Compact Solid State
TOTAL
3 Year Warranty
CUSTOMER
SATISFACTION
Power Controller
Delivers Big
Performance
SPECIFICATION SHEET
DIN-A-MITE® A
The DIN-A-MITE® A power controller provides a low-cost,
highly compact and versatile solid state option for controlling
electric heat. This controller is designed and manufactured
with the quality features expected from Watlow®. DIN-rail and
panel mounting is standard on every controller. There is no
need to worry about mercury, the DIN-A-MITE controller is
mercury free.
Features include single-phase zero cross switching up
to 25 amperes at 600VAC (see rating curve). A unique
integrated design removes the guesswork associated with
selecting a proper heat sink and adequate terminations for
the application.
Variable time-base, 4-20mA process control and VAC/VDC
input contactor versions are available. All options are model
number dependent and factory configurable. This power
controller also includes 200KA short circuit current rating
(SCCR) tested up to 480VAC to minimize damage in the event
of a short circuit when used with required fusing.
Features and Benefits
200KA SCCR with proper fusing
• Minimizes damage in the event of a short circuit
DIN-rail and panel mounting
• Provides versatility and quick, low-cost installation
Compact size
• Reduces panel space and cost
Touch-safe terminals
• Increases safety for installer and user
Mercury free
• Assures environmental safety
Faster switching with solid state
• Saves energy and extends heater life
UL® 508 listed, C-UL®, RoHS 2 and CE with filter
• Meets applications requiring agency approval
• Reduces end product documentation cost
Back-to-back SCR design
• Ensures a rugged design
Watlow® and DIN-A-MITE® are registered trademarks of Watlow Electric Manufacturing
Company.
UL® and C-UL® are registered trademarks of the Underwriter’s Laboratories, Inc.
Powered by Possibility
To be automatically connected to the nearest
North American Technical Sales Oce:
1-800-WATLOW2 • www.watlow.com
©2016 Watlow Electric Manufacturing Company all rights reserved.
inquiry@watlow.com
International Technical Sales Offices:
China +86 21 3532 8532
France +33 1 41 32 79 70
Germany +49 7253 9400 0
India +91 40 6661 2700
Italy +39 02 4588841
Japan +81 3 3518 6630
Korea +82 2 2169 2600
Mexico +52 442 256 2200
Singapore +65 6773 9488
Spain +34 91 675 1292
Taiwan +886 7 288 5168
UK +44 115 964 0777
WIN-DMA-1216
Specifications
Operator Interface
• Control input
• Input indication LED
Amperage
• Single-phase, see the output rating curve
• Max. I2t for fusing: 4000A2sec
• Latching current: 400mA max.
• Holding current: 200mA max.
• Power dissipation is 1.2 watts per ampere switched
• 200KA SCCR, Type 1 and 2 approved with the
recommended fusing; see user manual.
Line Voltage
• 24 to 660VAC model number dependent; see ordering
information
• Off-state leakage: 1mA at 77°F (25°C) max.
• 50/60Hz independent
Control Mode, Zero Cross
• Control option C: VDC input, contactor output
• Control option K: VAC input, contactor output
• To increase service life on contactor models, the cycle time
should be less than three seconds
• Control option F: 4 to 20mA DC input, variable time-base
control output (3 cycles on, 3 cycles off at 50% power)
Control Input
• AC contactor: 24VAC ±10%, 120VAC +10/-25%, 240VAC
+10/-25% @ 25mA max.
•
DC contactor: 4.5 to 32VDC: max. current @ 4.5VDC is 8mA
•
Loop powered linear current 4 to 20mA DC: loop-powered,
control option F0 only (requires current source with 8.0VDC
available, no more than two DIN-A-MITE inputs can be
connected in series)
Agency Approvals
• CE with proper filter:
204/108/EC Electromagnetic Compatibility Directive
EN 61326-1: Industrial Immunity Class A Emissions
2006/95/EC Low Voltage Directive
EN 50178 Safety Requirements
Installation category III, pollution degree 2
•
UL® 508 listed and C-UL® File E73741
• 2011/65/EU RoHS 2
Control Input Terminals
• Compression: will accept 24 to 16 AWG (0.2 to 1.5 mm2) wire
Line and Load Terminals
• Compression: will accept 18 to 8 AWG (0.8 to 8.4 mm2) wire
Operating Environment
• -4 to 176°F (-20 to 80°C); see the output rating curve chart for
your application
• 0 to 90% RH (relative humidity), non-conden sing
• Insulation tested to 3,000 meters
• Units are suitable for “Pollution degree 2”
Mounting
Options include DIN-rail or standard back panel mounting
• DIN EN 50022, 35 mm by 7.5 mm
• Mount cooling fins vertically
Dimensions
• 3.7 in. (94 mm) high x 2.0 in. (50 mm) wide x 3.9 in.
(98 mm) deep
• Weight: 0.71 lb (0.32kg)
Specifications are subject to change without notice.
Output Rating Curve
30
25
20
a Resistive Load
15
10
5
0
DIN-A-MITE Style A Ratings at 100% On
25 30 35 40 45 50 55 60 65 70 75 80 85
Max. Internal Enclosure Ambient Temperature (°C)
Ordering Information
Part Number
①
D
③
1 = 1-phase, 1 controlled leg
④
0 = Natural convection current rating 18A @50°C
⑤ ⑥
02 =
24 =
60 =
⑦ ⑧
C0 =
F0 =
K1 =
K2 =
K3 =
②
A
Cooling and Current Rating (see rating curve)
24 to 48VAC
120 to 240VAC
277 to 600VAC
4.5 to 32VDC input, contactor output
4 to 20mA DC input, variable time-base output
22 to 26VAC input, contactor output
100 to 120VAC input, contactor output
200 to 240VAC input, contactor output
③
Phase
1
Line and Load Voltage
④
Cooling &
Current
Rating
0
Phase
Control
–
⑤ ⑥
Line &
Load
Voltage
⑦ ⑧
Control
⑨
0
–
⑪ ⑫
00 =
XX =
⑩
User
Manual
⑩
0 =
English
1 =
German
2 =
Spanish
3 =
French
Standard part
Any letter or number, custom options
⑪ ⑫
Custom
Options
User Manual
Custom Options
Recommended Fuses and Fuse Holders
Semiconductor Fuses and
Holders
Part Nbr. Description
17-8025 25A fuse
17-5110 10-25A holder
DFJ Combination Fuses and
Holders
Part Nbr. Description
0808-0325-0020
0808-0325-0030
0808-0326-1530
20A fuse
30A fuse
15-30A holder