Watlow DC10-12P0-0010, DC10-24S5-0000, DC80-60K2-0000, DC90-24K2-0000, DC3T-60F0-0000 User manual

...
DIN-A-MITE
®
Style C
Solid-State Power Controller
User’s Manual
DIN-A-MITE Solid-State Power Controller
0600-0025-0009 Rev Q Made in the U.S.A.
Please consult this user’s manual when you place your new DIN-A-MITE into service. It contains all the necessary information to mount and wire the product into the application. This manual also contains all user-pertinent specifications and semiconductor fusing recommendations. Refer to national and local electrical code safety guidelines whenever you install electrical equipment.
The Watlow DIN-A-MITE power controller includes single-phase, 3-phase, 2-leg, and 3­phase, 3-leg, 120 to 600VÅ (ac) operation. Current switching capabilities range from 30 to
80A, depending on the model ordered. See the output rating curves.
Zero-cross variable time base or V(ac/dc) input contactor versions are available. Shorted SCR (silicon controlled rectifier) and open-heater protection is available on some zero-cross models. Phase angle and phase angle with current limit is also available on single-phase models. The model number indicates the power controller’s configuration.
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
2
WATLOW DIN-A-MITE Style C User's Manual
General Specifications
Operator Interface
• Command signal input and indication light
• Alarm output and indication light
• Current limit indication LED
Amperage Rating
See the output rating curve chart on page 5 for all
the natural convection, fan-cooled, and through­wall mount models.
Ratings are into a resistive heater load
• Maximum surge current for 16.6 milliseconds, 1,350 A peak
• Maximum I2t for fusing is 9100 A2s
• Latching current: 500mA minimum
• Holding current: 200mA minimum
• Fan current: 0.14 A for 24VÎ (dc); 0.12 A for 120VÅ (ac); 0.06A for 240VÅ (ac)
• Off-state leakage 1mA at 25°C (77°F) maximum
• Power dissipation is 1.2 watts per amp switched
per controlled leg.
• 200KA SCCR type 1 and 2 approved with the
recommended fusing (see page 4)
Line Voltage
• 24 to 48VÅ (ac) units: 20VÅ minimum to 53VÅ maximum
• 120 to 240VÅ (ac) units: 48VÅ minimum to 265VÅ maximum
• 277 to 600VÅ (ac) units: 85VÅ minimum to 660VÅ maximum
Alarms (zero cross models only)
Shorted SCR Alarm Option
• Alarm state when the input command signal is off and a 10 A or more load current is detected by the current transformer (two turns required for 5 A or three turns for 2.5 A).
Open Heater Alarm Option
• Alarm state when the input command signal is on and the load current detected by the current transformer is less than the alarm set point. Available with Input Control Signal option S only.
Alarm Output
• Energizes on alarm, non-latching
• Triac 24 to 240VÅ (ac), external supply with a current rating of 300 mA @ 25°C (77°F), 200mA @ 50°C (122°F), 100mA @ 80°C (176°F) and a holding current of 200 µA with a latching current of 5mA typical.
Agency Approvals
•ROHS
• CE with proper filter:
2004/108/EC Electromagnetic Compatibility Directive EN 61326: Industrial Immunity Class A emissions Not suitable for Class B environments. 2006/95/EC Low Voltage Directive EN 50178 Safety Requirements Installation category III, Pollution degree 2 Phase angle and phase angle with current limit Input
Control Signal Types (P and L) are not CE approved.
•UL
®
50 Type 4X Enclosure and UL ANSI/ISA 12.12.01
Temperature Code T4A
The through-wall heatsink package is suitable for use in
Class I, Division 2 Groups A, B, C and D Hazardous Locations or unclassified or non-hazardous locations.
çWARNING – EXPLOSION HAZARD
SUBSTITUTION OF ANY COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2.
çWARNING – EXPLOSION HAZARD
DO NOT DISCONNECT WHILE THE CIRCUIT IS LIVE OR UNLESS THE AREA IS KNOW TO BE FREE OF IGNITIBLE CONCENTRATIONS.
•UL
®
508 listed and C-UL®, File E73741
• Shock and vibration tested to IEC 60068-2-32
• Vibration tested to IEC 60068-2-6
Input Terminals
• Compression: Will accept 0.2 to 1.5 mm
2
(24 to 16
AWG) wire
• Torque to 0.5 Nm (4.4 in-lb) with a 3.5 mm (1/8 in) blade screwdriver
• Wire strip length 5.5 mm (0.22 in)
• Line and load wire insulation rating must be 75C or
higher, copper conductor only
Line, Load and Ground Terminals
• Compression: Will accept 2.5 to 25 mm
2
(14 to 3 AWG)
wire
• Torque to 2.7 Nm (24 in-lb) with a 6.4 mm (1/4 in) blade screwdriver, or a Type 1A #2 Pozi driver.
• Retorque after 48 hours to minimize wire cold flow.
• Retorque line and load terminals every 3 to 6 months.
• Wire strip length 11 mm (7/16 in)
Operating Environment
• See the output rating curve chart on page 5.
• 0 to 90% RH (relative humidity), non-condensing
• Storage temperature: -40 to +85°C (-40 to 185°F)
• Insulation only tested to 3,000 meters
DIN Rail Mount
• DIN EN 50022, 35 by 7.5 mm
• Minimum clipping distance: 34.8 mm (1.37 in)
• Maximum clipping distance: 35.3 mm (1.39 in)
Back Panel Mount
• Four mounting holes M4 (No. 8) fastener
Through-Wall Mount
• See page 8 for through-wall cutout
NOTE: Mount cooling fins vertically. Cooling fan power terminals: quick connect, 1/8" push on, 16-14 AWG wire. Amp part no. 640929-1 or equivalent
Weight
• 1.0 to 1.9 kg (2.2 to 4.2 lb) depending upon model
Specifications are subject to change without notice.
Note: The DIN-A-MITE C was changed in April of
2007 to add the shut down circuitry (fan failure) to all units shipped. The shut down temperature is approximately 117C.
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
WATLOW DIN-A-MITE Style C User's Manual
3
Additional Specifications: Phase Angle; Phase Angle Current Limit; & Single Cycle VTB
Operation
• Burst firing (zero-cross) control, single-cycle variable time base, Type S single-phase and 3-phase. Unit is not on for more than one full cycle under 50% power and not off for more than one full cycle above 50% power.
• Phase angle control, single-phase only
Input Command Signal
• 0 to 20mA, 4 to 20mA, 12 to 20mA, Î (dc), 0 to 5VÎ, 1 to 5VÎ, and 0 to 10VÎ
• Input impedance 250for 4 to 20mA, 5kfor linear voltage input
Output Voltage
• 100 to 120VÅ (ac), 200 to 208VÅ, 230 to 240VÅ, 277VÅ, 400VÅ, 480VÅ, 600VÅ, -15%/+10%, 50 or 60 Hz independent +/-5% (Input Control Signal Type L, P and S)
Phase Angle Accuracy
• Output on time is directly proportional to the command signal. Output on time is accurate to within 5% of the command signal input at 25 degrees C ambient. See chart below for command signal input to output power transfer function. Temperature stability at ambient temperature is less than 0.25%/degrees C.
Single Cycle VTB Accuracy
• Output power is directly proportional to the command signal. Output power is accurate to within 5% of the command signal input at 25 degrees C ambient. Temperature stability is less than 0.25%/degrees C ambient temperature change.
Soft Start (Phase Angle Input Control Signal Type P and L)
Typically:
• 5 seconds soft start on power up
• Soft start on thermostat overtemperature
• Soft start on 1/2 cycle drop out detection
• 1 second soft switching on set point change
Options
• Manual Control Kit (1kΩ, 1 turn potentiometer with dial scale labeled 0 to 100%) 08-5362
• Alarm option is not available on phase angle type P or type L.
Resolution
• Better than 0.1% of input span with respect to output change.
Control Mode, Zero-Cross
• Input Control Signal Type C: VÎ (dc) input contactor.
To increase service life, the cycle time should be less than 3 seconds.
• Input Control Signal Type K: VÅ (ac) input contactor.
To increase service life, the cycle time should be less than 3 seconds.
• Input Control Signal Type F: 4 to 20mAÎ (dc)
proportional variable time base control.
Input Command Signal
• AC contactor
24VÅ ±10%, 120VÅ +10%/-25%, 240VÅ (ac) +10%/-25% @ 25mA maximum per controlled leg
• Do not use the DIN-A-MITE Vac-input models with a temperature controller that includes an RC snubber circuit across its output. Remove the RC snubber circuit before placing the DIN-A-MITE into service.
• DC Contactor
4.5 to 32VÎ (dc): maximum current @ 4.5VÎ (dc) is 6mA per leg. Add 2mA per LED used to the total current.
• Loop powered linear current
4 to 20mAÎ (dc): loop-powered. Input Type F0 option only. (Requires current source with 8.0VÎ (dc) available. No more than two inputs connected in series.)
Linearity (Input Control Signal Type F)
• Full on point 19.5 to 19.9mAÎ (dc), maximum voltage
of 6.2V peak.
• ±5% input to output power accuracy, 0% to 100% of span (4.3 to 19.7mA or 12.3 to 19.7mA).
• Temperature stability is less than 0.15%/°C change.
Additional Specifications for Contactors and Proportional Controls
Phase Angle Command Signal Input to Output Power
Note: The DIN-A-MITE C was changed in April of
2007 to add the shut down circuitry (fan failure) to all units shipped. The shut down temperature is approximately 117C.
Find Quality Products Online at: sales@GlobalTestSupply.com
100.0
90.0
80.0
70.0
60.0
50.0
40.0
Output (%P)
30.0
20.0
10.0
0.0 0 102030405060708090100
Command Signal Input (%P)
www.GlobalTestSupply.com
DIN-A-MITE C Ordering Information
To order, complete the code number on the right with the information below:
Style C solid-state power controller
Phase
1 = single-phase, 1 controlled leg 2 = 3-phase, 2 controlled legs 3 = 3-phase, 3 controlled legs (use with four-wire wye) 8 = 2 independent zones (input control C, K) 9 = 3 independent zones (input control C, K)
Cooling and Current Rating Per Leg
0 = Natural convection standard DIN rail or panel heatsink 1 = Fan-cooled 120VÅ (ac) standard DIN rail or panel heatsink 2 = Fan-cooled 240VÅ (ac) standard DIN rail or panel heatsink 3 = Fan-cooled 24VÎ (dc) fan standard DIN rail or panel heatsink T =Natural convection through-wall or cabinet heatsink (UL 50)
Line and Load Voltage
02 = 24 to 48VÅ (ac) (Input Control Signal C, F, or K only) 12 = 100 to 120VÅ (ac) (Input Control Signal L, P or S only) 20 = 200 to 208VÅ (ac) (Input Control Signal L, P or S only) 24 = 120 to 240VÅ (ac) (Input Control Signal C, F or K only);
230 to 240VÅ (ac) (Input Control Signal L, P or S only) 27 = 277VÅ (ac) (Input Control Signal L, P or S only) 40 = 400VÅ (ac) (Input Control Signal L, P or S only) 48 = 480VÅ (ac) (Input Control Signal L, P or S only) 60 = 277 to 600VÅ (ac) (Input Control Signal C, F or K only);
600VÅ (ac) (Input Control Signal L, P or S only)
Input Control Signal
C0 =4.5 to 32VÎ (dc) contactor K1 = 22 to 26VÅ contactor K2 = 100 to 120VÅ contactor K3 = 200 to 240VÅ contactor F0 = Proportional 4 to 20 mA (loop powered) L(0 to 5) = Phase angle with current limiting (DC1 only, Alarm 0 only,
includes one current transformer - Single phase only) P(0 to 5) = Phase angle (DC1 only, Alarm 0 only - Single phase only) S(0 to 5) = Single-cycle variable time base (Select one of the following input options for L, P, S, (0 to 5))
0 = 4 to 20mA 1 = 12 to 20mA (for Input Control Signal option S only) 2 = 0 to 20mA 3 = 0 to 5VÎ (dc) proportional 4 = 1 to 5VÎ (dc) proportional 5 = 0 to 10VÎ (dc) proportional
Alarm
0 = No alarm S = Shorted-SCR alarm (not available on Phase options 8 & 9 or Control options L & P) H =Open-heater and shorted-SCR alarm (for Input Control Signal option S only)
User Manual Language
0 = English 1 = German 2 = Spanish 3 = French
Custom Part Numbers
00 = Standard part 1X = 1-second soft start (control option P, L) XX = Any letter or number, custom options, labeling, etc.
4
WATLOW DIN-A-MITE Style C User's Manual
__ __ __ __ - __ __ __ __ - __ __ __ __
D C
Current Rating Table
Model Current (first 4 digits at 50°C of part number) (122°F)
DC10 55 A DC1T 62 A DC11, DC12, DC13 75 A DC20, DC80 40 A DC2T, DC8T 46 A DC21, DC22, DC23 65 A DC81, DC82, DC83 DC30, DC90 30 A DC3T, DC9T 35 A DC31, DC32, DC33 55 A DC91, DC92, DC93
Note:
• Recommended fusing options to meet 200KA SCCR, type 1 and 2 approved. All other fuse and SCR com­binations are de­faulted to 5KA SCCR per UL508A and NEC guidelines.
Not CE compliant for conducted or radiated emissions
Semiconductor Fuses for Applications Through 600VÅ (ac):
Semiconductor Watlow Fuse Bussman Fuse Watlow Holder Ferraz Holder
Fuse Rating P/N P/N P/N P/N
30A 17-8030 FWP30A14F 17-5114 USM141i 40A 17-8040 FWP40A14F 17-5114 USM141i 50A 17-8050 FWP50A14F 17-5114 USM141i 63A 17-8063 FWP63A22F 17-5122 US221i 80A 17-8080 FWP80A22F 17-5122 US221i 100A 17-8100 FWP100A22F 17-5122 US221i
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
WATLOW DIN-A-MITE Style C User's Manual
5
Output Rating Curves
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80
25
30
35
40
45
50
55
60
65
70
75
80
90
85
Current (Amps) into a Resistive Load
Maximum Internal Enclosure Ambient Temperature (°C)
DIN-A-MITE Style C Ratings at 100% On
Natural Convection
3-phase, 3-leg
3-phase, 2-leg
Single-phase
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70
25
30
35
40
45
50
55
60
65
70
Current (Amps) into a Resistive Load
Maximum Internal Enclosure Ambient Temperature (°C)
DIN-A-MITE Style C Ratings at 100% On
75 80 85 90
Fan-Cooled
75
80
3-phase, 3-leg
3-phase, 2-leg
Single-phase
Extended Heater And SCR Life With Variable Time Base
Models: DC _ _ - [02, 24, 60] F0 - _ _ _ _
20% Power, 3 AC line cycles on, 12 cycles off
50% Power, 3 AC line cycles on, 3 cycles off
Phase Angle
Single-Cycle Variable Time Base
With single-cycle variable time base (VTBS) control, at 50% power, power is on one cycle, and off one cycle. At 25%, it is on for one cycle and off for three. Under 50%, the unit is not on for more than one consecutive cycle. Over 50%, the unit is not off for more than one consecutive cycle. This model will work with a linear voltage input, a 4 to 20mA input or a potentiometer input.
Phase angle control (control Type P) is infinitely variable inside the sine wave. This provides a variable voltage and/or current output. This option includes soft start and line voltage compensation. This model will work with a linear voltage input, a linear current source input or a potentiometer input. This is single-phase only. Alarms not available on phase angle models.
Models: DC _ _ - _ _ S _ - _ _ _ _
25% Power, 1 AC line cycle on, 3 cycles off
Models: DC1 _ - _ _ [L, P] _ - 0 _ _ _
With variable time base control, the power controller automatically adjusts the time base and output power with respect to process input. Accelerated life testing verified that the variable time base control significantly reduces expansion and contraction of the heater element. This extends heater and SCR life while improving the process temperature control. You save money on heaters, down time and maintenance.
50% Power, 1 AC line cycle on, 1 cycle off
Ó
6
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70
Current (Amps) into a Resistive Load
25
30
35
40
45
50
55
60
65
70
75
80
Ambient Air Around Heatsink Fins ( C)
DIN-A-MITE Style C Ratings at 100% On
Through-Wall Heatsink
75 80
Recommended maximum
enclosure temperature is 80 C (176 F)
3-phase,
2-l
eg
3
-
phase, 3-
l
eg
Single-phase
Combination Fuses for Applications Through 600VÅ (ac):
Semiconductor Watlow Fuse Bussman Watlow Holder Bussmann Holder
Fuse Rating P/N P/N P/N P/N
30A 0808-0325-0030 DFJ30 0808-0326-1530 CH30J1i 40A 0808-0325-0040 DFJ40 0808-0325-3560 CH60J1i 50A 0808-0325-0050 DFJ50 0808-0325-3560 CH60J1i 63A 0808-0325-0060 DFJ60 0808-0325-3560 CH60J1i 80A 0808-0325-0080 DFJ80 0808-0325-7010 J60100-1CR 100A 0808-0325-0100 DFJ100 0808-0325-7010 J60100-1CR
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
142 mm (5.59 in)
131 mm (5.17 in)
146 mm (5.74 in)
102 mm (4.0 in)
Front panel is touch-safe, no clearance is required.
102 mm (4.0 in) clearance for air flow and wire bending radius
102 mm (4.0 in) clearance for air flow and wire bending radius
150 mm (5.89 in)
44 mm
(1.73 in)
57 mm
(2.26 in)
127 mm (5.00 in)
79 mm
(3.10 in)
102 mm (4.0 in) minimum
Side
Rail Release Tab (pull down)
194.1 mm (7.64 in)
1. Push the unit in and down to catch the rail hook on top of the rail.
2. Rotate the bottom of the unit in toward the rail.
3. The rail clasp will audibly “snap” into place. If the DIN-A-MITE does not snap into place, check to see if the rail is bent.
4. Mount the cooling fins vertically.
ç
3
WARNING: Only authorized and qualified personnel should be allowed to install and perform preventive and corrective maintenance on this unit. Failure to follow this guideline could result in damage to equipment, and personal injury or death.
5
WARNING: Hot surface, do not touch the heat sink. Failure to follow this guideline could result in personal injury.
ç
Mount the cooling fins vertically.
Unit Dimensions - Fan-Cooled
ç Ó
3
5
1
1
2
Mount
Dismount
6
WATLOW DIN-A-MITE Style C User's Manual
1. Press down on the release tab while rotating the unit up and away from the rail.
3
4
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
WATLOW DIN-A-MITE Style C User's Manual
7
ç Ó
3
WARNING: Only authorized and qualified personnel should be allowed to install and perform preventive and corrective maintenance on this unit. Failure to follow this guideline could result in damage to equipment, and personal injury or death.
5
WARNING: Hot surface, do not touch the heat sink. Failure to follow this guideline could result in personal injury.
ç
Mount the cooling fins vertically.
Unit Dimensions - Rail-Mounted
ç Ó
3
5
142 mm (5.59 in)
131 mm (5.17 in)
146 mm (5.74 in)
102 mm (4.0 in)
Front panel is touch-safe, no clearance is required.
102 mm (4.0 in) clearance for air flow and wire bending radius
102 mm (4.0 in) clearance for air flow and wire bending radius
150 mm (5.89 in)
Rail Release Tab
(pull down)
44 mm
(1.73 in)
57 mm
(2.26 in)
127 mm (5.00 in)
79 mm
(3.10 in)
102 mm (4.0 in) minimum
Side
Front
138 mm (5.45 in)
54 mm (2.11 in)
46 mm (1.81 in)
38 mm (1.51 in)
123
456
48 mm
(1.89 in)
Allowance for M4 (#8 Fastener)
Allowance for M4 (#8 Fastener)
DIN-EN 50022 35 by 7.5 mm rail (clipping distance =
34.7 to 35.3 mm [1.366 to 1.390 in])
87 mm
(3.42 in)
Ground wire entry
146 mm (5.74 in)
83 mm
(3.25 in)
Top
13 mm
(0.50 in)
Side by side
clearance
for wire routing
Unit Dimensions - Through-Wall (Cabinet Panel)
Top
114 mm (4.50 in)
57 mm (2.25 in)
outside
(any gauge)
55 mm (2.17 in)
inside
(12 gauge)
Front panel is touch-safe, no clearance is required.
Sheet Metal (12 gauge)
ç Ó
3
5
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
8
WATLOW DIN-A-MITE Style C User's Manual
Mounting
Mounting procedure for UL® 50 Type 4X Enclosure and UL® / ANSI 12.12.01 Through­wall mount models
Materials included:
(1) Silicone gasket
(8) M5 screws and
lockwashers
(1) DIN-A-MITE C
through-wall
1. Drill and cut the panel as shown in the dimensioned drawing at right.
2. Remove the mounting screws from the heatsink.
3. Peel off the protective film from the silicone gasket. Stick the gasket to the heatsink so the gasket holes line up with the screw holes in the heatsink.
4. Mount the heatsink vertically. Torque to
2.26 to 2.82 Nm (20 to 25 in-lb).
Ground lug (2-8 GA
M5 (0.8 by 10 mm) (8) M5 Internal Tooth Lock Washer (8) included
178 mm (7.00 in)
122 mm (4.81 in)
Panel Opening Outline
102 mm (4.0 in) minimum clearance for air flow (top and bottom)
10 mm (0.4 in) minimum clearance for air flow (both sides)
Front
123
456
Current Transformer Dimensions
Typical Panel Opening
Drill 5.8 mm (0.228 in) (8)
Heatsink Outline
9.5 mm (0.375 in) Reference
10.8 mm (0.425 in)
41.3 mm
(1.625 in)
117.5 mm (4.625 in)
148.6 mm (5.850 in)
161.9 mm (6.375 in)
8.6 mm (0.338 in) Reference
7.0 mm (0.275 in)
78.8 mm
(3.103 in)
98.1 mm
(3.862 in)
105.1 mm (4.137 in)
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
26.3 mm (1.034 in)
WATLOW DIN-A-MITE Style C User's Manual
9
ç Ó
1
WARNING: Use National Electric (NEC) or other country-specific standard wiring practices to install and operate the DIN­A-MITE. Failure to do so may result in damage to equipment and property, and/or injury or loss of life.
Ó
3
WARNING: Only authorized and qualified personnel should be allowed to install and perform preventive and corrective maintenance on this unit. Failure to follow this guideline could result in damage to equipment, and personal injury or death.
Ó
4
WARNING: Do not use the DIN-A-MITE Vac-input models with a temperature controller that includes an RC snubber circuit across its output. Remove the RC snubber circuit before placing the DIN-A-MITE into service.
NOTE: Alarm options not available with multizone input option.
Input Wiring
ç Ó
1
Ó
3
Ó
4
(For models DC [1, 2, 3] _ - _ _ [C, F, K] _ - _ _ _ _)
7 8
9 10 11 12 13 14 15 16 17 18 19 20
1 2 3
4 5 6
Signal Alarm
Gain
Bias
Open
Heater
Limit
+
-
+
-
Adjustment
Potentiometers
Zone 1 VÎ (dc) Input: +
Zone 3 VÎ (dc) Input: +
Zone
1
Zone
2
Zone
3
-
-
7 8 9
10 11 12 13 14 15 16 17 18 19 20
1 2 3
4 5 6
Signal Alarm
Gain
Bias
Open
Heater
Limit
Adjustment
Potentiometers
+
-
+
-
+
-
Zone 1 VÎ (dc) Input: + Zone 2 VÎ (dc) Input: +
-
-
Zone 3 VÎ (dc) Input: +
-
Zone
1
Zone
2
Zone
3
2-zone
3-zone
Multizone Input Wiring
ç Ó
1
Ó
3
Ó
4
(For models DC [8, 9] _ - _ _ _[C, K] - 0 _ _ _)
V~ (ac) Input:
7 8
9 10 11 12 13
+
-
Zone 1
Zone 3
V~ (ac) Input:
Zone 1 V~ (ac) Input:
7 8
9 10 11 12 13
+
-
Zone 2 V~ (ac) Input:
Zone 3 V~ (ac) Input:
4.5Vdc 9.0Vdc 12.0Vdc 24.0Vdc 32.0Vdc
DC21-24C0-5000 13.18mA 15.02mA 16.09mA 20.14mA 22.53mA
Typical DIN-A-MITE Current Draw:
1 2 3
+
VÅ (ac) Input:
4 to 20mAÎ (dc) Input: +
4.5 to 32VÎ (dc) Input: +
7
8
-
9
7
8
-
9
7
-
8
9 10 11
+
12
-
13 14 15 16
+
17
-
18 19 20
Note: Use tool Bourns H91 to adjust
Signal Alarm
Zone
1
4 5 6
Adjustment
Potentiometers
Zone
2
Zone
Gain
Bias
Open
Heater
Limit
3
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
10
WATLOW DIN-A-MITE Style C User's Manual
NOTE: The potentiometer and resistors are customer­supplied. For the potentiometer control assembly only, order Watlow part number 08-5362.
ç
NOTE: The potentiometer is customer-supplied. For the potentiometer only, order Watlow part number 08-5362.
Input Wiring
7 8
9 10 11 12 13 14 15 16 17 18 19 20
Signal Alarm
Gain
Bias
Open
Heater
Limit
Adjustment
Potentiometers
+
-
4 to 20mAÎ (dc) Input +
7 8 9
+
-
Linear voltage VÎ (dc) Input +
-
-
123
456
Zone
1
Zone
2
Zone
3
1kΩ
Potentiometer
7 8
9 10 11 12 13 14 15 16 17 18 19 20
1 2 3
4 5 6
Signal Alarm
Gain
Bias
Open
Heater
Limit
+
-
CW
Adjustment
Potentiometers
Counterclockwise
Clockwise
Zone
1
Zone
2
Zone
3
1kΩ Potentiometer Input
Use with 0 to 5VÎ (dc) Input
4 to 20mA and Linear Voltage Input
ç Ó
1
Ó
3
(For models DC [1, 2, 3] _ - _ _ [L, P, S] _ - _ _ _ _)
Auto and Manual Input Application
4 to 20mA Î (dc) signal from the temperature controller
1kΩ
Potentiometer
0 to 5VÎ (dc) signal from the temperature controller
Clockwise
Counterclockwise
When you use the 4 to 20 mAÎ (dc) temperature controller output and the DIN-A-MITE control input 1 to 5VÎ (dc).
200Ω resistor
250Ω
1kΩ
Potentiometer
Clockwise
Manual
Auto
Auto
Manual
If you use the 0 to 5VÎ (dc) temperature controller output, order the DIN-A-MITE control input 0 to 5VÎ (dc).
7 8
9 10 11 12 13 14 15 16 17 18 19 20
1 2 3
4 5 6
Signal Alarm
Gain
Bias
Open
Heater
Limit
Adjustment
Potentiometers
+
-
CW
7 8 9
+
-
CW
-
+
Zone
1
Zone
2
Zone
3
Counterclockwise
ç Ó
1
Ó
3
(For models DC [1, 2, 3] _ - _ _ [L, P, S] [3, 4] - _ _ _ _ )
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
WATLOW DIN-A-MITE Style C User's Manual
11
Current
Transformer
(CT)
Heater
Load Wire
7 8
9 10 11 12 13 14 15 16 17 18 19 20
1 2 3
4
Signal Alarm
Gain
Bias
Open
Heater
Limit
+
-
CT1
CT1
Adjustment
Potentiometers
Input Signal: +
-
Zone
1
Zone
2
Zone
3
5
6
Input Wiring Phase Angle with Current Limit
The DC1 _ - _ _ L _ - 0 _ _ _ model is a phase angle-controller that can limit the maximum current to the load. A potentiometer on the DIN-A­MITE adjusts the current limit setting. Use the following steps to adjust the current limit on initial setup. The purpose of the procedure is to bring the power to the load slowly so that the desired maximum current to the load is not exceeded before the current limit is adjusted.
NOTE: The DIN-A-MITE is shipped factory-calibrated with the potentiometer adjusted fully clockwise (no current limiting). Adjust the potentiometer clockwise to increase the current; counterclockwise to decrease the current.
NOTE: A short overcurrent through the load may occur, as the circuitry detects the high current, if the input signal from the temperature controller is abruptly increased.
1. Attach a clamp-on ammeter to the load line.
2. Adjust the current limit potentiometer fully counterclockwise (for minimum current flow).
3. Turn the temperature controller on and adjust the input signal to the DIN-A-MITE for zero percent power.
4. Turn on the power to the DIN-A-MITE.
5. Gradually increase the input signal.
6. Adjust the current limit potentiometer clockwise until the current to the load is measurable. The current limit indicator (Zone 3) light should turn on until the output is allowed to go full on, with no limit. At that point, the indicator light will turn off.
7. Gradually increase the input signal to 100% power, then adjust the current limit potentiometer to obtain the desired maximum current to the load.
Ó
1
WARNING: Use National Electric (NEC) or other country-specific standard wiring practices to install and operate the DIN­A-MITE. Failure to do so may result in damage to equipment and property, and/or injury or loss of life.
Ó
2
WARNING: Wiring examples show L2 in phase-to-phase, 200VÅ (ac) and above configuration. In phase-to­neutral, 100VÅ (ac) and above applications, L2 is neutral and must not be fused or switched. Failure to follow this guideline could result in personal injury or death.
Ó
3
WARNING: Only authorized and qualified personnel should be allowed to install and perform preventive and corrective maintenance on this unit. Failure to follow this guideline could result in damage to equipment, and personal injury or death.
NOTE: The alarm options are not available with phase angle units.
Current Limit Adjustment Procedure
ç Ó
1
(Model DC1 _ - _ _ L [0, 1, 2, 3, 4, 5] - _ _ _ _ ) Linear current and linear voltage input
The Zone 3 indicator light serves as the current-limit indicator in phase-angle, current-limit models.
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
12
WATLOW DIN-A-MITE Style C User's Manual
Alarm Relay
or Indicator
V~
120 or 240V~
@ 300mA maximum
energizes on alarm
1A
7 8
9 10 11 12 13 14 15 16 17 18 19 20
1 2 3
4
Signal Alarm
Gain
Bias
Open
Heater
Limit
+
-
+
-
+
-
ALM
ALM
CT1
CT1
CT2
CT2
CT3
CT3
Adjustment
Potentiometers
Triac
Zone
1
Zone
2
Zone
3
ALM = Alarm CT = Current Transformer
Current
Transformer
(CT)
Heater
Load Wire
5
6
Single-phase Alarm
Non-latching Alarm Option DC _ _ - _ _ _ _ - [H, S] _ _ _
NOTE:If you plan to wire multiple DIN-A-MITE alarm outputs, you need to include an intermediate relay for each DIN-A-MITE used.
The Watlow DIN-A-MITE alarm option provides a common alarm output for open-heater or shorted SCR conditions. This is a non-latching
alarm.
• A shorted SCR alarm is detected when there is no command signal and a load current is detected. The alarm output is then energized.
• An open-heater or partial open-heater state is detected when a command signal is present and a reduced or no output current is detected. The alarm output is then energized.
Setup Procedure for Open-Heater Alarm
(For Input Control Signal type S option only)
1. With the temperature control wired to the DIN-A-MITE SCR power control, set the temperature control output to “full on” (20mA for 4 to 20mA output, or 5V for 0 to 5V output).
2. Adjust the open heater alarm adjustment potentiometer until the alarm indicator light on the front panel is full on, with no intermittent cycling.
3. Slowly adjust the potentiometer until the open heater indicator light just turns full off, with no intermittent cycling.
If you are getting false alarms, the adjustment is probably set too sensitive and should be re­adjusted towards the off condition of the open­heater indicator light. The open heater pot is adjusted counter clockwise to increase sensitivity to open heater detect (red light on sooner) or clockwise to desensitize to open heater detect (red light on later).
No setup procedure required for shorted SCR alarm.
Load Current -
Single phase load wire passes through one CT. Number of passes through CT:
5 to 9A 2 10 to 65A 1
T1
T2
T3
7 8
9 10 11 12 13 14 15 16 17 18 19 20
Gain
Bias
Open
Heater
Limit
+
-
+
-
+
-
ALM
ALM
CT1
CT1
CT2
CT2
CT3
CT3
Adjustment
Potentiometers
Signal Alarm
4 5 6
1 2 3
Zone
1
Zone
2
Zone
3
ALM = Alarm CT = Current Transformer
Heater
Current Transformers
white
black
3-phase, 2-leg Open Heater Alarm
NOTE:
Load wires must pass through each current transformer in the same direction.
(Model DC2 _ - _ _ S _ - H _ _ _ )
ç Ó
1
Ó
3
ç Ó
1
Ó
3
Load Current -
3-phase 2-leg load wire passes through 2 CTs. Number of passes through each:
5 to 6A 7 7 to 9A 6 10 to 14A 4 15 to 19A 3 20 to 33A 2 34A and up 1
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
WATLOW DIN-A-MITE Style C User's Manual
13
Fan-Cooled
ç Ó
1
Ó
3
7 8
9 10 11 12 13 14 15 16 17 18 19 20
Gain
Bias
Open
Heater
Limit
+
-
+
-
+
-
ALM
ALM
CT1
CT1
CT2
CT2
CT3
CT3
Adjustment
Potentiometers
Signal Alarm
4 5 6
1 2 3
Zone
1
Zone
2
Zone
3
ALM = Alarm CT = Current Transformer
T1
T2
T3
Heater
Current
Transformers (CT)
CT
black
white
white
black
white
Neutral
3-phase, 3-leg Alarm, Shorted SCR and Open Heater Alarm
ç
NOTE: Adjust the potentiometer clockwise to increase the current; counterclockwise to decrease the current.
Ó
1
WARNING: Use National Electric (NEC) or other country-specific standard wiring practices to install and operate the DIN­A-MITE. Failure to do so may result in damage to equipment and property, and/or injury or loss of life.
Ó
3
WARNING: Only authorized and qualified personnel should be allowed to install and perform preventive and corrective maintenance on this unit. Failure to follow this guideline could result in damage to equipment, and personal injury or death.
NOTE: The shorted SCR alarm option is not available with phase angle units.
Torque Guidelines
• Properly torque line and load terminals to 2.7 Nm (24 in-lb).
• Retorque after 48 hours to minimize wire cold flow.
• Retorque line and load terminals every 3 to 6 months.
ç Ó
1
Ó
3
3-phase, 2-leg Shorted SCR Alarm
(Model DC2 _ - _ _ [C, F, K, S] _ - S _ _ _ )
(Model DC3 _ - _ _ _ _ - [S, H] _ _ _ )
T1
T2
T3
7 8
9 10 11 12 13 14 15 16 17 18 19 20
Gain
Bias
Open
Heater
Limit
+
­+
­+
-
ALM
ALM
CT1
CT1
CT2
CT2
CT3
CT3
Adjustment
Potentiometers
Signal Alarm
4 5 6
1 2 3
Zone
1
Zone
2
Zone
3
ALM = Alarm CT = Current Transformer
Heater
ç Ó
1
Ó
3
Shorted SCR Alarm Only
NOTE:
Cooling fan terminals:
Quick connect 1/8" push on, #16-14 AWG
Amp part no. 640929-1 or equivalent
45
6
15
16
Current
Transformer (CT)
Neutral
T3
T2
T1
1 2 3
Find Quality Products Online at: sales@GlobalTestSupply.com
Fan power required 24VÎ (dc) 115V~ (ac) 240V~ (ac) (customer supplied)
Black wire (-)
24VÎ (dc)
Red wire (+)
Phase to neutral
L1 L2
Phase to phase
L1 L2
www.GlobalTestSupply.com
7
8
9 10 11 12 13 14 15 16 17 18 19 20
+
-
CT1
CT1
Signal Alarm
Zone
1
4 5 6
Adjustment
Potentiometers
Zone 2Zone
Gain
Bias
Open
Heater
Limit
3
14
WATLOW DIN-A-MITE Style C User's Manual
ç
Ó
1
WARNING: Use National Electric (NEC) or other country­specific standard wiring practices to install and operate the DIN-A-MITE. Failure to do so may result in damage to equipment and property, and/or injury or loss of life.
Ó
2
WARNING: Wiring examples show L2 in phase-to-phase, 200VÅ (ac) and above configuration. In phase-to­neutral, 100VÅ (ac) and above applications, L2 is neutral and must not be fused or switched. Failure to follow this guideline could result in personal injury or death.
Ó
3
WARNING: Only authorized and qualified personnel should be allowed to install and perform preventive and corrective maintenance on this unit. Failure to follow this guideline could result in damage to equipment, and personal injury or death.
Torque Guidelines
• Properly torque line and load terminals to 2.7 Nm (24 in-lb).
• Retorque after 48 hours to minimize wire cold flow.
• Retorque line and load terminals every 3 to 6 months.
Single-phase Output
ç Ó
1
Ó
2
Ó
3
3-phase, 2-leg Output
ç Ó
1
Ó
2
Ó
3
(Model DC1 _ - _ _ _ _ - _ _ _ _ )
(Model DC2 _ - _ _ _ _ - _ _ _ _ )
Semiconductor Fuse
1 2 3
+
7
-
8
+
9
-
10
+
11
-
12
ALM
13
ALM
14
CT1
15
CT1
16
CT2
17
CT2
18
CT3
19
CT3
20
Signal Alarm
Zone
1
4 5 6
Zone
Internal Busbar
Zone
3
2
Gain
Bias
Open
Heater
Limit
Limit Control
Contacts
(if required)
Adjustment
Potentiometers
Heater
Phase-to-phase 200V~ (ac) and above
L1
L2
Phase-to-neutral 100V~ (ac) and above
L1
Neutral
1 2 3
+
7
-
8
+
9
-
10
+
11
-
12
ALM
13
ALM
14
CT1
15
CT1
16
CT2
17
CT2
18
CT3
19
CT3
20
Internal Busbar
Signal Alarm
Zone
Zone
Zone
2
1
4 5 6
3
Semiconductor Fuses
Adjustment
Gain
Potentiometers
Bias
Open
Heater
Limit
Limit Control
Contacts
(if required)
L1
L2
L3
T3
Heater
T2
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
T1
WATLOW DIN-A-MITE Style C User's Manual
15
Neutral
Limit Control
Contacts
(if required)
Semiconductor Fuses
L2
L1
L3
7 8
9 10 11 12 13 14 15 16 17 18 19 20
Gain
Bias
Open
Heater
Limit
+
-
+
-
+
-
ALM
ALM
CT1
CT1
CT2
CT2
CT3
CT3
Adjustment
Potentiometers
Signal Alarm
4 5 6
1 2 3
Zone
1
Zone
2
Zone
3
Heater
3-phase, 3-leg Output, Four Wire Wye
ç Ó
1
Ó
2
Ó
3
Heater
2
Heater
3
Heater
1
L2
L2
L2
Limit Control
Contacts
(if required)
Semiconductor
Fuses
L1
L1
L1
Line
Voltage
3 Independent,
Single-Phase Heaters
7 8
9 10 11 12 13 14 15 16 17 18 19 20
Gain
Bias
Open
Heater
Limit
+
-
+
-
+
-
ALM
ALM
CT1
CT1
CT2
CT2
CT3
CT3
Signal Alarm
4 5 6
1 2 3
Zone
1
Zone
2
Zone
3
3-zone
Multizone Output Wiring
2-zone
(For models DC [8, 9] _
- _ _ [C, K] _
- 0 _ _ _
Ó
1
Ó
2
Ó
3
NOTE: Independent loads do not have to be on the same phase.
(Model DC3 _ - _ _ _ _ - _ _ _ _ )
NOTE:
Do not exceed 80 amps on center leg.
1 2 3
Signal
Zone
1
4 5 6
L2
Semiconductor
Alarm
Zone
Gain
Bias
Open
Heater
Limit
3
Zone
2
2 Independent,
Single-Phase
Heaters
L2
www.GlobalTestSupply.com
Fuses
Limit Control
Contacts
(if required)
Line
Voltage
L1
L1
+
7
-
8
Find Quality Products Online at: sales@GlobalTestSupply.com
+
9
-
10
+
11
-
12
ALM
13
ALM
14
CT1
15
CT1
16
CT2
17
CT2
18
CT3
19
CT3
20
16
WATLOW DIN-A-MITE Style C User's Manual
ç
Ó
1
WARNING: Use National Electric (NEC) or other country-specific standard wiring practices to install and operate the DIN­A-MITE. Failure to do so may result in damage to equipment and property, and/or injury or loss of life.
Ó
2
WARNING: Wiring examples show L2 in phase-to-phase, 200 VÅ (ac) and above configuration. In phase-to-neutral, 100 VÅ (ac) and above applications, L2 is neutral and must not be fused or switched. Failure to follow this guideline could result in personal injury or death.
Ó
3
WARNING: Only authorized and qualified personnel should be allowed to install and perform preventive and corrective maintenance on this unit. Failure to follow this guideline could result in damage to equipment, and personal injury or death.
NOTE: If you plan to wire multiple DIN-A-MITE alarm outputs, you need to include an intermediate relay for each DIN-A-MITE used.
System Wiring Example
Alternative Latching Alarm Circuit
If there is a need for a latching alarm in the case of an open heater or shorted SCR, the DIN-A-MITE alarm circuit could be used as shown in the latching alarm example at right. If the DIN-A-MITE triac alarm output energizes, it will energize the RY1 (external alarm relay) mechanical relay coil. Once the RY1 coil is energized it will latch on (via the RY1A normally open contact) until the power to the relay is removed. You could cycle the power via a reset switch. The RY1B contact set can be used for alarm signaling.
L3
480VÅ (ac)
AC Common
CR1 = High-Limit Contactor
L2
L1
Quencharc
CR1
Coil
Controller TC
High Limit TC
Breaker
-
F1
G1
+
H1
T1
S1
R1
PM6C2FA - ALAJAAA
L4
K4
T2
S2
R2
480V~ (ac)
120V~ (ac)
To DIN-A-MITE C
Pin 7+, 8- (page 17)
98
99
CC
CA
CB
B5
D6
D5
AC High
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
WATLOW DIN-A-MITE Style C User's Manual
17
Ungrounded Delta or Wye Load 3-phase, 2-leg DIN-A-MITE
NOTE: The current transformers must be in the controlled legs on a 2-leg DIN-A-MITE. The load wires must pass through the current transformers in the same direction.
Non-latching Alarm Option (models DC_ _ -
_ _ S _ - H _ _ _ )
Open Heater and Shorted SCR Alarm
The shorted SCR detector compares the input command signal and actual load current. If load current is present without an input signal then the shorted SCR alarm will energize a triac (on board the DIN-A-MITE) output.
An open-heater or partial open-heater state is detected when a command signal is present and a reduced or no output current is detected. The alarm output is then energized.
This is a non-latching alarm. This output can be used to drive various indication devices, such as a coil, light, buzzer, etc. See the alternative latching circuit section below.
Contactor (CR1)
Semiconductor
From Temperature Control Pin F1+, H1- (page 16)
Alarm Relay
V~
(ac)
120 or 240V~ (ac) @ 300mA maximum energizes on alarm
or Indicator
1A
High-limit
Fuses
7
8
9 10 11 12 13 14 15 16 17 18 19 20
1 2 3
+
-
+
-
+
-
ALM
ALM
CT1
DC20-48S0-H000
CT1
CT2
CT2
CT3
CT3
Potentiometers
DIN-A-MITE
2-Leg
Signal Alarm
Zone 2Zone
Zone
1
4 5 6
black
Adjustment
3
white
Gain
Bias
Open
Heater
Limit
Current
Transformers
6
54
Ungrounded
Wye Load
Delta Load
Triac
13
14
Reset Switch
RY1B
L1
RY1A
(External alarm relay contacts, set A)
RY1 Coil
VÅ
L2
Latching Alarm Relay Circuit
(External alarm relay contacts, set B)
Normally open
Common
Normally closed
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
18
WATLOW DIN-A-MITE Style C User's Manual
DIN-A-MITE®“C” Power Controller
WATLOW Electric Manufacturing Company 1241 Bundy Blvd. Winona, MN 55987 USA
Declares that the following products:
Designation: DIN-A-MITE
®
“C” Power Control
Model Numbers: DC(1, 2, 3, 8 or 9)(0, 1, 2, 3 or T) – (02, 12, 20, 24, 27, 40, 48 or 60) (CX, K1, K2, K3, FX, SX) -
(0, H or S)(followed by any 3 numbers or letters) X = any number 0 - 9
Classification: Power Control, Installation Category III, Pollution degree 2, IP20
Rated Voltage: 24 to 600 V
~ (ac), 50 or 60 Hz
Meets the essential requirements of the following European Union Directives by using the relevant standards show below to indicate compliance.
2004/108/EC Electromagnetic Compatibility Directive
EN 61326-1: 2013 Electrical equipment for measurement, control and laboratory use - EMC
requirements (Industrial Immunity, Class A
1,2,4
Emissions) Not for use in a Class B
environment without additional filtering.
EN 61000-4-2:2009 Electrostatic Discharge Immunity
EN 61000-4-3:2010 Radiated Field Immunity 10V/m 80 MHz- 1GHz, 3V/m 1.4GHz-2.7GHz
EN 61000-4-4:2012 Electrical Fast-Transient / Burst Immunity
EN 61000-4-5:2006 Surge Immunity (Reviewed to IEC 61000-4-5 2014)
EN 61000-4-6:2014 Conducted Immunity
EN 61000-4-11:2004 Voltage Dips, Short Interruptions and Voltage Variations
EN 61000-3-2:2009 Harmonic Current Emissions (Reviewed to IEC 61000-3-2 2014)
EN 61000-3-3:2013 Voltage Fluctuations and Flicker
3
16A
EN 61000-3-11:2000 Voltage Fluctuations and Flicker
75A with conditional connection
NOTES
1
Use of an external filter is required to comply with conducted emissions limits. See note 4 below.
2
A Line Impedance Stabilization Network (LISN) was used for conducted emissions measurements.
3
To comply with flicker requirements, command signal models FX and SX will require a reduced source impedance. Cycle time on ON/OFF models CX, and K1, K2, K3 may need to be up to 175 seconds at 16A or have a reduced source impedance.
2006/95/EC Low-Voltage Directive
EN 50178:1997 Electronic equipment for use in power installations.
Per 2012/19/EU W.E.E.E Directive Please Recycle Properly.
Compliant with 2011/65/EU RoHS2 Directive
4
Required External EMI Filters for DIN-A-MITE with More Than 6 Amp Loads
An external ElectroMagnetic Interference (EMI) filter must be used in conjunction with the DIN-A- MITE for loads in excess of six amperes (6A) at 150 to 250 KHz. Watlow has verified that a tank filter will suppress EMI created by SCR power controllers to comply with the conducted emissions limits.
ISO 9001since 1996.
Declaration of Conformity
DIN-A-MITE EMI Filters
Description Crydom Filter Watlow Filter
Single-phase, 230VÅ (ac)
1F25 14-0019
Three-phase, 440VÅ (ac)
3F20 14-0020
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
WATLOW DIN-A-MITE Style C User's Manual
19
ç WARNING: Tank filters may suppress desirable communications carried on power lines in
the 150 to 250 KHz region. The filters may suppress carrier current such as that used for infant monitors and medical alert systems. Verify that suppressed carrier current or other desirable communications on power lines creates no hazard to people or property. Failure to observe this warning could result in damage to property, and or injury to death for personnel.
ç WARNING: All filter installation and wiring must be performed by qualified personnel and
conform to local and national electrical codes.
In-line power filters have been shown to properly suppress EMI; however, these filters must be rated for the entire load current and are generally more expensive than the tank filter specified. An In-line filter may be required if carrier current communications are used on site.
Joe Millanes
Winona, Minnesota, USA
Name of Authorized Representative Place of Issue
Director of Operations September 2014 Title of Authorized Representative Date of Issue
Signature of Authorized Representative
T1
T2
T3
7
8
9 10 11 12 13 14 15 16 17 18 19 20
Gain
Bias
Open
Heater
Limit
+
­+
­+
-
ALM
ALM
CT1
CT1
CT2
CT2
CT3
CT3
Signal Alarm
Internal Busbar
4 5 6
1 2 3
Zone
1
Zone
2
Zone
3
Heater
Alternate
L1
Semiconductor
Fuses
Filter
5A
5A
5A
L3
L2
Limit Control
Contacts
(if required)
Tank Filter, Three Phase, 440V
Tank Filter, Single Phase, 230V
Semiconductor
Fuse
5A
Filter
1 2 3
+
7
-
8
+
9
-
10
+
11
-
12
ALM
13
ALM
14
CT1
15
CT1
16
CT2
17
CT2
18
CT3
19
CT3
20
Signal Alarm
Zone
1
4 5 6
Zone
Internal Busbar
Zone
3
2
Open
Heater
Limit
Gain
Bias
Limit Control
Contacts
(if required)
Adjustment
Potentiometers
Heater
Phase-to-phase 200V~ (ac) and above
L1
L2
Phase-to-neutral 100V~ (ac) and above
L1
Neutral
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com
20
WATLOW DIN-A-MITE Style C User's Manual
The Watlow DIN-A-MITE is warranted to be free of defects in material and workmanship for 36 months after delivery to the first purchaser for use, providing that the units have not been misapplied. Since Watlow has no control over their use, and sometimes misuse, we cannot guarantee against failure. Watlow's obligations hereunder, at Watlow's option, are limited to replacement, repair or refund of purchase price, and parts which upon examination prove to be defective within the warranty period specified. This warranty does not apply to damage resulting from transportation, alteration, misuse, abuse or improper fusing.
ReturnsWarranty
1.
• Ship to address
• Bill to address
• Contact name
• Phone number
• Method of return shipment
• Your P.O. number
• Detailed description of the problem
• Any special instructions
• Name and phone number of the person returning the product
2. Prior approval and an RMA number, from the Customer Service Department, is required when returning any unused product for credit. Make sure the RMA number is on the outside of the carton, and on all paperwork returned. Ship on a Freight Prepaid basis.
3. After we receive your return, we will examine it and try to verify the reason for the return.
4. In cases of manufacturing defect, we will enter a repair order, replacement order or issue credit for material returned.
5. To return products that are not defective, goods must be in new condition, in the original boxes and they must be returned within 120 days of receipt. A 20 percent restocking charge is applied for all returned stock controls and accessories.
6. If the unit is unrepairable, it will be returned to you with a letter of explanation.
7. Watlow reserves the right to charge for no trouble found (NTF) returns.