Watlow FIREBAR Flange Heater User Manual

WATLOW IND. FIREBAR
®
Flange Heater Installation & Maintenance Manual
I&M NUMBER: 316-42-2-1 Page: 1 Date: 6/11/2008 Rev: 2.00
________________________________________________________________________________________________________________________________________________________________________________________________________________________
Pre Installation
Check to make sure that heater received is the same as that ordered.
Elements may come in contact with each other during shipment. Minor adjustments to elements may be
required prior to installation to separate them. Extensive bending of elements should be avoided since dielectric strength between coil and sheath may be compromised.
Watlow heaters are built to comply with UL and CSA dielectric requirements, it may be necessary due to atmospheric conditions / humidity, to perform a dielectric test prior to startup. (Refer to megohm test under Installation section)
Safety
Electric heaters are inherently dangerous!! Care should be taken to read and completely understand the
Installation and Maintenance manual before installing and wiring the heater. Any installation and maintenance performed on the heater shall be done by a qualified electrician, in accordance with the "National Electric Code" and other electrical codes as they apply. It is the users responsibility to ensure that the heater being used is properly selected and installed in the application.
!
The Caution Symbol (exclamation point) alerts you to a "CAUTION", a safety or
functional hazard which could affect your equipment or its performance.
The warning symbol (lightning bolt) alerts you to a "WARNING", a safety hazard which
Installation
Proper heater selection and installation will result in efficient heat transfer, safe operation, and long heater life.
1. Megohm precheck
During shipping and/or storage, the possibility of moisture absorption by the insulation material within the element is possible. To ensure proper megohm values a minimum 500 VDC megohm meter (Megger) should be used to ensure that the megohm reading between the heater terminal and the heater sheath is more than 10 megohms when the unit is at room temperature.
If several units are interconnected, the megohm of the heater is obtained by taking the reading and dividing by the number of interconnected elements. This reading should be greater than 10 megohms.
If a low megohm value exists, two alternative methods can be used to remedy the situation. The best method is to remove all terminal hardware including thermostat if provided, and bake out the heater at no higher than 250°F (120°C) overnight or until an acceptable reading is reached. The second method is to energize the unit at low voltage in air until the megohm is at an acceptable reading. Care should be taken to prevent the heater sheath from exceeding 750°F (398°C) for Incoloy® and Stainless Steel elements.
2. Protection of heater elements from over temperature
The use of temperature controls to regulate heating process and prevent heater over temperature is
highly recommended to ensure safe heater operation. It is the users responsibility to ensure safety of the installation.
WARNING: Install high temperature control protection in systems where an over temperature fault condition could present a fire hazard or other hazard. Failure to install temperature control
could affect you and the equipment
WATLOW IND.n # 6 INDUSTRIAL LOOP RD. n HANNIBAL MO, 63401n PHONE 573-221-2816 n FAX 573-221-3723
WATLOW IND. FIREBAR
®
Flange Heater Installation & Maintenance Manual
I&M NUMBER: 316-42-2-1 Page: 2 Date: 6/11/2008 Rev: 2.00
________________________________________________________________________________________________________________________________________________________________________________________________________________________
protection where a potential hazard exists could result in damage to equipment and property, and injury to personnel.
Failure of components in a temperature control loop, such as the sensor, heater control relay or main
temperature control, can result in damage to a product in process, a melt down of a heater, and / or damaging fire.
To protect against this possibility, over temperature protection must be provided to interrupt or remove
power from the heater circuit. A bulb and capillary thermostat is not recommended for this function
since it may not respond quickly enough to adequately protect the heater. In cases where the thermostat bulb gets too hot before the system is turned off, the thermostat bulb could rupture. This could result in the thermostat remaining in the "ON" condition since there is insufficient fluid to move contacts apart. We recommend the temperature protection have appropriate third party
approval, and be applied in the classification for which it was tested and approved.
In order to help prevent premature failure and a potentially hazardous condition in cases where
consequences of failure may be severe, use an appropriate third party approved liquid level protection device. The liquid level should be such that the entire heater is fully submerged with enough liquid above the heater to adequately dissipate heat from itself as under normal operating conditions. Consult your local authorized sales representative for specific recommendations for your application.
3. Terminal Enclosures
Terminal enclosures should be selected to be compatible with the environment in which the heater will
be located. It is the users responsibility to determine the need for correct rating of the electrical housing. This should be based on appropriate national and local electrical codes. Failure to use a compatible enclosure could result in heater damage and personnel danger.
Standard terminal enclosures are designed for general purpose use and are rated NEMA 1. These
enclosures should be applied where there will be no danger of spilled liquids, dampness, dirt, and gaseous conditions. Enclosures for wet or hazardous locations are also available, but must be installed at the factory.
Although enclosures are supplied over the terminals, units should be located in an area that will minimize
the chance of being hit by falling or moving objects. The terminals must be protected at all times from moisture or vapor.
In hazardous locations, (as defined in NFPA 70 NEC, Article 501) explosion resistant housings must be
used.
In order to maintain termination integrity, the terminal enclosure should be kept below 400°F (204°C).
4. Orientation / Mounting
Watlow flange immersion heaters incorporate a standard ANSI flange for universal mounting in tanks
equipped with the same size mounting flange. A suitable gasket and mounting bolts are required for installation but are not provided with the heater. The correct gasket material should be based on the material being heated and the process temperature.
Proper installation and orientation of the FIREBAR® flange heater is important to insure maximum
efficiency and minimum sheath temperatures. The unique shape of this flat element offers many advantages, but they can only be realized if the heater is properly oriented. Every effort should be made to position the heater as recommended.
WATLOW IND.n # 6 INDUSTRIAL LOOP RD. n HANNIBAL MO, 63401n PHONE 573-221-2816 n FAX 573-221-3723
WATLOW IND. FIREBAR
®
Flange Heater Installation & Maintenance Manual
I&M NUMBER: 316-42-2-1 Page: 3 Date: 6/11/2008 Rev: 2.00
________________________________________________________________________________________________________________________________________________________________________________________________________________________
The recommended location for open tank heating is shown in Figure #1. The heater should be installed
as low as possible in the tank to take advantage of natural convection. Attention should be given to sludge build-up and low liquid level. Location in either of these situations could cause premature failure.
During installation of the heater it is important that special attention be given to the final orientation of the
element. The flat side of the element must be positioned vertically as shown in Figure #2. Maximum advantages are realized when the element is within +/- 25° of vertical. Positions outside this range are not recommended, and 90° from vertical should always be avoided.
Each flange is marked with "TOP" to help clarify the preferred orientation. For open tank heating, this
marking should normally be on top of the final plug position. If this is not practical, it may be positioned on the bottom, which will also orient the flat element vertical.
If heater is being installed in customer supplied circulation tank, a FIREBAR® Flange Circulation I&M
manual should be obtained from the factory to ensure safe installation of heater in tank. Failure to do this could result in premature heater failure due to improper fluid flow over elements
LIQUID LEVEL
ALLOWANCE FOR HEATER REMOVAL
2" MIN
SLUDGE
ANSI WELD NECK FLANGE TO MATCH HEATER FLANGE SIZE
Figure # 1
25
25
TOP
TOP
CORRECT ORIENTATION
Remove terminal enclosure to see element position
Figure # 2
WATLOW IND.n # 6 INDUSTRIAL LOOP RD. n HANNIBAL MO, 63401n PHONE 573-221-2816 n FAX 573-221-3723
INCORRECT ORIENTATION
Loading...
+ 4 hidden pages