Watlow DB20-60C0-0000, DB80-60K2-0000, DB20-02C0-0000, DB20-60K3-0000, DB90-02C0-0000 User manual

...
DIN-A-MITE
®
Style B
Solid-State Power Controller
User’s Manual
DIN-A-MITE Solid-State Power Controller
0600-0025-0005 Rev M Made in the USA
Please consult this user’s manual when you place your new DIN-A-MITE into service. It contains all the necessary information to mount and wire the product into the application. This manual also contains all user-pertinent specifications and semiconductor fusing recommendations. Refer to national and local electrical code safety guidelines whenever you install electrical equipment.
This DIN-A-MITE product is capable of switching up to 40 amps single-phase; 33 amps 3-phase, 2-leg; and 22 amps 3-phase, 3-leg at 600V
Å (ac). (See the output rating curve in the
specifications section of this manual.) The DIN-
A-MITE is electrically touch-safe, and includes DIN rail or standard back panel mounting. An optional shorted SCR (silicon controlled rectifier) alarm feature is available on specific models. UL
®
508-listed, C-UL®and CE with filter.
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
2
WATLOW DIN-A-MITE Style B User's Manual
General Specifications
Operator Interface
• Command signal input and indication light
• Alarm output and indication light
• Input indicator LED
Amperage Rating
• See the output rating curve chart on page 3.
• Ratings are into a resistive heater load.
• Maximum surge current for 16.6 milliseconds, 380 A peak
• Maximum I2t for fusing is 4000 A2s
• Latching current: 200mA minimum
• Holding current: 100mA minimum
• Off-state leakage 1mA at 25°C (77°F) maximum
• Power Dissipation: 1.2 watts per amp switched
• 200KA SCCR type 1 and 2 approved with the recommended fusing (see page 3)
Line Voltage
• 24 to 48V~ (ac) units: 20.4V~ minimum to 53V~ maximum
• 120 to 240V~ (ac) units: 48V~ minimum to 265V~ maximum
• 277 to 600V~ (ac) units: 85V~ minimum to 660V~ maximum
Control Mode, Zero-Cross
• Input Control Signal Type C: VÎ (dc) input contactor. To increase service life, the cycle time should be less than 3 seconds.
• Input Control Signal Type K: V~ (ac) input contactor. To increase service life, the cycle time should be less than 3 seconds.
• Input Control Signal Type F: 4 to 20mAÎ (dc) proportional variable time base control.
Input Command Signal
AC contactor
24VÅ ±10%, 120VÅ +10%/-25%, 240VÅ (ac)
+10%/-25% @ 25mA maximum per controlled leg
• Do not use the DIN-A-MITE Vac-input models with a temperature controller that includes an RC snubber circuit across its output. Remove the RC snubber circuit before placing the DIN-A-MITE into service.
DC Contactor
4.5VÎ to 32VÎ (dc): maximum current @ 4.5VÎ (dc) is 6.0mA per leg, plus 2mA per LED used.
Loop powered linear current
4mAÎ to 20mAÎ (dc): loop-powered. Input Type F0 option only. (Requires current source with 8.0VÎ (dc) available. No more than two DIN-A­MITE inputs connected in series)
Linearity (Input Control Signal Type F)
• Full on point 19.5 to 19.9mAÎ (dc), maximum voltage
of 6.2V peak.
• ±5% input to output power accuracy, 0% to 100% of
span (4.3 to 19.7mA).
• Temperature stability is less than 0.15%/°C change.
Alarm (not available on multizone models)
Shorted SCR Alarm Option
• Alarm state when the input command signal off and a 10 A or more load current is detected by the current transformer (two turns required for 5A and three turns for 2.5A).
Alarm output
• Energizes on alarm, non-latching
• Triac 24 to 240V~ (ac), external supply with a current rating of 300mA @ 25°C (77°F), 200mA @ 50°C (122°F), 100mA @ 80°C (176°F) and a holding current of 200µA with a latching current of 5mA typical.
Agency Approvals
•ROHS
• CE with proper filter:
2004/108/EC Electromagnetic Compatibility Directive
EN 61326: Industrial Immunity Class A emissions
2006/95/EC Low Voltage Directive
EN 50178 Safety Requirements
Installation category III, pollution degree 2
•UL
®
508 listed and C-UL®, File E73741
Input Terminals
• Compression: Will accept 0.2 to 1.5 mm2(24 to 16
AWG) wire
• Torque to 0.5 Nm (4.4 in-lb) maximum with a 3.5 mm
(1/8 in) blade screwdriver
• Wire strip length 5.5 mm (0.22 in)
• Line and load wire insulation rating must be 75C or
higher, copper conductor only
Line and Load Terminals
• Compression: Will accept 0.75 to 10 mm2 (18 to 8
AWG) wire
• Torque to 1.4 Nm (12 in-lb) with a 6.4 mm (1/4 in)
blade screwdriver, or a Type 1A #2 Pozi driver.
• Retorque after 48 hours to minimize wire cold flow.
• Retorque line and load terminals every 3 to 6 months.
• Wire strip length 6.35 mm (0.25 in)
• Ground terminal use spade terminal for No. 8 screw,
with upturned lugs.
Operating Environment
• See the output rating curve.
• 0 to 90% RH (relative humidity), non-condensing
• Storage temperature: -40 to +85°C (-40 to 185°F)
• Insulation only tested to 3,000 meters
DIN Rail Mount
• DIN EN 50022, 35 mm by 7.5 mm
• Minimum clipping distance: 34.8 mm (1.37 in)
• Maximum clipping distance: 35.3 mm (1.39 in)
Note: Mount cooling fins vertically.
Back Panel Mount
• Four mounting holes M4 (No. 8) fastener
Weight
• 0.7 kg (1.6 lb)
Specifications are subject to change without notice.
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
WATLOW DIN-A-MITE Style B User's Manual
3
DIN-A-MITE B Ordering Information
To order, complete the code number on the right with the information below:
Style B = solid-state power controller D B _ _ - _ _ _ _ - _ _ _ _
Phase
1 = single-phase, 1 controlled leg 2 = 3-phase, 2 controlled legs 3 = 3-phase, 3 controlled legs (for 4-wire wye) 8 = 2 independent zones (input control C or K) 9 = 3 independent zones (input control C or K)
Cooling and Current Rating Per Pole
0 = Natural convection standard DIN rail or panel heatsink
Line and Load Voltage
02 = 24 to 48VÅ (ac) 24 = 120 to 240VÅ (ac) 60 = 277 to 600VÅ (ac)
Input Control Signal
C0 = 4.5 to 32VÎ (dc) contactor K1 = 22 to 26VÅ contactor K2 = 100 to 120VÅ contactor K3 = 200 to 240VÅ contactor F0 = Proportional 4 to 20mA
Alarm
0 = No alarm S = Shorted SCR Alarm (not available with phase options 8 or 9 above)
User Manual Language
0 = English 1 = German 2 = Spanish 3 = French
Custom Part Numbers
00 = Standard part XX = Any letter or number, custom options, labeling, etc.
Current Rating Table
Model Current
at 50°C (122°F)
DB10 35A DB20, DB80 25A DB30, DB90 17A
Note:
• Recommended fusing options to meet 200KA SCCR, type 1 and 2 approved. All other fuse and SCR combinations are defaulted to 5KA SCCR per UL508A and NEC guidelines.
Output Rating Curves
0 5 10 15 20 25 30 35 40 45 50 55 60
25
30
35
40
45
50
55
60
65
70
75
80
90
85
Current (Amps) into a Resistive Load
Maximum Internal Enclosure Ambient Temperature (°C)
DIN-A-MITE Style B Ratings at 100% On
Natural Convection
3-phase, 3-leg
3-phase, 2-leg
Single-phase
Recommended Fuse and Fuse Holder
Fuse
Watlow
Semiconductor
Bussmann
Semiconductor
Watlow
Combination
Bussmann
Combination
20A 17-8020 FWC20A10F 0808-0325-0020 DFJ20 25A 17-8025 FWC25A14F 0808-0325-0025 DFJ25
32A 17-8030 FWP32A14F 0808-0325-0030 DFJ30 40A 17-8040 FWP40A14F 0808-0325-0040 DFJ40
50A 17-8050 FWP50A14F 0808-0325-0050 DFJ50
Holders (single)
Fuse Watlow Bussmann Ferraz
Bussmann
Combination
20A 17-5110 - - - - USM1i - - - ­25A 17-5110 - - - - USM1i - - - ­32A 17-5114 - - - - USM141i - - - ­40A 17-5114 - - - - USM141i - - - -
15 to 30A 0808-0326-1530 - - - - - - - - CH30J1i 35 to 60A 0808-0326-3560 - - - - - - - - CH60J1i
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
4
WATLOW DIN-A-MITE Style B User's Manual
1. Push the unit in and down to catch the rail hook on top of the rail.
2. Rotate the bottom of the unit in toward the rail.
3. The rail clasp will audibly “snap” into place. If the DIN-A-MITE does not snap into place, check to see if the rail is bent.
4. Mount the cooling fins vertically.
ç
3
WARNING: Only authorized and qualified personnel should be allowed to install and perform preventive and corrective maintenance on this unit. Failure to follow this guideline could result in damage to equipment, and personal injury or death.
5
WARNING: Hot surface, do not touch the heat sink. Failure to follow this guideline could result in personal injury.
ç
Mount the cooling fins vertically.
1
1
2
Mount
Dismount
Front
Allowance for #8 fastener, metric = M4
Grounding screw (#6)
Allowance for #8 fastener,
metric = M4
DIN-EN 50022 35 mm by 7.5 mm rail (clipping distance 34.7 mm (1.366 in)
to 35.3 (1.390 in)
49 mm
(1.91 in)
49 mm
(1.92 in)
83 mm
(3.25 in)
54 mm
(2.11 in)
46 mm
(1.81 in)
38 mm
(1.51 in)
Unit Dimensions - Rail-Mounted
1. Press down on the release tab while rotating the unit up and away from the rail.
4
3
ç Ó
3
5
Side by side
clearance
for wire routing
13 mm
(0.50 in)
Top
124 mm (4.88 in)
83 mm
(3.25 in)
94 mm
(3.69 in)
102 mm (4.00 in) clearance for air flow
and wire bending radius
Side
75 mm
(2.97 in)
26 mm
(1.03 in)
40 mm
(1.56 in)
102 mm (4.00 in)
71 mm
(2.80 in)
Find Quality Products Online at: sales@GlobalTestSupply.com
Rail release tab
(pull down)
102 mm (4.00 in) clearance for air flow
and wire bending radius
Zero electrical clearance required
www.GlobalTestSupply.com
41 mm
(1.60 in)
102 mm (4.00 in)
WATLOW DIN-A-MITE Style B User's Manual
5
ç Ó
1
WARNING: Use National Electric (NEC) or other country-specific standard wiring practices to install and operate the DIN-A-MITE. Failure to do so may result in damage to equipment and property, and/or injury or loss of life.
Ó
2
WARNING: Wiring examples show L2 in phase-to-phase, 200VÅ (ac) and above configuration. In phase-to­neutral, 100 VÅ (ac) and above applications, L2 is neutral and must not be fused or switched. Failure to follow this guideline could result in personal injury or death.
Ó
3
WARNING: Only authorized and qualified personnel should be allowed to install and perform preventive and corrective maintenance on this unit. Failure to follow this guideline could result in damage to equipment, and personal injury or death.
Ó
4
WARNING: Do not use the DIN-A-MITE Vac-input models with a temperature controller that includes an RC snubber circuit across its output. Remove the RC snubber circuit before placing the DIN-A-MITE into service.
NOTE: Shorted SCR (silicon- controlled rectifier) alarm option not available with multizone input option.
V~ (ac) Input:
4 to 20 mAÎ (dc) Input: +
7 8 9
+
-
4.5 to 32 VÎ (dc) Input: +
7 8 9
+
-
-
-
7 8
9 10 11 12 13 14 15 16
1
23
4
56
Input Wiring
ç Ó
1
Ó
3
Ó
4
(For models DB [1, 2, 3] _ - _ _ [C, F, K] _ - _ _ _ _)
Zone 1 VÎ (dc) Input: +
Zone 2 VÎ (dc) Input: +
-
-
7
8
9 10 11 12 13 14 15 16
1
23
4
56
Zone 1 VÅ (ac) Input:
Zone 2 VÅ (ac) Input:
7 8
9 10 11 12 13
Zone 1 VÎ (dc) Input: +
Zone 2 VÎ (dc) Input: +
-
-
Zone 3 VÎ (dc) Input: +
-
7 8
9 10 11 12 13 14 15 16
1
23
4
56
Zone 1 VÅ (ac) Input:
Zone 2 VÅ (ac) Input:
Zone 3 VÅ (ac) Input:
7 8
9 10 11 12 13
2-zone
3-zone
Multizone Input Wiring
ç Ó
1
Ó
3
Ó
4
(For models DB [8, 9] _ - _ _ [C, K] _ - _ _ _ _)
3-zone
Multizone Output Wiring
2-zone
(For models DB [8, 9] _
- _ _ [C, K] _
- _ _ _ _
ç Ó
1
Ó
2
Ó
3
NOTE: Independent loads do not have to be on the same phase.
NOTE: Terminals 2 and 5 not to exceed 40A.
NOTE: Use a grounding conductor terminal plate (fork terminal) having upturned lugs or the equivalent to hold the wire in position. Maximum 6 mm
2
(10
AWG) wire.
Torque Guidelines
• Properly torque line and load terminals to 1.4 Nm (12 in-lb).
• Retorque after 48 hours to minimize wire cold flow.
• Retorque line and load terminals every 3 to 6 months.
4.5Vdc 9.0Vdc 12.0Vdc 24.0Vdc 32.0Vdc DB20-24C0-0000 13.0mA 14.0mA 15.0mA 16.0mA 17.0mA DB10-24C0-0000 8.0mA 8.0mA 9.0mA 10.0mA 10.0mA
Typical DIN-A-MITE Current Draw:
7 8
9 10 11 12 13 14 15 16
Heater 1
Find Quality Products Online at: sales@GlobalTestSupply.com
Semiconductor Fuses
23
1
Zone 2
Zone 1
56
4
Heater 2
L2
L2
Line
Voltage
L1
L1
Limit Control
Contacts
(if required)
2 Independent,
Single-Phase
Heaters
Semiconductor Fuses
23
1
7 8
9 10 11 12 13 14 15 16
Zone 2
Zone 3
Zone 1
56
4
Heater
1
Heater
3
L2
L2
L2
Heater
2
www.GlobalTestSupply.com
3 Independent,
Single-Phase Heaters
Limit Control
Contacts
(if required)
Line
Voltage
L1
L1
L1
6
WATLOW DIN-A-MITE Style B User's Manual
ç Ó
1
WARNING: Use National Electric (NEC) or other country-specific standard wiring practices to install and operate the DIN-A-MITE. Failure to do so may result in damage to equipment and property, and/or injury or loss of life.
Ó
2
WARNING: Wiring examples show L2 in phase-to-phase, 200VÅ (ac) and above configuration. In phase-to­neutral, 100VÅ (ac) and above applications, L2 is neutral and must not be fused or switched. Failure to follow this guideline could result in personal injury or death.
Ó
3
WARNING: Only authorized and qualified personnel should be allowed to install and perform preventive and corrective maintenance on this unit. Failure to follow this guideline could result in damage to equipment, and personal injury or death.
NOTE: Use a grounding conductor terminal plate (fork terminal) having upturned lugs or the equivalent to hold the wire in position. Maximum 6 mm
2
(10 AWG)
wire.
Torque Guidelines
• Properly torque line and load terminals to 1.4 Nm (12 in-lb).
• Retorque after 48 hours to minimize wire cold flow.
• Retorque line and load terminals every 3 to 6 months.
L1
L2
Limit Control Contacts (if required)
Semiconductor Fuse
Phase-to-phase 200V~ (ac) and above
Neutral
Phase-to-neutral 100V~ (ac) and above
Heater
7 8
9 10 11 12 13 14 15 16
1
23
4
56
L1
Single-phase Output
ç Ó
1
Ó
2
Ó
3
L2
L1
L3
T1
T2
T3
Limit Control
Contacts
(if required)
Semiconductor Fuses
Heater
7 8
9 10 11 12 13 14 15 16
1
23
4
56
3-phase, 2-leg Output
ç Ó
1
Ó
2
Ó
3
Neutral
Limit Control
Contacts
(if required)
Semiconductor Fuses
L2
L1
L3
Heater
7
8
9 10 11 12 13 14 15 16
1
23
4
56
3-phase, 3-leg Output
ç Ó
1
Ó
2
Ó
3
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
WATLOW DIN-A-MITE Style B User's Manual
7
Alarm Relay
or Indicator
V~
120 or 240 V~
@ 300 mA maximum
energizes on alarm
1A
Current
Transformer
(CT)
Heater
Load Wire
7 8
9 10 11 12 13 14 15 16
1
23
4
56
CT
Alarm
Current Transformer and Alarm Wiring
ç Ó
1
Ó
2
Ó
3
DB _ _ - _ _ _ _ - S_ _ _
The Watlow DIN-A-MITE alarm option provides a common alarm output for shorted SCR conditions.
This is a non-latching alarm.
A shorted SCR alarm is detected when there is no command signal and a load current is detected. The alarm output is then energized.
Load Current Passes of Load
Wire Through the
Current Transformer
5 to 9A 2
10 to 30A 1
T1
T2
T3
Heater
Current
Transformer (CT)
7 8
9 10 11 12 13 14 15 16
1
23
4
56
CT
Neutral
3-phase, 3-leg Current Transformer Wiring
T1
T2
T3
Heater
Current
Transformer (CT)
7 8 9
10 11 12 13 14 15 16
1
23
4
56
CT
3-phase, 2-leg Current Transformer Wiring
ç Ó
1
Ó
2
Ó
3
ç Ó
1
Ó
2
Ó
3
ç Ó
1
WARNING: Use National Electric (NEC) or other country-specific standard wiring practices to install and operate the DIN-A-MITE. Failure to do so may result in damage to equipment and property, and/or injury or loss of life.
NOTE: If you plan to wire multiple DIN-A-MITE alarm outputs, you need to include an intermediate relay for each DIN-A-MITE used.
Ó
2
WARNING: Wiring examples show L2 in phase-to-phase, 200 VÅ (ac) and above configuration. In phase-to­neutral, 100VÅ (ac) and above applications, L2 is neutral and must not be fused or switched. Failure to follow this guideline could result in personal injury or death.
Ó
3
WARNING: Only authorized and qualified personnel should be allowed to install and perform preventive and corrective maintenance on this unit. Failure to follow this guideline could result in damage to equipment, and personal injury or death.
Torque Guidelines
• Properly torque line and load terminals to 1.4 Nm (12 in-lb).
• Retorque after 48 hours to minimize wire cold flow.
• Retorque line and load terminals every 3 to 6 months.
This configuration is for a 4 wire configured heater only!
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
8
WATLOW DIN-A-MITE Style B User's Manual
ç Ó
1
WARNING: Use National Electric (NEC) or other country­specific standard wiring practices to install and operate the DIN-A-MITE. Failure to do so may result in damage to equipment and property, and/or injury or loss of life.
Ó
2
WARNING: Wiring examples show L2 in phase-to-phase, 200 VÅ (ac) and above configuration. In phase-to­neutral, 100 VÅ (ac) and above applications, L2 is neutral and must not be fused or switched. Failure to follow this guideline could result in personal injury or death.
Ó
3
WARNING: Only authorized and qualified personnel should be allowed to install and perform preventive and corrective maintenance on this unit. Failure to follow this guideline could result in damage to equipment, and personal injury or death.
NOTE: If you plan to wire multiple DIN-A-MITE alarm outputs, you need to include an intermediate relay for each DIN-A-MITE used.
Torque Guidelines
• Properly torque line and load terminals to 1.4 Nm (12 in-lb).
• Retorque after 48 hours to minimize wire cold flow.
• Retorque line and load terminals every 3 to 6 months.
System Wiring Example
Latching Alarm Option (models DB _ _ -
_ _ _ _ - S _ _ _ )
Alternative Latching Alarm Circuit
If there is a need for a latching alarm, the DIN-A-MITE alarm circuit could be used as shown at right in the latching alarm example. If the DIN-A-MITE triac alarm output energizes, it will energize the RY1 (external alarm relay) mechanical relay coil. Once the RY1 coil is energized it will latch on (via the RY1A normally open contact) until the power to the relay is removed. You could cycle the power via a reset switch. The RY1B contact can be used for alarm signaling.
Breaker
120V~ (ac)
AC Common
AC High
L3
480VÅ (ac)
L2
L1
480V~ (ac)
CR1 = High-Limit Contactor
PM6C2CA - ALAJAAA
98
99
CC
CA
CB
B5
D6
D5
X1
W1
Y1
T1
S1
R1
L4
K4
T2
S2
R2
+
-
High Limit TC
Controller TC
CR1
Coil
Quencharc
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
WATLOW DIN-A-MITE Style B User's Manual
9
NOTE: The current transformer must be in the center uncontrolled leg on a 2-leg DIN-A-MITE.
Non-latching Alarm Option (models DB_ _ -
_ _ _ _ - S _ _ _ )
Shorted SCR (silicon-controlled rectifier) Alarm Non-latching Operation
The shorted SCR detector compares the input command signal and actual load current. If load current is present without an input signal then the shorted SCR alarm will energize the alarm triac output. This is a non-latching alarm. This output can be used to drive various indication devices, such as a coil, light, buzzer, etc. See the alternative latching circuit section below.
VÅ
13
14
Triac
RY1 Coil
Reset Switch
RY1A
L1
L2
RY1B
Normally open
Common
Normally closed
(External alarm relay contacts, set A)
(External alarm relay contacts, set B)
Latching Alarm Relay Circuit
Ungrounded Delta or Wye Load 3-phase, 2-leg DIN-A-MITE
Current
Transformer (CT)
Delta Load
Ungrounded
Wye Load
6
54
V~
(ac)
120 or 240V~ (ac) @ 300mA maximum energizes on alarm
Semiconductor
Fuses
Signal
Alarm Relay
or Indicator
1A
7 8
9 10 11 12 13 14 15 16
1
23
4
56
High-limit
Contactor (CR1)
CT
DB20-60C0-S000
NOTE: Use a grounding conductor terminal plate (fork terminal) having upturned lugs or the equivalent to hold the wire in position. Maximum 6 mm
2
(10 AWG)
wire.
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
10
WATLOW DIN-A-MITE Style B User's Manual
DIN-A-MITE®“B” Power Controller
WATLOW Electric Manufacturing Company 1241 Bundy Blvd. Winona, MN 55987 USA
Declares that the following products:
Designation: DIN-A-MITE® “B” Power Control Model Numbers: DB (1, 2, 3, 4, 8 or 9) 0 – (02, 24 or 60)(CX, FX, K1, K2, K3) – (0 or S)(followed by any 3 letters or
numbers) (where X = any number 0-9)
Classification: Power Control, Installation Category III, Pollution degree 2, IP20 Rated Voltage: 24 to 600 V
~ (ac), 50 or 60 Hz
Meets the essential requirements of the following European Union Directives by using the relevant standards show below to indicate compliance.
2004/108/EC Electromagnetic Compatibility Directive
EN 61326-1: 2013 Electrical equipment for measurement, control and laboratory use - EMC requirements
(Industrial Immunity, Class A
1,2,4
Emissions) Not for use in a Class B environment without
additional filtering.
EN 61000-4-2:2009 Electrostatic Discharge Immunity EN 61000-4-3:2010 Radiated Field Immunity 10V/m 80 MHz- 1GHz, 3V/m 1.4GHz-2.7GHz EN 61000-4-4:2012 Electrical Fast-Transient / Burst Immunity EN 61000-4-5:2006 Surge Immunity (Reviewed to IEC 61000-4-5 2014) EN 61000-4-6:2014 Conducted Immunity EN 61000-4-11:2004 Voltage Dips, Short Interruptions and Voltage Variations EN 61000-3-2:2009 Harmonic Current Emissions (Reviewed to IEC 61000-3-2 2014)
EN 61000-3-3:2013 Voltage Fluctuations and Flicker
3
16A
EN 61000-3-11:2000 Voltage Fluctuations and Flicker 75A with conditional connection
NOTES
1
Use of an external filter is required to comply with conducted emissions limits. See note 4 below.
2
A Line Impedance Stabilization Network (LISN) was used for conducted emissions measurements.
3
To comply with flicker requirements, command signal models F0 and F1 will require a reduced source impedance. Cycle time on ON/OFF models CX, and K1, K2, K3 may need to be up to 175 seconds at 16A or have a reduced source impedance.
2006/95/EC Low-Voltage Directive
EN 50178:1997 Electronic equipment for use in power installations.
Per 2012/19/EU W.E.E.E Directive Please Recycle Properly.
Compliant with 2011/65/EU RoHS2 Directive
4
Required External EMI Filters for DIN-A-MITE with More Than 6 Amp Loads
An external ElectroMagnetic Interference (EMI) filter must be used in conjunction with the DIN-A- MITE for loads in excess of six amperes (6A) at 150 to 250 KHz. Watlow has verified that a tank filter will suppress EMI created by SCR power controllers to comply with the conducted emissions limits.
Declaration of Conformity
DIN-A-MITE EMI Filters
Description Crydom Filter Watlow Filter
Single-phase, 230VÅ (ac)
1F25 14-0019
Three-phase, 440VÅ (ac)
3F20 14-0020
ISO 9001since 1996.
Semiconductor Fuse
Filter
23
Breaker or fused
disconnect
5A
A protective earth (PE) connection is required
A
N
PE
1
23
Filter
5A
5A
Semiconductor
Fuses
5A
Figure 2 - Tank filter,
three-phase, 440v
Breaker or
fused disconnect
A protective earth (PE) connection is required
A
B
C
PE
A third semiconductor fuse is not needed with a two-leg DIN-A-MITE
5
56
56
Heater
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
4
Heater
4
Alternate
6
WATLOW DIN-A-MITE Style B User's Manual
11
ç WARNING: Tank filters may suppress desirable communications carried on power lines in
the 150 to 250 KHz region. The filters may suppress carrier current such as that used for infant monitors and medical alert systems. Verify that suppressed carrier current or other desirable communications on power lines creates no hazard to people or property. Failure to observe this warning could result in damage to property, and or injury to death for personnel.
ç WARNING: All filter installation and wiring must be performed by qualified personnel and
conform to local and national electrical codes.
In-line power filters have been shown to properly suppress EMI; however, these filters must be rated for the entire load current and are generally more expensive than the tank filter specified. An In-line filter may be required if carrier current communications are used on site.
Joe Millanes
Winona, Minnesota, USA
Name of Authorized Representative Place of Issue
Director of Operations September 2014 Title of Authorized Representative Date of Issue
Signature of Authorized Representative
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
12
WATLOW DIN-A-MITE Style B User's Manual
The Watlow DIN-A-MITE is warranted to be free of defects in material and workmanship for 36 months after delivery to the first purchaser for use, providing that the units have not been misapplied. Since Watlow has no control over their use, and sometimes misuse, we cannot guarantee against failure. Watlow's obligations hereunder, at Watlow's option, are limited to replacement, repair or refund of purchase price, and parts which upon examination prove to be defective within the warranty period specified. This warranty does not apply to damage resulting from transportation, alteration, misuse, abuse or improper fusing.
Warranty Return Material Authorization (RMA)
Ship to address
Bill to address
Contact name
Phone number
Method of return shipment
Your P.O. number
Detailed description of the problem
Any special instructions
Name and phone number of person returning the product.
2. Prior approval and an RMA number from the Customer Service Department is needed when returning any product for credit, repair or evaluation. Make sure the RMA number is on the outside of the carton, and on all paperwork returned. Ship on a Freight Prepaid basis.
3. After we receive your return, we will examine it and try to verify the reason for returning it.
4. In cases of manufacturing defect, we will enter a repair order, replacement order or issue credit for material returned.
5. To return products that are not defective, goods must be be in new condition, in the original boxes and they must be returned within 120 days of receipt. A 20 percent restocking charge is applied for all returned stock controls and accessories.
6. If the unit is unrepairable, it will be returned to you with a letter of explanation.
7. Watlow reserves the right to charge for no trouble found (NTF) returns.
The DIN-A-MITE B User’s Manual is copyrighted by Watlow, Inc., © January 2016, with all rights reserved.