Water Mist WM-A1584 Installation, Operation And Maintenance Manual

Manual
Manual
Assessed to ISO 9001: 2000
Certificate number 018
Water Mist Fire Technologies Ltd
Unit 5, Youngs Industrial Estate
Stanbridge Road, Leighton Buzzard
Bedfordshire, LU7 4QB
WM-A1584 10 AMP POWER SUPPLY
INSTALLATION, OPERATION
AND MAINTENANCE MANUAL
(CEL Pt. No: 2500206)
NOTE:
It is important to read this manual before commencing installation.
Watermist Fire Technologies
Page 2
Contents
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
2. Warning
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
4
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .
Page 3
Water Mist Fire Technologies
1. Introduction
 ank you for purchasing this 10A Power Supply Unit.  is power supply is designed to the require-
2. Warning
IMPORTANT NOTE ON BATTERIES:
DANGER:
Batteries are electrically live at all times, take great care never to short circuit the battery
WARNING:
Batteries are often heavy, take great care when lifting and transporting batteries. For
weights above 24kg, lifting aids should be used.
WARNING:
Do not attempt to remove the battery lid or tamper with the battery internal workings.
Electrolyte is a highly corrosive substance and presents signifi cant danger to yourself and to anything
fresh water and seek immediate medical attention.
VRLA batteries are “low maintenance” requiring no electrolyte top-up or measurement of specifi c
gravity. Always refer to the battery manufacturer’s data.
WARNING:
If required, clean the case of the battery with a cloth that has been soaked or dampened
with distilled water. Do not use organic solvents (such as petrol, paint thinners, benzene or mineral
spirits) and other materials can substantially weaken the case.
WARNING:
Avoid charging the batteries in fl oat/standby applications outside of the range quoted by
WARNING:
Do not incinerate batteries. If placed in a fi re, the batteries may rupture, with the po-
 e volt-free contacts provided on the WM-A1584 must not be used directly to switch any voltage
which exceeds 60v AC @ 0.5 Amps or 24v DC @ 1 Amp.
 is equipment requires a 230v AC supply. All installation work should be carried out in accordance
with the recommendation of BS5839 Part 1 and the current edition of the IEE regulations by suitably
 is power supply is suitable for indoor use only and must be installed in a dry and clean area.
 is power supply must be earthed.
Loading...
+ 6 hidden pages