Waterford 104 MK II Installation And Operating Instructions

104 MK II WOOD-BURNING STOVE
SAFETY NOTICE
PLEASE READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND USE YOUR NEW ROOM HEATER. FAILURE TO FOLLOW INSTRUCTIONS MAY RESULT IN PROPERTY DAMAGE, BODILY INJURY OR EVEN DEATH. SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE. IF THIS STOVE IS NOT PROPERLY INSTALLED, A HOUSE FIRE MAY RESULT. FOR YOUR SAFETY, FOLLOW THE INSTALLATION DIRECTIONS. CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION IN YOUR AREA. THIS STOVE MUST BE CONNECTED TO A LISTED HIGH TEMPERATURE RESIDENTIAL TYPE AND BUILDING HEAT­ING APPLIANCE CHIMNEY OR AN APPROVED MASONRY CHIMNEY WITH FLUE LINER.
MANUFACTURED BY: WATERFORD STANLEY (MARKETING) LIMITED
BILBERRY, WATERFORD, IRELAND.
INSTALLATION AND OPERATING INSTRUCTIONS
104 - MKII
PRE-INSTALLATION ASSEMBLY
Step 1:
After removing the stove from the pack, open the fire door and remove packed contents from the Firebox. Empty the Jiffy Bag.
Step 2:
Lay the stove on its side. Insert and secure a leg in the recess at each corner of the base using 25mm x 6mm (1 in. x 1/4 in.) flat head screws and 6mm (1/4 in.) flat wash­ers.
Step 3:
Carefully stand the unit upright on its legs.
Step 4:
Remove the nut and washer from the knob. Place in posi­tion, insert the screw in position with spring washer and nut provided. See Sketch.
104 MK II
GENERAL INSTRUCTIONS
BUILDING CODES
Consult the LOCAL BUILDING CODE in all cases as to the particular requirements concerning the installation of SOLID FUEL TYPE ROOM HEATERS. This 104 MK II WOOD BURNING STOVE is intended to be installed in accordance with National Fire Protection Associations Standard for Chimneys, Fireplaces and Vents, NFPA 211-
1977.
This stove has been tested and listed by UNDERWRIT­ERS LABORATORIES INC, and as such carries the U.L. and U.L.C. LABEL. All building codes which recognise the value of U.L. Listing will accept applications for and approve installations of this product.
INSTALLATION INSTRUCTIONS
MUST BE FOLLOWED.
CHIMNEYS
The 104 MK II Wood Stove is a Radiant Room Heater and must be connected to a CHIMNEY of the proper size and type.
The complete installation must be done in accordance with current Standards and Local Codes. It should be noted that the requirements and these publications may be superseded during the life of this manual.
The chimney must have a CROSS-SECTIONAL AREA of at least 182.39 sq. cm. (28.27 square inches). It is best to connect to a chimney of the same size, as connection to a larger size may result in somewhat less draught. DO
NOT CONNECT TO A CHIMNEY SERVING ANOTHER APPLIANCE. Minimum chimney height 4.57 meters (15
ft.) from floor on which stove is installed. An existing masonry chimney should be inspected, and, if necessary, repaired by a competent mason or relined, using an approved relining system.
DO NOT CONNECT TO OR USE IN CONJUNCTION WITH ANY AIR DISTRIBUTION DUCTWORK UNLESS SPECIFICALLY APPROVED FOR SUCH INSTALLA­TION.
Note: Connection to type “B” Gas Vents, approved for
connection to a certain gas burning appliance only, will result in a fire.
CHIMNEY TYPES - USA ONLY
The stove must be connected to a U.L. 103 Listed Residential type H.T. and Building Heating Appliance. Chimney installed in accordance with the manufacturers instructions or a masonry chimney constructed in accor­dance with NFPA 211 Chimney vents and Solid Fuel Burning Appliances.
2
Step 5:
Take the hotplate (WIF 008) and place it in the large opening on the top. Do not remove the Hot Plate when the unit is in operation. Remove only for cleaning.
Step 6:
Attach the Spigot, item number 18, in the exploded view to the hob, item number 16 using the two 1/4” (6mm) counter sunk screws provided.
Check that all parts are securely fitted before firing the unit.
The stove is now ready for installation.
Fig.1
CHIMNEY TYPES - CANADA ONLY
The stove must be connected to an Underwriters Laboratories of Canada Labelled Factory Built 650 C Chimney, installed in accordance with the manufacturers instructions or a lined Masonry Chimney, constructed acceptable to the authority having jurisdiction.
CHIMNEY CONNECTOR
THE CHIMNEY CONNECTOR is a smokepipe used to connect the 104 MK II Stove to the approved chimney described above. The CHIMNEY CONNECTOR must be made of CORROSION RESISTANT STEEL 24 gauge or heavier (“black or blued” or equivalent treated steel).
SINGLE WALL STOVE PIPE MUST NOT PENETRATE COMBUSTIBLE WALLS OR CEILINGS.
A 127mm to 153mm (5 to 6 inch) increaser is included in the Stove kit. When using the 127mm to 153mm ( 5 to 6 inch) increaser, 153mm (6 inch) diameter connector pipe is used. Be sure to fasten the chimney connectors together and also to the flue outlet of the stove through the two holes provided. Use at least two screws for each joint. Be sure the joints are tight and fully secured.
CHIMNEY CONNECTOR USA ONLY
Connectors should maintain a pitch or rise of at least 1/4” (6mm) to the foot from the stove to the chimney. It should be installed so as to avoid sharp turns or other construc­tion features that would create excessive resistance to the flow of flue gases. It should be securely supported with joints fastened with sheet-metal screws, rivets, or other approved means. The entire length of a connector should be readily accessible for inspection, cleaning and replacement.
The connector may pass through walls or partitions con­structed of combustible materials provided the connector is either listed for wall pass-through or is routed through a device listed for wall pass-through and is installed in accordance with the conditions of the listing, NFPA 211 or CAN/CSA - B365. Any unexposed metal that is used as part of a wall pass-through system and is exposed to the flue gases shall be constructed of stainless steel or other equivalent material that will resist corrosion, softening, or cracking from flue gas at temperatures up to 982
o
C
CONNECTING TO MASONRY CHIMNEY
The connector to a masonry chimney must extend through the wall to the inner face or liner but not beyond,and must be firmly cemented to masonry.
The connector may pass through walls or partitions con­structed of combustible material to a masonry chimney provided the connector system selected is installed in accordance with the proper clearances and conditions. (See figures 2, 3, 4, 5 & 6 pages 3 & 4).
THIMBLES
Thimbles for chimneys or vent connector should be of fire clay (ASTM C 315, Specifications for Clay Flue Linings) galvanised steel of minimum thickness of 24 gauge, or material of equivalent durability. Thimbles should be installed without damage to the liner. The thimble should extend through the wall to, but not beyond, the inner face of the liner and should be firmly cemented to masonry.
Thimbles should be located to provide adequate pitch or rise of chimney or vent connectors and, where the ceiling above the appliance is constructed of combustible mate­rial, the location of the thimble should provide minimum clearance required for the connector as specified in Section under minimum clearances to combustibles.
Insulation material used as part of wall pass-through sys­tem should be of non-combustible material and should have a thermal conductivity of 1.0 Btu.in./ft.F (4.88kg.cal/hr.m.C) or less. All clearances and thickness­es are minimums; larger clearances and thicknesses are acceptable. Any material used to close up an opening for the connector should be of non-combustible material. A connector to a masonry chimney, except for system 2 (Under heading Chimney Connector Systems, Thimbles and Clearances), shall extend to piece through the wall pass-through system and the chimney wall to the inner face of the flue liner, but not beyond.
CHIMNEY CONNECTOR SYSTEMS, THIMBLES, AND CLEARANCES FROM COMBUSTIBLE WALLS
1. Minimum 3 1/2” (90mm) thick brick masonry wall framed into combustible wall with a min. of 12” (305mm) brick separation form clay liner to com­bustibles. Fire clay liner (ASTM C315 or equiva lent) min. 5/8” (16mm) wall thickness, should run from outer surface of brick wall to, but not beyond, the inner surface of chimney flue liner and should be firmly cemented in place.
3
Fig.2
Minimum clearance 12” (305mm) of brick
Minimum 12” (305mm) to combustibles
Minimum chimney clearance to brick and combustibles 2” (50mm)
2. Solid insulated listed factory-built chimney length of the same inside diameter as the chimney connector and having 1” (25mm) or more of insu­lation with a min. 9” (229mm) air space between the outer wall of the chimney length and com­bustibles. The inner end of the chimney length shall be flush with the inside of the masonry chimney flue and shall be sealed to the flue and to the brick masonry penetration with nonwater­soluble refractory cement. Supports should be securely fastened to wall surfaces on all sides. Fasteners between supports and the chimney length shall not penetrate the chimney liner.
4. Solid insulated listed factory-built chimney length with an inside diameter 2” (50mm) larger than the chimney connector and having 1” (25mm) or more of insulation, serving as a pass-through for a single wall sheet steel chimney connector of min. 24 gauge thickness, with a min. 2” (50mm) air space between the outer wall of chimney sec­tion and combustibles. Min. length of chimney section shall be 12” (305mm). Chimney section concentric with and spaced 1” (25mm) away from connector by means of sheet steel support plates on both ends of chimney section. Opening shall be covered and chimney section supported on both sides with sheet steel supports of min. 24 gauge thickness.
Supports should be securely fastened to wall surfaces on all sides and shall be sized to fit and hold chimney sec­tion. Fasteners used to secure chimney sections should not penetrate chimney flue liner.
3. Sheet steel chimney connector, min. 24 gauge in thickness, with a ventilated thimble, min 24 gauge in thickness, having two 1” (25mm) air channels, separated from combustibles by a min. of 6” (150mm) of glass fibre insulation. Opening should be covered and thimble supported with a sheet steel support, min. 24 gauge in thickness. Supports should be securely fastened to wall sur­faces on all sides and should be sized to fit and hold chimney section. Fasteners used to secure chimney sections should not penetrate chimney flue liner.
4
Fig3
Fig.4
Fig.5
Fig.6
(50mm)
(229mm)
minimum
Minimum clearance 9” (229mm)
(50mm)
(25mm)
(150mm)
glass fibre insulation
Two ventilated air channels each 1” (25mm) constructed of sheet steel
(50mm)
Minimum clearances 2” (50mm)
1” (25mm) air space to chimney length
Air space 2” (50mm)
Loading...
+ 7 hidden pages