus the Hysteresis
Hysteresis
Features
Process Temperature
Temperature
Cooling Action Switches off when the Process Temperature
drops below the Set Point
Figure 4.7 — On/Off Control for Heating and Cooling
Hysteresis
Set Point
Time
Watlow MicroDIN 4.7
Proportional Control
Some processes need to maintain a temperature or process value closer to the
set point than on/off control can provide. Proportional control provides closer
control by adjusting the output when the temperature or process value is within
a proportional band. When the value is in the band, the controller adjusts the
output based on how close the process value is to the set point: the closer to set
point the lower the output. This is similar to backing off on the gas pedal of a
car as you approach a stop sign. It keeps the temperature or process value from
swinging as widely as it would with simple on/off control. However, when a
system settles down, the temperature or process value tends to “droop” short of
the set point.
The proportional band can be viewed or changed with Propband (PID Group). To
only view the proportional control value use Proportional Term (PID Group).
Features
Figure 4.8 — Proportional Control
Temperature
Set Point
Overshoot
Proportional Band
Droop
Time
4.8 Watlow MicroDIN
Proportional plus Integral (PI) Control
The droop caused by proportional control can be corrected by adding integral
(reset) control to the system. When the system has settled down the integral
(reset) value is tuned to bring the temperature or process value closer to the set
point. However, this may increase the overshoot that occurs at startup or when
the set point is changed. Used more with fast, high loss loads.
View or change the integral or reset value with Integral or Reset. To only view
the integral control value use Integral Term (PID Group).
Overshoot
Set Point
Proportional Band
Droop Corrected
Temperature
Figure 4.9 — Proportional plus Integral Control
Features
Time
Watlow MicroDIN 4.9
Proportional plus Integral plus Derivative (PID) Control
Use derivative (rate) control to minimize the overshoot in a PI-controlled
system. Derivative (rate) adjusts the output based on the rate of change in the
temperature or process value. Used more with slow, lagging loads.
View or change derivative or rate with Derivative or Rate (PID Group). To only
view the derivative control value use Derivative Term (PID Group).
Reduced Overshoot
Set Point
Proportional Band
Features
Figure 4.10 — PID Control
Temperature
Time
4.10 Watlow MicroDIN
Alarms
An alarm takes some action, usually notifying an operator, when the process
temperature leaves a defined range. Auser can configure how and when an
alarm is triggered and whether it turns off automatically when the alarm
condition is over.
Figure 4.11 — Alarm Settings
Alarm Set Points
High Side Alarm Range
Alarm Hysteresis
Normal Operating Range
Temperature
Alarm Hysteresis
Low Side Alarm Range
Time
The alarm high set point defines the temperature or process value that will
trigger a high side alarm. The alarm high set point must be higher than the
alarm low set point and lower than the high limit of the sensor range.
The alarm low set point defines the temperature or process value that will
trigger a low side alarm. The alarm low set point must be lower than the alarm
high set point and higher than the low limit of the sensor range.
Alarm set points or deviation can be viewed or changed with Alarm High and
Alarm Low (Alarm Output Group).
Alarm High Set Point
Alarm Low Set Point
Features
Alarm Hysteresis
Alarm hysteresis is a zone defined by adding an hysteresis value to the alarm
low set point or subtracting the hysteresis value from the alarm high set point.
Once an alarm has occurred it will not clear until the process value is above the
alarm-low setting or below the alarm-high settings by a margin equal to the
hysteresis. Example: An alarm starts when the process value reaches the alarm
high setting. The alarm will not clear until it is below the high setting by an
amount equal to or greater than the alarm hysteresis.
The alarm hysteresis value can be viewed or changed with Alarm Hysteresis
(Alarm Output Group).
Watlow MicroDIN 4.11
Process or Deviation Alarms
A process alarm uses one or two fixed set points to define an alarm condition.
A deviation alarm uses one or two set points that are defined relative to the
control set point. High and low alarm set points are calculated by adding and/or
subtracting offset values from the control set point. If the set point changes, the
alarm set points automatically change with it.
Alarm Type (Alarm Output Group) allows you to view or change whether the
alarm will function as a process or deviation alarm.
The alarm deviation value can be viewed or changed with Alarm High and
Alarm Low (Alarm Output Group).
Alarm Latching
A latched alarm will remain active after the alarm condition has passed. It can
only be deactivated by the user. An alarm that is not latched will deactivate
automatically when the alarm condition has passed.
Alarm Latching Mode (Alarm Output Group) allows you to view or change
whether an alarm will latch.
The alarm state begins when the temperature
reaches the alarm high set point.
Features
Figure 4.12 — Alarm Latching
Temperature
Temperature
Process
Alarm High
Set Point
Normal Operating Range
The alarm state continues until the
temperature drops to the alarm high
set point minus the hysteresis. A
latching alarm could be turned off by
the operator at this point. A nonlatching alarm would turn off
automatically.
Alarm Low
Set Point
Time
4.12 Watlow MicroDIN
Alarm Silencing
Alarm silencing has two uses:
1. It is often used to allow a system to warm up after it has been started up.
With alarm silencing on, an alarm is not triggered when the process
temperature is initially lower that the alarm low set point. The process
temperature has to enter the normal operating range beyond the hysteresis zone
in order to activate the alarm function.
2. Alarm silencing also allows the operator to disable the alarm output while the
controller is in an alarm state. The process temperature has to enter the normal
operating range beyond the hysteresis zone in order to activate the alarm
function.
Alarm Silencing Mode (Alarm Output Group) allows you to view or change
whether alarm silencing is on.
Temperature
Alarm
enabled
here
Process
Temperature
Alarm High
Set Point
Normal Operating Range
Features
Figure 4.13 — Alarm Silencing
Startup,
Alarm
disabled
Time
Alarm
triggered
here
Alarm Low
Set Point
Watlow MicroDIN 4.13
Errors
Panel Indicator Lights
Figure 4.14 - Error
Information
Features
MicroDIN
MicroDIN
Temperature Controller
Temperature Controller
Power
Comms
Control
Output
Alarm
Input
Error
Address
Error Information — Unison Green/Red Flashing Code
ERROR 4 5 6 7 11 12 13 14 15
Error 4RAM malfunction (return to factory)
Error 5EEPROM data corrupted
Error 6PROM malfunction (return to factory)
Error 7SPI failure, onboard peripheral hardware not responding
Error 11New software installed (cycle power to correct)
Error 12Cal EEROM checksum, calibration data corrupted (recalibrate)
Error 13A-to-D hardware fail, A-to-D hardware not responding
(return to factory)
Error 14EEROM hardware fail, EEPROM peripheral not responding
(return to factory)
Error 15New unit, displays on first power up (return to factory)
Open Loop Detect
4.14 Watlow MicroDIN
Open loop detect can alert the user of trouble on the input or output side of the
control loop. An open loop error is triggered when 100 percent power is applied
at the control output for a period of time equal to the setting of integral (PID
Group), or when reset without the input registering a 5° (F or C) change.
If an open loop error occurs, shut down the system, check the input and control
output wiring and check the input and output devices.
The open loop detect feature can be turned on or off with Activate Open Loop
Detect (Error Group). Use Open Loop Error (Error Group) to check for an open
loop condition.
Bumpless Transfer
When the sensor opens (fails), the MicroDIN switches from automatic to manual
operation.
When transferring from automatic to manual operation, the control output, or
outputs, remain stable — a bumpless, or smooth, transition.
If the Input Error Action parameter is set to 0, bumpless transfer, and the
process has stabilized at a power level less than 75% ( ± 5%) for a two-minute
period prior to the sensor break, then the MicroDIN switches to manual
operation at the last automatic power level. If these conditions are not met, the
output goes to 0% power (output disabled).
If the Input Error Action parameter is set to Fixed Manual Output, the
MicroDIN switches to manual operation at the Fixed Manual Output percent
power value.
Manual operation provides open-loop control of the outputs from a range of
-100% to 100% output. The MicroDIN allows a negative output value only when
Output 1 is set to cool.
Automatic operation provides closed-loop on/off or PID control. When the
operator transfers from a closed loop to an open loop, the MicroDIN sets the
power level to the setting of the Input Error Action parameter. If Input Error
Action is set to 0, bumpless transfer, the controller retains the power level from
the closed-loop control. When the MicroDIN returns to closed-loop control, it
restores the previous set point process value.
Figure 4.15 — Bumpless Transfer
Set Point
Power
Temperature
100%
0%
Actual Temperature
Output Power
Time
≤75% power
2 min.
Features
Tie
Break
Locks in
Output
Power
Watlow MicroDIN 4.15
Notes
Features
4.16 Watlow MicroDIN
5
Chapter Five
Learn the Parameters
System Group ............5.2
Ambient (CJC) Temperature (1500).
Non-volatile Memory (24).............. 5.2
Units Type (900) ............................. 5.3
C or F (901)..................................... 5.3
Units Type ................................................. 5.3
C or F ......................................................... 5.3
Decimal Point ............................................ 5.3
ç
CAUTION:
Avoid writing
continuously to
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.
See Disable Nonvolatile Memory
Parameters
(System Group).
System Group – Monitor
System Error
• See Error Group.
Ambient (CJC) Temperature
• Read the ambient temperature in 0.1 degrees Fahrenheit.
• Read only
• Modbus: 1500
Range
0.0 to 180.0 F
Default
none
Active
always
System Group – Use
Non-volatile Memory
• Disable storage of parameters to non-volatile (EEPROM) memory.
This allows you to change parameters frequently without wearing
out the memory.
• Read/write
• Modbus: 24
Range
0: store parameters when they are changed
1: do not store parameters when they are changed
Default
0 (always reverts to 0 when the controller’s power is turned off
and on)
Active
always
Affects
all parameters
will not save any parameters when set to 1.
CAUTION:
Avoid writing
continuously to
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.
Parameters
See Disable Nonvolatile Memory
(System Group).
Input Group – Monitor
Input Actual
• Monitor the input value.
• During an input error state, this will read 9999 if Read Control
Output (Control Output Group) is set to heat or -1999 if it is set to
cool.
• Read only
• Modbus: 100
Range
input type range
Default
none
Active
always
Input Error
• Monitor the input error status.
• Read only
• Modbus: 101
Range
0: no error
1: analog-to-digital signal under range
2: sensor under range
3: sensor over range
4: analog-to-digital over range
• Set the filter time for the input, in seconds. This smooths out a
rapidly changing input signal. Positive values affect the monitor
readings only. Negative values affect both the monitor readings
and the control values.
• Read/write
• Modbus: 604
Range
-60.0 to 60.0
Default
0.0
Active
always
Input Error Action
• Select how the controller responds to an input error.
• Read/write
• Modbus: 902
Range
0: bumpless transfer (control output power remains constant,
see Chapter 5)
1: switch to the Fixed Manual Output (Control Output Group)
CAUTION:
Avoid writing
continuously to
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.
See Disable Non-
Parameters
volatile Memory
(System Group).
Control Output Group – Monitor
Output Power
• Monitor the control output power level. This can limit PID Output
Power (PID Group).
• Read only
• Modbus: 103
Range
heat: 0.0 to 100.0
cool: -100.0 to 0.0
Default
none
Active
always
Control Output Hardware
• Read the control output hardware type.
• Read only
• Modbus: 16
Range
3: dc
Default
3
Active
always
Control Output Group – Setup
Control Output Function
• Select whether the control output will control for heating or
cooling.
User Set Point ........................................... 5.12
Manual Output Power .............................. 5.12
ç
CAUTION:
Avoid writing
continuously to
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.
See Disable Nonvolatile Memory
(System Group).
Operation Group – Monitor
Operation Mode
• Monitor the operation mode. Normally follows the user selected
mode. It returns to the previous state after an error clears.
• Read only
• Modbus: 200
Range
0: off
1: auto
2: manual control (user selected)
3: manual control (due to error)
Default
auto
Active
always
Operation Group – Use
User Operation Mode
• Select whether the controller is under auto or manual control.
• Read/write
• Modbus: 301
Range
0: auto
1: manual
Default
0: auto
Active
always
Affects
Manual Output Power (Operation Group) manual or manual due
Cycle Time ................................................. 5.15
Control Output Hysteresis ....................... 5.16
PID Group – Monitor
ç
CAUTION:
Avoid writing
continuously to
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.
See Disable Nonvolatile Memory
(System Group).
PID Output Power
• Monitor the calculated PID power level. See Chapter 4 for
information about PID control.
• Read only
• Modbus: 204
Range
heat: 0.0 to 100.0
cool: -100.0 to 0.0
Default
none
Active
always
PID Group – Use
Auto-tune Set Point
• Set the auto-tune set point as a percent of the currently active set
point.
CAUTION:
Avoid writing
continuously to
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.
See Disable Nonvolatile Memory
(System Group).
Alarm Output Group – Monitor
Alarm Condition
• Monitor the alarm state.
• Read only
• Modbus: 106
Range
0: no alarm
1: high alarm
2: low alarm
3: high latched alarm
4: low latched alarm
5: high silenced alarm
6: low silenced alarm
7: high latched silenced alarm
8: low latched silenced alarm
9: waiting for in range alarm
10: disabled alarm
11 error alarm
• Select alarm type. A process alarm responds when the temperature
leaves a fixed range. Adeviation alarm responds when the
temperature deviates from the set point by a set number of
degrees.
• Read/write
• Modbus: 719
Range
0: process alarm
1: deviation alarm
Default
0: process
Active
if Alarm Output Function (Alarm Output Group) is set to alarm
Affects
Alarm Low (Alarm Output Group) changes to sensor low for
process alarms or -1999 for deviation alarm.
Alarm High (Alarm Output Group) changes to sensor high for
process alarms or 9999 for deviation alarm.
Alarm Hysteresis
• Sets the switching hysteresis for the alarm output. This defines a
band on the inside of the alarm set point. When the process
temperature is in this band, the alarm state will not change.
• Read/write
• Modbus: 720
Range
1 to 9999
Default
3
Active
if Alarm Output Function (Alarm Output Group) is set to alarm
Alarm Active Sides
• Select which side or sides the alarm is active on.
if Alarm Output Function (Alarm Output Group) is set to alarm
Alarm Latching Mode
• Turn alarm latching on or off. When latching is active, the alarm
will remain on after the alarm condition ends. It must be turned
off manually.
• Read/write
• Modbus: 721
Range
0: no
1: yes
Default
0: no
Active
if Set Alarm Output Function (Alarm Output Group) is set to
alarm
Alarm Silencing Mode
• Turn alarm silencing on or off. When silencing is active and the
controller is first turned on, the alarm cannot become active until
the process temperature leaves the alarm range. Also, alarms can
be manually silenced after one occurs. Entering the normal
operation range resets the silence.
• Read/write
• Modbus: 722
Range
0: no
1: yes
Default
0: no
Active
if Alarm Output Function (Alarm Output Group) is set to alarm
CAUTION:
Avoid writing
continuously to
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.
See Disable Nonvolatile Memory
(System Group).
Parameters
Error Group continued
Error Group
Monitor
Open Loop Error ........................................ 5.22
Open Loop Detect ...................................... 5.22
• Select how the controller responds to an input error.
• Read/write
• Modbus: 902
Range
0: bumpless transfer (control output power remains constant,
Chapter 4)
1: switch to the Fixed Manual Output (Control Output Group)
setting
2: shut off output
Default
0: bumpless transfer
Active
always
Error Clearing Mode
• Set the error clearing mode. When errors are latched, the error
message or indicator persists until it has been cleared manually.
Otherwise the error message or indicator clears automatically
when the condition that caused it no longer exists.
• Read/write
• Modbus: 607
Range
0: not latched (errors clear automatically)
1: latched (errors must be cleared manually)
CAUTION:
Avoid writing
continuously to
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.
See Disable Nonvolatile Memory
(System Group).
Diagnostics Group continued
Diagnostics Group
Model Number ........................................... 5.27
CAUTION:
Avoid writing
continuously to
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.
See Disable Nonvolatile Memory
(System Group).
Parameters
Calibration Group
Enter Calibration Mode ............................ 5.30
• Enter calibration mode, to calibrate the controller.
• Must be in diagnostics mode to enter calibration mode
• Read/write
• Modbus: 1600
Range
0 to 1414 and 1416 to 9999: exit calibration mode
1415: enter calibration mode
Default
0
Active
if the controller is in diagnostics mode
Calibration Commands
• Measure and store a selected input calibration value.
• Write
• Modbus: 1603
Range
0: no calibration
1: store 0.000mV input
2: store 50.000mV input
3: store CJC input (32°F Type J, compensated)
4: store ground input (S1, S2 and S3 shorted)
5: store RTD lead resistance (S1 and S2 shorted)
6: store 15.00 ohms
7: store 380.00 ohms
10: store 4mA input
• Check switches, fuses, breakers, interlocks, limits, connectors, • See Watlow Publication
etc. for energized condition and proper connection#COR-AG-76, “Putting it
All Together.”
• Measure power upstream for required level•
• Check wire size
• Check for bad connections
• Check and reset unit DIP switches 1-6 to correct address
• Check and reset unit DIP switch 8 to correct baud rate
• Look for a break in the daisy chain
• Verify correct connections and test wiring paths
• Check converter box wiring and its documentation
• Reconfigure computer's COM port setup and verify communications ok
• Check the communication card documentation for setable variables, operational testing
• Restart COMS software, check for settings agreement. Verify COM bus active
• Check sensor connections
• Check sensor connections and sensor wiring
• Change the Sensor Type parameter (Input Group) to match the sensor hardware
• Measure power upstream for required level
• Verify that the temperature surrounding unit is 32° to 149°F (0° to 65°C)
• Check sensor function. The Open Loop Detect parameter (Error Group) indicates it may be broken
• Check the Calibration Offset parameter (Input Group) value; set it to a lower level•
• Send the alarming MicroDIN unit a “clear alarm” signal (Modbus™: 331)•
Note: The condition causing the alarm must also be resolved for the alarm to clear•
• To clear the alarm, correct the alarm condition; check to see if the alarm is latched• See p. 5.18
• Check the alarm sides setting• See p. 5.20
• Check the alarm type setting• See p. 5.19
• Check the alarm logic for compatibility with system peripherals and annunciators• See p. 5.21
• Check the power limit setting• See p. 5.9
• Check the operation mode• See p. 5.18
• Check the alarm output function• See p. 5.19
• Check °F/°C setting• See p. 5.3
• Check the calibration offset value; set it to a lower level• See p. 5.6
See p. 3.7, 3.10, 3.11, A.14
• See p. 2.7
• See p. 2.7
• See p. 3.8
• See p. 3.8
• See p. 3.8
• See COM port information
• See COM baud
• See software document
• See p. 3.5, 3.6, 3.7
• See p. 3.5, 3.6, 3.7
• See p. 5.5
• See p. 3.7, 3.10, 3.11, A.14
• See p. A.14
• See p. 5.22
See p. 5.6
See p. 5.17
See p. 5.18, 5.19
information
Operations
• Return unit to factory• See back cover
• Cycle power to unit• See p. 3.10 - 3.11
• Return unit to factory• See back cover
• Return unit to factory• See back cover
• Cycle power to unit• See p. 3.10 - 3.11
• Recalibrate unit• See p. 6.6
• Return unit to factory• See back cover
• Return unit to factory• See back cover
• Return unit to factory• See back cover
Watlow MicroDIN 6.5
Calibrating MicroDIN
Note: For information on writing Modbus™ RTU
communications software for MicroDIN, see the
Appendix.
To enter the calibration mode, first enter the
diagnostics mode; send value 1789 to register
1512. Once in Diagnostics mode, to enter
calibration mode, send 1415 to register 1600.
To restore factory calibrations settings, send value 1
to register 1601.
Thermocouple Input Procedure
Equipment Required
•Type J reference compensator with reference
junction at 32°F/ 0°C, or type J thermocouple
calibrator set at 32°F / 0°C.
2) Connect the millivolt source to Terminal #1 (+) and
Terminal #2 (-) on the MicroDIN with copper wire.
-+
10123456789
RTD Input Procedure
Equipment Required
• 1KΩ precision decade box with 0.01Ω resolution
• Precision current source, 0-4mA range with
0.01mA resolution
Setup and calibration
1) Connect voltage to terminals #9, #10.
10123456789
24V‡ (ac/dc)
2)
Short terminals 1, 2 and 3 together with less than 0.1Ω.
• Send register 1603 value 4 to store ground input.
3)
Short terminals 1 and 3 together with less than 0.5Ω.
• Send register 1603 value 5 to store RTD lead
resistance.
4) Connect the decade box to terminals #1, #2 and #3
on the MicroDIN. Use 20 to 24 gauge copper wire.
-+
10123456789
10123456789
10123456789
3) Enter 0.000mV from the millivolt source to the
MicroDIN. Allow at least 10 seconds to stabilize.
• Send value 1 to register 1603 to store 0.000mV
input.
4) Enter 50.000mV from the millivolt source to the
MicroDIN. Allow at least 10 seconds to stabilize.
Operations
• Send value 2 to register 1603 to store 50.000mV
input.
5) Disconnect the millivolt source and connect the
reference compensator or T/C calibrator to terminal
#1 (+) and Terminal #2 (-).With Type J t/c wire, if
using a compensator, turn it on and short the input
wires. When using a Type J calibrator, set it to
simulate 32°F / 0°C. Allow 10 seconds for the
control to stabilize.
• Send register 1603 value 3 to store CJC input
(32°F, type J, compensated).
6) Rewire for operation and verify calibration.
6.6 Watlow MicroDIN
S1
H
-+
General Radio Model #1433-T
L
Ω
G
S3
S2
5) Enter 15.00Ω from the decade box to the MicroDIN.
Allow at least 10 seconds to stabilize.
• Send value 6 to register 1603 to store 15.00Ω.
6) Enter 380.00Ω from the decade box to the
MicroDIN. Allow at least 10 seconds to stabilize.
• Send register 1603 value 7 to store 380.00Ω.
7) Disconnect the decade box, and connect the current
source to Terminals #2 (-) and #3 (+).
8)
Enter 4.00mA from the current source to the
MicroDIN. Allow at least 10 seconds to stabilize.
• Send value 10 to register 1603 to store 4mA input.
Ordering Information .............................. A.15
Index ......................................................... A.16
Parameter Index ...................................... A.18
Required Parameter Setup Order ........... A.19
Warranty Information .................. Back Cover
Watlow MicroDIN A.1
Appendix
Modbus Remote Terminal Unit (RTU)
Modbus RTU enables a computer or PLC to read and write directly to registers
containing the controller’s parameters. With it you could read all 141 of the
controller’s parameters with five read commands.
Because of the wide array of choices available for setting up a MicroDIN
controller, only a subset of the prompts contain parameters in a given situation.
This manual explains the interrelations between prompts. AModbus read
command response of -32000 indicates that a register is not implemented;
-32001, register not active; or -32002, not read accessible. Awrite command will
return an exception response of 01 to indicate an illegal function, 02, illegal
register; or 03, illegal data. If you try to write to an inactive prompt the
controller will return an illegal data address message (02).
If you already have a software application that uses Modbus, you can simply
skip to the Temperature/process Controller Prompt Table or the Modbus RTU
Address Table in this chapter for the address information your program will
need. The rest of this section on the Modbus provides information for writing a
software application that uses Modbus.
Writing a Modbus Application
You need to code messages in eight-bit bytes, with no parity bit, one stop bit (8,
n, 1). Negative parameter values must be written in twos complement format.
Parameters are stored in two-byte registers accessed with read and write
commands to a relative address.
Messages are sent in packets that are delimited by a pause at least as long as
the time it takes to send 30 bits. To determine this time in seconds, divide 30 by
your baud rate.
Because changing some parameters automatically changes or defaults other
parameters, use the Complete Parameter Download Sequence table in this
chapter to order write commands.
Using a controller address of 0x00 for a write command broadcasts that
command to all the controllers in the network. This is a powerful feature if all
the controllers on a network use all or most of the same parameters.
Appendix
A.2 Watlow MicroDIN
Packet Syntax
Each message packet begins with a one-byte controller address, from 0x01 to
0xF7. The second byte in the message packet identifies the message command:
read (0x03 or 0x04); write (0x06 or 0x10); or loop back (0x08).
The next n bytes of the message packet contain register addresses and/or data.
The last two bytes in the message packet contain a two-byte Cyclical
Redundancy Checksum (CRC) for error detection.
Packet format: | nn | nn | nn nn…| nn nn |
∆∆∆∆∆∆
address
command
registers and/or data
CRC
Read Multiple Registers Command (0x03 or 0x04)
This command returns from 1 to 32 registers.
Packet sent to controller:| nn | 03 | nn nn | 00nn | nn nn |
∆∆∆∆∆∆∆∆
controller address (one byte)
read command (0x03 or 0x04)
starting register high byte
starting register low byte
number of registers high byte (0x00)
number of registers low byte
CRC low byte
CRC high byte
Packet returned by controller: | nn | 03 | nn | nn nn …nn nn | nn nn|
∆∆ ∆∆∆∆∆∆∆
controller address (one byte)
read command (0x03 or 0x04)
number of bytes (one byte)
first register data low byte
first register data high byte
register n data high byte
register n data low byte
CRC low byte
CRC high byte
Watlow MicroDIN A.3
Appendix
Example: Read register 0 (model number) of the controller at address 1.
Sent:01 03 00 00 00 01 84 0A
Received:01 03 02 03 DC B9 2D
Message:988 (0x03DC).
Example: Read register 1 and 2 (Process 1 and 2 values) of controller at address
This command writes a parameter to a single register. The controller will echo
back the command. An attempt to write to a read-only parameter returns an
illegal data address error (0x02).
Packet sent to controller:| nn | 06 | nnnn | nn nn | nnnn |
∆∆∆∆∆∆∆∆
controller address (one byte)
write to a register command (0x06)
register high byte
register low byte
data high byte
data low byte
CRC low byte
CRC high byte
Appendix
A.4 Watlow MicroDIN
Example: Set register 7 (SPI) to 200 (0x00C8) on controller at address 9.
Sent:09 06 00 07 00 C8 38 D5
Received:09 06 00 07 00 C8 38 D5
Write to Multiple Registers Command (0x10)
This command actually writes a parameter to only a single register. An attempt
to write to a read-only parameter returns an illegal data address error (0x02).
Packet sent to controller: | nn | 10 | nnnn | 00 01 | 02 | nn nn | nn nn |
∆∆∆∆∆∆∆∆∆∆∆
controller address (one byte)
write to multiple registers command (0x10)
starting register high byte
starting register low byte
number of registers to write high byte (0x00)
number of registers to write low byte (must be 0x01)
number of data bytes (must be 0x02)
data high byte
data low byte
CRC low byte
CRC high byte
Packet returned by controller:| nn | 10 | nn nn | 00 01 | nn nn |
∆∆∆∆∆∆∆∆
controller address (one byte)
write to multiple registers command (0x10)
starting register high byte
starting register low byte
number of registers to write high byte (0x00)
number of registers to write low byte (must be 0x01)
CRC low byte
CRC high byte
Loop Back Command (0x08)
This command simply echoes the message. This serves as a quick way to check
your wiring.
Packet sent to controller: | nn |08 | nn nn | nn nn |
controller address (one byte)
loop back command (0x08)
data high byte
data low byte
CRC low byte
CRC high byte
∆∆∆∆∆∆
Appendix
Watlow MicroDIN A.5
Example: Run loop back test on controller at address 40 (0x28).
Sent:28 08 55 66 77 88 31 B7
Received:28 08 55 66 77 88 31 B7
Exception Responses
When a controller cannot process a command it returns an exception response
and sets the high bit (0x80) of the command.
0x01 illegal command
0x02 illegal data address
0x03 illegal data value
Packet returned by controller: | nn | nn | nn | nn nn |
controller address (one byte)
command + 0x80
exception code (0x01 or 0x02 or 0x03)
CRC low byte
CRC high byte
∆∆∆∆∆
Appendix
Messages with the wrong format, timing or CRC are ignored. Aread command
sent to an inactive parameter returns 0x0000.
This C routine, calc_crc(), calculates the cyclical redundancy checksum, CRC,
for a string of characters. The CRC is the result of dividing the string by
0xA001. Modbus applications calculate the packet’s CRC then append it to the
packet.
#define POLYNOMIAL 0xA001;
unsigned int calc_crc(unsigned char *start_of_packet, unsigned char
*end_of_packet)
{
unsigned int crc;
unsigned char bit_count;
unsigned char *char_ptr;
/* Start at the beginning of the packet */
char_ptr = start_of_packet;
/* Initialize CRC */
crc = 0xffff;
/* Loop through the entire packet */
do{
/* Exclusive-OR the byte with the CRC */
crc ^= (unsigned int)*char_ptr;
/* Loop through all 8 data bits */
bit_count = 0;
do{
/* If the LSB is 1, shift the CRC and XOR the polynomial mask with the CRC */
annunciator — Avisual display that uses pilot lights to indicate the former or
existing condition of several items in a system.
burst fire — A power control method that repeatedly turns on and off full ac
cycles. Also called zero-cross fire, it switches close to the zero-voltage point of
the ac sine wave. Variable-time-base burst fire selectively holds or transits ac
cycles to achieve the desired power level. See zero cross.
calibration offset — An adjustment to eliminate the difference between the
indicated value and the actual process value.
CJC — see cold junction compensation.
closed loop — A control system that uses a sensor to measure a process
variable and makes decisions based on that feedback.
cold junction — see junction, cold.
cold junction compensation — Electronic means to compensate for the
effective temperature at the cold junction.
default parameters — The programmed instructions that are permanently
stored in the microprocessor software.
derivative —
derivative control (D) — The last term in the PID control algorithm. Action
that anticipates the rate of change of the process, and compensates to minimize
overshoot and undershoot. Derivative control is an instantaneous change of the
control output in the same direction as the proportional error. This is caused by
a change in the process variable (PV) that decreases over the time of the
derivative (TD). The TD is in units of seconds.
Deutsche Industrial Norm (DIN) — A set of technical, scientific and
dimensional standards developed in Germany. Many DIN standards have
worldwide recognition.
DIN — See Deutsche Industrial Norm.
droop — In proportional controllers, the difference between set point and
actual value after the system stabilizes.
duty cycle — The percentage of a cycle time in which the output is on.
external transmitter power supply — A dc voltage source that powers
external devices.
filter, digital (DF) — Afilter that slows the response of a system when inputs
change unrealistically or too fast. Equivalent to a standard resistor-capacitor
(RC) filter.
form A — A single-pole, single-throw relay that uses only the normally open
(NO) and common contacts. These contacts close when the relay coil is
energized. They open when power is removed from the coil.
form B — A single-pole, single-throw relay that uses only the normally closed
(NC) and common contacts. These contacts open when the relay coil is
energized. They close when power is removed from the coil.
form C — A single-pole, double-throw relay that uses the normally open (NO),
normally closed (NC) and common contacts. The operator can choose to wire for
The rate of change in a process variable. Also known as rate. See PID.
A.8 Watlow MicroDIN
a form Aor form B contact.
hysteresis — Achange in the process variable required to re-energize the
control or alarm output. Sometimes called switching differential.
integral — Control action that automatically eliminates offset, or droop,
between set point and actual process temperature. See auto-reset.
integral control (I) — A form of temperature control. The I of PID. See
integral.
isolation — Electrical separation of sensor from high voltage circuitry. Allows
use of grounded or ungrounded sensing element.
JIS — See Joint Industrial Standards.
junction, cold — Connection point between thermocouple metals and the
electronic instrument. See junction, reference.
junction, reference — The junction in a thermocouple circuit held at a stable,
known temperature (cold junction). Standard reference temperature is 32°F
(0°C).
Modbus™ — Adigital communications protocol owned by AEG Schneider
Automation for industrial computer networks.
Modbus™ RTU — Remote Terminal Unit, an individual Modbus™-capable device
on a network.
NEMA 4X — ANEMA specification for determining resistance to moisture
infiltration. This rating certifies the controller as washable and corrosion
resistant.
on/off controller — A temperature controller that operates in either full on or
full off modes.
open loop — A control system with no sensory feedback.
output — Control signal action in response to the difference between set point
and process variable.
overshoot — The amount by which a process variable exceeds the set point
before it stabilizes.
P control — Proportioning control.
PD control — Proportioning control with derivative (rate) action.
PDR control — Proportional derivative control with manual reset, used in fast
responding systems where the reset causes instabilities. With PDR control, an
operator can enter a manual reset value that eliminates droop in the system.
PI control — Proportioning control with integral (auto-reset) action.
PID — Proportional, integral, derivative. Acontrol mode with three functions:
proportional action dampens the system response, integral corrects for droop,
and derivative prevents overshoot and undershoot.
proportional — Output effort proportional to the error from set point. For
example, if the proportional band is 20° and the process is 10° below set point,
the heat proportioned effort is 50 percent. The lower the PB value, the higher
the gain.
proportional band (PB) — A range in which the proportioning function of the
control is active. Expressed in units, degrees or percent of span. See PID.
Appendix
Watlow MicroDIN A.9
Appendix
proportional control — A control using only the P (proportional) value of PID
control.
range — The area between two limits in which a quantity or value is measured.
It is usually described in terms of lower and upper limits.
rate — Anticipatory action that is based on the rate of temperature change, and
compensates to minimize overshoot and undershoot. See derivative.
rate band — A range in which the rate function of a controller is active.
Expressed in multiples of the proportional band. See PID.
reference junction — see junction, reference.
remote — Acontroller that receives its set point signal from another device
called the master.
remote set point — A signal that indicates the set point for the process, and is
sent from another device.
reset — Control action that automatically eliminates offset, or droop, between
set point and actual process temperature. Also see integral.
automatic reset — The integral function of a PI or PID temperature
controller that adjusts the process temperature to the set point after the system
stabilizes. The inverse of integral.
automatic power reset — A feature in latching limit controls that does not
recognize power outage as a limit condition. When power is restored, the output
is re-energized automatically, as long as the temperature is within limits.
manual reset — 1) A feature on a limit control that requires human
intervention to return the limit to normal operation after a limit condition has
occurred. 2) The adjustment of a proportional control to raise the proportional
band to compensate for droop.
resistance temperature detector (RTD) — A sensor that uses the resistance
temperature characteristic to measure temperature. There are two basic types
of RTDs: the wire RTD, which is usually made of platinum, and the thermistor,
which is made of a semiconductor material. The wire RTD is a positive
temperature coefficient sensor only, while the thermistor can have either a
negative or positive temperature coefficient.
RTD — See resistance temperature detector.
thermal system — A regulated environment that consists of a heat source,
heat transfer medium or load, sensing device and a control instrument.
thermocouple (t/c) — A temperature sensing device made by joining two
dissimilar metals. This junction produces an electrical voltage in proportion to
the difference in temperature between the hot junction (sensing junction) and
the lead wire connection to the instrument (cold junction).
thermocouple break protection — The ability of a control to detect a break
in the thermocouple circuit and take a predetermined action.
three-mode control — Proportioning control with integral (reset) and
derivative (rate). Also see PID.
time proportioning control — A method of controlling power by varying the
on/off duty cycle of an output. This variance is proportional to the difference
between the set point and the actual process temperature.
A.10 Watlow MicroDIN
transmitter — A device that transmits temperature data from either a
thermocouple or a resistance temperature detector (RTD) by way of a two-wire
loop. The loop has an external power supply. The transmitter acts as a variable
resistor with respect to its input signal. Transmitters are desirable when long
lead or extension wires produce unacceptable signal degradation.
WatLink— A Watlow software application for configuring and communication
with Watlow controllers via a EIA-485 network and a Microsoft Windowscompatible personal computer.
zero cross — Action that provides output switching only at or near the zerovoltage crossing points of the ac sine wave. See burst fire.
zero switching — See zero cross.
Watlow MicroDIN A.11
Appendix
Declaration of Conformity
A.12 Watlow MicroDIN
WATLOW CONTROLS
1241 Bundy Boulevard
Winona, Minnesota 55987 USA
Declares that the following product:
Designation:Series MicroDIN
Model Number(s):UD 1 A -1CES - (Any four numbers or letters)
Classification:Control, Installation Category II, Polution Degree II
Rated Voltage:24 to 28V‡ (ac/dc)
Rated Frequency:50/60 Hz
Rated Power Consumption: 5VA maximum
Meets the essential requirements of the following European Union Directive(s)
using the relevant section(s) of the normalized standards and related documents
shown:
EN 50082-2:1995 EMC Generic immunity standard, Part 2: Industrial
EN 61000-4-2: 1995 Electrostatic discharge
EN 61000-4-4: 1995 Electical fast transients
ENV 50140:1994 Radiated immunity
ENV 50141:1994 Conducted immunity
ENV 50204:1995 Cellular phone
EN 50081-2:1994 EMC Generic emission standard, Part 2: Industrial
EN 55011:1991 Limits and methods of measurement of radio disturbance
EN 61010-1:1993 Safety requirements for electrical equipment for
Déclare que le produit suivant :
Désignation :Série MicroDIN
Numéro(s) de modèle(s) : UD 1 A - 1CES - (quatre chiffres ou lettres
Classification :Commande, installation catégorie II, degré de
Tension nominale :24 à 28 V ‡ (c.a./c.c.)
Fréquence nominale :50/60 Hz
Consommation
d’alimentation nominale :5 VA maximum
Conforme aux exigences de la (ou des) directive(s) suivante(s) de l’Union
Européenne figurant aux sections correspondantes des normes et documents
associés ci-dessous :
EN 50082-2 : 1995 Norme générique d’insensibilité électromagnétique,
EN 61000-4-2 : 1995 Décharge électrostatique
EN 61000-4-4 : 1995 Courants électriques transitoires rapides
ENV 50140 :1994 Insensibilité à l’énergie rayonnée
ENV 50141 :1994 Insensibilité à l’énergie par conduction
ENV 50204 :1995 Téléphone cellulaire
EN 50081-2 : 1994 Norme générique sur les émissions
EN 55011 :1991 Limites et méthodes de mesure des caractéristiques
EN 61010-1 :1993 Exigences de sécurité pour le matériel électrique
characteristics of industrial, scientific and medical radiofrequency equipment (Class A)
73/23/EEC Low-Voltage Directive
measurement, control, and laboratory use, Part 1:
General requirements
Français
quelconques)
pollution II
89/336/EEC Directive de compatibilité électromagnétique
Partie 2 : Environnement industriel
électromagnétiques, Partie 2 : Environnement
industriel
d’interférences du matériel radiofréquence industriel,
scientifique et médical (Classe A)
73/23/EEC Directive liée aux basses tensions
de mesure, de commande et de laboratoire, Partie 1 :
Exigences générales
Erklärt, daß das folgende Produkt:
Beschreibung:Serie MicroDIN
Modellnummer(n):UD 1 A - 1 CES - (4 beliebige Zahlen oder
Klassifikation:Regelsystem, Installationskategorie II,
Nennspannung:24 bis 28 V‡ (ac/dc)
Nennfrequenz:50/60 Hz
Nominaler Stromverbrauch: Max. 5 VA
Erfüllt die wichtigsten Normen der folgenden Anweisung(en) der Europäischen
Union unter Verwendung des wichtigsten Abschnitts bzw. der wichtigsten
Abschnitte der normalisierten Spezifikationen und der untenstehenden
einschlägigen Dokumente:
Buchstaben)
Emissionsgrad II
Deutsch
89/336/EEC EWG Elektromagnetische Verträglichkeit
EN 50082-2:1995 EMC-Rahmennorm für Störsicherheit, Teil 2:
EN 61000-4-2: 1995 Elektrostatische Entladung
EN 61000-4-4: 1995 Elektrische schnelle Stöße
ENV 50140:1994 Strahlungsimmunität
ENV 50141:1994 Leitungsimmunität
ENV 50204:1995 Mobiltelefon
EN 50081-2:1994 EMC-Rahmennorm für Emissionen, Teil 2: Industrielle
EN 55011:1991 Beschränkungen und Methoden der Messung von
Industrielle Umwelt
Umwelt
Funkstörungsmerkmalen industrieller, wissenschaftlicher
und medizinischer Hochfrequenzgeräte (Klasse A)
72/23/EEC EWG Niederspannungsrichtlinie
EN 61010-1:1993 Sicherheitsrichtlinien für Elektrogeräte zur Messung,
Declara que el producto siguiente:
Designación:Serie MicroDIN
Números de modelo:UD 1 A - 1CES - (Cualquier combinación de cuatro
Clasificación:Control, categoría de instalación II, grado de
Tensión nominal:24 a 28V ‡ (Vca/Vcc)
Frecuencia nominal:50/60 Hz
Consumo nominal
de energía:5 VA máximo
Cumple con los requisitos esenciales de las siguientes directivas de la Unión
Europea, usando las secciones pertinentes de las reglas normalizadas y los
documentos relacionados que se muestran:
zur Steuerung und im Labor, Teil 1: Allgemeine
Richtlinien
Español
números y letras)
contaminación ambiental II
89/336/EEC Directiva de compatibilidad electromagnética
EN 50082-2: 1995 Norma de inmunidad genérica del EMC, parte 2: Ambiente
• RTD 2 or 3 wire, platinum, 100Ω@ 0°C calibration to JIS curve (0.003916Ω/Ω/°C),
or DIN curve (0.00385Ω/Ω/°C)
• Sensor break protection de-energizes control output to protect system or selectable
bumpless transfer to manual operation.
• °F or °C, user selectable
• Sensor Ranges:
Accuracy Ranges:Operating Ranges
B t/c1598 to 3092°F870to 1700°C32 to 3300°F0 to 1816°C
C (W5) t/c32 to 4200°F0 to 2315°C32 to 4200°F0 to 2315°C
D (W3) t/c32 to 4200°F0to 2315°C32 to 4200°F0 to 2315°C
E t/c-328 to 1472°F-200to 800°C-328 to 1470°F-200 to800°C
J t/c 32 to 1382°F0 to750°C32 to 1500°F0 to815°C
K t/c-328 to 2282°F-200 to 1250°C-328° to 2500°F-200 to 1370°C
N t/c32 to 2282°F0 to 1250°C32 to 2372°F0to 1300°C
PT2 t/c32 to 2540°F0 to 1393°C32 to 2543°F0 to 1395°C
R t/c32 to 2642°F0to 1450°C32 to 3200°F0 to 1760°C
S t/c32 to 2642°F0 to 1450°C32 to 3200°F0 to 1760°C
T t/c-328 to662°F-200to350°C-328 to750°F-200 to400°C
1.0 RTD (DIN) -328 to 1202°F-200to 650°C-328 to 1472°F-200 to800°C
0.1 RTD (JIS) -199.9 to 999.9°F-143 to636°C-328 to 1166°F-200to630°C
• Tenth degree resolution selectable over sensor operating range within limits of
-199.9 to 999.9, except for thermocouple types B, R, and S
Watlow MicroDIN A.13
Appendix
Primary Control Output (heating or cooling)
• Output update rate: 10 per second, 10Hz (maximum)
Internal Load Switching (nominal):
Switched dc (isolated) signal, 22 to 28VÎ (Vdc), current limited @ 30mA
Overload current and short circuit protection
External Load Switching (maximum):
• Open Collector 60VÎ(Vdc) @ 1A
Alarm Output
• Output update rate 2 per second (2Hz)
• Electromechanical relay, Form A, 2A@ 30VÎ (Vdc) or 240VÅ(Vac),
• Alarm output can be latching or non-latching, and process or deviation with
separate high and low values. Alarm silencing (inhibit) on power-up.
Accuracy
• Calibration accuracy and sensor conformity: ±0.1% of span ±1 @ 77°F ±5°F (25°C
±3°C) ambient, and rated line voltage ±10% with the following exceptions:
Type T; 0.12% of span for -200°C to -50°C
Types R and S; 0.15% of span for 0°C to 100°C
Type B; 0.24% of span for 870°C to 1700°C
• Accuracy span: Less than or equal to operating ranges, 1000°F/540°C minimum.
• Temperature stability: ±0.2°F/°F (±0.2°C/°C) rise in ambient maximum for
thermocouples, ±0.05°F/°F (±0.05°C/°C) rise in ambient maximum for RTD sensors
• Voltage stability: ±0.01% of span per percent of rated line voltage
Safety Agency Approvals
• UL/C-UL 508, File # E102269
Industrial Control Equipment
• CE to EN 61010 (pending)
Appendix
Electromagnetic Compatibility and Immunity
• Complies with EN 50081, EN 50082
Terminals
• Touch-safe set screw type, accepts 26 to 14 gauge wire
Power
• 24-28V‡(Vac/Vdc), -15%, +10% [20.4 to 30.8V‡(Vac/Vdc)]; 50/60Hz ±5% for VÅ(Vac)
• 5VA typical power consumption
• Data retention upon power failure via nonvolatile memory
• Sensor input isolation to switched dc output and communication circuitry
500VÅ(Vac) dielectric
Operating Environment
• 32 to 149°F (0 to 65°C)
• 0 to 90% RH, non-condensing
• Storage temperature: -40 to 158°F (-40 to 70°C)
Dimensions
• Width x Height x Depth
1.64" x 4.65" x 5.19" DIN rail mount
(42mm x 118mm x 132mm)
1.64" x 4.65" x 5.06" Chassis mount
(42mm x 118mm 129mm)
• Mounts on DIN rail per DIN EN 50022 (35mm x 7.5mm)
UL®is a registered trademark of Underwriters Laboratories.
Modbus™is a registered trademark of AEG Schneider Automation.
Adobe®and Acrobat®are registered trademarks of Adobe Systems Incorporated.
These specifications are subject to change without prior notice.
A.14 Watlow MicroDIN
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.