Water Maze CLP-5024, CLP Series, CLP-7034 Operator's Manual

CLP
OPERATOR’S MANUAL
CLP-5024CLP-7034
89139700-14
For technical assistance or the WATER MAZE dealer nearest you, visit our website at
www.wmaze.com
WARNING:
This product and accessories may contain a chemical known to the State of California to cause cancer and birth defects or other reproductive harm.
8.913-970.0 - L02/12/19
Introduction ..................................................................................................... 5
Unpacking ....................................................................................................... 5
Important Safety Information .......................................................................6-7
Installation Instructions .............................................................................. 7, 8
Check List Before Starting ..............................................................................8
Installation View .........................................................................................9-10
Start-up ......................................................................................................... 11
Operation CLP-5024/7034 .......................................................................11-12
Pressure Switch and Pressure Tank Operation ............................................ 13
Programming Instructions ........................................................................14-15
Valve Location & Function .......................................................................16-17
Operation Views .......................................................................................18-19
Water Panel Installation ................................................................................ 20
Standard ORP/pH Sensors ...........................................................................21
Sensor Maintenance ..................................................................................... 22
CONTENTS
Troubleshooting - Standard ORP/pH Sensors .............................................. 23
VSP20 Metering Pump ................................................................................. 24
General Maintenance & Service ...................................................................25
Ozone Generator .....................................................................................25-26
Ozone Generator Breakdown Exploded View & Parts List ......................27-28
Chemical Maintenance Program ..................................................................29
Daily Chemical Maintenance ........................................................................ 30
Centrifugal Pump Operation & Maintenance ................................................ 31
CLP-5024 Main Tank Plumbing Exploded View & Parts List ...................32-33
CLP-5024 & 7034 Electrical Box Exploded View & Parts List .................34-36
CLP-5024 Storage Tank Exploded View & Parts List .................................... 37
CLP-5024 Pumps Plumbing Exploded View & Parts List ........................38-39
CLP-5024 Plumbing Exploded View and Parts List .................................40-41
CLP-5024 Filter Plumbing Exploded View and Parts List ........................42-43
CLP-5024/7034 Water Panel Breakdown Exploded View & Parts List ....44-45
CLP-7034 Holding Tank Assemblies Exploded View & Parts List ............46-47
CLP-7034 Tank Drain & Oil Skimmer Exploded View & Parts List ...........48-49
CLP-7034 Main Tank Exploded View & Parts List ...................................50-51
CLP-7034 Transfer Pump Exploded View & Parts List .............................52-53
8.913-970.0 - L • WATERMAZE CLP 5024/7034
3
CONTENTS
CLP-7034 Carbon/Multi Media Filter Plumbing Expl. View & Parts List ...54-55
CLP-7034 Flow Meter Plumbing Exploded View & Parts List ..................56-57
CLP-7034 Ozone Pump Exploded View & Parts List ...............................58-59
CLP-7034 Filter Pump Exploded View & Parts List .................................60-61
CLP-7034 Surge Tank/Main Drain Exploded View & Parts List ...............62-63
CLP-7034 Manifold Exploded View & Parts List ......................................64-65
Metering Pump Exploded View & Parts List .................................................66
Transfer Pump Exploded View & Parts List ................................................... 67
Filter & Transfer Pumps Exploded View Parts List ...................................68-69
Ozone Pump Exploded View & Parts List .....................................................70
Ozone Pump Exploded View & Parts List .....................................................71
Submersible Sump Pumps Specifi cations .................................................... 72
Multi-Media/Carbasorb Filter Exploded View & Parts List ............................73
Carbasorb Filter Exploded View & Parts List ................................................ 74
Multi-Media Filter Exploded View & Parts List ..............................................75
6 Position Valve Exploded View & Parts List ................................................. 76
2" Multi-Port Valve Exploded View & Parts List .............................................77
Troubleshooting .......................................................................................78-83
Consumable Parts ........................................................................................ 84
CLP-7034 Maintenance Schedule ................................................................85
Warranty .......................................................................................................86
Model Number ____________________________________
Serial Number _____________________________________
Date of Purchase __________________________________ The model and serial numbers will be found on a decal attached
to the machine. You should record both serial number and date of purchase and keep in a safe place for future reference.
4
8.913-970.0 - L • WATERMAZE CLP 5024/7034
INTRODUCTION & SAFETY INFORMATION
INTRODUCTION
Your owner’s manual has been prepared to provide you with a simple and understandable guide for equipment operation and maintenance, based on the latest prod­uct information available at the time of printing. To keep your machine in top running condition follow the specifi c maintenance and troubleshooting procedures given in this manual. When ordering parts please specify model and serial number.
NOTE: WATER MAZE reserves the right to make changes at anytime without incurring any obligations.
Owner/User Responsibility:
The owner and/or user must have an understanding of the manufacturer’s operating instructions and warnings before using this WATER MAZE machine. Warning information should be emphasized and understood. If the operator is not fl uent in English, the manufacturer’s instructions and warnings shall be read to and discussed with the operator in the operator’s native language by the purchaser/owner, making sure that the operator comprehends its contents. The owner and/or user must study and maintain the manufacturers’ instructions for future reference.
WATER TREATMENT SYSTEM
OPERATOR’S MANUAL
SAVE THESE INSTRUCTIONS This manual should be considered a permanent part
of the machine and should remain with it if machine is resold.
When ordering parts, please specify model and serial number. Use only identical replacement parts.
This machine is to be used only by trained operators.
UNPACKING
1. CLP Machine Assembly
2. Sludge Tub
3. Sludge Tub Bag Support
4. Accessory Box
6. Operator’s Manual NOTE: Any damage to machine or components for
claims against the freight lines.
8.913-970.0 - L • WATERMAZE CLP 5024/7034
5
INTRODUCTION & SAFETY INFORMATION
WARNING
CAUTION
IMPORTANT
SAFETY
INFORMATION
CAUTION: To reduce the risk of
READ OPERATOR’S
MANUAL THOROUGHLY
PRIOR TO USE.
injury, read operating instructions carefully before using.
WARNING
KEEP WATER SPRAY
OPERATOR’S MANUAL WATER TREATMENT SYSTEM
AWAY FROM
ELECTRICAL WIRING.
corder à la source d'alimentation.
WARNING
RISK OF EXPLOSION:
DO NOT SPRAY
FLAMMABLE LIQUIDS.
Code national de l'électricité et les codes locaux pour tous les câblages.
WARNING: Follow the wiring instructions in this manual when connecting the system to the power lines.
AVERTISSEMENT: Suivre les instructions de câblage dans le présent manuel au moment de
raccorder le système aux lignes de transport d'électricité.
WARNING: All wiring must be performed by a quali­fi ed electrician.
AVERTISSEMENT: Tout le câblage doit être effectué par un électricien qualifi é.
2. Know the system application, limitations, and poten­tial hazards.
WARNING: Do not use to pump concentrations of flammable
6
injury, read operating instructions carefully before using.
ATTENTION: To reduce the risk of
1. Read the owner’s manual thor­oughly. Failure to follow the instruc­tions will cause a malfunction of the machine and result in death, serious injury and/or property damage.
WARNING: Ground system before connecting to the power supply.
AVERTISSEMENT: Mettre le sys­tème à la masse avant de le rac-
WARNING: Wire the system for correct voltage. See “Electrical” section of this manual and motor nameplate.
WARNING: Meet the National Electrical Code and local codes for all wiring.
AVERTISSEMENT: Respecter le
8.913-970.0 - L • WATERMAZE CLP 5024/7034
or explosive fl uids such as gasoline, fuel oil, kero­sene, etc. Do not use in explosive atmospheres. Pumps should only be used with liquids compatible with pump component materials. Failure to follow this warning can result in personal injury and/or property damage.
AVERTISSEMENT: Les pompes devraient être utili­sées uniquement avec des liquides compatibles avec les matériaux des composants des pompes. Le non-respect des précautions peut mener à des lé­sions corporelles et/ou des dommages à la propriété.
3. WARNING: Risk of electric shock. AVERTISSEMENT: Risque de choc électrique
All wiring should be performed by a qualified
electrician.
4. Never make adjustments on the machine while it is in operation, except for those prescribed in this manual.
5. The main power must be brought from the circuit breaker and wired into the electrical box on the CLP. This line must be run through conduit to protect it from damage. A power disconnect should be located next to the machine for maintenance purposes.
6. Before servicing the machine, refer to all the MSDS’s on the material identifi ed in the wastestream. You must comply with all warnings and wear all protec­tive clothing as stated on the MSDS’s.
7. Protect all electrical cords from sharp objects, hot surfaces, oil, sunlight, and chemicals. Avoid kinking the cords. Replace or repair damaged or worn cords immediately. All wiring should be run through conduit.
8. Inlet water temperature must not exceed 85°F.
9. Disconnect the power before servicing this machine. If the power disconnect is out of sight, lock it in the open position and tag it to prevent unexpected application of power.
10. The best insurance against an accident is precaution and knowledge of the equipment.
11. WATER MAZE is not liable for modifi cations or use of components not purchased from WATER MAZE.
12. Personal Safety:
a. Wear safety glasses and other applicable
protective clothing at all times when working on the CLP.
Refer to item #6 under Important Safety
Information.
b. Keep your work area clean, uncluttered and
properly lighted. Replace all unused tools and equipment.
INSTALLATION INSTRUCTIONS
WATER TREATMENT SYSTEM
c. Keep visitors at a safe distance from work area.
d. Make the workshop safe with padlocks and
master switches.
13. Running the system without water will damage the pumps and will void the warranty.
14. Release all pressure within the system before servicing any component.
15. Drain all liquids from the component before servicing.
16. Check hoses for weak or worn conditions before each use, making certain that all connections are secure.
17. Periodically inspect pump and system components. Perform routine maintenance as required.
18. Do not touch an operating motor. Modern motors are designed to operate at high temperatures.
19. Do not handle a pump or pump motor with wet hands, when standing on a wet or damp surface, or in water.
20. The pump motors are equipped with an automatic resetting thermal protector and may restart unex­pectedly. Tripping is an indication of motor overload­ing as a result of operating the pumps at low heads (low discharge restriction), excessively high or low voltage, inadequate wiring, incorrect motor connec­tions, or a defective motor or pump.
21. IMPORTANT NOTE: The sump pump is not a trash pump and is subject to premature failure unless sump pit baffl ing or additional protection is provided.
22. Do not stand on the bracket that supports the Electrical Box, Ozone Generator and the ORP/pH Controller or on tanks 1 or 2. During installation and maintenance obtain an OSHA approved ladder.
23. Keep machine from freezing.
24. Do not spray water directly at machine.
INSTALLATION INSTRUCTIONS
1. Because of the nature of the equipment, it is recom­mended these machines be installed indoors.
2. Locate the CLP on a containment pad to prevent contamination.
3. Level machine by using shims that will provide ample support and will not corrode or deteriorate over time.
4. Have a qualifi ed electrician connect the proper power supply to the electrical control box. It is rec­ommended that a ground fault circuit interrupter be installed in the circuit breaker for the CLP.
NOTE: An electrician needs to locate where the
power supply will enter the electrical box and punch a hole.
5. Install Orp/pH probes into cone bottom tank. Remove cap and immerse probes into water. Don't let probes dry. Save cap for future need.
6. Install the angle face dump valve on bottom of cone bottom tank. Run air hose from angle face dump valve to air valve assembly. Follow electrical wiring diagram for air switch wires.
7. Plumb oil decanter barrel.
8. Run ORP/pH pump hoses from pumps to injectors.
9. Run air from air compressor to machine. Use at least a 3 CFM air compressor with 60-100 psi.
10. Drill holes for 2" bulkheads and install bulkheads. Connect the sludge tub assembly by placing the sludge bag support into the sludge tub. Attach the sludge bag onto the sludge inlet fi tting using the screw clamp provided.
11. Attach the 2" fl ex hose to the sludge tub by screwing the hose barbs into the bulkhead connectors, then attach the 2" fl ex hose to the hose barb using a hose clamp. The return line should gravity return to the catch basin. The 2" inlet fl ex hose should connect between the cone tank discharge valve and the sludge bag inlet connector.
12. Build the inlet plumbing from the sump pump dis­charge port (min. 1-1/2" pipe) to the CLP 1-1/2" inlet line. If the pipe is to be under the concrete, use 2" pipe. Lower the sump pump into the sump pit.
13. Position the sump pump in the bottom of sump pit.
a. Elevate on a stand or cinder blocks, 6" off the
pit fl oor, to keep pump from sucking in rocks or other heavy material that may plug pump or plumbing.
b. Position the pump away from incoming water to
help prevent cavitation.
OPERATOR’S MANUAL
8.913-970.0 - L • WATERMAZE CLP 5024/7034
7
INSTALLATION INSTRUCTIONS
c. Tie a rope or chain to the pump handle and
bring out of the top of the pit for ease of pump removal. Do not lift pump by power cords or plumbing. Have a union installed on plumbing at the top of the pit. Position union so it can easily be reached and opened for pump removal.
14. The High Level Control Float FS1 (black, normally open) is the upper fl oat which controls the upper limits of the sump. It prevents the sump from fl ood­ing by opening SV1, the rain water solenoid valve. Float tether length must be a minimum of 2" long. Position the upper most point of fl oat a few inches below top of pit. The Fresh Water Make-up Float FS2 (grey, normally closed) controls the lower limits of the sump. It prevents the sump from running dry by opening SV2, the fresh water solenoid valve. Turn-on point for the Fresh Water Make-up Float must be at least 8" above the suction inlet of sump pump. The
OPERATOR’S MANUAL WATER TREATMENT SYSTEM
further the water must travel before reaching the sump, the higher the fl oat must be placed above the suction intake. On three phase units, a third fl oat is needed to protect the sump pump from the possibility of running dry. Position the Low Water Protector Float #7 (grey, normally closed) 6" above the suction inlet of sump pump. Single phase sump pumps have a fl oat built into them.
Floats must travel their complete arc without:
Water going over the top of the pit.
Touching sidewalls or bottom.
The pit running out of water.
Interfering with electrical wiring, plumbing, bottom
or sidewalls of sump, or any object. Attach the fl oats to the PVC line on the sump pump.
Check to assure the fl oats can operate freely.
(See Installation View.)
15. Run the electrical cords from the sump pump and fl oats to the electrical junction boxes near the inlet line and attach wires. If the sump pump and fl oats are located farther then 20 feet from the electrical junction boxes, then have an electrician install water tight junction boxes with conduit and proper sized wire to extend the electrical connections.
16. Connect the fresh water line (3/4" GHM garden hose not provided) to the “Fresh Water Inlet” port on the water panel (see Water Panel Illustration).
17. Connect the “Outlet to Pressure Washers” to your pressure washer by using a 5/8" garden hose (not provided). Valve #7 behind the water panel should remain closed until start-up. You may need a 1" line to
obtain a higher fl ow. If you are going a great distance or using a lot of elbows, you may not get full fl ow.
18. Connect the “Rain Water Overfl ow” to the sewer or storage (line not provided). Valve #8 behind the water panel should remain halfway open.
CAUTION: Discharge Permits are required and
must be obtained before any treated water is discharged.
ATTENTION: Des permis de déversement sont
requis et doivent être obtenus avant de procéder au déchargement de toute eau traitée.
19. Connect a hose to “Rinse Water” outlet if it is to be used. Make sure valve #6 behind the water panel stays closed until rinse water is needed (hose not provided).
NOTE: The use of rinse water in a closed loop
system will overfi ll the system and will lead to an overfl ow situation causing the rainwater overfl ow valve to open.
20. Run the "Return/Backwash" line back to the collec­tion pit or fi rst pit where the water will be collected. This is very important so that there is no stagnant water when recycling and also to give more set­ting for the backwash water. If not done properly, it could void warranty. Run at least a 2" line if above ground and 3" if below ground. The sludge tub and oil decanter barrel are plumbed together and run to the return line. Any back pressure could overfl ow the sludge tub and/or oil decanter barrel. A separate return line for the sludge tub and oil decanter barrel may be needed , the sludge tub can be elevated or a check valve can be installed.
CHECK LIST
BEFORE STARTING:
Yes No
1. Is inlet line connected from the sump pump to the inlet of the machine? ___ ___
2. Is the voltage correct? ___ ___
3. Is the return line connected? ___ ___
4. Is the Fresh Water Make-up hose connected? ___ ___
5. Is the Outlet to Pressure Washer hose connected. ___ ___
6. Is the Rainwater Overfl ow connected? ___ ___
START-UP:
8
8.913-970.0 - L • WATERMAZE CLP 5024/7034
CLP-5024 INSTALLATION VIEW
Inlet
pH Injector
Cone
Bottom Tank
Bag
Support
Sludge
Tub
WATER TREATMENT SYSTEM
OPERATOR’S MANUAL
Inlet Line
Sump Pump
Sump Pump
Installation
(3 Phase)
Sump
Pit
FS1
FS2
FS7
Inlet Line
2" Flex
Hose
Oil Decanter
Barrel
Inlet Line
Return
Backwash Line
Catch Basin
Sump
Pit
FS1
FS2
Sump Pump
Sump Pump
Sump Pump Not Supplied
with Machine. See
Specifi cation on Page 70.
8.913-970.0 - L • WATERMAZE CLP 5024/7034
Installation
89139700-3
9
CLP-7034 INSTALLATION VIEW
Cone Bottom Tank
Flow Meter
Inlet
Sludge Tub
OPERATOR’S MANUAL WATER TREATMENT SYSTEM
3 Way Ball Valve Assembly
Inlet Line
Sump Pump
Sump Pit
Sump Pump
Installation
FS1
FS2
Inlet Line
Sump Pit
Installation
(3 Phase)
Sump Pump
FS1
Oil
Decanter
Barrel
2" Flex Hose
Inlet Line
Return/Backwash
Line
Catch Basin
10
Sump Pump Not Supplied
with Machine. See
Specifi cation on Page 70.
8.913-970.0 - L • WATERMAZE CLP 5024/7034
FS2
FS7
89139700-21
Sump Pump
START-UP INSTRUCTIONS
WATER TREATMENT SYSTEM
• Make sure that the CLP is level.
• Turn on the Fresh Water Makeup hose.
• After checking for proper power supply voltage,
turn on the circuit breaker to the CLP Machine. NOTE: Make sure all switches are turned ”OFF”.
• Fill the sump pit with water, and check that the water level does not drop, which would indicate the pit is not sealed.
• Turn the sump pump switch to the ON position. The sump pump lamp will illuminate if sump pump is operating. (NOTE: the pump has an internally oper­ated fl oat for low water on single phase only. The sump pump should fi ll the cone bottom tank with water. FS3 in tank 1 will shut off the sump in the up position).
• Adjust the fl ow of water into the CLP using valve #1 by reading the indicator marks on the inlet fl ow meter. Set fl ow 2-4 GPM above demand.
• The ozone genertor is programmed to run from 11:00 p.m. to 4:00 a.m. every night. If more ozone is needed during the day time hours, program Ozone 2 and Ozone 3 on the PLC to the desired times needed.
• Turn the fi lter pump switch to the ON position. Tank #2 should fi ll and FS5 will turn off the fi lter pump when in the up position. The fi lter pump lamp will illuminate when pump is in operation.
• Adjust valve #10 so that the fi lter fl ow meter has the same or 2 GPM lower fl ow rate than the inlet GPM fl ow rate.
• Turn the transfer pump switch to the ON position. The pump should pressurize and shut off. NOTE: When the pump is put into operation the pressure switch may need to be adjusted. See inside cover of pressure switch for adjustment instructions. The 2 HP pump is set at 20 PSI ON and 40 PSI OFF. The transfer pump lamp will illuminate when pump is operating.
• Turn the ozone pump switch to the ON position.
• Check to ensure the oil skimmer is adjusted properly. Adjust if needed by screwing the funnel up or down, or angling the pipe to allow a small amount of water to free fl ow. If oil starts to build up on top of the cone tank, adjust the skimmer to allow increased fl ow.
NOTE: Only adjust the oil skimmer when the sump
pump is running.
• Place the ORP/pH probes in the bracket inside the CLP tank. Remove the liquid fi lled cap on the end of the probes and place them in the bracket. Make sure the tank is full of water and the probes are kept wet. Run the connector through the hole in the tank wall
near the bracket and attach the connectors to the controller. The connector with the white tag near it is the ORP and is connected to the top stud on the controller. The other is the pH and is connected to the bottom stud on the controller.
• Look over entire machine for leaks. The machine was hydrostatically tested at the factory but may have been damaged in shipment.
• Program the AMC controller (CLP-7034).
• Turn the ozone generator ON/OFF switch ON.
• Set ozone generator for proper air fl ow.
• Turn ORP/pH controller switch ON.
• Turn ORP/pH feed pumps ON.
• Adjust valves per instructions (See Standard Orp/ pH Controller pages).
OPERATION: CLP-5024/7034
The CLP-5024/7034 are a fully automatic, self-contained wash water recycling system suitable for treating waste­water generated from cleaning machinery and equip­ment. They are designed to separate free oil/greases and dirt.
At the heart of the automated system is an automatic maintenance controller (AMC). The AMC provides the benefi ts of reliability and versatility to control numerous functions. The AMC controls pump operations, machine mode light display, fi lter status, backwash requirements, recirculation, ozone injection, and sludge dumping.
Filter Mode
In a typical operation, wastewater is gravity fed from a wash pad catch basin to a sump pit (preventing large solids from entering the sump pump). Water resides in the sump pump pit until Tank #1 requires water. On Tank #1's demand, wastewater is pumped into the cone bot­tom tank. In the cone bottom tank the following occurs:
• Wastewater exits the tank by passing through a series of corrugated coalescing cones. These cones slow the fl ow of water (velocity drop) allow­ing the separation and settling of solids. Solids settle to the bottom of the tank and are later auto­matically removed (see automatic sludge dump). The coalescing cones oil attracting properties, combined with the 55° incline angle, maximizes free oil/water separation. Free oils are skimmed from the surface and discharged to a 26 gallon oil decanter for further separation.
• To control odor and kill bacteria, an ozone pump recirculates ozonated water through the upper section of the cone bottom tank.
OPERATOR’S MANUAL
8.913-970.0 - L • WATERMAZE CLP 5024/7034
11
OPERATING INSTRUCTIONS
Water is gravity fed from the 600 gallon tank to Tank #1 and remains there until Tank #2 requires water. When water is consumed from Tank #2 (by pressure washer, recirculation or sewer discharge) the fi lter pump circu­lates water from Tank #1 through the fi lters to Tank #2. Flow rates through the fi lters can be adjusted up to 30 gallons per minute (GPM). For best results the fl ow rate should be set to the lowest GPM that still allows the entire system to operate correctly (the lower fl ow rate increases wastewater/fi lter contact time and reduces the fi lters solids loading).
Water remains in Tank #2 until it is either discharged to the sewer (check your local regulations for limits in your area), reused by the pressure washer or used for recirculation of the pits and fi lters (see recirculation mode). In the event an excess amount of water enters the system (through rinse water or rain water) water is automatically discharged from Tank #2 through the rain water overfl ow solenoid valve to either the sewer or to a holding tank. If the system's water level becomes too low (i.e. evaporation, vehicle carry off), a fresh water
OPERATOR’S MANUAL WATER TREATMENT SYSTEM
make-up solenoid valve feeds fresh water to Tank #2 until proper levels are maintained.
Filters
To ensure optimum filter performance and life, the multi-media and carbon fi lters must periodically be backwashed (see automatic backwash mode).
• The multi-media fi lter consists of a blend of sand, garnet, gravel and anthracite. The media blend is effi cient in screening out solids to 25-30 microns. During the recirculation mode, the constant fl ow through the media fi lter provides a fi nal polish to the water.
• The carbon fi lter consists of degassed, virgin ac­tivated carbon. Carbon removes, through absorp­tion, pesticides, solvents, benzene, diesel fuels, acetone and other hydrocarbons as well as low levels of heavy metals.
Automatic Backwash Mode
Backwashing the media fi lters is required to rejuvenate the fi lter media. Backwashing removes collected materi­als and disperses the media to eliminate any channeling.
During normal operation of the CLP-5024/7034, the multi-media fi lter, carbon fi lter or both may become impacted with fi ltered solids, resulting in pressure head loss through the fi lters and in poor overall performance. The CLP-5024/7034 will backwash everyday if it needs to or not. The multi-media will start backwashing at midnight for 30 minutes. The CLP will then recover the water level in Tank #1 and then backwash the carbon fi lter. The operator cannot use the pressure washer at
that time, so it is important that the program imitates your schedule. If it doesn't, call factory for assistance in reprogramming your controller.
To backwash, the affected fi lter is isolated and the fl ow is reversed via air actuated three way valves. A slip stream solenoid is activated to allow proper water fl ow (30 GPM for multi-media valve 20, 15-20 GPM for carbon valve
21) and water is pumped from Tank #1 through the fi lter by the fi lter pump. This process continues for 30 minutes and the resulting backwash outfl ow is returned to the wash pad catch basin.
Once backwashing of the fi rst fi lter is completed the second fi lter will then be backwashed. At no time will both fi lters be backwashed at the same time.
Recirculation Mode
The purpose for recirculating the water through the pit system and the fi lters is to minimize odor, kill bacteria and provide high quality polished water.
Once each day the CLP will enter a recirculation mode. This mode consists of two separate stages.
Stage 1: The transfer pump sends water from Tank #2
through the return line to the wash pad catch basin. To prevent odor and kill bacteria, the return water is ozonated via a mazzi injector.
Stage 2: Water is recirculated through the fi lter pack.
The transfer pump circulates water from Tank #2 through a mazzi injector to Tank #1. From Tank #1 the fi lter pump circulates water through the fi lters to Tank #2.
Automatic Sludge Dump
During normal operation, the settling properties of the solids will result in sludge build-up inside the cone bottom tank cone. This sludge must be periodically removed. This is accomplished once each day by an automated sludge dump system.
To dump sludge, an air activated dump valve opens while simultaneously a water solenoid activates (to stir-up any impacted material in the bottom of the cone bottom tank) to allow sludge to fl ow to the sludge collection bag. To reduce excess water in the sludge bag, the water sole­noid is only activated for a few seconds. Once the dump valve closes, the sludge bag is allowed to de-water and excess water is returned, via gravity feed, to the wash pad catch basin.
If at any time, the user needs an additional sludge dump, a manual switch enables the automatic sludge dump cycle.
AUTOMATIC MAINTENANCE
CONTROLLER; 5024, 7034
12
8.913-970.0 - L • WATERMAZE CLP 5024/7034
PRESSURE SWITCH AND PRESSURE TANK OPERATION
WATER TREATMENT SYSTEM
WARNING
WARNING: Live electrical contacts are exposed, so dis­connect power fi rst and have work performed by a qualifi ed electrician.
RISK OF
ELECTRIC SHOCK: USE
CAUTION
WHEN HANDLING.
AVERTISSEMENT: Les con­tacts électriques sous ten­sion sont exposés, il faut
donc d'abord débrancher l'alimentation électrique et confi er le travail à un électricien qualifi é.
Remove cover of the pump pressure control switch to allow access to the two nuts used to adjust the pump operating pressure. The pressure switch on Water Maze equipment is set at the factory and should not have to be adjusted at start-up, but will need to be verifi ed at start up and maintained regularly at least monthly.
1. The nut on the larger spring in the pump pressure
switch, adjusts the pump cut in (cut on) and pump cut out (cut off) pressures simultaneously.
2. The nut atop the smaller spring in the pump pres-
sure switch only controls the cut out range and is used to narrow or widen the gap between the pump cut in and cut out pressures.
3. To cycle the pump less frequently, the gap should
be as wide as possible while still allowing the pump to shut off quickly when all outlets are closed. Adjust the smaller spring to widen the gap between pump in and out (on and off). 40­45 PSI (CLP, Rec2-20) or 30 PSI (EC1-300A) is desirable. Adjusting the larger spring should not be necessary.
4. When making pressure switch adjustments, make
sure all pump outlets are off or closed, except for the one outlet valve used to relieve and build pres­sure while making pressure switch adjustments.
Controls
Cut in/Cut out
Controls
Cut out Range
8913970-39
8.913-970.0 - L • WATERMAZE CLP 5024/7034
PRESSURE TANK
OPERATION
WARNING
RISK OF
EXPLOSION:
INSTRUCTIONS WHEN
CHANGING PRESSURE
FOLLOW
AVERTISSEMENT: Après avoir effectué l'entretien du réservoir, il est nécessaire de passer à une pression de précharge supérieure en raison d'un changement requis du paramètre du pressostat; le non-respect des directives ci-dessous peut causer une rupture ou une explosion, et pourrait causer des lésions corporelles graves ou fatales et/ou des dommages à la propriété.
• Do not adjust or add pressure if there has been a loss of air.
• Do not adjust the pre-charge pressure if there is visible exterior corrosion.
• Do not adjust the pre-charge pressure if there has been a reduction of the pump cycle time or the pre-charge pressure compared to its initial setting. A reduction in pump cycle time can result from loss of tank corrosion and any re-pressurization or additional pressure could result in rupture or explosion.
• Pressure tank pressure is factory set but will have to be checked regularly (at least monthly). Use an air pressure (tire) gauge. Before checking air pressure on the pressure tank, purge all water out of the tank by turning the pump on and pumping all water out of the pressure tank.
1. Our transfer pump water systems use a water pressure tank and water pump with these two pressure operation ranges:
Cut in (start pumping): 20 PSI
Cut out (stop pumping): 30 PSI (EC1-300A)
Cut out (stop pumping): 40-45 PSI (CLP, REC2-20)
2. Typical factory set air pressure on bladder-type residential water pressure tanks are shipped from the factory with a standard pre-charge of:
18 psig for models WX-101 and WX-102
18 psig for models WX-103 and WX-203
18 psig for models WX-205 and WX-350
3. Set the well tank air pressure to 2 PSI below the pump pressure switch cut-in pressure. This is usually 18 PSI.
WARNING! When the tank has been in service and a change to a higher pre-charge pressure is necessary because of a re­quired change in the pressure switch setting, failure to follow instructions below can cause a rupture or explosion and could cause serious or fatal personal injury and/or property damage.
OPERATOR’S MANUAL
13
PROGRAMMING INSTRUCTIONS
The heart of the CLP Automatic Maintenance System, the AMC Controller, has been pre programmed at the fac­tory with Maintenance Modes described in the Program Schedule shown below. In order for the CLP wastewater system to function properly, the controller clock must be set with the correct time-of-day and date.
Setting the Clock
After the time-of-day and date are set, the Automatic Maintenance System will automatically control the op­eration of your CLP and provide daily scheduled mainte­nance in accordance with the Program Schedule below.
If electrical power is cut from the CLP, the AMC Control­ler will retain its program for 7 days. If electrical power is not reconnected within 7 days, then the time-of-day, month and year must be reset.
1. Press the ESC key located next to the display win-
dow and under the arrow key pad (see fi gure below). Pressing the ESC key will access the Parameter
OPERATOR’S MANUAL WATER TREATMENT SYSTEM
Assignment Menu.
2. Using the up/down arrow keys ▲ or ▼, move the cursor to highlight ‘Setup’ and press OK to accept.
3. Move the cursor to highlight ‘Clock’ and press OK to accept.
Program CardParameter Assignment Menu
Mo 10:15 2006-10-13
4. Move the cursor to highlight ‘Set Clock’ and press OK to accept.

ESC OK
Arrow
Key Pad
NOTE: When setting time on clock, use only mili­tary time.
NTP Set Clock S/W Time
5. Move the cursor to the value wanting to be changed
using the left/right arrow keys or , and change the value by using the up/down arrow keys ▲ or ▼.
Set Clock
Mon. 10:15
YYYY-MM-DD
When you are done setting the time and date press OK to accept your changes.
6. Press ESC three times to exit to the main menu.
Program Schedule
The Automatic Maintenance Controller has been pre­programmed to the Program Schedule on the next page with Mode #1 starting at 12:00 midnight and continuing through all 6 maintenance modes to 4:16 a.m. If needed, the Mode start time and run times may be changed to suit a specifi c application. We suggest that you consult a factory representative prior to making any changes to the Program Schedule.
14
Stop Program Setup Network Diagnostics
Msg Cong Start Screen Clock LCD Menu Language Switch to OP
VALVE LOCATION &
8.913-970.0 - L • WATERMAZE CLP 5024/7034
PROGRAMMING INSTRUCTIONS
Maintenance
Mode Description Start Time Run Time Program Name
1 Media Filter Backwash 12:10 a.m. 30 minutes MMB Time 1
2 Carbon Filter Backwash 12:45 a.m. 30 minutes CRB Time 1
3 System Recirculation 1:30 a.m. 1.5 hours SR Time 1
4 Filter Recirculation 3:15 a.m. 1 hour FR Time 1
5 Automatic Sludge Dump 4:16 a.m. 1 minute P Time 1
6 Ozone Circulation 11:00 p.m. 5 hours Oz Time 1
WATER TREATMENT SYSTEM
Manual Start/Run:
Overriding the automatic maintenance schedule and
manually starting any of the Modes above can be done
in two ways:
1. To manually start and run any of the six maintenance
modes as shown in the Program Schedule above,
reset the AMC time-of-day clock to the start time as
shown in the schedule. For example, to manually
start the Media Filter Backwash cycle, temporarily
reset the AMC clock to 12:00 midnight. Don't forget
to set the clock back to its true time of day.
2. Maintenance Modes 1 through 4 are used by
WaterMaze personnel to test each CLP before it
leaves the factory, these four modes can be manually
started and run by following these instructions.
a. From the date and time screen hit the
left arrow and you'll see "ESC + C" displayed.
b. From the " ESC + C" screen follow the chart
below for the mode you want to test. For example to
start the Media Filter Backwash fi rst hit the "ESC"
button followed by the up arrow (
second delay between the two. Each mode will run
for 2 minutes to give time to check for proper operation,
set fl ows and etc.
), about a 1/2
OPERATOR’S MANUAL
Maintenance Mode
1
2
3
4 Filter Recirculation ESC FR Time 1
Description Button Button Program Name
Media Filter Backwash ESC MM TIme 1
Carbon Filter Backwash ESC CRB Time 1
System Recirculation ESC SR Time 1
8.913-970.0 - L • WATERMAZE CLP 5024/7034
15
VALVE INSTRUCTIONS
FUNCTION:
It is extremely important to know the location and func­tion of the valves on the CLP. Improper positioning of the valves can cause overfl ow or damage which could result in time consuming clean-up and repairs. Study the section on “Valve Location and Function.”
Valve 1 - Flow Control Valve
This valve controls the amount of water allowed
into the CLP from the sump pump. Adjust 2-4 gpm above your demand on the system (See Pages 13, 58).
Valves 2 & 3 - Ozone Pump
Should be open at all times (See pages 19, 42,
44).
NOTE: Only to be closed when removing or re-
placing the ozone pump.
OPERATOR’S MANUAL WATER TREATMENT SYSTEM
Valve 4 - Oil Skimming Bucket
Valve should be closed except when draining
off oil (See pages 13-14).
Valve 5 - Tank Valve
This valve should be open at all times except when
removing air valve for repair (see pages 13-14).
Valve 6 - Rinse Water Control Valve
This valve is opened only when rinse water is
needed (See page 44).
Valve 7 - Outlet to Pressure Washer Valve
After start-up, this valve is left fully open all of
the time. Controls water to the pressure washer (See page 44).
Valve 8 - Rain Water Overfl ow Valve
Left open partially. When SV#1 opens, water is
allowed to discharge while still providing water for the pressure washer (See page 44).
Valve 9 - Recycle Flow Control Valve
This valve is used to control the volume of
water going back to the collection pit for recycling through the system when the PLC or AMC acti­vates the solenoid, SV3, for recycling the system. Open partially to match fi lter fl ow meter allowing a smooth fl ow without cycling transfer pump as much as possible (See pages 46, 66).
Valve 10 - Filter Flow Control Valve
This valve controls the amount of water allowed
to fl ow through the fi lters. Adjust to the same or 2 gpm below valve #1 (See pages 36, 62).
Valve 11 & 12 - Filter Control Valve
When set on Filter, this valve allows water to pass
through the fi lter. When set on Backwash, the water passes through the fi lter in reverse, then passes back to the catch basin. The air valves control these valves (See pages 13-14).
Valve 13
Should be open at all times. Allows pressur-
ized water to fl ush sediment from the cone tank (See pages 13-14).
Valve 14
16
8.913-970.0 - L • WATERMAZE CLP 5024/7034
This valve should be open at all times to allow
pressurized water to fl ush out the sludge hose (See pages 14, 38, 66).
Valve 16
Should be open at all times. Allows fresh water
into tank 2 when SV#2 opens. Valve should be fully open (See page 44).
Valve 17
In the recirculation mode, this valve is used to
control the volume of water going to tank #1 when the PLC or AMC opens SV#4. Open partially to match fi lter fl ow meter allowing a smooth fl ow without cycling transfer pump as much as possible (See pages 38, 66).
Valve 20
Should be open partially to control the amount
of water fl ow to backwash the multi-media fi lter when the PLC or AMC opens SV#7. Set for 30 gpm (See pages 36, 62).
Valve 21
Should be open partially to control the amount of
water fl ow to the backwash carbon fi lter when the PLC or AMC opens air solenoid valves. Set for 15 gpm (See pages 40, 56).
WATER TREATMENT SYSTEM
OPERATOR’S MANUAL
8.913-970.0 - L • WATERMAZE CLP 5024/7034
17
OPERATOR’S MANUAL WATER TREATMENT SYSTEM
Tank #1
Control Panel
CLP-5024 OPERATION VIEW
Orp/pH Probes
STEP R
ON THIS PLATFORM
PRECAUTION/ATTENTION
DO NOT STAND O
WARNING
WARNING
DO NOT STAN
PRECAUTION/ATT
ON THIS PLATF
D
ENTI
OR STEP
ON
OR
M
Valve
2
300 Gallon Cone
Bottom Tank
Junction Box
Valve 1
Tank #2
Valve 11
Multi Media
Filter
Valve 21
Carbon
Filter
Inlet Line
Sump Pump
Sump Pump
Installation
(3 Phase)
Valve 12
Sump
Pit
FS1 FS2
FS7
Oil
Decanter
Barrel
Inlet Line
Sump Pump
Sludge Tub
Flow
Meter
Valve 13
Valve 5
Valve 4
Sump
Pit
FS1
FS2
18
Sump Pump Not Supplied
with Machine. See
Specifi cation on Page 70.
Sump Pump
Installation
8.913-970.0 - L • WATERMAZE CLP 5024/7034
89139700-5
CLP-7034 OPERATION VIEW
WATER TREATMENT SYSTEM
Flow Meter
Orp/pH Probe
Control
Tank #2
Tank #1
Panel
Valve 12
Valve 5
Valve
14
600 Gallon
Cone Bottom
Tank
Sludge
Tub
Valve 4
Oil
Decanter
Barrel
OPERATOR’S MANUAL
Multi-Media
Filter
Carbon Filter
3-Way Ball Valve
Assembly
8.913-970.0 - L • WATERMAZE CLP 5024/7034
Junction Box
Valve 13
89139700-25
19
OPERATOR’S MANUAL WATER TREATMENT SYSTEM
WATER PANEL INSTALLATION
SV1
SV2
To Fresh Water Line
To Sewer or Storage
To Pressure Washer
89139700-31
20
8.913-970.0 - L • WATERMAZE CLP 5024/7034
STANDARD ORP/PH CONTROLLER
WATER TREATMENT SYSTEM
STANDARD ORP/PH DIGITAL
CONTROLLER - MODEL 250
Operation
The Oxidation Reduction Potential (ORP) and pH of the water stream are controlled automatically by the digital controller. The controller receives input from the ORP sensor on the activity of the sanitizer and input from the pH sensor on the pH level of the waste stream. The level of ORP and pH being sensed, and the requested levels programmed in the controller will determine if outputs from the controller are sent to the feed pumps. If sani­tizer or pH adjust are needed, the output will turn the corresponding feed pump on. This will inject the required sanitizer or pH until programmed levels are reached and feed pump will stop.
If ORP or pH adjustment is needed the ozone pump will also turn on. The chemical is injected at the outlet of the ozone pump. If ORP is needed the controller also turns on the ozone generator. All will run until setpoint levels are reached.
Acid/Base Switching
Because most systems are dealing with a high pH situ­ation, the controller is factory set for acid feed. If you require a base feed, open plastic door on controller and
ORP Control Setpoint
The ORP setpoint is factory set at 550 mV, which is recommended to maintain water quality by killing germs and bacteria. There is no need for ORP calibration.
The sanitizing concentration required to generate a desired ORP value varies with pH and overall water quality, particularly Total Dissolved Solids (TDS) con­centration and organic load.
To change the ORP control setpoint:
• Press [SETPOINT],
• Press [ORP]: the display fl ashes,
• Use the [UP] and [DOWN] arrows to adjust the ORP value,
• Press [SETPOINT] again to save the new value.
pH Calibration
To calibrate the pH, use a reliable, fresh test kit (Phenol Red). Note the value of the pH and compare it to the display value.
To change the pH calibration:
• Press [CALIBRATION],
• Press [pH]: the display fl ashes,
• Use the [UP] and [DOWN] arrows to adjust the pH value,
• Press the [CALIBRATION] again to save the new value.
OPERATOR’S MANUAL
WATER MAZE ® 250
FEED
ALARM
PROPORTIONAL
CONTROL
MANUFACTURED BY SANTA BARBARA CONTROL SYSTEMS - SANTA BARBARA CALIFORNIA 93111 USA
ORP
OFF MANUAL AUTO
SAFETY
TIMER
SETPOINT
CALIBRATION
24V 50/60Hz 5A
pH
ORP / pH
DIGITAL CONTROLLER
pH
OFF MANUAL AUTO
LOW LIMIT HIGH LIMIT
FEED
ALARM
push the up and down arrows at the same time and let go. To toggle between acid (Ac) or base (bA) push the up arrow once then let the controller go though its start up procedure. Close plastic door.
Feed Mode
The feed mode for the pH and sanitizer can be set to "OFF", Manual or Automatic. Set to Automatic. To select the desired feed mode, press [ORP] or [pH] until the corresponding LED indicator light is illuminated. There is a short delay before activation. NOTE: Holding the switch for more than 5 seconds resets the setpoint and calibration for [ORP] or [pH] to original factory values.
pH Control Setpoint
The pH setpoint is preset at 6.8. To change the pH control setpoint:
• Press [SETPOINT],
• Press [pH]: the display fl ashes,
• Use the [UP] and [DOWN] arrows to adjust the pH value,
• Press [SETPOINT] again to save the new value.
8.913-970.0 - L • WATERMAZE CLP 5024/7034
21
SENSOR MAINTENANCE
Out-of-Range Alarms
The out-of-range alarms are factory set at 450 to 650 mV for ORP and 6.5 to 7.5 for pH. If the ORP is below the low limit, the red LED alarm fl ashes but the sanitizer feed continues.
If the pH limits are exceeded, the red LED alarm fl ashes and the pH feeder continues.
To change an alarm limit:
• Press [LOW LIMIT] or [HIGH LIMIT],
• Press [ORP] or [pH]; the display fl ashes,
• Use the [UP] and [DOWN] arrows to adjust the value,
• press [LOW LIMIT] or [HIGH LIMIT] again.
CAUTION: Increasing the out-of-range limits may cause overfeeding of chemicals.
ORP AND PH SENSOR
OPERATOR’S MANUAL WATER TREATMENT SYSTEM
The controller is virtually maintenance free. The enclo­sure and front panel can be cleaned with a soft cloth moistened with a mild soap and water solution or a glass cleaner. Do not use abrasives or harsh chemicals.
Sensor Cleaning/Testing
The sensor tips must be kept clean and free from chemical deposits and con­tamination to function properly. After saturation in the waste stream, the sensors may need to be cleaned on a weekly or monthly basis depending on the water quality and other facility-specifi c characteristics. Slow response and inconsis­tent readings are indications that the sensors are in need of cleaning.
To clean a sensor, carefully remove it from the compres­sion fi tting or holding bracket. Clean the tip of the sensor with a mild liquid detergent (Joy®, etc) solution. Rinse with fresh water and soak the sensor in a mild acid solution for fi ve minutes. Rinse with fresh water and reinstall the sensor.
MAINTENANCE
66-123 66-122
To check sensor for proper operation place a small amount of white vinegar, muriatic or hydrochloric acid into a cup and place sensor probe into solution. For the pH sensor, the needle should drop. For the ORP sensor, the needle should rise.
NOTE: Only clean one sensor at a time. Sensors must stay in some kind of liquid at all times.
Sensor Replacement
For preventative maintenance it is also recommended to replace the sensors on an annual basis or as perfor­mance diminishes.
Sensor Storage
Extended exposure to atmospheric conditions will cause the sensor tips to dry out. Always remove and properly store the sensors if they are to be winterized or inactive.
Store the sensors with the original cap provided, making sure that each cap is fi lled with clean water. If the stor­age containers have been misplaced, store the sensors individually in small glasses or plastic containers with clean water covering the sensor tips.
Terminal Block Wiring
B W G
B W G
B W G
ORP R W B Power pH
Rotary
Flowswitch
B=black, W=white, G=green, R=red
Dry-Contact
Alarm
22
8.913-970.0 - L • WATERMAZE CLP 5024/7034
TROUBLESHOOTING - ORP/PH SENSORS
All controllers are manufactured to the highest quality standards and thoroughly tested before leaving the factory. State-of-the-art designs and fabrication technology should ensure years for trouble-free operation.
PROBLEM SOLUTION
WATER TREATMENT SYSTEM
NO LIGHTS ARE ON WITH POWER ON
ILLOGICAL pH AND ORP VALUE DISPLAYS
ORP FEEDER DOES NOT ACTIVATE
pH FEEDER DOES NOT ACTIVATE
pH REQUIRES FREQUENT CALIBRATION
Check for power going to controller.
Check for damaged power connector.
Check internal fuse (1A slow blo) marked F3 on control board.
The sensor cable connections may be reversed. Verify that the sensor cables are properly connected to their respective BNC connectors on the controller unit.
Make sure the AUTO feed light for ORP is on.
Check the ORP setpoint.
Check ORP relay fuse (5A slow blow) marked F2 on control board.
Verify that the acid/base feed jumper JP14 on the control board is properly set.
Make sure the AUTO feed light for pH is on.
Check the pH relay fuse (5A slow blow) marked F2 on control board.
Clean or replace the sensor as outlined in the maintenance section.
OPERATOR’S MANUAL
INCONSISTANT OR SLOW pH OR ORP READINGS
CHEMICAL FEEDER RUNS CONTINUOUSLY
Verify that the sensor cables are properly connected to their respective BNC connectors and the controller unit.
Clean or replace the sensor as outlined in the maintenance section.
Replace the sensors if needed.
Make sure the AUTO feed mode is selected.
Verify that the chemical feeders are properly connected to their respective connectors or controller unit.
8.913-970.0 - L • WATERMAZE CLP 5024/7034
23
METERING PUMP
VSP20 METERING PUMP
#5-2359
(Variable Speed Peristaltic)
TECHNICAL INFORMATION
Materials:
Pump Head .................................. Polycarbonate
Pump Head Tubing .....Special Synthetic Rubber
Strainer and Injection Point Fitting ...............PVC
Feed Rate: 2.6 - 20 GPD Tubing Size: 7/16" O.D. x 1/4" I.D. Dimensions: Hgt. = 5", Wdt. = 6-1/4", Dpt. = 7"
Standard Accessories Provided with Pump:
Head Tubing
Injecting Fitting with Check Valve
Strainer
OPERATOR’S MANUAL WATER TREATMENT SYSTEM
Polyethylene Tubing (1/4" O.D. x 15')
Tubing Sleeve (for strainer connection)
Electrical Rating:
24V
.3 Amps
50/60 Hz
Maximum System Pressure: 25 PSI
(maximum allowable at injection fi tting)
24
8.913-970.0 - L • WATERMAZE CLP 5024/7034
GENERAL MAINTENANCE & SERVICE
GENERAL MAINTENANCE
AND SERVICE
Periodic Maintenance:
• Oil Skimmer Collection Drum
• Monitor the level of oil in the collection drum. Empty it as required.
• Check the electrical cords to ensure they are safe, no damage or cracking.
• Check inlet / outlet pipes for leaks or damage.
Winterizing
If a heated area is not provided in areas where freezing temperatures can be expected, the entire machine must be drained.
Testing Carbon
Remove the valve from the Carbasorb Filter and extract a carbon sample. Place carbon sample in the 4 oz. plastic bottle. (Fill the bottle 1/4 full of carbon, about 2 inches).
Fill the 2 oz. bottle with water and add 1 drop chlorine. Dip the chlorine test paper into the solution to ensure you have at least 100 parts per million of chlorine in the mixture. Add this solution to the carbon in the 4 oz. bottle. Cap and shake it periodically over a period of three min­utes. After three minutes, dip a new piece of chlorine test paper into the solution. Compare the color with the color chart that comes with the test paper. If the color matches the color on test paper, order new carbon. There may
be some dark discoloration from the carbon. Do not confuse this with the color caused by the chlorine.
OZONE GENERATOR
Ozone...Nature’s Purifi cation Agent
Ozone is produced in nature or artifi cially by man. In the earth’s atmosphere, ozone is formed when oxygen is exposed to ultraviolet light or an electrical charge as during thunderstorms. Ozone’s primary function in nature is to purify the air we breathe and screen us from harmful rays of the sun. In a similar fashion, the CLP system uses ozone to disinfect water because of characteristics that make it ideal for water treatment.
Ozone’s Characteristics
Ozone is well suited for water treatment, and it’s unique characteristics are described below:
Ozone has a number
Ozone works up to 3,000 times faster than chlorine to kill bacteria and destroy harmful microorganisms.
• Ozone is a more powerful oxidizing agent than chlorine and bromine, having a better ability to remove water contamination.
• Ozone will not form harmful by-products, like THM’s (a problem in drinking water), or chlora­mines, (by-products of chlorine that are respon­sible for odors, skin irritations and burning eyes.)
• Ozone will not alter the water’s pH, reducing pH fl uctuations.
• Ozone coagulates small particles in water so clarity is dramatically improved.
• Ozone acts as a deodorizer removing unpleasant odors from water.
How the CLP Ozone System Works
Because ozone is unstable, it cannot be packaged and used at a later date. For this reason, ozone is always produced where it is utilized.
Point-of-use ozone generation is simple. This powerful disinfectant is produced from ambient air surrounding the generator using special ultraviolet lamps located inside the system’s cabinet. To generate the ozone, air move­ment is created through the use of an air compressor or water venturi. As air passes over these unique lamps, the oxygen contained in the air is converted. The result­ing ozone gas is subsequently introduced to the water in the inlet pipeline, where oxidation and disinfection immediately takes place.
Ozone Generator Maintenance
WARNING: Never look at an un-
WARNING
EYE HAZARD: NEVER LOOK
AT UNSHIELDED
OZONE LAMP
Lamp: The light has a 9,000 hour life expectancy.
shielded ozone lamp while operat­ing the unit. This lamp will cause severe eye and skin damage. There is a green indicator light which will dim when the unit is operating properly and will turn bright green if there is a malfunc­tion. See product description for location of the indicator light.
ULTRAVIOLET LIGHT COMPLIANCE
Ultraviolet Light Safety Requirements
The device used in this product is a Class 1 certifi ed ozone generator product. Operating this product outside specifi cations or altering its original design may result
WATER TREATMENT SYSTEM
Troubleshooting Guide
8.913-970.0 - L • WATERMAZE CLP 5024/7034
25
OZONE SPECIFICATIONS
in hazardous radiation exposure, and may be considered an act of modifying or new manufacturing of a laser product under U.S. regulations contained in 21CFR Chapter 1, subchapter J.
CAUTION: Avoid exposure to direct or strongly refl ected germicidal ultraviolet rays.
DO NOT STARE INTO BEAM. ATTENTION: Éviter l'exposition aux rayons ultra-
violets germicides fortement réfl échis. NE PAS REGARDER DIRECTEMENT LE FAISCEAU.
DANGER: Ultraviolet radiation. Disconnect
OPERATOR’S MANUAL WATER TREATMENT SYSTEM
Power Before Replacing Lamp. ATTENTION: Radiation ultraviolette. Débrancher
l'alimentation avant de remplacer la lampe.
DANGER: Connect only to a circuit that is protect­ed by Ground Fault Circuit Interrupt (GFCI).
DANGER: Raccorder uniquement à un circuit qui est protégé par un disjoncteur différentiel de fuite à la terre (DDFT).
Testing the Lamp: (See Ozone Generator Testing Illus.)
To test the ozone lamp, use a voltmeter set on ohms. First remove the ozone cover and unplug the lamp plug from the ozone lamp.
OZONE GENERATOR TESTING
Four Pin
Connector
Ballast
NOTE: There are two fi laments - an upper and a lower -
inside the lamp. Place one of the voltmeter leads on one of the lamp prongs and, with the other lead, touch all of the three remaining prongs. If continuity is not achieved on both upper and lower fi laments, replace the ozone lamp (Part #6-0534)
To test the power pack, use a voltmeter set on the cor­rect voltage (120V or 240V). Place one of the voltmeter leads into the lamp plug where the white wire goes into it and plug the other voltmeter lead into the lamp plug where the blue wire goes into it. If no voltage is present replace the ozone ballast (Part #6-05231 - 120V, Part #6-05232 - 240V). When ordering an ozone ballast, you also need the 4-pin connector (Part #6-05233).
Replacing the lamp: (See Ozone Generator Breakdown)
Lamp replacements are available from your WATER MAZE Dealer should they need to be replaced. Simply
turn off the power to the CLP at the breaker, remove the screws on the power pack cover and remove the cover. Disconnect the plug on the end of the ozone lamp. Now, loosen the lamp holder locking ring from around the end of the lamp by turning it counterclockwise and remove it. Remove the lamp by grabbing the rubber bushing around the end of the lamp and pulling it straight out. Remove the rubber bushing from the lamp and install it on your new lamp, making sure the outer edge of the bushing is fl ush with the outer edge of the silver end cap on the lamp. Now, slide the lamp back into the reaction chamber. The lamp holder may now be reinstalled and tightened. Reinstall the plug onto the lamp and replace the power pack cover.
CAUTION: Keep the lamp free of fi ngerprints and dust particles by only handling the metal end caps on the lamp. You can clean the lamp with rubbing alcohol and a soft cloth. A dirty lamp will not allow maximum ozone output.
SPECIFICATIONS
26
Energy required 110V:
105VAC MIN., 125VAC MAX., .800 AMP/Ballast Energy required 220V:
210VAC MIN., 230V MAX., .450AMP/Ballast
Ozone
Lamp
Prongs
Power Consumption: 20 Watts Average Lamp Life: 9,000 Hours
Lamp Wave length: 185 nm
89139700-34
8.913-970.0 - L • WATERMAZE CLP 5024/7034
OZONE GENERATOR BREAKDOWN EXPLODED VIEW
21
Ballast
WATER TREATMENT SYSTEM
5
Prongs
Ozone Lamp
19
OPERATOR’S MANUAL
11
9
23
10
4
1
12
11
16
17
13
14
6
On/Off
Switch
8
Ozone
Lamp
15
3
UCION
N
AUTION
A
C
PREC
IGHT OPERATIO
L
. e
v
uous light indicates UV
ecti f
mador está def
r o f
TEUR
A
o f
rans
ATTENTION
OT!
H
!
UD!
ALIENTE!
A
C
H
C
. o
ectuos
mateur est r
ENT
TT
A
/
!
ARNING!
W
ION
VICING.
VICING. R R
!
ENC
OM ELECTRICAL OM ELECTRICAL
R
T
R
A
VICI VICI R
Y BEFORE SE
Y BEFORE SE L L
AR SE AR SER
D
AR
D
PAR
DISCONNECT F
P
DISCONNECT F
TION ÉLECTRI TION ÉLECTRI
SUPP SUPP
TA TA
ANTES DE ANTES DE
L’ALIMEN L’ALIMEN
AIRE UNE RÉ
AIRE UNE RÉ DESCONECTE LA CORRIENTE ELECTRICA DESCONECTE LA CORRIENTE ELECTRICA
F F
COUPER COUPER
ANT DE
ANT DE AV AV
ON!
I
. .
UE
UE O O
Q Q
TION.
TION. A A
8.900-455.0
OZONE GENERATOR
INDICATOR
ight contin
2
22
r A b light or ballast de
INDICADORA
OPERACION DE LA LUZ
ans
r Una luz luminosa indica que la luz ultra­violeta o t
INDIC
OPÉRATION DE LE LAMPE
Une lumière claire indique que la lumière
aviolette ou le t
r ult défectueux.
7
24
8.913-970.0 - L • WATERMAZE CLP 5024/7034
18
20
89139700-26
27
Loading...
+ 61 hidden pages